Emerson Rosemount HART Modbus VeriCase 3308 Series, Rosemount HART Modbus VeriCase 5300 Series User Manual

Page 1
Quick Start Guide
00825-0500-4530, Rev AD
April 2019
Rosemount™ VeriCase User Guide
Rosemount 3308 and 5300 Series Level Transmitters with HART® and Modbus
Page 2
Quick Start Guide April 2019
Contents
Overview......................................................................................................................................3
Check contents and verification sheet.......................................................................................... 4
Verify the Rosemount 3308 transmitter....................................................................................... 6
Verify the Rosemount 5300 transmitter..................................................................................... 10
Generate a report.......................................................................................................................13
FAQs.......................................................................................................................................... 14
2 Rosemount VeriCase
Page 3
A
C
D
B
G
F
E
April 2019 Quick Start Guide

1 Overview

The Rosemount™ VeriCase is a mobile verification tool for the Rosemount 3308 and 5300 Level Transmitters with HART® and Modbus
®
communications.
The Rosemount VeriCase accuracy is within ±1 mm.
Figure 1-1 identifies the parts inside the case that you should be familiar with
before performing verification.
Note
The Rosemount VeriCase does not have any hazardous approvals certifications and should only be used outside of such classified areas.
Figure 1-1: Rosemount VeriCase
A. Transmitter mount B. Terminal connections C. Cable switch
D. Temperature display
E. Power input F. Ground connection
G. USB cable connection
Quick Start Guide 3
Page 4
Quick Start Guide April 2019

2 Check contents and verification sheet

2.1 Check contents

Procedure
Open the Rosemount VeriCase and check that it contains the following items:
USB stick containing
User Instructions
Microsoft® Excel® workbook
Calibration certificate
HART modem drivers
Rosemount Radar Master (for Rosemount 5300 Level Transmitter)
Instrument Inspector Application™ (for Rosemount 3308 Wireless Level
Transmitter)
Printed calibration parameters
Printed certificate
110/220V Power Supply
12 VDC Power Cable
USB A-B cable
Two terminal connection cables with banana plugs and grippers
2.2
4 Rosemount VeriCase

Check the verification sheet

Procedure
1. Open the Excel workbook found on the USB memory stick.
2. Check that the following details in the workbook correspond to the printed certificate found inside the Rosemount Vericase:
Serial number and calibration date
Cable lengths
Values for temperature correction table
Page 5
April 2019 Quick Start Guide

2.3 Power up the Rosemount VeriCase

The Rosemount VeriCase can be powered by either a 110V/220V power supply or a 12VDC power adapter supplied with the Rosemount VeriCase. To power up the Rosemount VeriCase and connect it to a transmitter head:
Procedure
1. Connect the power cable.
2. Screw the transmitter firmly onto the mount of the faceplate.
3. Insert the terminal connectors in the + and – terminals on the faceplate and attach the other ends to the terminals of the transmitter.
4. Connect the USB A-B cable between your computer and the Rosemount VeriCase.
5. To start the verification procedure, the switch should be turned from position 0 to position 1.
Quick Start Guide 5
Page 6
Quick Start Guide April 2019

3 Verify the Rosemount 3308 transmitter

Prerequisites
1. Fill in the details in the Verification Data tab of the Excel workbook. Record the serial number of the device from the nameplate of the transmitter.
2. (Optional) Select the Imperial Units check box to enter data in inches and Fahrenheit.
Note
There is a possible inaccuracy of 1.25 mm (0,05 in.) when inches are used for the display.
Procedure
1. Start Instrument Inspector Application.
2. Under HART, double-click the device icon.
6 Rosemount VeriCase
Page 7
April 2019 Quick Start Guide
3. Make sure the cable switch on the Rosemount VeriCase is set to position 1.
4. Select Service Tools Routine Maintenance, and then select Verification.
5. In the Verification window, select Next.
6. Enter the Distance and the Electronics Temperature, displayed on the Verification window, to the Excel workbook.
Note
Make sure you convert the distance from meters to millimeters.
Quick Start Guide 7
Page 8
Quick Start Guide April 2019
7. Enter the VeriCase temperature, displayed on the device, to the Excel workbook.
8. Switch to the next cable on the Rosemount VeriCase, and then select Next.
9. Repeat Step 6-Step 8 for all six cable lengths.
10. When all the cables are measured, select Finish, and then select Next.
8 Rosemount VeriCase
Page 9
April 2019 Quick Start Guide
11. After the configuration is restored, disconnect communication to the transmitter.
Quick Start Guide 9
Page 10
Quick Start Guide April 2019

