Emerson Rosemount 520 Quick Start Guide

Quick Start Guide
00825-0100-4520, Rev BA
Rosemount™ 520 Level Transmitter
January 2021
Quick Start Guide
January 2021
NOTICE
This guide provides basic guidelines for Rosemount 520 Level Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, or Intrinsically safe installations. Refer to the Rosemount 520 Reference Manual for more information.This manual is also available electronically on
Emerson.com/Rosemount
Explosions could result in death or serious injury.
Installation of this transmitter in hazardous areas must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review approvals section of the Rosemount 520 Reference Manual for any restrictions associated with a safe installation.
Before connecting a HART®-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incentive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contract with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
.
Contents
System readiness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mount the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Connect wiring and power up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Verify transmitter configuration (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Trim the transmitter (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
January 2021
Quick Start Guide

1.0 System readiness

1.1 HART Communication

The Rosemount 520 utilizes the HART Communications Protocol. The most notable advantage of employing HART Communications is that digital information can be transmitted over legacy 4–20mA analog instrumentation wiring. In addition to providing device diagnostics and process alerts, the ability to communicate to the device remotely simplifies basic configuration, calibration, and maintenance. A task-oriented, user optimized interface eliminates errors and speeds routine maintenance tasks.
For the Rosemount 520, HART Protocol facilities two basic operation configurations.
Point-to-point
In this configuration, digital signals are superimposed on the 4–20 mA loop current. One process variable is sent on the 4–20 mA signal and other secondary or calculated process variables can be transmitted digitally over the 4–20 mA signal.
Multidrop
Multidrop refers to the connection of several transmitters to a single communication transmission line. Communication between the host and the transmitters occurs digitally with the analog output of the transmitters deactivated. With HART Revision 7, up to 63 transmitters can be connected on a single twisted pair of wires. Multidrop installation requires consideration of the update rate necessary from each transmitter, the combination of transmitter models, and the length of the transmission line.
For more information, reference “Connect wiring and power up” on page 13.

1.2 Configuration tools

There are several tools that can be used to configure the Rosemount 520.
The Field Communicator is a portable, handheld device used to configure field devices or perform diagnostics for effective troubleshooting in the field without having to use a laptop. The Field Communicator supports all HART devices and is available in an intrinsically safe version.
HART modems allow AMS devices using a PC serial port, PC USB port, or Bluetooth® connectivity. Serial and USB HART modems attach directly to a PC or laptop computer and do not require an external power supply. Bluetooth HART modems require a self-contained power source (AAA batteries) as well as a Bluetooth-ready workstation PC.
HART modems also allow the AMS Instrument inspector to communicate with HART devices using a PC USB or serial port. The AMS Instrument inspector is a PC-based application that performs configuration and maintenance functions for the Rosemount 520 Transmitter. AMS Instrument Inspector is only fully compatible with MACTek VIATOR USB Modem.
Trex communicator to communicate with HART
Quick Start Guide
The Rosemount 520 is not shipped with the AMS Instrument Inspector; the AMS Instrument Inspector can be downloaded free of charge at
Emerson.com/ams-instrument-inspector
.

1.3 Confirm HART Revision capability

If using HART-based control or asset management systems, confirm the HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 Protocol.

1.4 Confirm correct device driver

Verify the latest device driver (DD/DTM™) is loaded on your system to ensure proper communication.
Download the latest DD/DTM at Emerson.com
.

2.0 Handling

Proper handling of the Rosemount 520 is critical. To avoid damaging the transmitter, avoid doing the following:
Lifting by the cable if the transmitter is mounted with fittingsRemoving the protective diaphragm cap before installationApplying pressure to the diaphragm using fingers, tools, or sharp objectsUsing sharp objects to clean the diaphragmSubmerging or blocking the vent tubeBending the cable within a radius of less than 90mm
January 2021

3.0 Mount the transmitter

Note
All installation methods described in the following sections are grounded. If a different installation method is used, the transmitter must be grounded to meet EMC and hazardous location requirements.
January 2021
A
B
C
D
F
E
G
38
Ø 12
55
125 160
50
41
194.5
Quick Start Guide

