 Specification for SiteLink-12 
DESCRIPTION: The SiteLink-12 is a 32-bit microprocessor-based communications device that provides 
an interface for up to twelve Liebert Unit Controllers (IGM’s). The SiteLink-12 communicates to either the 
SiteScan Monitoring System, or a third party software program utilizing a designated open standard 
protocol (i.e. Modbus or BACnet). This device communicates to the SiteScan Monitoring System via a 
twisted pair called the ARC156 network through an EIA-485 port at either 156K / 9600 or 38.4kbps baud.  
It communicates to the third party software monitoring system via a 9-pin DTE male EIA-232 connector 
(Portal Interface) or at the 5 pin EIA485 port communicating at either 9600bps or 38.4kbps baud. Twelve 
EIA-422 ports are provided to connect Liebert Information Gathering Modules. 
DIMENSIONS:   Module:  7 1/2" H x 11 1/4" W 
    19.05cm H x 28.58cm W 
  Enclosure:  12”H x 14.25" W x 2.85" D 
  (Painted steel)  419.1mm x 301.3mm x 78.6mm 
  See Enclosure Diagrams for mounting options. 
POWER:  24VAC ± 10%, 50-60 Hz, 7.2VA power consumption.  
  (120/24VAC 40VA Transformer available) 
ENVIRONMENTAL  
OPERATING RANGE: 0° to 130° F (-17.8° to 54.4° C), 10 to 90% relative humidity, non-condensing 
COMMUNICATION:  CMnet EIA-485 Port - Control Module network screw terminals 
  Switch selectable baud rates ARC156 / 9600 or 38.4bps 
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2 
  Two (2) Portal Interface – One EIA-232, One EIA-485 2 / 4 wire (for Third Party 
software selectable baud rate, 9600bps or 38.4kbps 
  One (1) Access port (for diagnostics) 
  Twelve (12) EIA-422 Ports (for Liebert unit connection) - screw terminal 
MEMORY:  1024 kB Flash memory and 1024 kB non-volatile battery-backed RAM. 
PROTECTION:  Voltage, current, and ESD protection on incoming power and ARC156 network 
BATTERY:  Seven-year lithium battery provides a minimum or 10,000 hours or data  
  retention during power outages. 
 Liebert Corporation           Page 1 of 5                    SL-27216 Rev. 4; 7/03 

 Specification for SiteLink-12 
LISTED:  UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), FCC Part 15 – Subpart B 
   - Class A. 
DIAGNOSTIC LED's: 
 Power:    lights when power is being supplied to the module. 
Run: flashes to indicate a normal condition  
Error:    lights when an error is detected 
CMnet Transmit:    lights when the SiteLink-12 transmits data over the ARC156 network 
CMnet Receive:    lights when the SiteLink-12 receives data from the ARC156 network  
Port A Transmit:    lights when the SiteLink-12 transmits data over Port A  
Port A Receive:    lights when the SiteLink-12 receives data from Port A  
Port B Transmit:    lights when the SiteLink-12 transmits data over Port B  
Port B Receive:    lights when the SiteLink-12 receives data from Port B  
Unit (IGM Port) Transmit:  lights when the SiteLink-12 transmits data over an IGM port  
Unit (IGM Port) Receive:  lights when the SiteLink-12 receives data from an IGM port 
1"
2.54cm
Port A 
Configuration 
Jumpers
Port A
Port B
LEDs
2wire 4wire
Tx +
Net+
Tx -Net-
n/c
Rx +
n/c
Rx -
Signal 
Ground
OpenProtocol
Commun ications
Port B
Run
Error 
CMnet receive 
CMnet transmit 
PortA receive 
PortA transmit 
PortBreceive 
Port B trans mit 
Aux1 
Aux2
Unit 1
+
EIA-232
RxTx
n/c 
485-2w 
485-4w
EIA-232
EIA-485
DTR
DCD
-
Tx
Rx
Communications
PortA
Unit 2
Tx-Rx
+
Unit3
Tx-Rx
+
ToRe duce 
TheRisk of
Fire or Elec tric
Shock, 
Do Not
Interconnect 
the Outputs of 
DifferentClass
2Circuits
Tx-Rx
Format 
Button
Options
Unit 4
+
Rotary Address
Switches
10's 1's
Format
Module
Address
SiteLink-12
Liebert
OpenE nergy
Management Eq uipment
R
88FO
E143900
TYPE: 003212
Unit 5
Unit 6
Unit 7
Rx
Tx-Rx
Tx
-
+
Tx
+
+
11 1/4"
28.58cm
Rx
Power 
Switch
Gnd and 
24VAC
Class 2
12VA, 0.5A
Use Copper
Auxiliary
Device
Port
Shield
Access
Port
Ground
24 Vac
On 
Off
Terminals
Keypad/ 
Display Port
Net -
Net +
CMnet Port
71/2"
19.05cm
Access Port
Power
24Vac, 50-60 Hz
Conductors On ly
TM
CMnet
ARC156K
9600/38.4K
CMnet Baud 
Rate Jumper
Unit 8
Unit 9
Unit 10
Unit 11
Unit 12
Tx-Rx
+
Rx
Tx-Rx
Tx
+
Tx-Rx
-
+
+
Tx-Rx
-
+
MODULE DIMENSIONS AND LAYOUT 
 Liebert Corporation           Page 2 of 5                    SL-27216 Rev. 4; 7/03 

 Specification for SiteLink-12 
COMMUNICATIONS WIRING DIAGRAM 
C M n e t
S h i eld
N
 e t
N e t
-
+
Net -
Ne t +
18-24 ga Twisted - Pair, Shielded, 
Low Impedance, Low Capacitanc 
Recommended wire is: 
Magnum Cable A3-ARC-156-2 
ENCLOSURE DIMENSIONS 
e
 Liebert Corporation           Page 3 of 5                    SL-27216 
Rev. 4; 7/03 

 Specification for SiteLink-12 
Enclosure Wall Mounting 
 Liebert Corporation           Page 4 of 5                    SL-27216 
Rev. 4; 7/03 Rev. 4; 7/03 

 Specification for SiteLink-12 
Enclosure Floor Mounting 
 Liebert Corporation           Page 5 of 5                    SL-27216 
Rev. 4; 7/03 Rev. 4; 7/03