Declaration of conformity.......................................................................................................... 32
China RoHS................................................................................................................................ 34
2Rosemount 848T
Page 3
May 2019Quick Start Guide
1About this guide
This guide provides basic guidelines for the Rosemount™ 848T Temperature
Transmitter. It does not provide instructions for detailed configuration,
diagnostics, maintenance, service, troubleshooting. Refer to the Rosemount
848T Reference Manual for more instruction. The manual and this guide are
also available electronically on Emerson.com/Rosemount
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in
accordance with the appropriate local, national, and international standards,
codes, and practices. Review the approvals section of this manual for any
restrictions associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere,
make sure the instruments in the loop are installed in accordance with
intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
Physical access
• Unauthorized personnel may potentially cause significant damage to
and/or misconfiguration of end users’ equipment. This could be
intentional or unintentional and needs to be protected against.
• Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by
unauthorized personnel to protect end users’ assets. This is true for all
systems used within the facility.
CAUTION
This device complies with Part 15 of the FCC Rules. Operation is subject
to the following conditions:
• This device may not cause harmful interference.
• This device must accept any interference received, including
interference that may cause undesired operation.
• This device must be installed to ensure a minimum antenna separation
distance of 20 cm from all persons.
Quick Start Guide3
Page 4
Quick Start GuideMay 2019
NOTICE
Battery hazards remain when cells are discharged.
The power module may be replaced in a hazardous area. The power module
has surface resistivity greater than one gigaohm and must be properly
installed in the wireless device enclosure. Care must be taken during
transportation to and from the point of installation to prevent electrostatic
charge build-up.
Shipping considerations for wireless products.
• The unit was shipped to you without the power module installed.
Remove the power module prior to shipping.
• Each power module contains two “C” size primary lithium batteries.
Primary lithium batteries are regulated in transportation by the U. S.
Department of Transportation, and are also covered by IATA
(International Air Transport Association), ICAO (International Civil
Aviation Organization), and ARD (European Ground Transportation of
Dangerous Goods). It is the responsibility of the shipper to ensure
compliance with these or any other local requirements. Consult current
regulations and requirements before shipping.
4Rosemount 848T
Page 5
A
B
C
May 2019Quick Start Guide
2Mount the transmitter
2.1Mount to a DIN rail without a junction box
Procedure
1. Pull up the DIN rail mounting clip located on the top back side of the
transmitter.
2. Hinge the DIN rail into the slots on the bottom of the transmitter.
3. Tilt the Rosemount™ 848T and place onto the DIN rail.
4. Release the mounting clip.
Figure 2-1: Mounting the Rosemount 848T to a DIN Rail
A. Rosemount 848T without installed enclosure
B. DIN rail
C. DIN rail mounting clip
Quick Start Guide5
Page 6
A
B
C
A
B
C
Quick Start GuideMay 2019
2.2Mount to a panel with a junction box
Figure 2-2: Aluminum/Plastic Junction Box
A. Aluminum or plastic junction box
B. Mounting screws (4)
C. Panel
Figure 2-3: Stainless Steel Junction Box
A. Stainless steel junction box
B. Mounting screws (2)
C. Panel
(1)
(1)
(1) Mount using four ¼–20 x 1.25-in. screws.
6Rosemount 848T
Page 7
5.1
(130)
10.2
(260)
6.6
(167)
4.7 (114)
7.5 (190)
May 2019Quick Start Guide
2.3Mount to a 2-in. pipe stand
Prerequisites
Use the optional mounting bracket (option code B6) to attach the
Rosemount™ 848T to a 2-in. pipe stand when using a junction box.
1. Remove the four cover screws to remove the junction box cover.
2. Run the sensor and power/signal wires through the appropriate preinstalled cable glands.
3. Install the sensor wires into the correct screw terminals.
4. Attach the FOUNDATION™ Fieldbus wires to the screw terminals.
5. Replace the FOUNDATION Fieldbus cover and tighten all cover screws.
Quick Start Guide9
Page 10
F
A
B
C
D
E
Quick Start GuideMay 2019
3.2Using conduit entries
Figure 3-2: Conduit Entries
A. Sensor 1 and 2
B. Sensor 3 and 4
C. Sensor 5 and 6
D. Sensor 7 and 8
E. Power/signal
F. Cover screw
Procedure
1. Unscrew the four cover screws to remove the junction box cover.
2. Remove the five conduit plugs and install the user-supplied conduit
fittings.