3.1 Internal mounting

1. Secure the bracket to the tank wall.
2. Secure the transmitter by use of the provided spring. The spring is fitted into the two holes in the bracket. The transmitter can be mounted and dismounted without the use of tools.
3. Secure the transmitter cable to the tank wall.
Note
Emerson recommends protecting the cable by appropriate means to avoid the cable being damaged from, for example, sloshing waves. Emerson recommends installing the transmitter in locations with limited or no turbulence. Emerson recommends avoiding this specific mounting method for service tanks due to challenges associated with performing service and maintenance. Other mounting methods, such as pole mounting, flexible rubber tube mounting and flexible PTFE tube mounting are recommended for installation inside service tanks.
Figure 1. Installation Drawing
A. Optional junction box B. Optional bulkhead fitting C. Dead zone D. Lowest tank bottom
E. Transmitter F. Mounting bracket G. Mounting spring
Quick Start Guide

3.2 Pole mounting

1. Install a suitable deck socket on top of the tank.
2. Secure the transmitter inside the pipe by use of the provided nut and gasket. The recommended torque is 20 N-m.
Figure 2. Installation Drawing
A
34 26
January 2021
40
B
C
A. Optional junction box B. Tank top C. Dead zone D. Lowest tank bottom E. Transmitter
D
F
E
30
193
H
I
G
24
26 41
F. Pipe max. length 2000 mm (yard supply) G. Gasket H. Welding nipple for pole, length 40 mm I. 1-in. end cap
January 2021
A
B
C
D
E
F
JHG
I
34
26
30
25
55
80
193
24
26
41

3.3 1-in. pipe end mounting

1. Secure the provided nipple pipe to the tank wall or to a ball valve.
2. Secure the transmitter to the nipple pipe by use of the provided nut and gasket. The recommended torque is 20 N-m.
Figure 3. Installation Drawing
Quick Start Guide
A. Optional junction box B. Tank top C. Dead zone D. Tank bottom E. Vent pipe
F. Gasket G. Nut H. Nipple pipe, length 80 mm I. Transmitter J. Ball valve (yard supply)
Quick Start Guide
C
A
G
F
E
I
D
K
B
H
L
J
D

3.4 Flange mounting

1. Install a suitable flange connection to the tank wall.
2. Secure the provided flange to the tank flange connection.
3. Secure the transmitter in the flange by use of the provided nut and gasket. The recommended torque is 20 N-m.
Note
Emerson recommends installing a ball valve between the tank wall and transmitter to facilitate transmitter service and maintenance.
Figure 4. Installation Drawing
January 2021
A. Optional junction box B. Refer to Table 1 C. Tank top D. Refer to Table 1 E. Dead zone F. Tank bottom
G. Vent pipe H. Flange I. Gasket J. Transmitter K. Refer to Table 1 L. Nipple pipe connector
January 2021
Table 1. Flange Size for Flange Mounting
Standard D (mm) B (mm) K (mm) d x n (mm)
DN25 PN16 115 16 85 14 x 4
DN40 PN16 150 18 110 18 x 4
JIS25A—16K 125 14 90 19 x 4
JIS40A—16K 140 16 105 19 x 4
1-in. ANSI/150 108 16 79 16 x 4
11/2-in. ANSI/150 127 17.5 98.6 16 x 4
Quick Start Guide
Quick Start Guide

3.5 Flange with 1-in. ball valve mounting

1. Install a suitable flange connection to the tank wall.
2. Secure the provided flange and ball valve to the tank flange connection.
3. Secure the transmitter in the ball valve by use of the provided nut and gasket. The recommended torque is 20 N-m.
Figure 5. Installation Drawing
G
C
A
January 2021
F
DK
A. Optional junction box B. Refer to Table 2 C. Tank top D. Refer to Table 2 E. Dead zone F. Tank bottom G. Vent pipe
E
HIJ
D
B
LMN
64
315
H. Flange I. 1-in. ball valve J. 1-in. nipple pipe connector 1-to 1-in. K. Refer to Table 2 L. Gasket M. 1-in. nut N. Transmitter
Table 2. Flange Size for Flange with 1-in Ball Valve
Standard D (mm) B (mm) K (mm) d x n (mm)
DN25 PN16 115 16 85 14 x 4
JIS25A—16K 125 14 90 19 x 4
1-in. ANSI/150 108 16 79 16 x 4
10
January 2021

