Emerson Rosemount 705 Reference Manual

Page 1
Rosemount™ 705 Wireless Totalizing Transmitter
Reference Manual
00809-0200-4705, Rev AB
May 2017
Page 2
Page 3
00809-0200-4705, Rev AB
Contents
1Section 1: Introduction
2Section 2: Configuration
3Section 3: Mounting
Contents
May 2017
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Product recycling/disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Connecting the turbine meter or pulse output device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Configuring the transmitter on the bench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Supported engineering unit codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5 Joining the device to a network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Installing the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.1 Installing the transmitter in a direct mount configuration . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.2 Installing the transmitter in a remote mount configuration . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Wireless considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3.1 Selected an installation location and position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.2 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3.3 Verifying operating atmosphere . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4 Remote antenna (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4.1 WN remote antenna option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.5 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.6 Grounding the transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4Section 4: Commissioning
4.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Configuring the transmitter to communicate with the wireless network. . . . . . . . . . . . . . . . . 22
4.3 Using AMS Device Manager to configure the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4 Using a Field Communicator to change parameters within the device . . . . . . . . . . . . . . . . . . . 23
Contents
4.5 K-factor consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.6 Verifying operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.6.1 AMS Device Manager. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
iii
Page 4
Contents
May 2017
5Section 5: Operation and Maintenance
5.1 Basic operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1.1 Rollover information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1.2 Enabling the LCD continuous operation feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.2 Determining device health. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3 Interpreting LCD screen messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3.1 Startup screen sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3.2 Diagnostic button screen sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.3.3 Network connection status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.4 Device diagnostic screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.4 Replacing the power module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5 Modbus
5.6 Reset/restore device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.7 Suspend (pause) the totalization in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.8 Average flow rate filtering period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.9 Low-Flow cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
®
, EtherNet/IP™ and OPC mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Reference Manual
00809-0200-4705, Rev AB
5.10 Input sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.11 How to reset the totalized volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.12 Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
AAppendix A: Specifications and Reference Data
A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A.1.1 Functional specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A.1.2 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A.1.3 Frequency input specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
A.1.4 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
A.2 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
A.3 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
BAppendix B: Product Certifications
B.1 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.2 Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.3 FCC and IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.4 Ordinary Location Certification from CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.5 Installing in North America. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.6 USA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.7 Canada. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
B.8 Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
iv
Contents
Page 5
00809-0200-4705, Rev AB
CAppendix C: High Gain Remote Antenna Option
Contents
May 2017
B.9 International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
B.10 Brazil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B.11 EAC - Belarus, Kazakhstan, Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B.12 Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
C.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
C.2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.1 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.2 Coaxial length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.3 Coaxial material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.4 Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.5 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.6 RF lightning arrestor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.7 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.8 Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.3 Installation considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.1 Antenna mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.2 Antenna height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.3 Coaxial cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.4 Installing coaxial drip loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.5 Applying coaxial sealant moisture protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.4 Transient/lightning considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.4.1 Gateway transient protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.4.2 RF lightning arrestor ground connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
C.6 Installing the high gain remote antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
DAppendix D: Mapping of Alert Messages in the HART® Command 48
Additional Status
Contents
v
Page 6
Contents
May 2017
Reference Manual
00809-0200-4705, Rev AB
vi
Contents
Page 7
NOTICE
00809-0200-4705, Rev AB
Rosemount™ 705 Wireless Totalizing Transmitter
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1 800 999 9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1 800 654 7768 (24 hours a day) Equipment service needs
International
1 952 906 8888
The Rosemount 705 Transmitter and all other wireless devices should be installed only after the Smart Wireless Gateway has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation.
Title Page
May 2017
Title Page
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact an Emerson
Sales Representative.
vii
Page 8
Title Page
NOTICE
May 2017
Reference Manual
00809-0200-4705, Rev AB
Failure to follow these installation guidelines could result in death or serious injury.
Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.
Shipping considerations for wireless products:
The unit was shipped to you without the power module installed. Remove the power module prior to shipping.
Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping.
Power module considerations:
The power module with the wireless unit contains two “C” size primary lithium/thionyl chloride batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical, or mechanical damage. Contacts should be protected to prevent premature discharge.
Battery hazards remain when cells are discharged.
Power modules should be stored in a clean and dry area. For maximum battery life, storage temperature should not exceed 30 °C.
The power module has surface resistivity greater than one gigaohm and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
viii
Title Page
Page 9
00809-0200-4705, Rev AB

Section 1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, operating, and maintaining the Rosemount
Section 2: Configuration provides instruction on commissioning and operating Rosemount 705
Transmitter. Information on software functions, configuration parameters, and online variables is also included.
Section 3: Mounting contains mechanical and electrical installation instructions.
Section 4: Commissioning contains techniques for properly commissioning the device.
Section 5: Operation and Maintenance contains operation and maintenance techniques.
Appendix A: Specifications and Reference Data supplies reference and specification data, as well as
ordering information.
Appendix B: Product Certifications contains approval information.
Appendix C: High Gain Remote Antenna Option contains specification data and installation of high
gain antenna.
Appendix D: Mapping of Alert Messages in the HART
important alerts in the HART command 48 additional status field for the Rosemount 705 Transmitter.
705 Wireless Totalizing Transmitter. The sections are organized as follows:
Introduction
®
Command 48 Additional Status contains
May 2017

1.2 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration. The product and packaging should be disposed of in accordance with local and national legislation.
Introduction
1
Page 10
Introduction
May 2017
Reference Manual
00809-0200-4705, Rev AB
2
Introduction
Page 11
00809-0200-4705, Rev AB

Section 2 Configuration

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Connecting the turbine meter or pulse output device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Configuring the transmitter on the bench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
Supported engineering unit codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Joining the device to a network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10

2.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Configuration
May 2017
Failure to follow these installation guidelines could result in death or serious injury.
Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.

2.2 Connecting the turbine meter or pulse output device

The Rosemount™ 705 Wireless Totalizing Transmitter is compatible with a number of simple turbine meters or pulse output devices. When ordered in the optional configuration for direct connection, option code D1, the Rosemount 705 Transmitter is compatible with one inch turbine meter direct connections. Figure 2-1 on page 8 shows the correct input connections to the pulse terminals on the transmitter. To ensure a proper turbine meter connection, anchor the turbine meter lead wires into the appropriate compression terminals and tighten the screws. In noisy environments, be sure to properly ground the transmitter using the ground terminal.
Config uration
7
Page 12
Configuration
A
C
B
May 2017
Reference Manual
00809-0200-4705, Rev AB
Wiring the transmitter
For the R1 option (remote mount), if the turbine meter or pulse output device is installed in a high-voltage environment and a fault condition or installation error occurs, the sensor leads and transmitter terminals could carry lethal voltage. Use extreme caution when making contact with the leads and terminals.
Use the following steps to wire the sensor and power supply to the transmitter:
1. Remove the transmitter enclosure cover.
2. Attach the turbine meter leads according to the diagram Figure 2-1 on page 8.
Note
For noisy electrical environments, it is best practice to ground the loop accordingly.
3. Connect the black power module.
4. Verify the connection and power by viewing the LCD display and seeing the power up sequence.
5. Replace the cover and tighten.
Figure 2-1. Rosemount 705 Transmitter Terminal Block
A. Pulse input connection
®
B. HART C. Terminal block ground connection
terminal connection
Note
Connections are not polarity sensitive.

2.3 Configuring the transmitter on the bench

When using a Field Communicator, any configuration changes must be sent to the transmitter using the Send key (F2). AMS
Device Manager configuration changes are implemented when the Apply button is
clicked.
8
Configuration
Page 13
00809-0200-4705, Rev AB
Configuring on the bench with AMS Device Manager
AMS Device Manager is capable of connecting to devices directly, using a HART modem, or with the Gateway. When configuring on the bench with a HART modem, double click the device icon, then select the Configure/Setup tab (or right click and select Configure/Setup). Configure the device settings using the Direct Connection menu. When configuring with the Gateway, double click the device icon then select the Configure/Setup tab (or right click and select Configure/Setup). Configure the device settings using the Wireless Connection menu. To check or change sensor configuration using a Field Communicator, enter the following Fast Key sequence: 2, 1, 2.

