Emerson Rosemount 65Q User Manual

Page 1
Product Data Sheet
September 2014
00813-0100-4827, Rev DA
Resistance Temperature Sensors for Hygienic and Sanitary Applications
Resistance temperature sensors for applications in the food and beverage, pharmaceutical and life-science
industries
Aseptic process connections suitable for CIP and SIP dead-pocket free measurement applications
Exchangeable measuring insert to ensure process integrity
Enhanced system accuracy with transmitter-sensor matching, meets pharmaceutical industry
Page 2
Rosemount 65Q
September 2014
Rosemount 65Q Sensor
Optimize plant efficiency and increase measurement reliability with industry proven design and specifications
RTD elements for a reliable and accurate measurement point
Available in a wide variety of process connections for sanitary and hygienic applications
Meets EHEDG and 3-A Standard requirements for use in a variety of sanitary
Flying leads, terminal blocks, and cable connections to suit different wiring needs
State of the art manufacturing procedures provide robust element packaging, increasing reliability
Industry-leading calibration capabilities allow for Callendar-van-Dusen values to give increased accuracy when paired with
Rosemount transmitters
Streamline operations and maintenance with sensor and thermowell design
Process connections allow for quick and easy connection to industry-standard sanitary process connection points
Integral thermowell protection on 65Q allows for ordering sanitary sensor and thermowell together
Explore the benefits of a Complete Point Solution from Rosemount Temperature Measurement
An “Assemble Sensor to Specific Transmitter” option enables Emerson to provide a
complete point temperature solution, delivering an installation-ready transmitter and sensor assembly.
Emerson has a complete portfolio of Single Point and High Density Temperature
Measurement solutions, allowing you to effectively measure and control your processes with the reliability you trust from Rosemount products.
Experience global consistency and local support from numerous worldwide Rosemount Temperature sites
World-class manufacturing provides globally consistent ‘‘‘‘‘‘‘‘‘‘‘
product from every factory and the capability to fulfill the ‘‘‘‘‘‘‘‘ ‘ needs of any project, large or small.
2
Experienced Instrumentation Consultants help select
the right product for any temperature application and advise on best installation practices.
An extensive global network of Emerson service and support
personnel can be on-site when and where they are needed.
www.rosemount.com
Page 3
September 2014
Content
Rosemount 65Q
Rosemount 65Q Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rosemount 65Q Sanitary Sensor
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . 4
Specifications
Dimensional Drawings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
www.rosemount.com
3
Page 4
Rosemount 65Q
Rosemount 65Q Sanitary Sensor
The Rosemount 65Q Sanitary Sensor has designs that provide flexible and reliable temperature measurements in hygienic process environments.
Features include:
– 50 to 450 °C temperature range
Industry-standard RTD sensor design
3-A and EHEDG Standards approval
Variety of enclosure and connection head options
Global hazardous-location approvals (Option Code I1)
Calibration services to give you insight to sensor performance (Option
Codes V10, V11)
Electropolishing Surface Finish (Option Code R20)
September 2014
Assemble to Transmitter option (Option Code XA)
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 10 for more information on Material Selection.