3.6 Flexible rubber tube mounting

The transmitter and flange are secured to the rubber tube by tightening clips. This is done by the factory, prior to delivery.
1. Install a suitable pipe in the tank.
2. Insert the rubber tube into the pipe and secure the provided flange to the deck socket.
Figure 6. Installation Drawing
A
D
K
M
B
C
D
L
I
Quick Start Guide
J
E
F
A. Optional junction box B. Refer to Table 3 C. Tank top D. Refer to Table 3 E. Dead zone F. Lowest tank bottom
H. Washer I. Tightening clip J. Rubber tube K. Refer to Table 3 L. Flange M. Cable gland PG11, DIN 89280
G. Transmitter
Table 3. Flange Size for Flexible Rubber Tube and PTFE Tube
Standard D (mm) B (mm) K (mm) d x n (mm)
DN50 PN16 165 19 125 18 x 4
JIS50A—16K 155 20 120 19 x 4
2-in. ANSI/150 153 19 120 19 x 4
G
I
H
11
Quick Start Guide

3.7 Flexible PTFE tube mounting

The transmitter is secured to the PTFE tube by a nut and a ferrule. The PTFE tube is secured to the flange by fittings. This is done by the factory, prior to delivery.
1. Install a suitable pipe in the tank.
2. Insert the PTFE tube into the pipe and secure the provided flange to the deck socket.
Note
The recommended minimum tube bending radius is 130 mm.
January 2021
Figure 7. Installation Drawing
A
B
D
C
E
F
A. Optional junction box B. Refer to Table 3 C. Tank top D. Refer to Table 3 E. Dead zone F. Lowest tank bottom G. Transmitter H. Spacer
M
I. HY-Lok nut and ferrules J. HY-Lok fitting with nut and ferrules K. Refer to Table 3 L.Hydraline SV M. Hydraline SB hose jacket N. Hose fitting with BSP O. Flange P. Cable gland PG11, DIN 89280
D
K
P
O
N
L
H
1
/2-in. PTFE hose braided with stainless steel
1
/2-in. male thread
M
J
I
G
12
January 2021
Quick Start Guide

4.0 Connect wiring and power up

4.1 Signal cable

Shielded twisted pair cable should be used for best result. Use wire with minimum diameter of 0.51 mm (24 AWG). To ensure the functionality of the digital communication the following table shall be used to determine the maximum signal cable length:
Table 4. Signal Cable Length
Transmitter cable length Signal cable maximum length
0 m < x 25 m 825 m
25 m < x 50 m 770 m
50 m < x 100 m 660 m
100 m < x 200 m 440 m
200 m < x 300 m 220 m
Note
The calculated signal cable lengths are based on a conventionally constructed
cable with a capacitance equal to or less than 200 pF/m.
Maximum allowed transmitter cable length for installation in hazardous area is
75 m. Maximum allowed total cable length, transmitter cable plus signal cable, must be determined by IS loop calculations.

4.2 Transmitter cable

The vent tube must be directed to an area with atmospheric pressure. If the transmitter cable terminates in an area with overpressure or negative pressure relative to the atmospheric pressure in the tank, the vent tube must be directed to an area with atmospheric pressure equal to the pressure inside the tank.

4.3 Power supply

The power supply and load limitations are described in Figure 8 on page 14. The total resistance load is the sum of the resistance of the signal cable and the load resistance of the controller, indicator, and related equipment. Note that the resistance of intrinsic safety barriers, if used, must be included.
13
Quick Start Guide
~
A
B
Figure 8. Load Limitation
Maximum loop resistance = 43.5 x (Power supply voltage – 10) HART communication requires a minimum loop resistance of 250 ohm.
Table 5. Load Resistance and Voltage Supply Limits
Parameter Limit
R
( ) 250
1
R
( ) 1130
2
V
(V) 10
min
V
(V) 15.75
1
V
(V) 36
2
January 2021

4.4 Wiring diagrams

Figure 9. Point-to-Point
A. Field Communicator or PC with HART modem B. Rosemount 520
14
January 2021
~
A
BBB
Figure 10. Multidrop
A. Field Communicator or PC with HART modem
B. Rosemount 520
Quick Start Guide
15
Quick Start Guide
January 2021

5.0 Verify transmitter configuration (optional)

Transmitters are shipped from Emerson fully configured per request or by the standard factory default configuration. The configuration can be verified using any HART capable configuration tool. Configuration instructions for the Field Communicator are included in this step.