2.4 Supported engineering unit codes

The following engineering units are supported by the Rosemount 705 Transmitter.
Total volume Volumetric flow rate
US gallons per second
US gallons per minute
US gallons
US gallons per hour
Configuration
May 2017
Liters
Imperial gallons
Cubic meters
Cubic yards
Cubic inches
US gallons per day
Liters per second
Liters per minute
Liters per hour
Imperial gallons per second
Imperial gallons per minute
Imperial gallons per hour
Imperial gallons per day
Cubic meters per second
Cubic meters per minute
Cubic meters per hour
Cubic meters per day
Cubic yards per second
Cubic yards per minute
Cubic yards per hour
Cubic yards per day
Cubic inches per second
Cubic inches per minute
Cubic inches per hour
Cubic inches per day
Config uration
Pulses
Hertz
9
Page 14
Configuration
May 2017
If a custom volume unit is desired, the Rosemount 705 Transmitter can be configured to report the totalized pulses, and a custom conversion can be done on the host system side. Similarly, if a custom flow rate unit is desired, the transmitter can be configured to report pulses per second (Hertz), and a custom conversion can be done on the host system side. When reporting pulses or hertz, the configured K-factor has no affect on the reported values.
Units Fast key
Volume 2, 1, 2
Flow 2, 2, 1

2.5 Joining the device to a network

To communicate with the Gateway, and ultimately the Host System, the transmitter must be configured to communicate with the wireless network.
Using a Field Communicator or AMS Device Manager, enter the Network ID and Join Key so they match the Network ID and Join Key of the Gateway and the other devices in the network. If the Network ID and Join Key are not identical, the transmitter will not communicate with the network. The Network ID and Join Key may be obtained from the Gateway on the Network>Settings page on the web server or by clicking network information in the upper right hand corner. Using a Field Communicator, the Network ID and Join Key can be configured using a Field Communicator with the Fast Key Sequence: 2, 1, 3.
Reference Manual
00809-0200-4705, Rev AB
The final device network configuration piece is the update rate which, by default, is one minute. It can be changed at commissioning, or at any time, by using AMS Device Manager or the Gateway’s web server. The update rate should be between one second and 60 minutes. To change the update rate with a Field Communicator, use the Fast Key sequence: 2, 1, 4.
If doing a bench top initial configuration, after completion remove the power module until installation. When the device is installed, insert the power module and close the housing cover securely. Always ensure a proper seal so metal touches metal, but do not over tighten.
10
Configuration
Page 15
Reference Manual
00809-0200-4705, Rev AB

Section 3 Mounting

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Installing the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Wireless considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Remote antenna (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Grounding the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19

3.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Mounting
May 2017
Failure to follow these installation guidelines could result in death or serious injury.
Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.
Mounting
11
Page 16
Mounting
May 2017
Reference Manual
00809-0200-4705, Rev AB

3.2 Installing the transmitter

The Rosemount™ 705 Wireless Totalizing Transmitter can be installed in one of two configurations:
Direct mount (D1): The turbine meter is connected directly to the Rosemount 705 Transmitter housing’s conduit entry. For installation instructions, see “Installing the transmitter in a direct mount
configuration” on page 12.
Remote mount (R1): The turbine meter or pulse output device is mounted separate from the Rosemount 705 Transmitter housing, then connected to the transmitter via conduit. For installation instructions, see
“Installing the transmitter in a remote mount configuration” on page 14.
3.2.1 Installing the transmitter in a direct mount configuration
Figure 3-1. Direct Mount
B
C
A
A. Turbine meter B. Rosemount 705 Transmitter C. 1-in. NPT connection to flow meter and two piece pipe union
Note
Direct mount installation should not be employed when using tubing and connectors such as Swagelok fittings.
1. Install the turbine meter according to standard installation practices making sure to use thread sealant on all of the connections.
2. Attach the turbine meter wiring to the terminals as indicated on the wiring diagram (Figure 3-2). This procedure is already included for the D1 (direct mount) option.
®
12
Mounting
Page 17
A
C
B
00809-0200-4705, Rev AB
Figure 3-2. Rosemount 705 Terminal Block
A. Pulse input connection B. HART C. Terminal block ground connection
3. Attach the transmitter housing to the turbine meter using the threaded conduit entry.
4. Seal threads on 1-in. NPT turbine meter connection. Take union apart and turn on bottom
5. Attach mill spec connector to turbine meter pickup.
®
terminal connection
fitting to turbine meter.
Mounting
May 2017
6. Screw on the remaining union part.
Note
Sealant should already be applied to threads on the D1 (direct mount) option.
Note
Wireless devices should only be powered up after the Smart Wireless Gateway, in order of proximity from the Smart Wireless Gateway beginning with the closest device. This results in a simpler and faster network installation.
7. Connect the black power module
Figure 3-3. Power Module Installation
Mounting
8. Close the housing cover and tighten to safety specification. Always ensure a proper seal so metal touches metal, but do not over tighten.
9. Position the antenna so it is vertical, either straight up or straight down.
a. The antenna should be approximately 3 ft. (0.91 m) from any large structures or
buildings, to allow clear communication to other devices.
13
Page 18
Mounting
Possible antenna rotation shown. Antenna rotation allows for best installation practices in any configuration.
A
B
C
May 2017
Reference Manual
00809-0200-4705, Rev AB
Figure 3-4. Antenna Positioning
3.2.2 Installing the transmitter in a remote mount configuration
Figure 3-5. Remote Mount Installation
A. Turbine meter B. Rosemount 705 Transmitter C. 1-in. supplied cable gland adapter for turbine meter.
Included: (1) Cable gland (1) Cable gland adapter for turbine meter 10 ft.. of cable connection wiring
1. Install the turbine meter or pulse output device according to standard installation practices being sure to use thread sealant on all of the connections.
2. Pull the cable connection wiring through the supplied cable gland adapter for the turbine meter. Then pull the cable wiring through the transmitter cable gland.
Note
Pay attention to the orientation of the cable gland to ensure proper connection to transmitter.
3. Attach the turbine meter or pulse output device wiring to the terminals as shown in the wiring diagrams beginning on page 8.
Note
Wireless devices should only be powered up after the Smart Wireless Gateway, in order of proximity from the Gateway beginning with the closest device. This results in a simpler and faster network installation.
14
Mounting
Page 19
00809-0200-4705, Rev AB
4. If commissioning the Rosemount 705 Transmitter, connect the power module as shown in Figure 3-3
on page 13.
5. Close the housing cover and tighten to safety specifications. Always ensure a proper seal by installing the electronic housing covers so metal touches metal, but do not over tighten.
6. Position the antenna vertically, either straight up or straight down, as shown in Figure 3-4 on page 14.
The antenna should be approximately 3 ft. (1 m) from any large structures or buildings, to allow clear
communication to other devices.

3.3 Wireless considerations

Power up sequence
Mounting
May 2017
The Smart Wireless Gateway should be installed and functioning properly before any wireless field devices are powered. Install the Black Power Module, SmartPower into the Rosemount 705 Transmitter to power the device. Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation. Enable Active Advertising on the Gateway to ensure that new devices join the network faster. For more information see the Smart Wireless Gateway Reference Manual
Solutions model number 701PBKKF
.
Antenna position
The antenna should be positioned vertically, either straight up or straight down, and it should be approximately 3 ft. (1 m) from any large structure, building, or conductive surface to allow for clear communication to other devices.
Figure 3-6. Antenna Position
Mounting
Preparing (or sealing) the conduit entries
Due to possible damage from moisture after installation, ensure that each conduit entry is either sealed with a conduit plug with appropriate thread sealant, or has an installed conduit fitting or cable gland with appropriate thread sealant.
15
Page 20
Mounting
A
A
COMM
P/N 00753-9200-0020
1
2
3
4
May 2017
Reference Manual
00809-0200-4705, Rev AB
Figure 3-7. Locating Conduit Entries
A. Conduit entry
Connecting the Field Communicator to the transmitter
The power module needs to be connected for the Field Communicator to interface with the Rosemount 705 Transmitter.
Figure 3-8. Field Communicator Connections
3.3.1 Selected an installation location and position
When choosing an installation location and position, take into account access to the transmitter. For best performance, the antenna should be vertical with space between objects in a parallel metal plane, such as a pipe or metal framework, as the pipes or framework may adversely affect the antenna’s performance.
16
Mounting
Page 21
00809-0200-4705, Rev AB
3.3.2 Electrical
Caring for the power module
The Rosemount 705 Transmitter is self-powered. The included Black Power Module contains two “C” size primary lithium/thionyl chloride batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the power module are maintained. Care should be taken to prevent thermal, electrical, or mechanical damage. Contacts should be protected to prevent premature discharge.
Making turbine meter connections
Make turbine meter connections through the cable entry in the side of the connection head. Be sure to provide adequate clearance for cover removal and lead attachments (remote option).
3.3.3 Verifying operating atmosphere
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Mounting
May 2017
Isolating the transmitter from sources of heat
The transmitter will operate within specifications for ambient temperatures between –40 and 185 °F (–40 and 85 °C). Heat from the process is transferred from the switch to the transmitter housing. If the expected process temperature is near or beyond specification limits, consider using an extension, or remote mount the transmitter to thermally isolate it from the process.
Temperature limits
Options Operating limit Storage limit
With LCD display
Without LCD display
–4 to 175 °F –20 to 80 °C
–40 to 185 °F
–40 to 85 °C
–40 to 185 °F
–40 to 85 °C
–40 to 185 °F
–40 to 85 °C
Mounting
17
Page 22
Mounting
May 2017