Table 1. 65Q RTD Assembly (Pt 100) for Hygienic and Food and Beverage Applications
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Model Product description
0065Q 65Q RTD Sensor with Twell for Sanitary Applications
Connection head IP rating
C Rosemount Aluminum 68 M20 x 1.5
D Rosemount Aluminum 68
1 Rosemount, Aluminum with LCD Display Cover 68 M20 x 1.5
2 Rosemount, Aluminum with LCD Display Cover 68
5
6
E Connection Head DIN A Polished Stainless Steel 68 M20 x 1.5
F Connection Head DIN A Polished Stainless Steel 68
R Connection Head DIN B Polished Stainless Steel 66 M20 x 1.5
S Connection Head DIN B Polished Stainless Steel 66
J GR-A/BL (BUZ), Aluminum 65 M20 x 1.5 (with cable gland)
Connection Head DIN A Polished Stainless Steel with LCD Display Cover
Connection Head DIN A Polished Stainless Steel with LCD Display Cover
68 M20 x 1.5
68
(1)
Connection thread
1
/2-in. NPT
1
/2-in. NPT
1
/2-in. NPT
1
/2-in. NPT
1
/2-in. NPT
L TZ-A/BL (BUZH) Aluminum 65 M20 x 1.5 (with cable gland)
T TZ-A/BK, Polyamide, Black 65 M20 x 1.5 (with cable gland)
4
www.rosemount.com
Page 5
September 2014
Table 1. 65Q RTD Assembly (Pt 100) for Hygienic and Food and Beverage Applications
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Sensor lead wire termination
Rosemount 65Q
0 Flying Leads – No Springs on DIN plate
2 Terminal Block – DIN 43762
Sensor type Temperature range
1 RTD, Single Element, 4-wire – 50 to 450 °C
2 RTD, Dual Element, 3-wire – 50 to 450 °C
5 RTD, Single Element, 3-wire – 50 to 450 °C
Extension
S Tubular with Extension, Welded Screw Bush M24 x 1.5
Z Tubular with Extension, Head Connection Adjustable Loose Screw Nut M24 x 1.5
Extension length (N) in millimeters
(2)
0050
0065
(3)
50 mm
65 mm
0130 130 mm
XXXX Non-standard extension length – non-standard lengths are available from 50 to 990 mm
Thermowell material
D 1.4404 (AISI 316L) Stainless Steel, 0.8 μm electropolishing
Immersion length (L) in millimeters
0025 25 mm – not available for Mounting Style code T02
0050 50 mm
0065 65 mm
0100 100 mm
0150 150 mm
0200 200 mm
0250 250 mm
XXXX Non-standard immersion length – non-standard lengths are available from 25 to 2500 mm
Thermowell mounting style Process connection Stem style
C02 Flanged 1-in. Tri-Clamp™ (diameter 50.4 mm) Stepped, 10/6 mm
C04 Flanged 11/2-in. Tri-Clamp (diameter 50.4 mm) Stepped, 10/6 mm
C06 Flanged 2-in. Tri-Clamp (diameter 64 mm) Stepped, 10/6 mm
C08 Flanged 21/2-in. Tri-Clamp (diameter 77.4 mm) Stepped, 10/6 mm
C10 Flanged 3-in. Tri-Clamp (diameter 91 mm) Stepped, 10/6 mm
C12 Flanged 4-in. Tri-Clamp (diameter 119 mm) Stepped, 10/6 mm
C14 Flanged
1
/2-in. Tri-Clamp (diameter 24.9 mm) Stepped, 10/6 mm
(4)
(4)
(4)
(4)
(4)
(4)
(4)
www.rosemount.com
5
Page 6
Rosemount 65Q
Table 1. 65Q RTD Assembly (Pt 100) for Hygienic and Food and Beverage Applications
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
C16 Flanged
K02 Weld-in Ball (adjustable), diameter 25 mm, PEEK Seal Straight, 6 mm
K04 Weld-in Ball (adjustable), diameter 25 mm, SST Seal Straight, 6 mm
M10 Tapered with Coupling Nut
3
/4-in. Tri-Clamp (diameter 37.4 mm) Stepped, 10/6 mm
(6)
Suitable connection for tube nominal size DN 10 Stepped, 10/6 mm
September 2014
(4)
(5)
(5)
(4)
M25
M32
M40
M50
T02 Threaded Parallel
T12 Threaded Tapered
Tapered Union with Coupling
(6)
Nut
Tapered Union with Coupling
(6)
Nut
Tapered Union with Coupling
(6)
Nut
Tapered Union with Coupling
(6)
Nut
Suitable connection for tube nominal size DN 25 Stepped, 10/6 mm
Suitable connection for tube nominal size DN 32 Stepped, 10/6 mm
Suitable connection for tube nominal size DN 40 Stepped, 10/6 mm
Suitable connection for tube nominal size DN 50 Stepped, 10/6 mm
1
/2-in. (1/2-in. BSPF) (G1/2) Stepped, 10/6 mm
1
/2-in. NPT Stepped, 10/6 mm
V04 VAR IVE NT® DN 1 1/2 - 3 inch (Dim. 68 mm) Standard
Options (include with selected model number)
Sensor options
A3
A4
Product certifications
Single Element Class 1/3 DIN B Sensor
Dual Element Class 1/3 DIN B Sensor
0 to 100 °C (–32 to 212 °F)
0 to 100 °C (–32 to 212 °F)
(4)
(4)
(4)
(4)
(7)
(4)
I1 EEx ia ATEX/IBExU Intrinsic Safety Approval
Cable gland option
