TEMPERATURE /HUMIDITY TRANSMITTER - WALL (4-20 MA)
Description
The THW420 combination
temperature/humidity transmitter
is designed to meet applications
that require local indication of both
temperature and humidity in a
single, aesthetically pleasing
enclosure.
This device incorporates a 10K ohm
(Ω) platinum RTD. The transmitter
requires 24 VDC. The sensor provides an
accurate and predictable four-wire, 4-20 mA
output signal for temperature and a second
4-20 mA output signal for humidity.
Dimensions
0.95"
(241mm)
0.75"
(191mm)
SIDE
VIEW
Wall
4.5"
(1143mm)
FRONT
VIEW
2.25"
(572mm)
2.75"
(699mm)
TOP VIEW
Specifications
Output 4 to 20 mA
Sensor 10K Ω platinum RTD
Supply Voltage 24 VDC
Tolerance of Resistance
(Accuracy)
Response Time 20 seconds for a 63% step
Environmental Operating
Range (Transmitter)
±1.5°F (±0.83°C)
±2% RH (from 15 to 95% RH)
45°F to 96°F; 0 to 100% RH
(7°C to 35°C); 0 to 100% RH
Termination
The THW420 transmitter must be powered from a
24 VDC supply. The combination temperature/
humidity sensor is terminated as follows:
•The humidity transmitter requires a three-wire
termination for the 4-20mA output using 24 VDC.
•The temperature sensor also requires a three-
wire termination. In most cases, it obtains power
from the analog input to which it is connected and
no external power is required.
Though interference from external sources is not a
major problem with current transmitters, Liebert
recommends separating the wiring from line voltage
wiring and from wiring used to supply highly inductive loads such as motors, generators and coils. Liebert also recommends making power connections
with twisted pair wire of at least 22 AWG and crimptype connectors.
0-5V
0-5V
0-5V
CALRUN
C9
X
J2
J3
20
H
Products, Inc.
Copyright 2000
REV. 101600
XCOMBO T&B
J1
To GND (common)
of controller*
From +24VDC
of controller or
power supply
Gnd
V+
Ch1
Ch3
CAL
Te mp
R19
Short
Norm
Open
Ch2
Te mp
T&B
SWITCH
SW1
To controller’s
analog input
(temperature signal,
4-20mA)
To controller’s
analog input
(humidity signal,
4-20mA)
* NOTE:
The GND (common)
terminal is common
between the Power
and Sensor
+24VDC should be
used at all times
U3
SW2 OUTPUT SELECT
ON
4-20ma
Ch1
4-20ma
Ch2
RESIST.
Ch3
%RH
SW2
DISPLAY CYCLE
IN SECONDS
10
3
T
POT1
Building Automation
RTH1 RTH2
Terminations
CAUTION
!
Liebert recommends wiring the sensor
WITHOUT power applied because
accidental arcing may damage the product
and will void the warranty.
Controller
Ground
4-20 mA
Input #1
+
4-20 mA
Input #2
+
-
Ordering Information
Quantity Part # Description
THW420 Combination Temperature/Humidity Transmitter Wall 4-20 mA @ 45°F to 96°F and 0 to 100% RH
SL-31080 Product Specification/Installation Sheet page 1 6/03 (Rev. 0)
Mounting
Junction box
2" x 4"
Mounting
screws
Cover
Locking
screws
Delta
base
Wall
Enclosure Mounting Instructions
Mounting hardware is provided for both junction box
and drywall installation.
1. Pull the wires through the opening in the base
plate.
2. For junction box installation: Secure the
base to the box using the #6-32 x 1/2" mounting
screws provided.
For drywall installation: Drill two 3/16" holes
3-1/4" apart on center. Insert the drywall
anchors and secure the base using the #6 x 1"
sheet metal screws provided.
3. Terminate the unit according to the guidelines
in Termination on page 1.
4. Attach the cover by latching it to the top of the
base, rotating the cover down and snapping it
into place.
5. Secure the cover by backing out the lock-down
screws using a 1/16" allen wrench until they are
flush with the bottom of the cover.
NOTE
In a wall-mount application, the wall temperature and the
temperature of the air within the wall cavity can cause
erroneous readings. The mixing of room air and air from
within the wall cavity can lead to condensation and premature
failure of the sensor.
To prevent these conditions, seal the conduit leading to the
junction box and seal the hole in the drywall by using an
adhesive backed, foam insulating pad.
Troubleshooting Guide
The following table lists common problems and possible solutions. For more information, consult your local
dealer, Liebert representative or the Liebert Worldwide Support Group.
Problems Possible Solutions
Unit will not operate
Humidity reading is maximum
20 mA or 100%
Humidity reading is minimum
4 mA or 0%
Humidity reading in software
appears to be off more than
specified accuracy
Temperature sensor in frontend software is reading high
Temperature sensor in frontend software is reading low
• Check +24 VDC power supply at controller.
• Disconnect the sensor and check power wires for +24 VDC.
• Make sure the sensor is installed properly, and is not shorted.
• Quick Check: Remove the sensor. If the reading does not change, contact technical
support.
• Verify that the humidity sensor installed.
• Quick Check: Short the sensor terminal block with a wire. Does the reading change? If so,
the sensor may be faulty; if not, contact technical support.
• Check all software parameters.
• If available, check the sensor against a calibrated control such as a hygrometer.
• Determine if the sensor is exposed to an external source more than room.
• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.
• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.
SL-31080 Product Specification/Installation Sheet page 2 6/03 (Rev. 0)