3.4 Remote antenna (optional)

The remote antenna option provides flexibility for mounting the Rosemount 705 Totalizer based on wireless connectivity, lightning protection, and current work practices.
When installing remote mount antennas for the transmitter, always use established safety procedures to avoid falling or contact with high-power electrical lines.
Install remote antenna components for the transmitter in compliance with local and national electrical codes and use best practices for lightning protection.
Before installing, consult with the local area electrical inspector, electrical officer, and work area supervisor.
The transmitter remote antenna option is specifically engineered to provide installation flexibility while optimizing wireless performance and local spectrum approvals.
To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change the length of cable or the antenna type.
If the supplied remote mount antenna kit is not installed per these instructions, Emerson is not responsible for wireless performance or non-compliance with spectrum regulations.
Reference Manual
00809-0200-4705, Rev AB
The remote mount antenna kit includes coaxial sealant that is for the cable connections, lightning arrestor, and antenna.Find a location where the remote antenna has optimal wireless performance. Ideally this will be 15–25 ft. (4.6–7.6 m) above the ground or 6 ft. (2 m) above obstructions or major infrastructure. To install the remote antenna, use one of the following procedures. The WN option is 25 ft. (7.6 m).
3.4.1 WN remote antenna option
1. Mount the antenna on a 1.5- to 2-in. pipe mast using the supplied mounting equipment.
2. Connect the lightning arrestor directly to the top of the Rosemount 705 Totalizer.
3. Install the grounding lug, lock washer, and nut on top of lightning arrestor.
4. Connect the antenna to the lightning arrestor using the supplied LMR-400 coaxial cable ensuring the drip loop is not closer than 1 ft. (0.3 m) from the lightning arrestor.
5. Use the coaxial sealant to seal each connection between the wireless field device, lightning arrestor, cable, and antenna.
6. Ensure the mounting mast and lightning arrestor are grounded according to local/national electrical code.
Note
Any spare lengths of coaxial cable should be placed in 12-in. (0.3 m) coils.
18
Mounting
Page 23
A
B
C
00809-0200-4705, Rev AB

3.5 LCD display

If an LCD display is ordered, it will be shipped attached to the transmitter.
The optional LCD display can be rotated in 90° increments by squeezing the two tabs, pulling out, rotating and snapping back into place.
If the LCD diplay pins are inadvertently removed from the interface board, carefully re-insert the pins before snapping the LCD display back into place.
Installing the LCD display
To install the LCD display, use Figure 3-9 on page 19 and the following instructions:
1. Remove the LCD display cover. Do not remove the instrument cover in explosive environments when the circuit is live.
2. Put the four-pin connector into the LCD display, rotate to the desired position and snap into place.
Note the following LCD display temperature limits:
Operating: –4 to 175 °F (–20 to 80 °C) Storage: –40 to 185 °F (–40 to 85 °C)
Mounting
May 2017
3. Replace the transmitter cover.
Note
Only use Rosemount Wireless LCD display part number: 00753-9004-0002. The transmitted data may not match data displayed on LCD display due to differences in update rate and screen refresh rate.
Figure 3-9. Optional LCD Display
A. LCD pins B. LCD display C. LCD cover

3.6 Grounding the transmitter

Mounting
The Rosemount 705 Transmitter operates best with the housing grounded. Floating systems, however, can cause extra noise that may affect the accuracy of the transmitter. If the signal appears noisy or erratic, grounding at a single point may solve the problem. Grounding of the electronics enclosure should be done in accordance with local and national installation codes. Grounding is accomplished through the process connection using the internal or external case grounding terminal.
19
Page 24
Mounting
May 2017
Reference Manual
00809-0200-4705, Rev AB
Determining grounding requirements
Each process installation has different grounding requirements. Use the options recommended by the facility for the specific turbine meter or pulse output device.
1. Connect turbine meter wiring shield to the grounded transmitter housing.
2. Ensure the transmitter housing is electrically isolated from the turbine meter or pulse output device wiring.
B
A
A. Turbine meter B. Transmitter ground point C. Rosemount 705 Transmitter
C
20
Mounting
Page 25
Reference Manual
00809-0200-4705, Rev AB

Section 4 Commissioning

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
Configuring the transmitter to communicate with the wireless network . . . . . . . . . . . . . . . . . page 22
Using AMS Device Manager to configure the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Using a Field Communicator to change parameters within the device . . . . . . . . . . . . . . . . . . . page 23
K-factor consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Verifying operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25

4.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Commissioning
May 2017
Failure to follow these installation guidelines could result in death or serious injury.
Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.
Note
The Rosemount only after the Smart Wireless Gateway has been installed and is functioning properly.
Wireless devices should be powered up in order of proximity from the Gateway, beginning with the device closest to the Gateway. This will result in a simpler and faster network installation.
705 Wireless Totalizing Transmitter and all other wireless devices should be installed
Commissioning
21
Page 26
Commissioning
May 2017
Reference Manual
00809-0200-4705, Rev AB

4.2 Configuring the transmitter to communicate with the wireless network

In order to communicate with the Smart Wireless Gateway, and ultimately the Host System, the transmitter must be configured to communicate with the wireless network. This step is the wireless equivalent of connecting wires from a transmitter to the Host System. Using a Field Communicator or
AMS
Device Manager, enter the Network ID and Join Key so they match the Network ID and Join Key of the gateway and other devices in the network. If the Network ID and Join Key are not identical, the Rosemount 705 Transmitter will not communicate with the network. The Network ID and Join Key may be obtained from the Smart Wireless Gateway on the Setup>Network>Settings page on the web server, shown in Figure 4-1.
Figure 4-1. Gateway Network Settings
22
Commissioning
Page 27
00809-0200-4705, Rev AB
Commissioning
May 2017

4.3 Using AMS Device Manager to configure the transmitter

1. Right click on the Rosemount 705 Transmitter and select Configure.
2. When the menu opens, select Join Device to Network and follow the method to enter the Network
ID and Join Key.

4.4 Using a Field Communicator to change parameters within the device

The most common parameters changed are the Network ID and Join Key. The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence. Set both Network ID and Join Key.
Function Fast Key sequence Menu items
Wireless setup 2, 1, 1 Network ID, Set Join Key

4.5 K-factor consideration

The K-factor value is used to tell the Rosemount 705 Transmitter how much volume corresponds to an input pulse. The K-factor is entered in units of “Pulses per Gallon”. It is important to configure the transmitter with the proper K-factor that corresponds to the turbine meter that it is attached to. If the K-factor is not configured properly, the accuracy of the reported totalized volume and flow rate may be adversely affected. Any time the attached turbine meter is replaced, the K-factor setting should be verified and/or modified accordingly to maintain a proper match.
If the K-factor is not specified to be pre-configured when ordering the Rosemount 705 Transmitter, it will be shipped without any K-factor configured. In this case, the K-factor must be configured before any valid values can be obtained for the totalized volume or the average flow rate. The transmitter will report a value of NaN (Not a Number) when the K-factor has not been configured.
When changing the K-factor, the Rosemount 705 Transmitter will recalculate a new totalized volume assuming that all captured input pulses correspond to the new K-factor value. This means the current value of the totalized volume held in the transmitter may change as a result of changing the K-factor. If this is not desired, the value of totalized volume can be noted, and reset the volume to the original value after the new K-factor has been configured. To avoid any loss of volume accumulation, this procedure should only be done when the flow through the attached turbine meter has been stopped.
Commissioning
23
Page 28
1 Refresh Alert s 2 No Active Alerts 3History
1Clear Alert History 2 List of Previous alerts
1PV 2SV 3TV 4QV
1PV / SV / TV / QV 2PV / SV/ TV / QV Status 3 Gauge
1 Variable S ummary 2 Mapped Variables 3 All Variables 4 Last Update Time
1 Totalized V olume 2 Average Flow Rate 3Electronics Temp 4 Supply Voltage 5 Percent of Range
1 Totalized Volume
Average Flow Rate Electroni cs Temp Supply Vol tage
Percent of Range 2Status 3 Gauge
1 Totalized V olume 2 Average Flow Rate 3 Data Hist ory
1 Device Variable 2 Variable Unit s 3 Sample Interval 4 Date of Newest V al 5 Time of Newest Val 6 View Da ta Hist ory 7Refresh
1 Comm: Connec ted 2 Join Mode 3 Available Nghbrs 4 Advertisem ents 5 Join Att empts
1 Routine Mai ntenance 2 Reset /Restore
1 Measurement History 2 Locate Device 3 Install New Power Module 4Set Total Volume 5 Sensor Life
1Lifetime Counts 2Reset Lifetime Cnts
1 Device Reset 2 Restore to Default Settings
1 Si mulate
1 Totalized V olume 2 Average Flow Rate 3 Elect ronics Temperature
1 Dev Status: Good 2 Comm: Connected 3 Totalized Volume 4 Status 5 Average Flow Rate 6 Status 7 Update Rate 8 Join Device to N/W 9 Device Information
1 Over view 2 Configure 3 Service Tools
1 Guided Setup 2 Manual Setup 3 Alert Setup
1 Alerts 2 Variables 3 Trends 4 Communication 5 Maintenance 6 Simulate
1 Refresh Alerts 2 No Actuve Alerts 3 History 4 F: 5 A: 6 M:
1 Alert Description 2 Alert Image
1 Identification 2 Revisions 3 Radio 4 Security
1 Basic Setup 2 Configure Totalizing Option 3 Join Device to N/W 4 Configure Update Rate 5 Configure Device Display 6 Configure Process Alerts
1 Long Tag 2 Tag 3 Model 4 Transmitter S. N. 5 Date 6 Description 7 Message 8 Model Numbers 9 Device Image
1 Universal 2 Field Device 3 Software 4 Hardware 5 DD Revision
1 MAC Address 2 Manufacturer 3 Device Tyoe 4 Device Revision 5 Software Revision 6 Hardware Revision 7 Xmit Power Level 8 Min Brdcst Rate
1 Model Number 1 2 Model Number 2 3 Model Number 3
1 Wireless 2 Totalizing Option 3 Display 4 HART 5 Security 6 Device Information 7 Power
1 Write Protect Status: Disabled 2 Lock Status: Unlocked 3 Over the Air Upgrade: Unlocked
1 Write Protect Status: Disabled 2 Lock Stat: Unlocked 3 Lock/Unlock 4 Over the Air Upgrade
1 Network ID 2 Join Device to N/W 3 Broadcast Info
1 Turbine Configuration 2 Flow Configuration
1 Power Mode 2 Power Source
1 K-factor 2 Volume Unites 3 Roll Over Point 4 Input Sensitivity
1 Flow Units 2 Low Flow Cutoff 3 Filter Period
1 Upper Range Value 2 Lower Range Value 3 Upper Sensor Limit 4 Lower Sensor Limit
1 Totalized Volume/Avg Flow Rate 2 Status 3 HI-HI Alarm 4 HI Alarm 5 LO-LO Alarm 6 LO Alarm
1 Mode 2 Units 3 Alert Limit 4 Dead Band
1 Roll Over Point 2 Roll Over Exceeded 3 Roll Over Warning 4 Lifetime Warning 5 Roll Over Warn Thres 6 Lifetime Warn Thres
1 Display Mode 2 Config Data History
1 Meas and Status Log 2 Config Data History 3 Variable Mapping 4 Percent Range
1 Long Tag 2 Tag 3 Transmitter S. N. 4 Date 5 Descrption 6 Message
1 Totalized Volume 2 Average Flow Rate 3 Alert Options
1 Totalized Volume 2 Average Flow Rate 3 Electronic Temp 4 Supply Voltage 5 Percent of Range
1 Primary Variable 2 Secondary Variable 3 Third Variable 4 Fourth Variable
Commissioning
May 2017
Figure 4-2. Handheld Tree
Reference Manual
00809-0200-4705, Rev AB
24
Commissioning
Page 29
A b c d e
f g h
i d - 1 2
3 4 5 6 7 8
n e t w k
13 0 5
I D
S u p l y
7. 2 1
v o l t s
00809-0200-4705, Rev AB