G2 Cable Gland, EEx d, Brass 7.5 mm - 11.9 mm
Cover chain option
G3 Cover Chain (only available with Connection Head Material codes C and D)
Extension ring
G6
Aluminum Extension Ring for Dual Transmitter Mounting (only available with Connection Head Material codes C and D)
Material certification
Q8 Thermowell Material Certification
Extension ring
R20 Electropolishing Surface Finish of wetted parts, Ra = 0.4 μm
Assemble to options
(8)
XA
Assemble Sensor to Specific Temperature Transmitter
6
www.rosemount.com
Page 7
September 2014
Table 1. 65Q RTD Assembly (Pt 100) for Hygienic and Food and Beverage Applications
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Standard calibration (with A, B, C and Callendar-van Dusen constants)
Rosemount 65Q
V10 Works Certificate – Sensor Calibration from –50 to 450 °C (-58 to 842 °F)
V11 Works Certificate – Sensor Calibration from 0 to 100 °C (-32 to 212 °F)
Temperature range
X8
Works Certificate – Sensor Calibration Over Specified Temperature Range with A, B, C, and Callendar-van Dusen constants
Typical model number: 0065Q C 0 1 S 0050 D 0200 C04 XA
(1) IP 68 rating requires a suitable cable gland on the conduit connection thread. All threads must be sealed.
(2) Standard length for use with Connection Head codes C, D, 1, and 2.
(3) Standard length for use with Connection Head codes E, F, J, L, R, S, T, 5,and 6.
(4) For U < 50 mm, outer diameter 6 mm straight, below part of process connection.
(5) Valid for DIN B connection heads only.
(6) According to DIN 11851.
(7) For U
(8) If ordering X A with a transmitter, specify the same option on the transmitter model number.
≤ 65 mm, the outer diameter is 6 mm for straight stem styles.
p
www.rosemount.com
7
Page 8
Rosemount 65Q
Introduction
September 2014
Rosemount Series 65Q Temperature Sensor is designed for use in hygienic and aseptic applications exclusively to meet the stringent quality requirements in the Food and Beverage, and Pharmaceutical industries. Rosemount temperature products are manufactured according to Good Manufacturing Practice (GMP) guidelines and comply with the standards of the European Hygienic Equipment Design Group (EHEDG) as well as 3A standards.
National and international guidelines
Products that may have a direct or indirect impact on public health, must be produced according to national and international guidelines. The guidelines contain rules for the implementation and organization of methods, production, production environments, and inspections.
The European Hygienic Equipment Design Group (EHEDG) is a foundation in which mainly users and manufacturers or hygienic equipment are represented. EHEDG provides guidance of the hygienic engineering aspects of manufacturing of safe and wholesome food, e.g. through production, publication, and updating of guidelines, equipment approval through certification to assist equipment suppliers and food manufacturers and advisory function to legislators and standards groups.
EHEDG cooperation with 3-A
EHEDG cooperates with 3-A Sanitary Standards, Inc. in the development of hygienic construction material selection and design standards for food and dairy processing equipment. 3-A Sanitary Standards and Practices have been developed for use by the dairy industry, dairy equipment manufacturers, and milk regulatory agencies as voluntary guidelines. These voluntary guidelines are used as a benchmark for product performance, hygienic quality, and ultimately food safety. 3-A Sanitary Standards and Practices are generally accepted by federal, state, and local public health authorities in the United States and other public health authorities around the world.
While 3-A Sanitary Standards have been in development and use since the late 1920’s. EHEDG is a fairly recent development that applies test criteria and laboratory test data for determining cleanability and acceptance for equipment use in the processing of foods or comestibles. Both EHEDG and 3-A Sanitary Standards may be applied not only to Food and Beverage processing equipment, but can also be applied to Biotech and Bio-pharm equipment to ensure product acceptance and safety.
