Thermostat Controller Installation Instructions
General
This product has been designed and manufactured for the sole intended use of controlling EasyHeat ILH (interior pipe heating) heating
cable sets. Improper installation, use, operation and or maintenance of these cables can cause re and/or result in electrical shock.
Warning
1. If after carefully reading these instructions you still have
questions regarding installation or operation of this product,
call the numbers listed below for assistance.
2. The SL-2G contains an integral ground fault circuit interrupter
(GFCI). If the GFCI trips and cannot be reset, a fault exists in
the ILH heating cable set. Do not attempt to bypass the
GFCI. Bypassing the GFCI will result in the risk of re or
electrical shock.
3. The SL-2G contains an integral temperature sensing bulb.
The sensing wire must not be kinked or compressed during
installation. When used with the ILH product, the sensing wire
must be secured to piping with tape, and not with cable ties
or pipe clamps, as these will damage the sensing wire.
Sensing wire damage will result in improper control of the
heating cables and may result in frozen pipes and the risk of
re or electrical shock.
4. All ILH cable sets must be installed in compliance with the
latest editions of the: National Electrical Code; Canadian
Electrical Code; State or Provincial Codes;
and Local Codes.
5. These instructions must be saved and made available to
owners or users of this product and transferred to future
owners. If additional copies of these instructions are required,
contact at Easy Heat at the address noted below.
6. Do not connect more than one cable set to the SL-2G
controller, the maximum cable size that can be connected
to the SL-2G is 1440Watts (12 Amps).
Sensing Wire Sensing Bulb
Specications
• Voltage 120 VAC
• Current 12 Amps Maximum
• Temperature Range 2° C to 25°C ± 2°C
• CSA Certied
LIMITED WARRANTY AND LIABILITY
Easy Heat warrants that if there are any defects in material or workmanship in this product
during the rst twelve (12) months after the date of its purchase, we will replace the
product with an equivalent model, not including any labor or other installation costs.
Our obligation to replace the product as described above is conditioned upon (a)
the installation of the product conforms to the specications set forth in our installation
instructions and (b) the product not having been damaged by unrelated mechanical
or electrical activities.
Product replacement as described above shall be your sole and exclusive remedy for a
breach of this warranty. This limited warranty does not cover any service costs relating
to repair or replacement.
We shall not be liable for any incidental, special or consequential damages as a result of
any breach of this warranty or otherwise, whether or not caused by negligence. Some
states do not allow the exclusion or limitation of incidental or consequential damages,
so the above limitation or exclusion may not apply to you.
The warranty above is exclusive and makes no other warranties with respect to description
or quality of the product. No afrmation of fact or promise made by us, by words or
action, shall constitute a warranty. If any model or sample was shown to you, the model or
sample was used merely to illustrate the general type and quality of the goods and not to
represent that the goods would necessarily be of that type or nature. No agent, employee
or representative of ours has authority to bind us to any afrmation, representation or
warranty concerning the goods sold unless such afrmation, representation or warranty
is specically incorporated by written agreement.
US T. (800) 537-4732 / F. (888) 324-2440
CAN T. (800) 794-3766 / F. (800) 361-4574
©2009 EASYHEAT www.easyheat.com 14066-001 Rev. 5
Any implied warranty of merchantability or tness for particular purpose that may arise in
connection with the sale of this product shall be limited in duration to twelve (12) months
from the date of purchase. We disclaim all other implied warranties, unless we are
prohibited by law from doing so, in which case all such implied warranties shall expire at
the earliest time permitted by applicable law. Some states do not allow limitations on how
long an implied warranty lasts, so the above limitation may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary
from state to state or province to province.
To obtain a replacement under this warranty any inoperative product or component
must be returned, with proof of purchase, to Easy Heat at the addresses noted herein.
Buyer is responsible for all costs incurred in removal and re-installation of product and
must pre-pay shipment to factory or point of purchase.
In Canada In USA
Heating Cable Warranty Dept. Heating Cable Warranty Dept.