4.6 Verifying operation

There are four ways to verify operation: using the optional local display (LCD), using the Field Communicator, using the Smart Wireless Gateway's integrated web interface, or by using AMS Suite. If the Rosemount 705 Transmitter was configured with the Network ID and Join Key, and sufficient time has passed, the transmitter will be connected to the network.
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of the Network ID and Join Key, and verify that Active Advertising has been enabled on the Gateway. The Network ID and Join Key in the device must match the Network ID and Join Key of the Gateway.
Operating the local display
The LCD displays the configured values at the update rate, or can optionally be enabled for continuous display. See Enabling the LCD continuous operation feature .
Diagnostic button display sequence
More detailed diagnostic information can be obtained by removing the display cover of the Rosemount 705 Transmitter, and momentarily depressing the DIAG button. The LCD will display the diagnostic screens as shown in Figure 4-4.
Commissioning
May 2017
Press the Diagnostic button to display the TAG, Device ID, Software Revision, Network ID, Network Join Status and Device Status screens.
Figure 4-3. Diagnostic Screen Sequence
Tag Device ID Network ID
Network join
status
n e t w k
Device status
O K
Network join status
The chevron-shaped status bar at the top of the screen indicates the progress of the network join process. When the status bar is filled, the device is successfully connected to the wireless network. This is shown, in Figure 4-4 on page 26.
Commissioning
25
Page 30
Commissioning
N E T w K
S R C H N G
n e t w k
N E G O T
n e t w k
L I M - O P
May 2017
Reference Manual
00809-0200-4705, Rev AB
Figure 4-4. Network Join Status Screens
Searching for
network
Joining network
Connected with
limited bandwidth
Connected
n e t w k
O K
Connecting with a Field Communicator
A Rosemount 705 DD is required for HART® Communication.
Func tion Fast Key sequence Menu items
Join Status, Communication Status, Join Mode, Number of
Communications 2, 1, 3
Available Neighbors, Number of Advertisements Heard,
Number of Join Attempts
Checking for communication using the Smart Wireless Gateway
In the integrated web interface from the Gateway, navigate to the devices page. This page shows whether the device has joined the network and if it is communicating properly.
Note
The time to join the new device(s) to the network is dependent upon the number of devices being joined and the number of devices in the current network. For one device joining an existing network with multiple devices, it may take up to five minutes. It may take up to 60 minutes for multiple new devices to join the existing network.
4.6.1 AMS Device Manager
When the device has joined the network, it will appear in the AMS Device Manager as illustrated below.
26
Commissioning
Page 31
00809-0200-4705, Rev AB
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of the Network ID and Join Key, and verify that Active Advertising has been enabled on the Gateway. The Network ID and Join Key in the device must match the Network ID and Join Key of the Gateway.
The Network ID and Join Key may be obtained from the Gateway in the upper right hand corner labeled network information. The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence.
Function Fast Key sequence Menu items
Wireless 2,1,3 Join Device to Network
Commissioning
May 2017
Commissioning
27
Page 32
Commissioning
May 2017
Reference Manual
00809-0200-4705, Rev AB
28
Commissioning
Page 33
00809-0200-4705, Rev AB
Operation and Maintenance

Section 5 Operation and Maintenance

Basic operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Determining device health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
Interpreting LCD screen messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
Replacing the power module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 37
Modbus
Reset/restore device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Suspend (pause) the totalization in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Average flow rate filtering period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Low-Flow cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
Input sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
How to reset the totalized volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
®
, EtherNet/IP™ and OPC mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
May 2017

5.1 Basic operation

5.1.1 Rollover information
The totalized volume will automatically restart at a volume of zero when the configured rollover point has been reached. The table below describes some estimates to how long a rollover will take at max values of 10 million. Best practices are to reset the total before the device rollover occurs. The totalized volume will accumulate in the transmitter up to a configurable rollover point. Once the totalized volume reaches the rollover point, the totalized value will automatically continue totalizing the volume starting from zero. The rollover point defaults to 100 million, but can be configured to any value between one and two billion. Note the resolution of the totalized volume is reduced as the value gets larger. Refer to
the table below or see the menu tree
Configured units code Earliest rollover Typical longest LCD wait Typical longest value wait
Cu.M 75 years 137 days 39 minutes
L 27 days 3 hours 2 seconds
UK Gal 125 days 15 hours 10 seconds
US Gal 104 days 12 hours 9 seconds
Barrel 11 years 21 days 6 minutes
Cu.F 2 years 3 days 1 minute
Cu.Y 57 years 105 days 30 minutes
Cu.I 0 day 3 minutes 0 seconds
:
Note
The rollover value itself is not affected by the volume engineering units. For example, if the rollover value is configured to 100 million with engineering units of gallons, a change to volume units of cubic meters will cause the rollover value to still be 100 million, but will rollover at 100 million cubic meters rather than 100 million gallons.
Operation and Maintenance
Pulses 1 day 50 seconds 0 seconds
29
Page 34
Operation and Maintenance
X X X X X
X X X X x x x
x x x x x x
May 2017
5.1.2 Enabling the LCD continuous operation feature
The Rosemount™ 705 Wireless Totalizing Transmitter has the ability to keep the LCD always on for local indication of the total volume and average flow for the attached output device. Power module life will be reduced when operating in this mode. For example, at a one minute update rates the power module life would be reduced from a 10 year life to an estimated eight year life. More information on the power module life impact for various update rates can be found at
Emerson.com/Rosemount/Power-Module-Life-Estimator
Enabling continuous LCD updates
AMS™ Device Manager
1. Connect the Rosemount 705 Transmitter to the HART® Communicator and access the Rosemount 705 DD.
2. Double click on the Rosemount 705 icon and select Configure>Guided Setup> Configure Device Display
Through the handheld
1. Connect the Rosemount 705 Transmitter to the HART Handheld device.
2. Fast keys 2, 1, 5 (Configure>Manual Setup> Display> Display Mode)
Reference Manual
00809-0100-4248, Rev CA

5.2 Determining device health

In addition, system considerations must be observed to ensure the device is still connected to the wireless network and reporting values. On an Emerson Smart Wireless Gateway, this can be done by referring to the parameter: PV_HEALTHY. The PV_HEALTHY has a “True” state when the device is on the network and its updates are current, not late or stale, and the PV value is functioning properly. A “False” state of PV_HEALTHY means the device is either off of the network, the data updates are not current, or there is an issue measuring PV. In the case of a “False” state of PV_HEALTHY, it is recommended to assume the device is not connected to the network and to take appropriate action.