3. Run pairs of sensor wires through each conduit fitting.
4. Install the sensor wires into the correct screw terminals.
5. Attach the FOUNDATION™ Fieldbus wires to the screw terminals.
6. Replace the enclosure cover and tighten all cover screws.
3.3
Sensor wiring and power supply
• Compatible with eight independently configurable channels including
combinations of 2- and 3-wire RTDs, thermocouples, mV, ohm, and mA
sensors.
• All sensor and power terminals are rated to 42.4 Vdc.
• FOUNDATION Fieldbus network powered with a terminal voltage of 9.0–
32.0 Vdc and 22 mA maximum current draw.
• For best network performance twisted, shielded pair cabling should be
used. Proper gage wire should be selected to maintain the 9.0 Vdc
minimum.
10Rosemount 848T
Page 11
111122223333
May 2019Quick Start Guide
Figure 3-3: Sensor Wiring Diagrams
2-wire RTD and
Ohms
(1) Emerson provides 4-wire sensors for all single-element RTDs. Use these RTDs in
3-wire configurations by clipping the fourth lead or leaving it disconnected and
insulated with electrical tape.
(2) The transmitter must be configured for a 3-wire RTD in order to recognize an
RTD with a compensation loop.
3-wire RTD and
Ohms
(1)
Thermocouples/
Ohms and
millivolts
2-Wire RTD with
compensation
(2)
loop
The wiring of 3-wire RTDs for this unit is different than some earlier
Rosemount™ 848T models. Pay careful attention to the wiring diagram on
the label, especially if this unit is replacing an older unit.
Quick Start Guide11
Page 12
A
C
B
Quick Start GuideMay 2019
3.4Wiring analog inputs
Figure 3-4: Rosemount™ 848T Analog Input Wiring Diagram
A. Analog input connectors
B. Analog transmitters
C. Power supply
3.5
12Rosemount 848T
Typical configuration for FOUNDATION Fieldbus networking
Note
Each segment in a FOUNDATION™ Fieldbus trunk must be terminated at both
ends.
Page 13
A
BC
D
EE
F
May 2019Quick Start Guide
A. 6234 ft. (1900 m) max (depending upon cable characteristics)
B. Integrated power conditioner and filter
C. Terminators
D. Trunk
E. Sput
F. Signal wiring
3.5.1Ground the transmitter
Proper ground is crucial to reliable temperature readings.
3.5.2Ungrounded thermocouple, mV, and RTD/Ohm inputs
Option 1
Procedure
1. Connect FOUNDATION™ Fieldbus signal wiring shield to the sensor
wiring shield(s).
2. Ensure the shields are tied together and electrically isolated from the
transmitter enclosure.
3. Only ground the shield at the power supply end.
4. Ensure that the sensor shield(s) is electrically isolated from the
surrounding grounded fixtures.
Quick Start Guide13
Page 14
A
B
C
D
A
B
C
D
Quick Start GuideMay 2019
A. Sensor wires
B. Rosemount™ 848T
C. Power supply
D. Shield ground point
Option 2
Procedure
1. Connect sensor wiring shield(s) to the transmitter enclosure (only if
the enclosure is grounded).
2. Ensure the sensor shield(s) is electrically isolated from surrounding
fixtures that may be grounded.
3. Ground FOUNDATION™ Fieldbus signal wiring shield at the power
supply end.
A. Sensor wires
B. Rosemount™ 848T
C. Power supply
D. Shield ground point
3.5.3Grounded thermocouple inputs
Procedure
1. Ground sensor wiring shield(s) at the sensor.
2. Ensure the sensor wiring and FOUNDATION™ Fieldbus signal wiring
shields are electrically isolated from the transmitter enclosure.
3. Do not connect the FOUNDATION Fieldbus signal wiring shield to the
sensor wiring shield(s).
14Rosemount 848T
Page 15
A
B
C
D
A
CD
F
G
B
E
May 2019Quick Start Guide
4. Ground FOUNDATION Fieldbus signal wiring shield at the power supply
end.
A. Sensor wires
B. Rosemount™ 848T
C. Power supply
D. Shield ground point
3.6Analog device inputs
Procedure
1. Ground analog signal wire at the power supply of the analog devices.
2. Ensure the analog signal wire and the FOUNDATION™ Fieldbus signal
wire shields are electrically isolated from the transmitter enclosure.
3. Do not connect the analog signal wire shield to the FOUNDATION
Fieldbus signal wire shield.
A. Analog device power supply
B. 4–20 mA loop
C. Analog device
D. Rosemount™ 848T
E. FOUNDATION Fieldbus
F. Power supply
G. Shield ground points
3.6.1Transmitter enclosure (optional)
Ground in accordance with local electrical requirements.
