Emerson SITETPI-E V3 User Manual

Page 1
SITETPI-E V3
Product Specification/Installation Sheet

Description

The Liebert SiteTPI-E is an Ethernet­ready device intended to interface specifically to a SiteScan Web system.
It is a 32-bit microprocessor-based device designed to monitor third-party equipment via an EIA-485/232 Modbus interface.
Logically the device sits on the Ethernet network, providing the interface to SiteScan Web. This effectively creates a router/gateway and third-party interface in a single device. Screw terminal blocks are provided to terminate power, communication and input signal wiring.

Module Dimensions and Layout

10/100 BaseT
Ethernet port
BACnet port
Local access port
Rnet port
Port S2
Ethernet Port E1
100 LAN LINK
BACnet
Over ARCNET156 KBaud
BT485
Net +
Net -
BACnet
Shield
Local Access
Gnd
Rnet +
Rnet
Rnet -
+12V
EIA-
232
485
Tx
Net+
Rx
Net-
DTR
n/c
DCD
n/c
Signal Gnd
BT485
Tx
Rx
EIA-232
EIA-485
®
Port S2
BACnet transmit BACnet receive
Archive Valid Port S1 transmit Port S1 receive
Battery low
11.295"
(286.9mm)
3V Lithium Battery
CR-123A
SiteTPI-E
CONTROL MODULE
Open Energy
Management Equipment
R
88FO
E143900
TYPE: 002001
Error Codes:
Chase = OK 0 = Download required
1 = Control Program Error
2 = RAM full
3 = Comm setup error
4 = System error
8 = Formatting
Module
Status
Blinking Dot = 'Run'
Power
LED
Enhanced Access
Format
Port on S2 and Rnet
On
Off
IP Addr
Assigned +100
Default
Power connector
Without Keypad Display:
24Vac, 24VA, 1A, 50-60 Hz 26Vdc, 10W, 0.4A
Use Copper Conductors Only Class 2
MSTP
Address
on S1
Enable
0
Disable
Module
Address
10's 1's
Enable
Disable
PTP
on S2
Port S1
2 wire 4 wire
Signal Ground
n/c
Rx +n/c
Net-
Net+
Tx +
EIA-232
EIA-485
485-2w 485-4w
Power
On Off
Ext. Batt.
Int. Batt.
Rx -
Tx -
External
Battery
EIA-232
DCD
DTR
Option Comm
0.23"
(5.8mm)
Ground
24V ac/dc
Gnd +3V
Rx
Tx
Made in USA
1.25"
(32mm)
2.5"
(64mm)
BT485
7.5"
(190.5mm)
2.5"
(64mm)
1.25"
(32mm)
Diagnostic LED indicators
Port S1
Options comm
1
Page 2

Power Wiring Diagrams

Enclosure Dimensions

2
Page 3

Enclosure Mounting

The enclosure may be mounted on a wall or on the floor. Refer to the following diagrams for your application.

Enclosure Wall Mounting Diagram

Enclosure Floor Mounting Diagram

3
Page 4

Specifications

Power 24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W
Dimensions W x D x H: in. (mm)
Communication
Environmental Operating Range
Memory
Protection Built-in surge and transient protection circuitry
Battery 3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation
Fault Detection Hardware watchdog timer
Agency Listings UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 - Subpart B - Class A
Module:
11.295 x 0.56 x 7.5 (286.9 x 14.2 x 190.5)
• One (1) Ethernet 10/100BaseT RJ-45 port
• One (1) Configurable Serial Port - EIA-232 or 485 (2- or 4-wire)
• 5-position Terminal Block
• One (1) CMnet EIA-485 Port - Control Module network screw terminals
• Switch-selectable baud rates ARC156 / 9600 or 38.4bps
• Recommended wire: MAGNUM Cable P/N A3-ARC-156-2
BACnet Port (ARCNET156 or EIA-485 communication): In ARCNET156 mode, the port speaks BACnet ARC156. In EIA-485 mode, DIP switch settings specify baud rate and protocol: BACnet MS/TP or Modbus (RTU or ASCII).
Port S1 (BMS connection): Normally configured for a Building Management System; may be configured for EIA-485 or EIA-232. Supports BACnet MS/TP, BACnet PTP and Modbus (RTU or ASCII) protocols.
Port S2 (MFR connection): Connection to manufacturer’s equipment; jumper enables EIA-485 or EIA-232 mode. Supports BACnet MS/TP, BACnet PTP and Modbus (RTU or ASCII) protocols.
Rnet: Local laptop and/or BACview access port. Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device as defined in BACnet 135-2001 Annex L.
20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing. Note: Control modules should be installed within the building.
16 MByte non-volatile battery-backed SDRAM (with 12 MBytes available for use) 8 MByte Flash memory, 32-bit memory bus
Enclosure (painted steel):
14.25 x 2.85 x 12 (362 x 72.4 x 304.8)

Diagnostic LEDs

Indicator Description Indicator Description
BACnet transmit Blinks when data is transmitted Port S1 transmit Blinks when data is transmitted
BACnet receive Blinks when data is received Port S1 receive Blinks when data is received
Archive Valid N/A Battery low Blinks when the battery is low

Wiring Specifications

Connection Supported Wire Types Maximum Wire Length Rating
Ethernet 10 BaseT CAT 5 328 ft. (100m) N/A
Port S1 ARCnet MAGNUM Cable P/N A3-ARC-156-2 3000 ft. (915m) N/A
Port S2 EIA-485
Port S2 EIA-232
18-22 AWG Stranded & Shielded; 18 AWG* (recommended) Non Plenum - Belden 9461; Plenum - Belden 88761
18-22 AWG Stranded & Shielded; 18 AWG* (recommended) Non Plenum - Belden 9461; Plenum - Belden 88761
1000 ft. (300m) N/A
50 ft. (15m) N/A

Ordering Information

Quantity Part # Description
SiteTPI-E SiteScan Web Third-Party Interface Module - Ethernet Ready
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com
© 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-28105 (2/06) Rev. 1