5.3 Interpreting LCD screen messages

The transmitted data may not match data displayed on LCD display due to differences in update rate and screen refresh rate.
5.3.1 Startup screen sequence
The following screens will display when the power module is first connected to the Rosemount 705 Tr an sm i tt er.
All segments On: used to visually determine if there are any bad segments on the LCD display
30
Operation and Maintenance
Page 35
00809-0200-4705, Rev AB
Operation and Maintenance
May 2017
Device identification: used to determine Device Type
A b c d e
f g h
Device information - Tag: user entered tag which is eight characters long - will not display if all characters are blank
Totalized volume screen: accumulated total volume over time
Average rate screen: average rate value
Operation and Maintenance
Electronics screen: feature board temperature value, can be modified to a specific variable in the DD
31
Page 36
Operation and Maintenance
May 2017
Reference Manual
00809-0100-4248, Rev CA
S u p l y
7. 2 1
v o l t s
a l e r t
p r e s n t
Supply voltage screen: voltage reading at the power module terminals, can be modified to a specific variable in the DD
Alert screen: at least one alert is present - this screen will not display if no alerts are present
5.3.2 Diagnostic button screen sequence
The following five screens will display when the device is operating properly and the Diagnostic Button has been pressed:
A b c d e
f g h
Device information - Tag: User entered tag which is 8 characters long - will not display if all characters are blank
32
i d - X X
X X X X X X
Device identification: Used to determine Device ID
Software revision: Indication of the software revision of the
device
Operation and Maintenance
Page 37
00809-0200-4705, Rev AB
Operation and Maintenance
May 2017
n e t w k
13 0 5
I D
n e t w k
O K
S u p l y
7. 2 1
v o l t s
Network ID: Assuming the device has the correct join key, this ID tells the user what network the device can connect with
Network connection status: The device has joined a network and has been fully configured and has multiple parents
Supply voltage: Voltage reading at the power module terminals
5.3.3 Network connection status screens
These screens display the network status of the device. Only one will be shown in the fourth position of the diagnostic button screen sequence.
n e t w k
u n k n w n
n e t w k
Diagnostic button screen 4.1: The device is attempting to start the radio
Diagnostic button screen 4.2: The device has just restarted
I N I T
Operation and Maintenance
33
Page 38
Operation and Maintenance
May 2017
Reference Manual
00809-0100-4248, Rev CA
n e t w k
i d l e
n e t w k
D I S C N T
N E T w K
S R C H N G
Diagnostic button screen 4.3: The device is starting to join the process
Diagnostic button screen 4.4: the device is in a disconnected state and requires a “Force Join” command to join the network
Diagnostic button screen 4.5: The device is searching for the Network
34
n e t w k
N E G O T
n e t w k
c o n e c t
Diagnostic button screen 4.6: The device is attempting to join a network
Diagnostic button screen 4.7: The device is connected to the Network, but is in a “Quarantined” state
Operation and Maintenance
Page 39
00809-0200-4705, Rev AB
Operation and Maintenance
May 2017
n e t w k
Diagnostic button screen 4.8: The device is joined and operational, but is running with limited bandwidth for sending periodic data
L I M - O P
n e t w k
Diagnostic button screen 4.9: the device has joined a network and has been fully configured and has multiple parents
O K
5.3.4 Device diagnostic screens
The following screens will show the device diagnostics depending on the state of the device, continuing after Diagnostic Button Screen 5.
s u p l y
f a i l u r
Diagnostic button screen 6.1: There is a critical error which may prevent the electronics board from operating correctly
Diagnostic button screen 6.2: There is a warning which should be addressed, but should not affect the device output
Diagnostic button screen 7.1: Terminal voltage has dropped below level of operating limit. Replace the Black Power Module model number 701PBKKF (part number: 00753-9220-0001)
Operation and Maintenance
35
Page 40
Operation and Maintenance
May 2017
Reference Manual
00809-0100-4248, Rev CA
s u p l y
l o w
r a d i o
f a i l u r
c o n f g
f a i l u r
Diagnostic button screen 7.2: Terminal voltage is below the recommended operating range - if this is a self-operated device, the power module should be replaced - for line powered devices, the supply voltage should be increased
Diagnostic button screen 8: device cannot retrieve information from the radio in the device - the device may still be operational and publishing HART data
Diagnostic button screen 9: Configuration of the transmitter is invalid such that critical operation of the device may be affected
- check the extended configuration status to identify which configuration item(s) need to be corrected
36
Diagnostic button screen 10: Switch attached to the
s n s r
f a i l u r
b d W T h
l i m i t d
Note
Use Rosemount Wireless LCD display part number: 00753-9004-0002.
transmitter has failed, and valid readings from that switch are no longer possible - check the switch and switch wiring connections - check additional status for more detailed information of the failure source
Diagnostic button screen 11: Device has not yet received all of the requested wireless bandwidth needed to operate as configured
Operation and Maintenance
Page 41
00809-0200-4705, Rev AB

5.4 Replacing the power module

Operation and Maintenance
May 2017
When the power module needs to be replaced, remove the power module cover and the depleted power module. Replace the power module with a new Black Power Module, SmartPower number 701PBKKF (part number: 00753-9220-0001). Then replace the cover and tighten it to specification. Always ensure a proper seal so metal touches metal, but do not over-tighten. After the power module has been replaced, navigate to AMS Device Manager to reset the power module function. This also can be done via the handheld 3, 5, 1, 3.
When replacing the power module, the device will stop totalizing data. The device will resume from where the last total was periodically recorded (within a five minute window). Example: The best practice when replacing the power module is to make note of the totalized volume before removing the power module. After installing a new power module, the totalized volume can be set to the previous recorded value.
Solutions model
Handling the power module
The black power module with the wireless unit contains two “C” size primary lithium/thionyl chloride batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the battery pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to prevent premature discharge.
Use caution when handling the power module, it may be damaged if dropped from heights in excess of 20 ft.
Battery hazards remain when cells are discharged.
Environmental considerations
As with any battery, local environmental rules and regulations should be consulted for proper management of spent batteries. If no specific requirements exist, recycling through a qualified recycler is encouraged. Consult the materials safety data sheet for battery specific information.
Shipping considerations
The unit was shipped to you without the power module installed. Remove the power module prior to shipping.
Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation, and are also covered by International Air Transport Association (IATA), International Civil Aviation Organization (ICAO), and European Ground Transportation of Dangerous Goods (ARD). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping.
Operation and Maintenance
37
Page 42
Operation and Maintenance
May 2017
00809-0100-4248, Rev CA

5.5 Modbus®, EtherNet/IP™ and OPC mapping

Following is a table of parameters that can be used for Modbus, EtherNet/IP and OPC mapping. These parameters are used by the Smart Wireless Gateway and can be found in the web interface of the Gateway. Some of these parameters are analog values and some are discrete, and this is noted in the description. The Setpoint parameters are used to drive the output channel and for the readback of the state of the output channel.
Table 5-1. Parameters for Modbus, EtherNet/IP, and OPC Mapping
Parameter name Description Read/Write
Reference Manual
SUPPLY_VOLTAGE
ELECTRONICS_TEMPERATURE Maps the electronics temperature Read
TOTALIZED_VOLUME Maps the totalized volume the device has measured Read
AVE RAG E_ FLOW _R ATE
ACCUMULATOR_RESET
ACCUMULATOR_STATE What is the current totalized value of the device Read
Maps the supply voltage of the device. For monitoring the health of your power module use SUPPLY_VOLTAGE_HEALTHY
Maps the instantaneous flow rate over that period of time set by the DD
Use this parameter to reset the number of total counts on the device
Read
Read
Write
Mapping the Rosemount 705 Transmitter parameters
Below is the Gateway screen where the accumulator reset, accumulator state, totalized_volume, average_flow variables and parameter can be mapped. This is important to understand how to reset the totalized volume of the device via Modbus, OPC, or EtherNet/IP.
Figure 5-1. Smart Wireless Gateway Modbus Register Map
38
Operation and Maintenance
Page 43
00809-0200-4705, Rev AB
To reset the total of the Rosemount 705 Transmitter via Modbus, follow the steps below.
1. Navigate to Modbus connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
To reset the total of the Rosemount 705 Transmitter via OPC, follow the steps below.
1. Navigate to OPC connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
To reset the total of the Rosemount 705 Transmitter via EtherNet/IP, follow the steps below.
1. Navigate to EtherNet/IP connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
Operation and Maintenance
May 2017

5.6 Reset/restore device

The Rosemount 705 Transmitter can be reset remotely over the wireless network, or locally via the wired maintenance port. Resetting the device will cause the device to temporarily drop offline and rejoin to the configured wireless network. When resetting the device, you can choose to reset the device with the same configuration as it already has, or to revert the configuration settings to the original values that were present when the device left the manufacturer. When reverting the configuration settings to original values, not the turbine meter K-factor will also be reverted, so the turbine meter should be verified to ensure the correct K-factor is being used.
Fast Keys
3, 5, 2

5.7 Suspend (pause) the totalization in the device

The Rosemount 705 Transmitter allows the totalization to be stopped, which will hold the current totalized volume value and ignore any new input pulses. This can be done through a host connection to the wireless gateway.