5.1 Verify configuration using the Field Communicator

A Rosemount 520 Device Driver (DD) must be installed on the Field Communicator to verify configuration. Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com information.
Fast Key sequences for the latest DD are shown below in Table 6. A check ( indicates the basic configuration parameters. At minimum, these parameters should be verified as part of configuration and startup.
Table 6. Fast Key Sequences (Device Revision 2, DD Revision 1)
Function Fast Key sequence
Alarm and Saturation Levels 2, 2, 2, 5, 7
Damping 2, 2, 1, 1, 5
Range Values 2, 2, 2
Tag 2, 2, 6, 1, 1
Units 2, 2, 1, 1, 4
Analog Output Alarm Direction 2, 2, 2, 5, 2
Transfer Function 2, 2, 1, 1, 6
Digital Zero Trim 3, 4, 1, 3
Upper Sensor Trim 3, 4, 1, 1
Lower Sensor Trim 3, 4, 1, 2
Scaled D/A Trim (4–20 mA Output) 3, 4, 2
Digital to Analog Trim (4–20 mA Output) 3, 4, 2
Date 2, 2, 6, 1, 5
Descriptor 2, 2, 6, 1, 6
Message 2, 2, 6, 1, 7
Long Tag 2, 2, 6, 1, 2
Scaled Variable 3, 2, 3
Burst Mode 2, 2, 4, 3
Rerange with Keypad 2, 2, 2, 1
Loop Test 3, 5, 1
Sensor Temperature/Trend 3, 3, 2
Simulate Digital Signal 3, 5, 2
Transmitter Security (Write Protect) 3, 4, 4, 1
for more
)
16
January 2021
Quick Start Guide

6.0 Trim the transmitter (optional)

Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim. A zero trim is a single-point adjustment to compensate for mounting position. When performing a zero trim, ensure the vent tube is vented to atmospheric pressure.

6.1 Zero trim using the Field Communicator

1. Connect the Field Communicator (see “Connect wiring and power up” on page 13 for instructions).
2. At the main menu, input the 3, 4, 1, 3 Fast Key sequence.
3. Follow the commands to perform a zero trim.
17
Quick Start Guide

7.0 Product certifications

Rev 1.1

7.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at
Emerson.com/Rosemount

7.2 Europe

I1 ATEX Intrinsic Safety
Certificate: Baseefa15ATEX0075X Standards: EN60079-0:2012+A11:2013, EN60079-11:2012 Markings: II 1 G Ex ia IIC T4 Ga (–40 °C T
Table 7. Input Parameters
Parameter HART
Voltage U
i
Current I
i
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. The Rosemount 520 Transmitter enclosure is manufactured of titanium and may present a frictional ignition risk and must be protected from impact or abrasion if located in a zone 0.
2. When a junction box is not used, the free ends of the cable must be afforded a degree of protection of at least IP20.
3. The optional polyester junction box present a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth.
Installation in Hazardous Locations
When installing the Rosemount 520 in hazardous areas, to reduce the risk of electrostatic charges the resistance of the titanium transducer to earth should be less than10
i
.
+85 °C)
a
30 V
200 mA
1.0 W
i
42 nF
77 H
January 2021
9
Ω.

7.3 International

I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 15.0050X Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: Ex ia IIC T4 Ga (–40 °C T
Table 8. Input Parameters
Parameter HART
Voltage U
i
Current I
i
Power P
i
Capacitance C
Inductance L
18
i
+85 °C)
a
30 V
200 mA
1.0 W
i
42 nF
77 H
January 2021
Quick Start Guide
Special Conditions for Safe Use (X):
1. The Rosemount 520 Transmitter enclosure is manufactured of titanium and may present a frictional ignition risk and must be protected from impact or abrasion if located in a zone 0.
2. When a junction box is not used, the free ends of the cable must be afforded a degree of protection of at least IP20.
3. The optional polyester junction box present a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth.
Installation in Hazardous Locations
When installing the Rosemount 520 in hazardous areas, to reduce the risk of electrostatic charges the resistance of the titanium transducer to earth should be less than10