Mounting configurations
The Rosemount 65Q can be ordered with flying leads or terminal block. Ordered with flying leads, the sensors are designed with an integral mounting plate, and are for use with a head-mount transmitter attached directly to the sensor. The flying lead configuration facilitates removal of the sensor and transmitter as one assembly. The configuration with terminal block allows only the mounting of transmitter into the cover of several DIN size connection heads or requires the use of field mount transmitter.
Series 65Q RTD – sanitary applications
Rosemount Series 65Q Integral Mount Temperature Sensors are designed for use in hygienic, food and beverage applications when fitted with the Tri-Clamp, adjustable Weld-in Ball or Tapered Union with Coupling Nut according to DIN 11851 (Dairy Connection) process connections which do not need to meet as harsh aseptic requirements as requested for BioPharm applications. Alternatively for direct insertion into non-hygienic processes, the Series 65Q Temperature Sensor can be ordered optional with G½-in. (½-in. BSPF) or ½-in. NPT thread mounting.
The 65Q is available alone or as complete assemblies including connection heads, thermowells with weld-on process connections. This offering is designed to be used in complete temperature assemblies including Rosemount Temperature Transmitters. The RTD sensors meet most critical parameters of international standards - DIN EN 60751 incorporating Amendments 1 and 2. All sensors are available in a variety of lengths and ranges with terminal block or flying leads.
8
www.rosemount.com
Page 9
September 2014
Red
Red
White
Red
Red
White
White
Red Red
Green
Black
Blue Blue
White
Red
Red
Red
Red
White
White
White
White
Red
Red
Red
Red
Figure 1. Rosemount 65Q Lead Wire Termination
Series 65 RTD flying leads (Code 0)
Rosemount 65Q
Single element
3-wire
Series 65 RTD terminal block termination (Code 2)
Single element
3-wire
Single element
4-wire
Single element
4-wire
Dual element
3-wire
Dual element
3-wire
www.rosemount.com
9
Page 10
Rosemount 65Q
Specifications
September 2014
Material selection
Emerson provides a variety of Rosemount product with various product options and configurations including materials of construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented is intended as a guide for the purchaser to make an appropriate selection for the application. It is the purchaser’s sole responsibility to make a careful analysis of all process parameters (such as all chemical components, temperature, pressure, flow rate, abrasives, contaminants, etc.), when specifying product, materials, options and components for the particular application. Emerson Process Management is not in a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options, configuration or materials of construction selected.
Nominal resistance
In accordance with DIN EN 60751, the nominal resistance is defined as follows:
100 Ω RTD at 0 °C
Temperature coefficient α = 0.00385 Ω x °C/Ω), averaged
between 0 and 100 °C
Ambient temperature
Housing without head-mounted transmitter
Metal housings: -40 to +130 °C
Plastic housings: -40 to +85 °C
Housing with head-mounted transmitter
-40 to +85 °C
Maximum process pressure
Lower maximum pressure can be due to the process connection Pressure ratings at 20 °C:
Tri-Clamp: 10 bar
Weld-in Ball with PEEK-Seal: 6 bar
Weld-in Ball with SST-Seal: 40 bar
Threaded: 40 bar
Tapered Union with Coupling Nut: 10 bar
VARIVENT: 10 bar
Limit deviations
Tolerance Class A as standard: t = ± (0.15 + 0.002 x t); valid for the temperature range from 0 to +350 °C
Lead wire configuration
As single element (1Pt 100) with 3 or 4 lead wires or dual element (2Pt 100) with 3 lead wires
Response time
Less than 12 seconds to reach 63% step change in water flowing at 0.4 m/s
Process temperature range
-50 to +450 °C The measurement range can be limited by the gasket in the process connection.
Shock and vibration resistance
According to DIN EN 60751: 2.8 g peak / 10…500 Hz
Self heating
0.15 °K/mW when measured per method defined in DIN EN 60751
Insulation resistance
1,000 MΩ minimum insulation resistance when measured at 500 Vdc and at room temperature
Sheath material
321 Stainless Steel with mineral-insulated cable construction
Lead wire
PTFE insulated, silver coated copper wire
10
www.rosemount.com
Page 11
September 2014
Rosemount 65Q
Identification data
The model and serial numbers are marked on each sensor.