5.8 Average flow rate filtering period

The average flow rate filtering period controls how heavily the average flow rate is filtered. The default setting of one second will cause the Rosemount 705 Transmitter to report the average flow rate over a time interval of one second. Setting the period to a larger value will reduce noisy flow rate measurements, but will increase the time constant of the reported value.
Operation and Maintenance
Fast Keys
2, 2, 2, 2, 3
39
Page 44
Operation and Maintenance
May 2017

5.9 Low-Flow cut-off

The low flow cutoff value can be configured to cause the Rosemount 705 Transmitter to report zero flow for any rates below the configured threshold. Totalized volume will be unaffected by the low flow cutoff
setting. The transmitter will continue to totalize any detectable volume - even for very small flow rates.
Reference Manual
00809-0100-4248, Rev CA
Fast Keys
2, 2, 2, 2, 2

5.10 Input sensitivity

The input sensitivity setting is used to adjust the minimum input voltage required for the Rosemount 705 Transmitter to count pulses. There are two settings “Normal” and “Reduced”. Under most circumstances, the “Normal” setting will provide the most accurate flow readings. The “Reduced” setting should be used in environments where outside interference is causing a degradation of transmitter performance, such as picking up extra counts/showing a flow rate when the turbine meter is not rotating. If the “Reduced” setting is selected, care should be taken to verify the device is properly
reporting flow, particularly at low frequencies.
Fast Keys
2, 2, 2,1, 4

5.11 How to reset the totalized volume

The totalized volume can be reset via the wireless network, through the wireless gateway, using a button located behind the electronics/LCD display side housing cover, or by connecting to the local wired maintenance port. To avoid any loss of volume accumulation, the totalizer should only be reset when the
flow through the attached turbine meter has been stopped.
Fast Keys
3, 5, 1, 4

5.12 Service support

To expedite the return process outside of the United States, contact the nearest Emerson representative.
Within the United States, call the Emerson Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for the following information:
Product modelSerial numbersThe last process material to which the product was exposed
40
Operation and Maintenance
Page 45
00809-0200-4705, Rev AB
The center will provide:
A Return Material Authorization (RMA) numberInstructions and procedures that are necessary to return goods that were exposed tohazardous
substances.
Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods.
Operation and Maintenance
May 2017
Operation and Maintenance
41
Page 46
Operation and Maintenance
May 2017
Reference Manual
00809-0100-4248, Rev CA
42
Operation and Maintenance
Page 47
Specifications and Reference Data
May 2017
Reference Manual
00809-0200-4705, Rev AB

Appendix A Specifications and Reference Data

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 43
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 45
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 47
Spare parts and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 48

A.1 Specifications

A.1.1 Functional specifications
Wireless output
IEC 62591 (WirelessHART
Radio frequency power output from antenna
External (WK option) antenna: Maximum of 10 mW (10 dBm) EIRP Extended Range, External (WM option) antenna: Maximum of 18 mW (12.5 dBm) EIRP High Gain, Remote (WN option) antenna: Maximum of 40 mW (16 dBm) EIRP
Local display
The optional integral LCD display can display discrete state and diagnostic information. Display updates at each wireless update or constantly when the device has the optional LCD display always on option.
Humidity limits
0–99 percent relative humidity
Wireless update rate
User selectable, one second to 60 minutes.
A.1.2 Physical specifications
Electrical connections
Wireless power module
Replaceable, Intrinsically Safe Lithium-Thionyl Chloride power module with PBT polymer enclosure. Ten year life at one minute update rate.
Note
Continuous exposure to ambient temperature limits (–40 °F or 185 °F) (–40 °C or 85 °C) may reduce specified power module life by less than 20 percent.
1. Reference conditions are 70 °F (21 °C), and routing data for three additional network devices.
®
) 2.4 GHz DSSS
(1)
Field Communicator connections
Communication terminals
Terminal tabs are permanently fixed to terminal block
Materials of construction
Enclosure
Housing - Low-copper aluminum, or stainless steel
Paint - Polyurethane
Cover O-ring - Buna-N
Terminal block and power module pack
PBT
Antenna
PBT/PC integrated omni-directional antenna
Conduit entries
1
/2–14 NPT
Weight
Low - copper aluminum
Rosemount display - 4.6 lb (2.0 kg) Rosemount 705 Transmitter with M5 LCD display -
4.7 lb (2.1 kg)
Stainless steel
Rosemount 705 Transmitter without LCD display -
8.0 lb (3.6 kg) Rosemount 705 Transmitter with M5 LCD display -
8.1 lb (3.7 kg)
Enclosure ratings (705)
NEMA 4X, and IP66/67
Mounting
Transmitters may be attached directly to switch, brackets also permit remote mounting. See “Dimensional drawings” on
page 45.
705 Wireless Totalizing Transmitter without LCD
Specifications and Reference Data
43
Page 48
Reference Manual
00809-0200-4705, Rev AB
Specifications and Reference Data
May 2017
A.1.3 Frequency input specifications
0 to 10 kHz
A.1.4 Performance specifications
Electromagnetic Compatibility (EMC)
All models
Meets all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation <1% span during EMC disturbance.
Vibration effect
Wireless output unaffected when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10–60 Hz
0.21mm displacement peak amplitude/60-2000 Hz 3g).
Wireless output unaffected when tested per the requirements of IEC60770-1 field with general application or pipeline with low vibration level(10–60 Hz 0.15 mm displacement peak amplitude/60–500 Hz 2 g).
(1)
Temperature limits
Description
Without LCD display
With LCD display
Operating limit Storage limit
–40 to 185 °F
–40 to 85 °C
–4 to 175 °F –20 to 80 °C
–40 to 185 °F
–40 to 85 °C
–40 to 185 °F
–40 to 85 °C
1. During surge event device may exceed maximum EMC deviation limit or reset; however, device will self-recover and return to normal operation with specified start-up time.
44
Specifications and Reference Data
Page 49
Specifications and Reference Data
1.50 [38]
A
D
B
C
2.49 [63]
4.20 [107]
7.81 [198]
11.16 [284]
E
7.88 [200]
F
0.42 [11]
6.05 [154]
May 2017

A.2 Dimensional drawings

Figure A-1. Rosemount 705 Transmitter
Shown with 2.4 GHz/WirelessHART extended range antenna
Reference Manual
00809-0200-4705, Rev AB
Shown with optional digital display and 2.4 GHz/WirelessHART Antenna
A. 2.4 GHz/WirelessHART extended range antenna B. 1-in. NPT connection to flow meter C. Ground screw assembly
Dimensions are in inches (millimeters).
Shown without optional digital display
D. Possible antenna rotation E. Digital display cover F. Transmitter electronics
Specifications and Reference Data
45
Page 50
Reference Manual
D
1.03 [26]
4.03 [102]
C
1.38[35]
B
A
Specifications and Reference Data
00809-0200-4705, Rev AB
Figure A-2. Rosemount 705 Transmitter Mounting Configurations with Optional Pipe Mounting Bracket
May 2017
A. 2-in. U-bolt for pipe mounting B. Ground screw assembly
Dimensions are in inches (millimeters).
C.1-in. NPT connection to flow meter D. Turbine meter connection
46
Specifications and Reference Data
Page 51
Specifications and Reference Data
May 2017
Reference Manual
00809-0200-4705, Rev AB

A.3 Ordering information

Table A-1. Rosemount 705 Wireless Totalizing Transmitter Ordering Information
The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
Product description
705 Totalizing Transmitter (with connector mil-c-5015)
Transmitter output
X Wireless
Transmitter t ype
D1 Direct mount
R1 Remote mount (10 ft. leads included)
Housing
D Dual compartment housing - aluminum
E Dual compartment housing - SST
Conduit threads
1
1
/2–14 NPT
Certifications
NA No Hazardous Location Approval
I5 U.S.A Intrinsically Safe
I6 Canada Intrinsically Safe
N5 U.S.A. Division 2, Non-incendive
N6 Canada Division 2, Non-incendive
I1 ATEX Intrinsic Safety
IU ATEX Intrinsic Safety for Zone 2
I7 IECEx Intrinsic Safety
IY IECEx Intrinsic Safety for Zone 2
Wireless options
Wireless update rate, operating frequency and protocol
WA3 User configurable update rate, 2.4 GHz DSSS, IEC 62591 (WirelessHART)
Omni directional wireless antenna and SmartPower solutions
WK1 External antenna, adapter for black power module (I.S. power module sold separately)
WM1 Extended range, external antenna, adapter for black power module (I.S. power module sold separately)
WJ1 Remote antenna, adapter for black power module (I.S.power module sold separately)
(2)
WN1
Other options
High-gain, remote antenna, adapter for black power module (I.S. power module sold separately)
(1)
Display
M5 LCD display
Specifications and Reference Data
47
Page 52
Reference Manual
00809-0200-4705, Rev AB
Specifications and Reference Data
May 2017
Table A-1. Rosemount 705 Wireless Totalizing Transmitter Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
Mounting bracket
B4 Universal L mounting bracket for 2-in. pipe mounting - SST bracket and bolts
Configuration
C1
Calibration Factor (k-factor) Configuration. Factory configure date, descriptor, message fields, and wireless parameters
Typical model number: 705 X D1 D 1 I6 WA3 M5 B4 C1
1. Black Power Module must be shipped separately, order model 701PBKKF or part number: 00753-9220-000.
2. Limited availability, consult factory for details.
Spare parts and accessories
Spare parts and accessories
00705-9000-0001 Cable assembly, 1 ft. long for direct mount option
00705-9000-0002 Cable Assembly, 10 ft. long for remote mount option
03151-9270-0003 Remote housing bracket kit
701PBKKF Black power module
48
Specifications and Reference Data
Page 53
Product Certifications
May 2017

Appendix B Product Certifications

Rev 1.1
European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
FCC and IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Ordinary Location Certification from CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Installing in North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
USA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
Brazil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51
EAC - Belarus, Kazakhstan, Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51
Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 52
Reference Manual
00809-0200-4705, Rev AB

B.1 European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at
Emerson.com/Rosemount
.

