Emerson SiteLink-2E, SiteLink-4E, SiteLink-12E User Manual

SITELINK-E
Product Specification/Installation Sheet

Description

The Liebert SiteLink-E is a product platform that comes in three models: SiteLink-12E, -4E and -2E. The models differ only in the number of Emerson family ports at the bottom of the module.
SiteLink-E supports Emerson interfaces as a BACnet router that provides the communications link between Liebert units and other protocols and modules.
The SiteLink-E is designed to communicate with Liebert equipment— environmental units, UPSs and Power Distribution Units—and route the information over a BACnet, Modbus or LONWorks™ network to a Building Automation System (BAS) workstation.

Module Dimensions and Layout

Diagnostic LED indicators
Ethernet port
BACnet port
Rnet port
Local access port
Xnet remote expansion port
10/100 BaseT Ethernet Port
100 LAN LINK
BACnet
Over ARCNET156 KBaud
BT485
Net +
Net -
ARCNET
Shield
Gnd Rnet + Rnet -
Rnet
+12V
Xnet +
Xnet
Xnet -
Remote
Expansion
Gnd
Port 1 Port 2 Port 3 Port 4 Port 5 Port 6 Port 7 Port 8 Port 9 Port 10 Port 11 Port 12
Net-
Net+
Net+
®
Net-
Module
Error Codes
Chase = OK 0 = Download required
1 = Control Program Error
2 = RAM full
3 = Comm setup error
4 = System error
8 = Formatting
Blinking Dot = 'Run'
Local Access
Net-
Net+
Net+
Status
Net-
Format
Net-
Net+
11. 3"
(287mm)
3V Lithium Battery
On
Off
Enhanced Access
on Rnet
CR-123A
Assigned
Default
IP Addr
+100
Address
0
10's 1's
Address
SiteLink-12E
Net-
Net-
Net+
Net-
Net+
Net+
Module
Enable
Disable
Net+
SiteLink-12E
Power connector
ARCNET Transmit ARCNET Receive
Archive Valid Port S1 Transmit Port S1 Receive
Battery low
Enable
Disable
PTP
MSTP
on S1
on S1
485-4w 485-2w
Port 9-12
EIA-485
EIA-232
Net-
Net-
Net+
Net+
Net-Rx
Net-Rx
Net+Rx
Net+Rx
2 wire 4 wire
EIA-232
EIA-485
Net-
Net+
Net+, Net-, Net+Rx, Net-Rx
Tx, Rx, Gnd, Gnd
Net-
Net+
Net-Rx
Net+Rx
24Vac, 24VA, 1A, 50-60 Hz
26Vdc, 10W, 0.4A
Port S1
Signal Ground
Rx -
n/c
Rx +n/c
Tx -
Tx +
Net-
Net-Rx
Net+Rx
Power
On Off
Ext. Batt.
Int. Batt.
EIA-232
DCD
DTR
Rx
Tx
External
Battery
Ground
24ac/26dc
Gnd +3V
BT485
0.23"
(5.8mm)
(25.4mm)
(190.5mm)
5.5"
(139.7mm)
(25.4mm)
1"
7.5"
1"
Port S1
1

Enclosure Mounting

The enclosure may be mounted on a wall or on the floor. Refer to the following diagrams for your application.

Enclosure Mounting Diagrams

1"
(25.4mm)
11"
(279.4mm)
0.88"
(22.2mm)
12.5"
(317.5mm)
0.88"
(22.2mm)
A
1"
(25.4mm)
11"
(279.4mm)
1"
(25.4mm)
0.88"
(22.2mm)
12.5"
(317.5mm)
2
DETAIL A
0.107"
R
(2.71mm)
0.4"
(10.2mm)
0.188"
R
(4.76mm)
1"
(25.4mm)
0.88"
(22.2mm)