• Two terminal connection cables with banana plugs and grippers
2.2
4Rosemount VeriCase
Check the verification sheet
Procedure
1. Open the Excel workbook found on the USB memory stick.
2. Check that the following details in the workbook correspond to the
printed certificate found inside the Rosemount Vericase:
• Serial number and calibration date
• Cable lengths
• Values for temperature correction table
Page 5
April 2019Quick Start Guide
2.3Power up the Rosemount VeriCase
The Rosemount VeriCase can be powered by either a 110V/220V power
supply or a 12VDC power adapter supplied with the Rosemount VeriCase. To
power up the Rosemount VeriCase and connect it to a transmitter head:
Procedure
1. Connect the power cable.
2. Screw the transmitter firmly onto the mount of the faceplate.
3. Insert the terminal connectors in the + and – terminals on the
faceplate and attach the other ends to the terminals of the
transmitter.
4. Connect the USB A-B cable between your computer and the
Rosemount VeriCase.
5. To start the verification procedure, the switch should be turned from
position 0 to position 1.
Quick Start Guide5
Page 6
Quick Start GuideApril 2019
3Verify the Rosemount 3308 transmitter
Prerequisites
1. Fill in the details in the Verification Data tab of the Excel workbook.
Record the serial number of the device from the nameplate of the
transmitter.
2. (Optional) Select the Imperial Units check box to enter data in inches
and Fahrenheit.
Note
There is a possible inaccuracy of 1.25 mm (0,05 in.) when inches are
used for the display.
Procedure
1. Start Instrument Inspector Application.
2. Under HART, double-click the device icon.
6Rosemount VeriCase
Page 7
April 2019Quick Start Guide
3. Make sure the cable switch on the Rosemount VeriCase is set to
position 1.
4. Select Service Tools→Routine Maintenance, and then select
Verification.
5. In the Verification window, select Next.
6. Enter the Distance and the Electronics Temperature, displayed on the
Verification window, to the Excel workbook.
Note
Make sure you convert the distance from meters to millimeters.
Quick Start Guide7
Page 8
Quick Start GuideApril 2019
7. Enter the VeriCase temperature, displayed on the device, to the Excel
workbook.
8. Switch to the next cable on the Rosemount VeriCase, and then select
Next.
9. Repeat Step 6-Step 8 for all six cable lengths.
10. When all the cables are measured, select Finish, and then select
Next.
8Rosemount VeriCase
Page 9
April 2019Quick Start Guide
11. After the configuration is restored, disconnect communication to the
transmitter.
Quick Start Guide9
Page 10
Quick Start GuideApril 2019
4Verify the Rosemount 5300 transmitter
Prerequisites
Open the Rosemount Radar Master and record the serial number and
firmware revision of the device to be tested in the Verification data tab of
the workbook. This information can be found in the Device Properties
window in the Device menu in Rosemount Radar Master.
Note
Inches or millimeters should be selected for measurement units (there is a
possible inaccuracy of 1.25 mm (0,05 in.) when inches are used for the
display).
Procedure
1. Configure device for verification.
a) Select Device→Backup Config to File… and save a backup
file of the current device.
The backup file needs to be reloaded once the verification is
complete.
b) Select Setup→Tank and configure the following parameters
for the transmitter that will be tested:
• Probe type: User Defined
• Probe length: Longest cable length +50 cm (20 in)
• Probe Impedance: 100 Ω
• Reference Pulse Amplitude: 3000 mV
10Rosemount VeriCase
Page 11
April 2019Quick Start Guide
c) Make sure that the below parameters are set with the
d) Save these configuration changes and restart the device.
2. Perform the verification test.
a) Set the cable switch to position 1. Wait for the values to
stabilize before taking a reading from the Device Display
window in Rosemount Radar Master.
b) Record the distance value, the internal temperature of
transmitter, and the Rosemount VeriCase temperature.
c) Repeat the procedure in 2.b for all six cable lengths in the
Rosemount VeriCase.
Quick Start Guide11
Page 12
Quick Start GuideApril 2019
Postrequisites
Once the verification is complete, restore the original configuration by
uploading the backup file to the transmitter.
4.1
Upload backup file to transmitter
Procedure
1. Select Device→Upload Config from File… and reload the saved file.
2. After the backup has been restored, disconnect power and
communication to the transmitter.
12Rosemount VeriCase
Page 13
April 2019Quick Start Guide
5Generate a report
Once testing is complete, a report can be generated from the Excel
workbook. It is possible to generate a verification report and/or a Q4
certificate.
Prerequisites
To generate a Q4 certificate, the analog output of the transmitter under
verification should be tested at 4 mA, 12 mA and 20 mA and the results
should be saved in the Q4 Data tab before generating the certificate.
Procedure
1. In the Verification Data tab, select the Export Verification Data
button to generate a verification report.
2. In the Q4 tab, select the Export Verification Data button to generate
a Q4 certificate.
Quick Start Guide13
Page 14
Quick Start GuideApril 2019
AFAQs
Q: Can verification of a FOUNDATION™ Fieldbus transmitter be performed
using the Rosemount VeriCase?
A: Yes, but an external FOUNDATION Fieldbus modem (and power supply if
explosion-proof) is required as the FOUNDATION Fieldbus modem is not
built into the Rosemount VeriCase.
Q: What do I do if a device fails?
A: Ensure the device is correctly configured and repeat the test. If the results
are the same, log a support request in the same way as you would do with
other level instrumentation, providing all the details of the test including the
results and the backup files.
Q: How do I know if a device has passed the test?
A: Refer to the Rosemount 5300 Product Data Sheet for accuracy
specifications. A device has passed if the final result is inside the combined
accuracy for the Rosemount 5300 and the Rosemount VeriCase as shown in
the Excel workbook.
Q: What does the offset value in the results mean? Do I need to adjust
anything in the guided wave radar settings?
A: The offset is generated from the Rosemount VeriCase rather than the
probe. This is compensated automatically and there is no need for manual
adjustments.
Q: Why is the transmitter rebooted every time I switch cable length?
A: The transmitter is rebooted so that the measurement can be reset to lock
on to a new value without echo logic or filtering affecting the measurement.
Q: How often should the Rosemount VeriCase be calibrated?
A: Once a year or if the calibration seals have been broken.
Q: The calibration of the Rosemount VeriCase has expired. What do I do?
A: Every world area has an assigned administrator to coordinate
recalibrations. Contact your administrator for further instructions.
14Rosemount VeriCase
Page 15
April 2019Quick Start Guide
Quick Start Guide15
Page 16
*00825-0500-4530*
00825-0500-4530, Rev. AD
Quick Start Guide
April 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.