Quick Start Guide15
Page 16
Quick Start GuideMay 2019
4Verify the tag
The Rosemount 848T has a removable commissioning
tag that contains both the Device ID (the unique code
that identifies a particular device in the absence of a
device tag) and a space to record the device tag (the
operational identification for the device as defined by
the Piping and Instrumentation Diagram [P&ID]).
When commissioning more than one device on a
FOUNDATION™ Fieldbus segment, it can be difficult to
identify which device is at a particular location. The
removable tag aids in this process by linking the
Device ID to physical location. The installer should
note the physical location of the transmitter on both
the upper and lower location of the commissioning
tag. The bottom portion should be torn off for each
device on the segment and used for commissioning
the segment in the control system.
16Rosemount 848T
Page 17
May 2019Quick Start Guide
5Verify the transmitter configuration
Each FOUNDATION™ Fieldbus host or configuration tool has a different way of
displaying and performing configurations. Some use Device Descriptions
(DD) or DD wizards for configuration and to display data consistently across
platforms. There is no requirement that a host or configuration tool support
these features.
The following is the minimum configuration requirement for a temperature
measurement. This guide is designed for systems not using DD wizards. For
a complete list of parameters and configuration information refer to the
Rosemount™ 848T Reference Manual.
Quick Start Guide17
Page 18
Quick Start GuideMay 2019
6Product certifications
Rev 2.12
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
Ordinary Location Certification from FM Approvals
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by FM Approvals, a nationally recognized test laboratory
(NRTL) as accredited by the Federal Occupational Safety and Health
Administration (OSHA).
North America
The US National Electrical Code™ (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
6.1U.S.A
6.1.1I5 FM Intrinsically Safe and Nonincendive
Certificate
Standards
Markings
Note
Transmitters marked with Nonincendive CL I, DV 2 can be installed in
Division 2 locations using general Division 2 wiring methods or
Nonincendive Field Wiring (NIFW). See Drawing 00848-4404.
6.1.2IE FM FISCO
Certificate
18Rosemount 848T
3011568
FM Class 3600:1998, FM Class 3610:2010, FM Class
3611:2004, FM Class 3810:2005, ANSI/ISA 60079-0:2009,
ANSI/ISA 60079-11:2009, NEMA 250:1991, IEC 60529:2011
IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +60 °C); NI CL I,
DIV 2, GP A, B, C, D; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50 °C ≤ T
≤ +70 °C) when installed per Rosemount™ drawing
00848-4404.
3011568
a
Page 19
May 2019Quick Start Guide
Standards
FM Class 3600:1998, FM Class 3610:2010, FM Class
3611:2004, FM Class 3810:2005, ANSI/ISA 60079-0:2009,
ANSI/ISA 60079-11:2009, NEMA 250:1991, IEC 60529:2011
Markings
IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +60 °C); NI CL I,
DIV 2, GP A, B, C, D; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50 °C ≤ T
≤ +70 °C) when installed per Rosemount™ drawing
00848-4404.
6.1.3N5 Nonincendive and Dust-Ignitionproof
Certificate
Standards
Markings
3011568
FM Class 3600:1998, FM Class 3611:2004, FM Class
3810:2005, ANSI/ISA 60079-0:2009, NEMA 250:1991, IEC
60529:2011
NI CL I, DIV 2, GP A, B, C, D; DIP CL II/III, DIV 1, GP E, F, G; T4A(–
50 °C ≤ Ta ≤ +85 °C); T5(–50 °C ≤ Ta ≤ +70 °C) when installed
per Rosemount™ drawing 00848-4404; Type 4X
6.1.4NK Nonincendive
Certificate
Standards
Markings
3011568
FM Class 3600:1998, FM Class 3611:2004, FM Class
3810:2005, ANSI/ISA 60079-0:2009, NEMA 250:1991, IEC
60529:2001
NI CL I, DIV 2, GP A, B, C, D; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50
°C ≤ Ta ≤ +70 °C) when installed per Rosemount™ drawing
00848-4404
a
Note
Only the N5 and NK are valid with the S002 option.