4 Verify the Rosemount 5300 transmitter

Prerequisites
Open the Rosemount Radar Master and record the serial number and firmware revision of the device to be tested in the Verification data tab of the workbook. This information can be found in the Device Properties window in the Device menu in Rosemount Radar Master.
Note
Inches or millimeters should be selected for measurement units (there is a possible inaccuracy of 1.25 mm (0,05 in.) when inches are used for the display).
Procedure
1. Configure device for verification. a) Select Device Backup Config to File… and save a backup
file of the current device. The backup file needs to be reloaded once the verification is
complete.
b) Select Setup Tank and configure the following parameters
for the transmitter that will be tested:
Probe type: User Defined
Probe length: Longest cable length +50 cm (20 in)
Probe Impedance: 100 Ω
Reference Pulse Amplitude: 3000 mV
10 Rosemount VeriCase
Page 11
April 2019 Quick Start Guide
c) Make sure that the below parameters are set with the
following values:
Propagation Factor: 1,000
Tank Connection Length: 0
Remote housing: None
Probe angle: 0
Vapor DC: 1
Measurement mode: Liquid product level, solid product
level or product level and interface level
d) Save these configuration changes and restart the device.
2. Perform the verification test. a) Set the cable switch to position 1. Wait for the values to
stabilize before taking a reading from the Device Display window in Rosemount Radar Master.
b) Record the distance value, the internal temperature of
transmitter, and the Rosemount VeriCase temperature.
c) Repeat the procedure in 2.b for all six cable lengths in the
Rosemount VeriCase.
Quick Start Guide 11
Page 12
Quick Start Guide April 2019
Postrequisites
Once the verification is complete, restore the original configuration by uploading the backup file to the transmitter.
4.1

Upload backup file to transmitter

Procedure
1. Select Device Upload Config from File… and reload the saved file.
2. After the backup has been restored, disconnect power and communication to the transmitter.
12 Rosemount VeriCase
Page 13
April 2019 Quick Start Guide

5 Generate a report

Once testing is complete, a report can be generated from the Excel workbook. It is possible to generate a verification report and/or a Q4 certificate.
Prerequisites
To generate a Q4 certificate, the analog output of the transmitter under verification should be tested at 4 mA, 12 mA and 20 mA and the results should be saved in the Q4 Data tab before generating the certificate.
Procedure
1. In the Verification Data tab, select the Export Verification Data button to generate a verification report.
2. In the Q4 tab, select the Export Verification Data button to generate a Q4 certificate.
Quick Start Guide 13
Page 14
Quick Start Guide April 2019

A FAQs

Q: Can verification of a FOUNDATION™ Fieldbus transmitter be performed using the Rosemount VeriCase?
A: Yes, but an external FOUNDATION Fieldbus modem (and power supply if explosion-proof) is required as the FOUNDATION Fieldbus modem is not built into the Rosemount VeriCase.
Q: What do I do if a device fails?
A: Ensure the device is correctly configured and repeat the test. If the results are the same, log a support request in the same way as you would do with other level instrumentation, providing all the details of the test including the results and the backup files.
Q: How do I know if a device has passed the test?
A: Refer to the Rosemount 5300 Product Data Sheet for accuracy specifications. A device has passed if the final result is inside the combined accuracy for the Rosemount 5300 and the Rosemount VeriCase as shown in the Excel workbook.
Q: What does the offset value in the results mean? Do I need to adjust anything in the guided wave radar settings?
A: The offset is generated from the Rosemount VeriCase rather than the probe. This is compensated automatically and there is no need for manual adjustments.
Q: Why is the transmitter rebooted every time I switch cable length?
A: The transmitter is rebooted so that the measurement can be reset to lock on to a new value without echo logic or filtering affecting the measurement.
Q: How often should the Rosemount VeriCase be calibrated?
A: Once a year or if the calibration seals have been broken.
Q: The calibration of the Rosemount VeriCase has expired. What do I do?
A: Every world area has an assigned administrator to coordinate recalibrations. Contact your administrator for further instructions.
14 Rosemount VeriCase
Page 15
April 2019 Quick Start Guide
Quick Start Guide 15
Page 16
*00825-0500-4530*
00825-0500-4530, Rev. AD
Quick Start Guide
April 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRF@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
©
2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...