7.4 Brazil

I2 INMETRO Intrinsic Safety
Certificate: UL-BR 16.0260X Standards: ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013 Markings: Ex ia IIC T4 Ga (–40 °C T
Table 9. Input Parameters
Parameter HART
Voltage U
i
Current I
i
Power P
i
Capacitance C
Inductance L
i
i
Special Conditions for Safe Use (X):
1. The Rosemount 520 Transmitter enclosure is manufactured of titanium and may present a frictional ignition risk and must be protected from impact or abrasion if located in a zone 0.
2. When a junction box is not used, the free ends of the cable must be afforded a degree of protection of at least IP20.
3. The optional polyester junction box present a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth.
30 V
200 mA
1.0 W
42 nF
77 H
+85 °C)
a
9
Ω.
19
Quick Start Guide

7.5 Additional certifications

SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 15-HS1462157-PDA Intended Use: Marine & Offshore Applications – Pressure transmitter used for
determining tank levels
SBV Bureau Veritas (BV) Type Approval
Certificate: 43940 Requirements: Bureau Veritas Rules for the Classification of Steel Ships Application: Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS;
Pressure transmitter type 520 cannot be installed on diesel engines
SLL Lloyd’s Register (LR) Type Approval
Certificate: 16/60006 Requirements: Lloyd’s Register’s Type Approval System and Test Spec 1. Application: ENV Categories 1-4
SDN Den Norske Veritas (DNVGL) Type Approval
Certificate: TAA000007Z Requirements: Det Norske Veritas’ Rules for Classification of Ships, High Speed and
Light Craft, and Det Norske Veritas’ Offshore Standards
Application:
Location classes
Type 520
Temperature B
Humidity B
Vibration A
EMC A
Enclosure D/IP66/IP68
January 2021
SKR Korean Register (KR) Type Approval
Certificate: CPH21541-AE002 Certificate: SHI23018-AE001 Requirements: Pt. 6, Ch. 2, Art. 301 of the Rules for Classification, Steel Ships
SNK Nippon Kaiji Kyokai (NK) Type Approval
Certificate: TA17262M Requirements: Chapter 1, Part 7 of "Guidance for the Approval and Type Approval of
Materials and Equipment for Marine Use" and the relevant Society's Rules
SCS China Classification Society (CCS) Type Approval
Certificate: TAA000007Z
Requirements: Det Norske Veritas’ Rules for Classification of Ships, High Speed and
Light Craft, and Det Norske Veritas’ Offshore Standards
20
January 2021
EU Declaration of Conformity
No: RMD 1107 Rev. C
Page 1 of 2
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount 520 Level Transmitter
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function name - printed)
Chris LaPoint
(name - printed)
1-Feb-19
(date of issue)
Figure 11. Rosemount 520 Declaration of Conformity
Quick Start Guide
21
EU Declaration of Conformity
No: RMD 1107 Rev. C
Page 2 of 2
EMC Directive (2004/108/EC) This directive is valid until 19 April 2016 EMC Directive (2014/30/EU) This directive is valid from 20 April 2016
Harmonized Standards:
EN 61326-1:2013, EN 61326-2-3:2013
ATEX Directive (94/9/EC) This directive is valid until 19 April 2016 ATEX Directive (2014/34/EU) This directive is valid from 20 April 2016
Baseefa15ATEX0075X - Intrinsic Safety
Equipment Group II Category 1 G
Ex ia IIC T4 Ga
Harmonized Standards:
EN60079-0:2012+A11:2013, EN60079-11:2012
ATEX Notified Bodies
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
January 2021
Quick Start Guide
23
Emerson Automation Solutions
Damcos A/S
Aaderupvej 41 DK-4700 Naestved Denmark
+45 55 78 72 00 +45 55 78 72
Emerson Automation Solutions Marine System
(Shanghai) Co. Ltd.
T3-7, 128 Long Gui Road JinQiao Export Process Xone (South). Post Code: 201201 Shanghai, China
+86 21 5858 9666 801 +86 21 3897 266 CN.NTM@Emerson.com
Emerson Automation Solutions
Rosemount Tank Radar AB
Box 13045 SE-40251 Gothenburg Sweden
+46 31 337 00 00 +46 31 25 30 22
Quick Start Guide
00825-0100-4520, Rev BA
January 2021
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners. © 2021 Emerson. All rights reserved.
The contents of this publication are presented for information purposes only, and while efforts has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services described herein or their use or applicability. Standard Terms and Cond itions of Sale can be issued by contacting Damcos A/S. We reserve the right to modify or improve the designs and specifications of our products at any time without notice.
Loading...