Explosionproof for Class I, Division 1, Groups B, C, and D; T4(–
40 °C ≤ Ta ≤ +40 °C) when installed per Rosemount drawing
00848-1041; Dust-Ignitionproof for Class II, Division 1, Groups
E, F, and G; Class III; Class I, Division 2, Groups A, B, C, and D;
T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405; Conduit Seal Required
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D;
T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405; Class I, Division 2, Groups A, B, C, D;
T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D;
T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405; Class I, Division 2, Groups A, B, C, D;
T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405
Page 21
May 2019Quick Start Guide
6.2.4N6 CSA Division 2 and Dust-Ignitionproof (enclosure required)
Class I, Division 2, Groups A, B, C, and D; T3C(–50 °C ≤ Ta ≤ +60
°C) when installed per Rosemount drawing 00848-4405; DustIgnitionproof for Class II, Division 1, Groups E, F, and G; Class
III; Conduit Seal Required
6.3Europe
6.3.1I1 ATEX Intrinsic Safety
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a
Baseefa09ATEX0093X
EN 60079-0:2012, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–50 °C ≤ Ta ≤ +60 °C) when installed
per drawing 00848-4406
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards and light alloy or
zirconium enclosures must be protected from impact and friction
when installed.
2. The equipment is not capable of withstanding the 500 V insulation
test required by EN 60079-11:2011, clause 6.3.13. This must be
taken into account when installing the equipment.
Fieldbus (input)
Ui = 30 VUO = 12.5 V
Ii = 300 mAIO = 4.8 mA
Pi = 1.3 WPO = 15 mW
Ci = 2.1 nFCO = 1.2 μF
Li = 0LO = 1 H
Quick Start Guide21
Sensor field terminal (output)
Page 22
Quick Start GuideMay 2019
6.3.2IA ATEX FISCO Intrinsic Safety
Certificate
Standards
Markings
Baseefa09ATEX0093X
EN 60079-0:2012, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–50 °C ≤ Ta ≤ +60 °C) when installed
per drawing 00848-4406
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards and light alloy or
zirconium enclosures must be protected from impact and friction
when installed.
2. The equipment is not capable of withstanding the 500 V insulation
test required by EN 60079-11:2011, clause 6.3.13. This must be
taken into account when installing the equipment.
FISCO (input)Sensor field terminal (output)
Ui = 17.5 VUO = 12.5 V
Ii = 380 mAIO = 4.8 mA
Pi = 5.32 WPO = 15 mW
Ci = 2.1 nFCO = 1.2 μF
Li = 0LO = 1 H
6.4International
6.4.1I7 IECEx Intrinsic Safety
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. The apparatus must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards and light alloy or
zirconium enclosures must be protected from impact and friction
when installed.
22Rosemount 848T
IECEx BAS 09.0030X
IEC 60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (–50 °C ≤ Ta ≤ +60 °C)
Page 23
May 2019Quick Start Guide
2. The apparatus is not capable of withstanding the 500 V insulation
test required by IEC 60079-11:2011, clause 6.3.13. This must be
taken into account when installing the appartus.
6.4.2IG IECEx FISCO Intrinsic Safety
Certificate
Standards
Markings
IECEx BAS 09.0030X
IEC 60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +60 °C)
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards and light alloy or
zirconium enclosures must be protected from impact and friction
when installed.
2. The equipment is not capable of withstanding the 500 V insulation
test required by EN 60079-11:2012, clause 6.3.13. This must be
taken into account when installing the equipment.
FISCO (input)Sensor field terminal (output)
Ui = 17.5 VUO = 12.5 V
Ii = 380 mAIO = 4.8 mA
Pi = 5.32 WPO = 15 mW
Ci = 2.1 nFCO = 1.2 μF
Li = 0LO = 1 H
6.4.3N7 IECEx Type n (with enclosure)
Certificate:
Standards:
Markings:
IECEx BAS 09.0032X
IEC 60079-0:2004, IEC 60079-15:2005
Ex nA nL IIC T5(–40 °C ≤ Ta ≤ +65 °C)
Special Conditions for Safe Use (X):
1. Provision must be made, external to the apparatus, to ensure the
rated voltage of the apparatus supply is not exceeded by transient
disturbances of more than 40%.
2. The electrical circuit is connected directly to earth; this must be
taken into account when installing the apparatus.
Quick Start Guide23
Page 24
Quick Start GuideMay 2019
6.4.4NJ IECEx Type n (without enclosure)
Certificate:
Standards:
Markings:
IECEx BAS 09.0031U
IEC 60079-0:2004, IEC 60079-15:2005
Ex nA nL IIC T4 (–50 °C ≤ Ta ≤ +85 °C), T5(–50 °C ≤ Ta ≤ +70 °C)
Schedule of Limitations (U):
1. The component must be installed in a suitable component certified
enclosure that provides a degree of protection of at least IP54 and
meets the relevant material and environmental requirements of IEC
60079-0: 2004 and IEC 60079-15: 2005.
