Emerson Rosemount 8750WA Quick Installation Manual

Quick Installation Guide
Start
(Flanged Sensors)
(Wafer Sensors) Step 5: Grounding Step 6: Wiring Step 7: Basic Configuration Product Certifications
End
00825-0100-4750, Rev BB January 2013
Rosemount 8750WA
Rosemount 8750WA Magnetic Flowmeter System (Transmitter and Sensor)
www.rosemount.com
¢00825-0100-4725.¤
Quick Installation Guide
IMPORTANT NOTICE
WARNING
WARNING
Emerson Process Management Rosemount Flow
7070 Winchester Circle, Boulder, CO 80301 Tel (USA) 800 522 6277 Tel (International) +1 (303) 527 5200 Fax +1 (303) 530 8459
00825-0100-4750, Rev BB
Rosemount 8750WA
© 2013 Rosemount Inc. All rights reserved. All marks property of owner.
This installation guide provides basic guidelines for the Rosemount® 8750WA. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flame-proof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 8750WA reference manual (document number 00809-0100-4750) for more instructions. The manual and this QIG are also available electronically on www.rosemount.com.
January 2013
Failure to follow these installation guidelines could result in death or serious injury:
Installation and servicing instructions are for use by qualified personnel only. Do not perform any servicing other than that contained in the operating instructions, unless qualified. Verify that the operating environment of the sensor and transmitter is consistent with the appropriate FM or CSA approval.
The sensor liner is vulnerable to handling damage. Never place anything through the sensor for the purpose of lifting or gaining leverage. Liner damage can render the sensor useless.
To avoid possible damage to the sensor liner ends, do not use metallic or spiral-wound gaskets. If frequent removal is anticipated, take precautions to protect the liner ends. Short spool pieces attached to the sensor ends are often used for protection.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be tightened in the proper sequence to the specified torque limits. Failure to observe these instructions could result in severe damage to the sensor lining and possible sensor replacement.
2
Quick Installation Guide
STEP 1: PRE-INSTALLATION
5.82
(148)
6.48 (165)
7.49 (190)
LOI Cover
4.97
(126)
8.81
(224)
3.00 (76)
3.07 (78)
4.97
(126)
1
/2”-14 NPT* (3 places)
1
/2”-14 NPT, (2 places)*
00825-0100-4750, Rev BB January 2013
Rosemount 8750WA
Before installing the Rosemount 8750WA Magnetic Flowmeter Transmitter, there are several pre-installation steps that should be completed to make the installation process easier:
• Identify the options and configurations that apply to your application
• Set the hardware switches if necessary
• Consider mechanical, electrical, and environmental requirements
Mechanical Considerations
The mounting site for the Rosemount 8750WA transmitter should provide enough room for secure mounting, easy access to conduit ports, full opening of the transmitter covers, and easy readability of the LOI screen (see Figure 1 and Figure 2).
If the Rosemount 8750WA transmitter is mounted separately from the sensor, it is not subject to limitations that might apply to the sensor.
Figure 1. Rosemount 8750WA32E Dimensional Drawing
NOTE:
*M20 and PG 13.5 connections are available with the use of threaded conduit adapters.
3
Rosemount 8750WA
4.31
(109)
LOI Keypad
Cover
9.01
(229)
11.15 (283)
2.81 (71)
3.11 (79)
12.02 (305)
0.44 (11)
Ground Lug
1
/2–14 NPT
Conduit
Connection
(4 Places)
WITH STANDARD COVER
NOTE
Dimensions are in inches (millimeters)
2.96 (75)
WITH LOI COVER
Figure 2. 8750WA12E Dimensional Drawing
Quick Installation Guide
00825-0100-4750, Rev BB
January 2013
4
Quick Installation Guide
STEP 1 CONTINUED...
00825-0100-4750, Rev BB January 2013
Rosemount 8750WA
Environmental Considerations
To ensure maximum transmitter life, avoid excessive heat and vibration. Typical problem areas:
• high-vibration lines with integrally mounted transmitters
• warm-climate installations in direct sunlight
• outdoor installations in cold climates. Remote-mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and provide easy access for configuration or service.
Both remotely and integrally mounted Rosemount 8750WA transmitters require external power so there must be access to a suitable power source.
Installation Procedures
Rosemount 8750WA installation includes both detailed mechanical and electrical installation procedures.
Mount the Transmitter
At a remote site the transmitter may be mounted on a pipe up to two inches in diameter or against a flat surface.