Ingress Protection (IP) ratings
The particular rating is applicable only for complete assemblies including a connection head and tubular thermowell. IP varies from 65 to 68 due to a wide selection on different connection heads, DIN A and B size, made of different materials such as aluminum, polyamide, and stainless steel.
System components
Sensor
The 65Q sensor consists of an exchangeable mineral-insulated measuring insert, wherein a small, drop-form thin film RTD element is encapsulated. This design protects the relatively strain-free element, thereby maintaining accuracy and long-term stability. The sensor is mounted into a swaged or straight stainless steel sheath. The sensor outer diameter is 3.2 mm. The minimum sensor length for an exchangeable sensor is 100 mm. The RTD sensor is fitted into a housing with connection head and welded thermowell.
Extension
Standard material Stainless Steel 1.4404 (316 L)
Standard diameter of 10 mm
Preferred standard lengths; 50, 65, and 130 mm
Connection heads (see Tab l e 2 )
The connection heads can be of different types (size DIN A and B) and materials (plastic, aluminum, stainless steel). Its fitting to the rest of the probe and the gland for the cable entry, assure an IP grade of 65 at minimum. All supplied heads have a process connection M24x1.5.
Polished stainless steel DIN A (sanitary applications)
Smoothly contoured design which minimizes crevices for easy
wipe-down
Sanitary Stainless Steel housing for easy-to-clean applications
Mounting of one DIN A or B sized transmitter on DIN plate
Local indication with integral LCD Display Meter
Polished stainless steel DIN B (sanitary applications)
Smoothly contoured design which minimizes crevices for easy
wipe-down
Sanitary Stainless Steel housing for easy-to-clean applications
Mounting of one DIN B sized transmitter on DIN plate
Rosemount aluminum DIN A
Rosemount design
Mounting of one or two transmitters on DIN plate and for
second one optional by the use of extension ring
TZ-A/BL (BUZH)
Thermowell
Thermowell stem styles
Straight thermowell with an outer diameter of 6 mm diameter
must be used for immersion lengths less than 50 mm
More stable Stepped Thermowell with an outer diameter of
10mm reduced to 6 mm must be used for immersion lengths
1
greater than 50 mm (65 mm on parallel thread G
/2-in.
(1/2-in. BSPF))
Thermowell materials
Stainless Steel 1.4404 (316L) for hygienic applications
Thermowell surface qualities
R
< 0,8 μm as standard, electropolishing
a
R
< 0,4 μm optional, electropolishing
a
DIN B head with enlarger space for mounting a DIN A size
(644H) or DIN B size transmitter into the cover by the use of terminal block or two transmitters with flying lead sensors
GR-A/BL (BUZ)
DIN B head with enlarger space for mounting a DIN A size
(644H) or DIN B size transmitter on DIN plates
TZ-A/BK
DIN B head with enlarger space for mounting a DIN A size
(644H) or DIN B size transmitter into the cover by the use of terminal block or two transmitters (248H) with flying lead sensors
Suggested for use in high humidity environments and at low
temperatures to avoid problems due to condensation
www.rosemount.com
11
Page 12
Rosemount 65Q
Table 2. Connection Head Features
September 2014
Typ e Material
Polished DIN A SST 68 Threaded DIN plate, 644, 248 M20 x 1.5, 1/2-in. NPT Yes
Polished DIN B SST 66 Threaded DIN plate, 248 M20 x 1.5, 1/2-in. NPT No
Rosemount Aluminum 68 Threaded DIN plate, 644, 248 M20 x 1.5, 1/2-in. NPT Yes
TZ-A/BK Polyamide 65 Screw-on cap On cover, terminal block 644, 248 M20 x 1.5 No
TZ-A/BL Aluminum 65 Screw-on camp On cover, terminal block 644, 248 M20 x 1.5 No
GR-A/BL Aluminum 65 Screw-on camp DIN plate, 644, 248 M20 x 1.5 No
IP
rating
Lid version Transmi tter moun ting
Conduit connection
LCD display
meter cover
12
www.rosemount.com
Page 13
September 2014
26
N
U
T
D
T
1
D = Process Connection Diameter T1 = Extension Outer Diameter T = Thermowell Outer Diameter U = Immersion Length N = Extension Length
26
N
U
T
1
T
D
B
D = Process Connection Diameter T = Thermowell Outer Diameter T
1
= Extension Outer Diameter UP = Immersion Length (parallel) U
T
= Immersion Length (tapered)
N
P
= Extension Length (parallel)
N
T
= Extension Length (tapered)
Mounting style and process connection
Achieving absolute control through every step of the manufacturing process is essential in order for the production of sanitary fittings to be successful. By achieving such control, each fitting will perform more satisfactorily when incorporated into the process installation, reducing installation time, and ensuring process integrity.