2. Provision must be made, external to the component, to ensure the
rated voltage of the component supply is not exceeded by transient
disturbances of more than 40%.
3. The electrical circuit is connected directly to earth; this must be
taken into account when installing the apparatus.
1. The apparatus must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards (see manufacturer's
instructions manual) and light alloy or zirconium enclosures must be
protected from impact and friction when installed.
2. The apparatus is not capable of withstanding the 500 V isolation test
required by ABNT NBR IEC 60079-11. This must be taken into
account when installing the apparatus --- see manufacturer's
instructions manual.
1. The apparatus must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must
be suitable to prevent electrostatic hazards (see manufacturer's
instructions manual) and light alloy or zirconium enclosures must be
protected from impact and friction when installed.
2. The apparatus is not capable of withstanding the 500 V isolation test
required by ABNT NBR IEC 60079-11. This must be taken into
account when installing the apparatus --- see manufacturer's
instruction manual.
6.9.1IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Markings
Special Condition for Safe Use (X):
See certificate for special conditions.
[FOUNDATION Fieldbus]: 0Ex ia IIC T4 Ga X, T4(–50 °C ≤ Ta ≤ +60
°C)
See certificate for entity parameters.
6.9.2IN Technical Regulation Customs Union (EAC) FISCO
Markings:
Special Condition for Safe Use (X):
See certificate for special conditions.
[FISCO]: 0Ex ia IIC T4 Ga X, T4(–50 °C ≤ Ta≤ +60 °C)
See certificate for entity parameters.
6.10Combinations
KG
Combination of I1/IA, I5/IE, I6/IF, and I7/IG
6.11Conduit Plugs and Adapters
ATEX Flameproof and Increased Safety
Certificate
Standards
Markings:
FM13ATEX0076X
EN 60079-0:2012, EN 60079-1:2007, IEC 60079-7:2007
2 G Ex de IIC Gb
Special Conditions for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure
in type of protection increased safety “e” the entry thread shall be
suitably sealed in order to maintain the ingress protection rating (IP)
of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric
thread forms. G½ and PG 13.5 thread forms are only acceptable for
existing (legacy) equipment installations.
1. When the thread adapter or blanking plug is used with an enclosure
in type of protection increased safety “e” the entry thread shall be
suitably sealed in order to maintain the ingress protection rating (IP)
of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric
thread forms. G½ and PG 13.5 thread forms are only acceptable for
existing (legacy) equipment installations.
Table 6-2: Conduit Plug Thread Sizes
ThreadIdentification mark
M20 x 1.5M20
½–14 NPT½ NPT
G½G½
Table 6-3: Thread Adapter Thread Sizes
Male threadIdentification mark
M20 x 1.5–6HM20
½–14 NPT½–14 NPT
¾–14 NPT¾–14 NPT
Female threadIdentification mark
M20 x 1.5–6HM20
½–14 NPT½–14 NPT
PG 13.5PG 13.5
6.12Additional certifications
6.12.1 SBS American Bureau of Shipping (ABS) Type Approval
Bureau Veritas Rules for the Classification of Steel Ships
Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUTIMS
6.12.3 SDN Det Norske Veritas (DNV) Type Approval
Certificate
Intended Use
Application
Det Norske Veritas’ Rules for Classification of Ships, High
Speed & Light Craft and Det Norske Veritas’ Offshore
Standards
TemperatureD
HumidityB
VibrationA
EnclosureB/IP66: Al
TAA00000K8
Location classes
EMCA
6.12.4 SLL Lloyds Register (LR) Type Approval
C/IP66: SST
Certificate
Application
Quick Start Guide31
11/60002
Environmental categories ENV1, ENV2, ENV3, and ENV5
Page 32
Quick Start GuideMay 2019
7Declaration of conformity
32Rosemount 848T
Page 33
May 2019Quick Start Guide
Quick Start Guide33
Page 34
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 848T
List of Rosemount 848T Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated
diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
X O O O O
O
༣փ㓴Ԧ
Housing
Assembly
O O O X O
O
Րᝏಘ㓴Ԧ
Sensor
Assembly
X O O O O
O
ᵜ㺘Ṭ㌫ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ
This table is proposed in accordance with the provision of SJ/T11364.
O:
Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of
GB/T 26572.
X:
Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.
Quick Start GuideMay 2019
8China RoHS
34Rosemount 848T
Page 35
May 2019Quick Start Guide
Quick Start Guide35
Page 36
* 00825-0100-4697*
00825-0100-4697, Rev. TC
Quick Start Guide
May 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.