Pipe Mounting
To mount the transmitter on a pipe:
1. Attach the mounting bracket to the pipe using the mounting hardware.
2. Attach the Rosemount 8750WA transmitter to the mounting bracket using the mounting
screws.
Identify Options and Configurations
The standard application of the 8750WA includes a 4–20 mA output and control of the sensor coils and electrodes. Other applications may require one or more of the following configurations or options:
• Multidrop Communications
• Digital Output
• Digital Input
• Pulse Output Additional options may apply . Be sure to identify those options and configurations that apply to your situation and keep a list of them nearby for consideration during the installation and configuration procedures.
5
Quick Installation Guide
STEP 1 CONTINUED...
00825-0100-4750, Rev BB
Rosemount 8750WA
January 2013
Hardware Jumpers/Switches
The 8750WA electronics board is equipped with three or four user-selectable hardware switches depending on the transmitter model ordered. These switches set the Failure Alarm Mode, Internal/External Analog Power, Internal/External Pulse Power (8750WA32), and Transmitter Security. The standard configuration for these switches when shipped from the factory is as follows:
Failure Alarm Mode: HIGH Internal/External Analog Power: INTERNAL Internal/External Pulse Power: EXTERNAL (8750WA32 only) Transmitter Security: OFF
Changing Hardware Switch Settings
In most cases, it is not necessary to change the setting of the hardware switches. If you need to change the switch settings, complete the steps outlined in the manual.
Electrical Considerations
Before making any electrical connections to the Rosemount 8750WA, consider the local and plant electrical standards and be sure to have the proper power supply, conduit, and other accessories.
Rotate Transmitter Housing
The integral electronics housing can be rotated on the sensor in 90° increments by loosening the four mounting bolts on the bottom of the housing, and reinstalling the bolts. When reinstalling the housing, be sure the surface is clean and there is no gap between the housing and the sensor.
6
Quick Installation Guide
STEP 2: HANDLING
½- through 4-Inch Sensors
6-Inch and Larger Sensors
00825-0100-4750, Rev BB January 2013
Handle all parts carefully to prevent damage. Whenever possible, transport the system to the installation site in the original shipping containers. PTFE-lined sensors are shipped with end covers that protect it from both mechanical damage and normal unrestrained distortion. Remove the end covers just before installation.
Figure 3. Rosemount 8750WA Flanged Sensor Support for Handling
Rosemount 8750WA
7
Quick Installation Guide
STEP 3: MOUNTING
5 Pipe Diameters
2 Pipe Diameters
Flow
00825-0100-4750, Rev BB
Rosemount 8750WA
January 2013
Upstream/Downstream Piping
To ensure specification accuracy over widely varying process conditions, install the sensor a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane (see Figure 4).
Figure 4. Upstream and Downstream Straight Pipe Diameters
The 8750WA sensor may be installed with as few as zero pipe diameters upstream. Consult the factory for performance in applications with less than ideal straight runs.
Flow Direction
The sensor should be mounted so the FORWARD end of the flow arrow, shown on the sensor identification tag, points in the direction of flow through the sensor.
Sensor Orientation
The sensor should be installed in a position that ensures the sensor remains full during operation. Vertical installation allows upward process fluid flow and keeps the cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted to low piping sections that are normally full. In these cases, orient the electrode plane to within 45 degrees of horizontal.
8
Quick Installation Guide
STEP 3 CONTINUED...
FLOW
FLOW
45° Electrode Plane
45° Electrode Plane
00825-0100-4750, Rev BB January 2013
Figure 5. Sensor Orientation
Rosemount 8750WA
The electrodes in the Rosemount 8750WA flanged sensor are properly orientated when the two measurement electrodes are in the 3 and 9 o’clock positions, as shown on the right of Figure 5.
The electrodes in the Rosemount 8750WA wafer sensor are properly orientated when the top of the sensor is either vertical or horizontal, as shown in Figure 6. Avoid any mounting orientation that positions the top of the sensor at 45° from the vertical or horizontal position.
Figure 6. Rosemount 8750WA Wafer Sensor Mounting Position
9
Quick Installation Guide
STEP 4: INSTALLATION
00825-0100-4750, Rev BB
Rosemount 8750WA
January 2013
Flanged Sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Metallic or spiral-wound gaskets can damage the liner. Gaskets are required on each side of a grounding ring. All other applications (including sensors with lining protectors or a grounding electrode) require only one gasket on each end connection.