Process connections are available in several sizes
Process connection is continuously welded on the thermowell
in such a way to obtain a welding radius of 3.2 mm at minimum, between the lower surface of the connection and the sensor stem according to 3A standards
All process connections are available in material 1.4404
(316L)
Surface roughness on wetted parts: R
as standard, optional with R
0.4 μm, both electropolishing
a
Tri -C lam p
Welded on the thermowell it allows immersion lengths from
25 to 500 mm, they depend on pipe nominal size used; see details on dimension table
Available in
sizes than 4-in. are available upon request
1
/2 -to-4 in. (19 to 10.16 mm) tube OD sizes, larger
of 0.8 μm is available
a
Rosemount 65Q
Dimensions (mm)
Nominal size
1
/2-in. (12.7 mm) 24.9 6
3
/4-in. (19 mm) 24.9 6
1-in. (25.4 mm) 50.4 6
11/2-in. (38 mm) 50.4 6
2-in. (50.8 mm) 63.9 6
21/2-in. (63.5 mm) 77.4 6
3-in. (76.2 mm) 90.9 6
4-in. (101.6 mm) 119.1 6
(1) Diameter 6 mm as standard for immersion
length U thermowell diameter 10 mm with reduced measuring tip of 6 mm.
50 mm. For U ≥ 50 mm Stepped
D T T1
(1)
10
(1)
10
(1)
10
(1)
10
(1)
10
(1)
10
(1)
10
(1)
10
Available in material 1.4404 (316L), surface finish R
μm is available as standard, optional with R electropolishing
Can be cleaned in place, fast and easy to take down, provide
lead-tight connections and readily adaptable to other forms of piping, allow in-line temperature measurement by the use of counter part and suitable seal O-ring on customer site
Meet the 3-A Sanitary Standard
Meets ASME BPE 2002 standards
Tapered union with coupling nut according to DIN 11851 (dairy connection)
Immersion lengths from 25 to 500 mm
Available in DN10 - DN50 tube OD sizes, larger sizes than 50
DN are available upon request
Available in material 1.4404 (316L), surface finish R
μm is available as standard, optional with R electropolishing
Self-centering, external coupling nut can be easily cleaned
www.rosemount.com
of 0.8
a
of 0.4 μm, both
a
of 0.8
a
of 0.4 μm, both
a
Dimensions (mm)
Nominal size
DN 10 22.5 38 6
DN 25 44 63 6
DN 32 50 70 6
DN 40 56 78 6
DN 50 68.5 92 6
(1) Diameter 6 mm as standard for immersion
length U thermowell diam eter 10 mm with reduced measuring tip of 6 mm.
D B T T
(1)
(1)
(1)
(1)
(1)
50 mm. For U ≥ 50 mm Stepped
1
10
10
10
10
10
13
Page 14
Rosemount 65Q
PARALLEL
26
N
P
U
P
T
T
1
TAP ER ED
26
N
T
U
T
T
T
1
26
N
T
D
U
D = Process Connection Diameter T = Thermowell Outer Diameter U = Immersion Length N = Extension Length
26
N
U
6
25
U = Immersion Length (adjustable)
N = Extension Length (adjustable)
Weld-in ball connection
Immersion lengths from 25 to 500 mm, mostly used for
temperature measurement in vessels
September 2014
Available in material 1.4404 (316L), surface finish R
μm is available as standard, optional with R
of 0.4 μm, both
a
of 0.8
a
electropolishing
Used for Food and Beverage applications
Available with PEEK or SST seal
Threaded process connection
Immersion lengths from 25 mm (tapered threads) and 40 mm
(parallel threads) to 500 mm
Available in material 1.4404 (316L)
Used for temperature measurement in non-hygienic processes
VARIVENT process connection
Immersion lengths from 35 to 500 mm
Available in D = 68 mm
Suitable for hygienic and aseptic applications
Dimensions (mm)
T T
(1)
6
(1) Diameter 6 mm as standard for
immersion length U
≤ 65 mm. For UT ≥ 50 mm or Up
U
p
65 mm Stepped thermowell diameter 10 mm with reduced measuring tip of 6 mm.