B.2 Telecommunication Compliance

All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum. Nearly every
country requires this type of product certification. Emerson working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
is

B.3 FCC and IC

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.
B.4 Ordinary Location Certification
from CSA
The transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by CSA, a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

B.5 Installing in North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

B.6 USA

I5 U.S.A. Intrinsically Safe (IS)
Certificate: CSA 70011131 Standards: FM 3600 – 2011, FM 3610 – 2010,
UL Standard 50 – Eleventh Edition, UL 61010-1 – 3 ANSI/ISA-60079-0 (12.00.01) – 2013, ANSI/ISA-60079-11 (12.02.01) – 2013, ANSI/IEC 60529 – 2004
Markings: IS CL I, DIV 1, GP A, B, C, D T4; Class 1, Zone 0, AEx
ia IIC T4 Ga; T4 (-50 °C ≤ T installed per Rosemount Type 4X; IP66
See the table at the end of this section for entity parameters
N5 U.S.A. Division 2, Nonincendive
Certificate: CSA 70011131 Standards: FM 3600 – 2011, FM 3611 – 2004,
UL Standard 50 – Eleventh Edition, UL 61010-1 (3 ANSI/IEC 60529 – 2004
Markings: NI CL I, DIV 2, GP A, B, C, D T4;
T4 (-50 °C ≤ T
rd
Edition,
+70 °C) when
a
drawing 00705-1020;
rd
Edition),
+70 °C); Type 4X; IP66
a
Product Certifications
49
Page 54
00809-0200-4705, Rev AB
Product Certifications
May 2017
Special Conditions for Safe Use (X):
1. For use only with the Model 701P or Rosemount P/N 753-9220-XXXX Smart Power Battery Module.
2. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

B.7 Canada

I6 Canada Intrinsically Safe (IS)
Certificate: CSA 70011131 Standards: CAN/CSA C22.2 No. 0-10,
CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No.142-M1987, CAN/CSA-60079-0 - 2011, CAN/CSA-60079-11 - 2014, CSA Std C22.2 No. 60529 - 2005, CAN/CSA-C22.2 No. 61010-1 - 2012
Markings: IS CL I, DIV 1, GP A, B, C, D T4;
Ex ia IIC T4 Ga, T4; T4 (–50 °C ≤ T when installed per Rosemount drawing 00705-1020; Type 4X; IP66
See the table at the end of this section for entity parameters.
N6 Canada Division 2, Nonincendive
Certificate: CSA 70011131 Standards: CAN/CSA C22.2 No. 0-10,
CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 213-M1987 (R2013), CAN/CSA-60079-0 - 2011, CAN/CSA Std C22.2 No. 60529 - 2005, CAN/CSA-C22.2 No. 61010-1 - 2012
Markings: Suitable for Class 1, Division 2,
Groups A, B, C, D T4; T4 (–50 °C ≤ T Type 4X; IP66
+70 °C)
a
+70 °C);
a
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The Rosemount 705 Transmitter enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 area.
IU ATEX Intrinsic Safety for Zone 2
Certificate: Baseefa14ATEX0375X Standards: EN 60079-0: 2012, EN 60079-11: 2012 Markings: II 3 G Ex ic IIC T4 Gc, T4(–60 °C ≤ T
+70 °C)
For use with Rosemount SmartPower Power Module part number 753-9220-0001, or for use with Emerson SmartPower option 701PBKKF. See the table at the end of this section for entity parameters.
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module may be replaced in a hazardous area. The Power Modules have a surface resistivity greater than 1GΩ and must be properly installed I the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
3. The Rosemount 705 Transmitter enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 area.
a
Special Conditions for Safe Use (X):
1. For use only with the Model 701P or Rosemount P/N 753-9220-XXXX Smart Power Battery Module.
2. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

B.8 Europe

I1 ATEX Intrinsic Safety
Certificate: Baseefa14ATEX0375X Standards: EN 60079-0: 2012, EN 60079-11: 2012 Markings: II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ T
For use with Rosemount SmartPower number 753-9220-0001, or for use with Emerson SmartPower option 701PBKKF. See the table at the end of this section for entity parameters.
50
power module part
+70 °C)
a

B.9 International

I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 14.0173X Standards: IEC 60079-0: 2011, IEC 60079-11: 2011 Markings: Ex ia IIC T4 Ga, T4 (-60 °C ≤ T
For use with Rosemount SmartPower power module part number 753-9220-0001, or for use with Emerson SmartPower option 701PBKKF. See the table at the end of this section for entity parameters.
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The Rosemount 705 Transmitter enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 area.
+70 °C)
a
Product Certifications
Page 55
Product Certifications
May 2017
Reference Manual
00809-0200-4705, Rev AB
IY IECEx Intrinsic Safety for Zone 2
Certificate: IECEx BAS 14.0173X Standards: IEC 60079-0: 2011, IEC 60079-11: 2011 Markings: Ex ic IIC T4 Gc, T4 (-60 °C ≤ T
For use with Rosemount SmartPower power module part number 753-9220-0001, or for use with Emerson SmartPower option 701PBKKF. See the table at the end of this section for entity parameters
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The Rosemount 705 Transmitter enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 area.
+70 °C)
a

B.10 Brazil

I2 INMETRO Intrinsic Safety
Certificate: UL-BR 17.0019X Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011,
ABNT NBR IEC 60079-11:2009 Markings: Ex ia IIC T4 Ga, T4 (–60 °C ≤ T See the table at the end of this section for entity parameters
+70 °C)
a

B.11 EAC - Belarus, Kazakhstan, Russia

IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate: TC RU C-US.MIO62.B.03122 Markings: 0Ex ia IIC T4 Ga X, T4 (–60 °C ≤ T See the table at the end of this section for entity para.meters
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
Turbine meter terminal
output parameters
Voc/Uo = 2.5 V V
Isc/Io = 253 μA I
P
= 640 μW P
max/Po
Ca/Co = 2.9 μF Ci = 2.2 nF
La/Lo= 500 mH Li = 4.7 mH
Turbine meter terminal
input parameters
a
max/Ui
max/Ii
max/Pi
+70 °C)
= 10 V
= 1 mA
= 1 mW
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Product Certifications
51
Page 56
00809-0200-4705, Rev AB

B.12 Installation drawings

Figure B-1. Rosemount 705 Wireless Totalizing Transmitter
Product Certifications
May 2017
52
Product Certifications
Page 57
Product Certifications
May 2017
Reference Manual
00809-0200-4705, Rev AB
Product Certifications
53
Page 58
00809-0200-4705, Rev AB
Product Certifications
May 2017
54
Product Certifications
Page 59
High Gain Remote Antenna Option
May 2017
Reference Manual
00809-0200-4705, Rev AB

Appendix C High Gain Remote Antenna Option

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55
Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 56
Installation considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57
Transient/lightning considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 58
Installing the high gain remote antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59

C.1 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
When installing remote mount antennas for the wireless field device, always use established safety procedures to avoid falling or contact with high-power electrical lines.
Install remote antenna components for the wireless field device in compliance with local and national electrical codes and use best practices for lightning protection.
Before installing consult with the local area electrical inspector, electrical officer, and work area supervisor.
The wireless field device remote antenna option is specifically engineered to provide installation flexibility while optimizing wireless performance and local spectrum approvals. To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change the length of cable or the antenna type.
If the supplied remote mount antenna kit is not installed per these instructions, Emerson responsible for wireless performance or non-compliance with spectrum regulations.
Be aware of overhead electrical power lines.
is not
High Gain Remote Antenna Option
55
Page 60
00809-0200-4705, Rev AB