99 Union Street 2 Connecticut South Drive
Elmira ON N3B 3L7 East Granby CT 06026
Installation Instructions
2ºC/36ºF
9ºC/48ºF
17ºC/63ºF
25ºC/77ºF
1. Please fully read these instructions prior to installation and
operation.
2. Determine a suitable mounting location for the SL-2G
control. The control must be placed in a location that is
within 4’ of a 120VAC electrical outlet and within 8’ of the
pipe being heated and controlled.
3. Mount the SL-2G to a rigid support such as a wall by way of
the rear mounting slots.
4. The SL-2G thermostat control is suitable for dry location
(in-door) installations only.
5. Carefully uncoil and straighten the sensing wire/sensing bulb
and attach it to the outer surface of the pipe being heated.
The bulb on the end of the sensing wire must be located in
an area that is experiencing the same freezing or damaging
cold temperatures that the pipe is experiencing. The sensing
wire must not be kinked or compressed during installation.
When used with the ILH product, the sensing wire must be
secured to piping with tape, and not with devices such as
cable ties or pipe clamps, as these will damage the sensing
wire. The sensing wire must be protected from damage.
Sensing wire damage will result in improper control of the
heating cables and may result in frozen pipes and the risk of
re or electrical shock.
Power Cord to be hanked
to maximum 4” dia
6. Plug the SL-2G power cordset into a 120 VAC receptacle.
The lighted plug on the cordset will illuminate indicating that
there is power being supplied to the SL-2G control. Turn the
SL-2G control knob to the maximum setting of 25°C (77°F).
The GFCI receptacle indicator light should be off. If the GFCI
receptacle indicator light is illuminated press the “Reset”
button on the receptacle, the GFCI receptacle indicator
light should then turn off. If the GFCI cannot be reset, then a
fault exists. Do not attempt to bypass the GFCI. Bypassing the
GFCI will result in the risk of re or electrical shock.
7. Set the desired protection temperature for your application
by adjusting the control activation temperature between
2° C and 25°C (36°F to 77°F).
8. Plug in your ILH heating cable to the GFCI receptacle on the
front of the SL-2G control.
Mounting
Slots
Neon Light
Clear Plug
Senseor Wire
Assembly
3-16 AWG Power Cord,
4ft (from cabinet) CSA type SJT 105°C
Operation Instructions
1. The SL-2G thermostat control is designed to energize
ILH heating cables when ambient temperatures drop
below the set value. By controlling heating cable operation
with the SL-2G, energy consumption is minimized.
2. The bulb on the end of the sensing wire senses the
temperature. If the temperature of the bulb drops below
the pre-set temperature value the cable will energize, and
remain energized until the sensing bulb senses temperatures
above the pre-set value.
3. The SL-2G can be tested for functionality by submerging the
sensing bulb in ice water for 10 minutes; the GFCI receptacle
will be energized.
4. Disconnect the power to the SL-2G during the summer
months.
5. At the beginning of the heating season and monthly during
operation, inspect the SL-2G control and its connection to
the electrical power source. Similarly, check the GFCI on a
monthly basis. Testing of the GFCI is dependent upon the
temperature of the sensing bulb.
a) If the ambient is below 21°C, turn the thermostat
control knob to the maximum setting; the GFCI will be
energized. Push the “TEST” button on the GFCI recptacle; a
“click” should be heard and the receptacle indicator light
will turn on. Push the “RESET” button on the GFCI recptacle
to reset the power (the indicator light will turn off).
b) If the ambient temperature is above 22°C, you will need
to “cool down” the sensing bulb to test the GFCI. It is
recommended to wait until the bulb is below 21°C as
in step a), however if this is not possible you will need to
submerge the sensing bulb in ice water for 10 minutes and
then follow the instructions as described in a) above.
6. The GFCI will not be affected by power interruptions.
7. Discontinue use and remove any unit that has been
damaged or has deteriorated for any reason.
8. Other conditions to look for are chewing by animals, water
damage/corrosion or physical abuse.