1
10
≤ 50 mm or
T
14
Dimensions (mm)
Nominal size
DN 32 - 125 68
D
www.rosemount.com
Page 15
September 2014
h<d/2
d
Installation
Series 65Q Temperature Sensors can be mounted on the wall of pipes or vessels. The counterparts for the process connections and the respective gaskets or sealing rings are generally not supplied with the sensors, and are on the customer's responsibility (FDA material certification, EHEDG and 3A requirements shall be observed). As a general rule, the sensors should be installed in a manner which does not adversely affect their ability to be cleaned. The immersion length may have an influence on the accuracy of the sensors, If it is too short, an error might be generated in the measured temperature, due to the lower temperatures of the process medium near the walls and the heat transfer which occurs through the sensor stem. To avoid this effect of inaccuracy, the immersion length should be, if possible, at least 90 to 120 mm. In pipes with smaller diameter, the axis line of the duct must be reached, and even slightly exceeded by the sensor tip.
Figure 2. Installation Drawing
Rosemount 65Q
In hygienic applications a strict installation rule exists so as not to leave any dead spaces along the run of process fluid. In case of disassembling of the sensor, new gaskets equal to the originals and specific torques must be employed for the reassembly procedure, to assure the stated IP grade of the connection heads.
TriClamp Flange partially fulfills this requirement. For Weld-in Ball Connection, care should be taken by the user in the execution of the welding on the process side; e.g. suitable
weld material, welding radius > 3 mm, absence of pits, crevices etc.)
Tapered Union with Coupling nut according to DIN 11581 (Dairy Process Connection) process connection doesn't meet
as harsh aseptic requirements as requested for BioPharm applications.
Alternatively, for direct insertion into non-hygienic processes, the Series 65Q Temperature Sensor can be ordered with optional G
1
/2-in. (1/2-in. BSPF) or NPT thread mounting.
www.rosemount.com
15
Page 16
Rosemount 65Q
40
25
25
25
25
25
3.2
L
L
3.2
Dimensional Drawings
September 2014
Connection Heads
Rosemount
Aluminum
Codes C, D, 1, 2
Sensor Lead Wire Terminations
Flying leads
Code 0
DIN A
SST
Codes, E, F, 5, 6
DIN B
Polished SST
Codes R, S
Terminal block
Code 2
TZ-A/BL
Aluminum
Code L
FR-A/BL
Aluminum
Code J
TZ-A/BK
Polyamide
Code T
16
www.rosemount.com
Page 17
September 2014
Rosemount 65Q
Thermowells and Process Connections
Tri -C lam p
Threaded parallel Stepped thermowell
Weld-in ball (adjustable)
Tapered union with coupling nut Threaded tapered
Straight thermowell VARIVENT
www.rosemount.com
All dimensions are in millimeters.
17
Page 18
Rosemount 65Q
00813-0100-4827 Rev DA
Product Data Sheet
September 2014
Emerson Process Management
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.) 1-800-999-9307 T (International) (952) 906-8888 F (952) 906-8889
www.rosemount.com
Emerson Process Management
Asia Pacific Pte Ltd 1 Pandan Crescent Signapore 128461 T +65 6777 8211 F +65 6777 0947 Service Support Hotline: +65 6770 8711
Email: Enquiries@AP.EmersonProcess.com
www.rosemount.com
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale The Emerson logo is a trade mark and service mark of Emerson Electric Co. Tri-Clamp, Rosemount, and the Rosemount logotype are registered trademarks of Rosemount Inc. VARIVENT is a registered trademark of GEA Process Engineering Limited. All other marks are the property of their respective owners. © 2014 Rosemount Inc. All rights reserved.