SITETPI-E V3
Product Specification/Installation Sheet
Description
The Liebert SiteTPI-E is an Ethernetready device intended to interface
specifically to a SiteScan Web system.
It is a 32-bit microprocessor-based
device designed to monitor third-party
equipment via an EIA-485/232
Modbus interface.
Logically the device sits on the
Ethernet network, providing the
interface to SiteScan Web. This
effectively creates a router/gateway
and third-party interface in a single
device. Screw terminal blocks are
provided to terminate power,
communication and input signal
wiring.
Module Dimensions and Layout
10/100 BaseT
Ethernet
port
BACnet
port
Local access
port
Rnet port
Port S2
Ethernet Port E1
100 LAN LINK
BACnet
Over ARCNET156 KBaud
BT485
Net +
Net -
BACnet
Shield
Local Access
Gnd
Rnet +
Rnet
Rnet -
+12V
EIA-
232
485
Tx
Net+
Rx
Net-
DTR
n/c
DCD
n/c
Signal Gnd
BT485
Tx
Rx
EIA-232
EIA-485
®
Port S2
BACnet transmit
BACnet receive
Archive Valid
Port S1 transmit
Port S1 receive
Battery low
11.295"
(286.9mm)
3V Lithium Battery
CR-123A
SiteTPI-E
CONTROL MODULE
Open Energy
Management Equipment
R
88FO
E143900
TYPE: 002001
Error Codes:
Chase = OK
0 = Download required
1 = Control Program Error
2 = RAM full
3 = Comm setup error
4 = System error
8 = Formatting
Module
Status
Blinking Dot = 'Run'
Power
LED
Enhanced Access
Format
Port on S2
and Rnet
On
Off
™
IP Addr
Assigned +100
Default
Power
connector
Without Keypad Display:
24Vac, 24VA, 1A, 50-60 Hz
26Vdc, 10W, 0.4A
Use Copper Conductors Only
Class 2
MSTP
Address
on S1
Enable
0
Disable
Module
Address
10's 1's
Enable
Disable
PTP
on S2
Port S1
2 wire 4 wire
Signal Ground
n/c
Rx +n/c
Net-
Net+
Tx +
EIA-232
EIA-485
485-2w
485-4w
Power
On Off
Ext. Batt.
Int. Batt.
Rx -
Tx -
External
Battery
EIA-232
DCD
DTR
Option
Comm
0.23"
(5.8mm)
Ground
24V ac/dc
Gnd
+3V
Rx
Tx
Made in USA
1.25"
(32mm)
2.5"
(64mm)
BT485
7.5"
(190.5mm)
2.5"
(64mm)
1.25"
(32mm)
Diagnostic
LED indicators
Port S1
Options
comm
1

Enclosure Mounting
The enclosure may be mounted on a wall or on the floor. Refer to the following diagrams for
your application.
Enclosure Wall Mounting Diagram
Enclosure Floor Mounting Diagram
3

Specifications
Power 24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W
Dimensions
W x D x H: in. (mm)
Communication
Environmental
Operating Range
Memory
Protection Built-in surge and transient protection circuitry
Battery 3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation
Fault Detection Hardware watchdog timer
Agency Listings UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 - Subpart B - Class A
Module:
11.295 x 0.56 x 7.5 (286.9 x 14.2 x 190.5)
• One (1) Ethernet 10/100BaseT RJ-45 port
• One (1) Configurable Serial Port - EIA-232 or 485 (2- or 4-wire)
• 5-position Terminal Block
• One (1) CMnet EIA-485 Port - Control Module network screw terminals
• Switch-selectable baud rates ARC156 / 9600 or 38.4bps
• Recommended wire: MAGNUM Cable P/N A3-ARC-156-2
• BACnet Port (ARCNET156 or EIA-485 communication): In ARCNET156 mode, the port speaks
BACnet ARC156. In EIA-485 mode, DIP switch settings specify baud rate and protocol: BACnet
MS/TP or Modbus (RTU or ASCII).
• Port S1 (BMS connection): Normally configured for a Building Management System; may be
configured for EIA-485 or EIA-232. Supports BACnet MS/TP, BACnet PTP and Modbus (RTU or
ASCII) protocols.
• Port S2 (MFR connection): Connection to manufacturer’s equipment; jumper enables EIA-485 or
EIA-232 mode. Supports BACnet MS/TP, BACnet PTP and Modbus (RTU or ASCII) protocols.
• Rnet: Local laptop and/or BACview access port. Conforms to the BACnet Advanced Application
Controller (B-AAC) Standard Device as defined in BACnet 135-2001 Annex L.
20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing.
Note: Control modules should be installed within the building.
16 MByte non-volatile battery-backed SDRAM (with 12 MBytes available for use)
8 MByte Flash memory, 32-bit memory bus
Enclosure (painted steel):
14.25 x 2.85 x 12 (362 x 72.4 x 304.8)
Diagnostic LEDs
Indicator Description Indicator Description
BACnet transmit Blinks when data is transmitted Port S1 transmit Blinks when data is transmitted
BACnet receive Blinks when data is received Port S1 receive Blinks when data is received
Archive Valid N/A Battery low Blinks when the battery is low
Wiring Specifications
Connection Supported Wire Types Maximum Wire Length Rating
Ethernet 10 BaseT CAT 5 328 ft. (100m) N/A
Port S1 ARCnet MAGNUM Cable P/N A3-ARC-156-2 3000 ft. (915m) N/A
Port S2 EIA-485
Port S2 EIA-232
18-22 AWG Stranded & Shielded; 18 AWG* (recommended)
Non Plenum - Belden 9461; Plenum - Belden 88761
18-22 AWG Stranded & Shielded; 18 AWG* (recommended)
Non Plenum - Belden 9461; Plenum - Belden 88761
1000 ft. (300m) N/A
50 ft. (15m) N/A
Ordering Information
Quantity Part # Description
SiteTPI-E SiteScan Web Third-Party Interface Module - Ethernet Ready
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
© 2006 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-28105 (2/06) Rev. 1