Figure 7. Flanged gasket placement
Flange Bolts
Suggested torque values by sensor line size and liner type are listed in Table 1 on page 11. Consult the factory if the flange rating of the sensor is not listed. Tighten flange bolts on the upstream side of the sensor in the incremental sequence shown in Figure 8 on page 11 to 20% of the suggested torque values. Repeat the process on the downstream side of the sensor. For sensors with more or less flange bolts, tighten the bolts in a similar crosswise sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of the suggested torque values or until the leak between the process and sensor flanges stop.
If leakage has not stopped at the suggested torque values, the bolts can be tightened in additional 10% increments until the joint stops leaking, or until the measured torque value reaches the maximum torque value of the bolts. Practical consideration for the integrity of the liner often leads the user to distinct torque values to stop leakage due to the unique combinations of flanges, bolts, gaskets, and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct tightening methods can result in severe damage. Sensors require a second tightening 24 hours after the initial installation. Over time, sensor liner materials may deform under pressure.
10
Quick Installation Guide
00825-0100-4750, Rev BB January 2013
Figure 8. Flange Bolt Torquing Sequence
Table 1. Suggested Flange Bolt Torque Values for ASME B16.5 (ANSI) Flanged Sensors
PTFE Liner Polyurethane/Neoprene liner
Size
Code
Line Size
005 0.5 inch (15 mm) 8 8 - ­010 1 inch (25 mm) 8 12 - ­015 1.5 inch (40 mm) 13 25 7 18 020 2 inch (50 mm) 19 17 14 11 030 3 inch (80 mm) 34 35 23 23 040 4 inch (100 mm) 26 50 17 32 060 6 inch (150mm) 45 50 30 37 080 8 inch (200 mm) 60 82 42 55 100 10 inch (250 mm) 55 80 40 70 120 12 inch (300 mm) 65 125 55 105 140 14 inch (350 mm) 85 110 70 95 160 16 inch (400 mm) 85 160 65 140 180 18 inch (450 mm) 120 170 95 150 200 20 inch (500 mm) 110 175 90 150 240 24 inch (600 mm) 165 280 140 250 300 30 inch (750 mm) 195 360 36 inch (900 mm) 280 400 40 inch (1000 mm) - - ­420 42 inch (1050 mm) - - ­480 48 inch (1200 mm) - - -
(1) Sensors ordered with flange option code “A1” use MSS-SP44 Class 150 flanges. (2) Sensors ordered with flange option code “AA” use AWWA Table D flanges
Sensors ordered with flange option code “AB” use AWWA Table E flanges
(3) Neoprene Liner only
Class 150
(pound-feet)
(1)(2) (1)(2)
Class 300
(pound-feet)
- 165
- 245
Rosemount 8750WA
Class 150
(pound-feet)
(1)(2)
(1)(2) (2)(3) (2)(3) (2)(3)
Class 300
(pound-feet)
-
-
-
-
-
11
Quick Installation Guide
00825-0100-4750, Rev BB
Rosemount 8750WA
January 2013
Wafer Sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Metallic or spiral-wound gaskets can damage the liner. Gaskets are required on each side of a grounding ring. See Figure 9 below.
Figure 9. Wafer gasket placement
Spacer Installation
Horizontal meters
Vertical meters
O-ring
Alignment
1. On 1.5 - through 8-inch (40 through 200 mm) line sizes. Rosemount strongly recommends installing the alignment spacers provided to insure proper centering of the wafer sensor between the process flanges. The smaller line sizes, 0.5 and 1 in. (15 and 25 mm), do not require alignment spacers.
2. Insert studs for the bottom side of the sensor between the pipe flanges and center the alignment spacer in the middle of the stud. See Figure 9 for the bolt hole locations recommended for the spacers provided. Stud specifications are listed in Table 2.
3. Place the sensor between the flanges. Make sure that the alignment spacers are properly centered on the studs. For vertical flow installations slide the oring over the stud to keep the spacer in place. See Figure 9. To ensure the spacers match the flange size and class rating for the process flanges see Table 3.
4. Insert the remaining studs, washers, and nuts.
5. Tighten to the torque specifications shown in Table 4 on page 13. Do not overtighten the bolts or the liner may be damaged.
Table 2. Stud Specifications
Nominal Sensor Size Stud Specifications
0.5 – 1 inch (15 – 25 mm) 316 SST ASTM A193, Grade B8M Class 1 threaded mounted studs
1.5 – 8 inch (40 – 200 mm) CS, ASTM A193, Grade B7, threaded mounting studs
NOTE
Using carbon steel bolts on smaller line sizes, 0.5 and 1 in. (15 and 25 mm), rather than the required stainless steel bolts, will degrade performance.
12
Loading...
+ 26 hidden pages