C.2 Functional specifications

C.2.1 Output
WirelessHART® 2.4 GHz DSSs (direct sequence spread spectrum)
Radio Frequency Power Output from Antenna:
High gain remote (WN option) antenna:
Maximum of 40 mW (16 dBm) EIRP (Equivalent Isotropically Radiated Power)
High gain remote antenna (WJ1 option):
Maximum of 40 mW (16 dBm) EIRP 25 ft. of cable.
C.2.2 Coaxial length
25 ft. (7.6 m) with Type N Connections
C.2.3 Coaxial material
Heavy duty, low loss LMR400 cableMinimum coaxial bend diameter: 1.0 ft. (0.3 m)
High Gain Remote Antenna Option
May 2017
C.2.4 Antenna
Remote mount omni directional antennaFiberglass and aluminum construction8 Db Gain WJ1 - 6dBiMeets MIL-STD-810G (Method 510.5, Procedure I and II)
C.2.5 Physical specifications
Weight: 1.0 lb. (0.4 kg)
C.2.6 RF lightning arrestor
In-line lightning arrestor
Electrical connection: Lightning arrestor MUST be grounded per local electrical codes and regulations.
Mounting bracket
Horizontal or vertical mast accommodationSupported mast diameter: 1.0 to 2.5-in. (2.5 to 6.4 cm)Aluminum bracketNickel/zinc plated mounting U-bolts
C.2.7 Ratings
NEMA® 4X, and IP66/67
C.2.8 Vibration
3 g Max vibration
56
High Gain Remote Antenna Option
Page 61
High Gain Remote Antenna Option
May 2017

C.3 Installation considerations

C.3.1 Antenna mounting
Mount antenna vertically (±5°)
C.3.2 Antenna height
Mount antenna 14 ft. (4.3 m) above infrastructure with clear line of sight.
C.3.3 Coaxial cable
Ensure that coaxial cable is securely affixed to the mast to avoid excessive cable movement.
C.3.4 Installing coaxial drip loop
Ensure a drip loop is installed not closer than 1.0 ft. (0.3 m) from the transmitter. It may also be convenient to affix the drip loop to the lower portion of the mast ensuring condensation or rainwater will flow away from the coaxial connections.
Reference Manual
00809-0200-4705, Rev AB
Figure C-1. Drip Loop Location
A
A. Coaxial drip loop
C.3.5 Applying coaxial sealant moisture protection
Utilize the coaxial sealant that is included in the high gain remote mounting kit package. Follow included instructions for application on the coaxial connection.

C.4 Transient/lightning considerations

C.4.1 Gateway transient protection
When installing, consider including transient/lightning protection on interface connections (Ethernet, Modbus
®
, and coaxial connections) to other equipment.
C.4.2 RF lightning arrestor ground connection
Ensure grounding connection is made on the RF lightning arrestor ground connection point.
High Gain Remote Antenna Option
57
Page 62
n`
n
n
.53
2.75 4 PLS
[X]
A
B
C
E
D
00809-0200-4705, Rev AB

C.5 Dimensional drawings

Figure C-2. Device Connection and RF Lightning Arrestor
High Gain Remote Antenna Option
May 2017
A. Antenna B. Min drip loop 12-in. (0.3 m) C. 25 ft. (7.6 m) Cable
D. Lightning arrestor E. Mounting bracket
58
High Gain Remote Antenna Option
Page 63
High Gain Remote Antenna Option
May 2017

C.6 Installing the high gain remote antenna

1. Mount the transmitter following best practice mounting procedures as outlined in the Quick Installation Guide and this manual.
2. Connect the RF Lightning protector to the device and tighten.
A
A. RF lightning protector
3. Connect antenna to mounting bracket and tighten nut carefully.
Reference Manual
00809-0200-4705, Rev AB
High Gain Remote Antenna Option
59
Page 64
00809-0200-4705, Rev AB
4. Unwind coaxial cable and connect the cable to both the antenna and the lightning protector connected to the transmitter, leaving one loop minimum for a drip loop. Ensure the drip loop is lower than the device, allowing water to flow away from the device.
High Gain Remote Antenna Option
May 2017
5. Apply the coaxial sealant around each of the coaxial connections and at the lightning arrestor, making sure the RF connections are completely sealed.
60
High Gain Remote Antenna Option
Page 65
High Gain Remote Antenna Option
May 2017
6. Attach U-bolts to mounting bracket in correct orientation ensuring antenna will be positioned in a vertical position.
Reference Manual
00809-0200-4705, Rev AB
7. Tighten U-bolts to mast and ensure antenna is pointed in a vertical direction.
High Gain Remote Antenna Option
61
Page 66
00809-0200-4705, Rev AB
High Gain Remote Antenna Option
May 2017
62
High Gain Remote Antenna Option
Page 67
Mapping of Alert Messages in the HART® Command 48 Additional Status
May 2017
Reference Manual
00809-0200-4705, Rev AB
Appendix D Mapping of Alert Messages in the
HART® Command 48 Additional Status
This appendix outlines the most important alerts in the HART command 48 Additional Status Field for the Rosemount
DeltaV Modbus
A complete list of Additional Status bits is available in the Smart Wireless Gateway.
Ta bl e D - 1 to Tab l e D - 2 displays the device variable and variable mapping indexes for the Rosemount 705
Transmitter.
Ta bl e D - 3 to Tab l e D - 5 shows a list of the most important alert messages that may be displayed in the
AMS command 48 Additional Status field.
for alert monitoring, and in the Smart Wireless Gateway for Additional Status mapping in
®
Device Manager and Field Communication together with the location of the Alert in the HART
705 Wireless Totalizing Transmitter. The information in this section can be used by
, OPC, etc.
To view Active Alerts, from the Home screen, go to Service To ol s>Active Alerts.
Table D-1. Device Variable Index
Device variable Index
0 Supply voltage
1 Electronics temperature
2Totalized volume
3 Average flow rate
Table D-2. D e fa ult Vari a ble Mapping Index (can be modified)
Variables Index
PV Totalized volume
SV Average flow rate
TV Electronics temperature
QV Supply voltage
Table D-3. Failure Alerts (F:)
Message Additional status
Electronics Failure Byte 8 :: Bit 6
Configuration Error Byte 2 :: Bit 6
(1)
Description
A failure has been detected in the device memory and/or electronics
The device has detected a configuration error based on a change to the device
Radio Failure Byte 1 :: Bit 6
Supply Voltage Failure Byte 6 :: Bit 2
1. Location of the Alert in the HART command 48 Status field.
Mapping of Alert Messages in the HART
®
Command 48 Additional Status
The wireless radio has detected a failure or stopped communicating
The supply voltage is too low for the device to broadcast
63
Page 68
00809-0200-4705, Rev AB
Table D-4. Maintenance Alerts (M:)
Mapping of Alert Messages in the HART
Command 48 Additional Status
May 2017
®
Message Additional status
Totalized Volume Rollover Byte 3 :: Bit 2
Average Flow Rate Saturated Byte 3 :: Bit 0
Electronics Temperature Beyond Limits
Supply Voltage Low Byte 8 :: Bit 4
1. Location of the Alert in the HART command 48 Status field.
Byte 8 :: Bit 5
(1)
Table D-5. Advisory Alerts (A:)
Message Additional status
Database Memory Warning Byte 0 :: Bit 2
Totalized Volume Warning Byte 3 :: Bit 1
Totalized Volume Stopped Byte 3 :: Bit 5
Description
The totalized volume has exceeded the maximum value and automatically reset to zero
The average flow rate is beyond the operating limits of the device and the reported value is saturated
The terminal temperature has exceeded the transmitter’s maximum range
The supply voltage is low and may soon affect broadcast updates
(1)
Description
The device has failed to write to the database memory. Any data written during this time may have been lost
The totalized volume has exceeded the warning threshold value
The totalized volume accumulation has been suspended by user
Sensor Input Life Alert Byte 3 :: Bit 3
HI HI Volume Alert Byte 5 :: Bit 4
HI Volume Alert Byte 5 :: Bit 5
LO Volume Alert Byte 5 :: Bit 6
LO LO Volume Alert Byte 5 :: Bit 7
HI HI Flow Alert Byte 5 :: Bit 0
HI Flow Alert Byte 5 :: Bit 1
LO Flow Alert Byte 5 :: Bit 2
LO LO Flow Alert Byte 5 :: Bit 3
Button Stuck Byte 1 :: Bit 5
Non-Critical User Data Warning Byte 2 :: Bit 1
The lifetime pulse count value has exceeded the configured warning threshold
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A process value has surpassed the user defined limit
A button on the Electronics Board is detected as stuck in the active position
A user written parameter does not match expected value
64
Simulation Active Byte 8 :: Bit 0
1. Location of the Alert in the HART command 48 Status field.
Mapping of Alert Messages in the HART
The device is in simulation mode and may not be reporting actual information
®
Command 48 Additional Status
Page 69
Page 70
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Reference Manual
00813-0100-4021, Rev RB
May 2017
Europe Regional Office
Emerson Automation Solutions Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Terms and Conditions of
Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co. SmartPower, DeltaV, AMS, Rosemount, and Rosemount logotype are trademarks of Emerson. HART and WirelessHART are registered trademarks of the FieldComm Group. Swagelok is a registered trademark of Swagelok Company. EtherNet/IP is a trademark of ControlNet International under license by ODVA. Modbus is registered trademark of Gould Inc. National Electrical Code is a registered trademark of National Fire Protection Association, Inc. All other marks are the propert y of their respective owners. © 2017 Emerson. All rights reserved.
Loading...