Emerson SiteLink-4 User Manual

Specification for SiteLink-4
DESCRIPTION: The SiteLink-4 is a 32 bit microprocessor-based communications device that provides an interface for up to four Liebert Unit Controllers (IGM’s). The SiteLink-4 communicates to either the SiteScan Monitoring System, or a third party software program utilizing a designated open standard protocol (i.e. Modbus or BACnet). This device communicates to the SiteScan Monitoring System via a twisted pair called the ARC156 network through an EIA-485 port at either 156K / 9600 or 38.4kbps baud. It communicates to the third party software monitoring system via a 9-pin DTE male EIA-232 connector (Portal Interface) or at the 5 pin EIA485 port communicating at either 9600bps or 38.4kbps baud. Four EIA-422 ports are provided to connect Liebert Information Gathering Modules.
DIMENSIONS: Module: 7 1/2" H x 11 1/4" W
19.05cm H x 28.58cm W
Enclosure: 12”H x 14.25" W x 2.85" D (painted steel) 419.1mm x 301.3mm x 78.6mm
See Enclosure Diagrams for mounting options.
POWER: 24VAC ± 10%, 50-60 Hz., 7.2VA power consumption (120/24VAC 40VA transformer available).
ENVIRONMENTAL OPERATING RANGE: 0° to 130° F (-17.8° to 54.4° C), 10 to 90% relative humidity, non-condensing
COMMUNICATION: CMnet EIA-485 Port - Control Module network screw terminals
Switch selectable baud rates ARC156 / 9600 or 38.4bps
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2
Two (2) Portal Interface – One EIA-232, One EIA-485 2 / 4 wire (for Third Party software selectable baud rate, 9600bps or 38.4kbps
One (1) Access port (for diagnostics)
Four (4) EIA-422 Ports (for Liebert unit connection) - screw terminal
MEMORY: 1024 kB Flash memory and 1024 kB non-volatile battery-backed RAM.
PROTECTION: Voltage, current, and ESD protection on incoming power and CMnet.
Liebert Corporation Page 1 of 5 SL-27213 Rev. 4; 7/03
Specification for SiteLink-4
BATTERY: Seven-year lithium battery provides a minimum or 10,000 hours or data retention during power outages.
LISTED: UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), FCC Part 15 – Subpart B
- Class A.
DIAGNOSTIC LED's:
Power: lights when power is being supplied to the module. Run: flashes to indicate a normal condition Error: lights when an error is detected CMnet Transmit: lights when the SiteLink-4 transmits data over the ARC156 network CMnet Receive: lights when the SiteLink-4 receives data from the AERC156 network Port A Transmit: lights when the SiteLink-4 transmits data over Port A Port A Receive: lights when the SiteLink-4 receives data from Port A Port B Transmit: lights when the SiteLink-4 transmits data over Port B Port B Receive: lights when the SiteLink-4 receives data from Port B Unit (IGM Port) Transmit: lights when the SiteLink-4 transmits data over an IGM port Unit (IGM Port) Receive: lights when the SiteLink-4 receives data from an IGM port
MODULE DIMENSIONS AND LAYOUT
1"
2.54cm
Port A Configuration Jumpers
Port A
Port B
LEDs
2wire4wire
Tx +
Net+
Tx -Net-
n/c
Rx +
n/c
Rx -
Signal Grou nd
Open Protocol
Communications
Port B
Run Error CMnet rec eive CMnet transmit PortA receive PortA transmit PortB receive PortB transmit Aux1 Aux2
Unit 1
+
n/c 485-2w 485-4w
EIA-232 EIA-485
EIA-232
Tx
Rx
DTR
DCD
RxTx
-
Tx-Rx
+
Communications
Port A
Unit 2
Unit 3
Tx-Rx
+
Format Button
Options
Format
SiteLink-4
Unit 4
Tx-Rx
+
Rotary Address
Switches
10's 1's
Module
Address
Liebert
Open Energy
ManagementEquipment
R
88FO
E143900
TYPE: 003212
11 1/4"
28.58cm
Power Switch
Gnd and 24VAC Terminals
Keypad/ Display Port
CMnet Port
Access Port
71/2"
19.05cm
Class 2
12VA, 0. 5A
Use Copper
On Off
Auxiliary
Device
Port
Shie ld
Net +
Access
Port
Grou nd
24 Vac
Net -
Power
24Vac,50-60Hz
ConductorsOnly
Caution
ToR educe The
Riskof Fireor
Electrical
Shock, DoNot
TM
Interconnect
the Out puts of
DifferentClass
2Circuits.
CMnet
ARC156K
9600/3 8.4K
CMnet Baud Rate Jumper
Liebert Corporation Page 2 of 5 SL-27213 Rev. 4; 7/03
Loading...
+ 3 hidden pages