Emerson PS2-Y7A User Manual

Emerson PS2-Y7A User Manual

PRESSURE CONTROLS

PS2 SERIES

 

 

PS2 SERIES PRESSURE SWITCH

DUAL CONTROL

PS2 Dual Pressure Controls are designed for use on high and low pressure applications in refrigeration, air conditioning, and heat pump systems. This control reacts to changes in either low or high side pressures, providing single-device control of the compressor or other electrical device.

PS2-Y7A

FEATURES

Adjustable pressures and differentials

Narrow adjustable differential depending on model

Range and differential pointer in units bar and psig

Range and differential individually lockable by tab

High rated SPDT contacts for all versions

Captive terminal and cover screws

Manual toggle for system checkout and override

Factory installed wire bridge for reduced installation effort

High side convertible from manual to auto reset.

Automatic and manual reset models available

SPECIFICATIONS

 

Electrical Ratings..................................

SPDT Switch Rated for 12 FLA and 72 LRA at 240 VAC

.........................................................................................

and 16 FLA and 96 LRA at 120 VAC

UL/CUL File Number..................................................................................................

E85974

........................................................................................

CE per (LVD) Low Voltage Directive

MODEL NUMBER NOMENCLATURE - Example: PS2-Y7A

SERIES

 

FUNCTION

PRESSURE RANGE

CONNECTION TYPE

 

 

 

 

 

 

PS2

 

 

-Y

7

A

 

 

 

 

 

 

 

X = Auto Reset

 

Internal range and differential adjustments

 

A = 1/4"" SAE Male Flare

Dual Adjustable

 

 

 

7 = Left Side: 9"Hg to 102 psig (-0.3 to 7 bar)

K = 1 m (3 ft.) Cap Tube, 1/4"" Flare Nut

Y = Low Side: Auto Reset

 

External range and differential

Pressure Switch

 

Right Side: 87 to 464 psig (6 to 32 bar)

L = 1 m (3 ft.) Cap Tube, 1/4"" ODM Solder Connection

 

High Side: Convertible Reset

adjustments

 

 

 

 

 

 

 

 

PS2 PRESSURE SWITCH DUAL CONTROL

 

 

LOW PRESSURE SIDE

 

HIGH PRESSURE SIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

DIFFERENTIAL

 

FACTORY

PRESSURE

 

 

FACTORY

CONNECTION

MODEL

ITEM

FUNCTION

RANGE

 

RANGE

 

SETTING

RANGE

DIFFERENTIAL

 

SETTING

TYPE

NUMBER

NUMBER

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto Reset

4.4 to 102 psig,

 

15 to 73 psig

 

49/65 psig

87 to 464 psig

Fixed

 

290 psig

1/4" SAE Male Flare

PS2-Y7A

099008

0.3 to 7 bar

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual Reset

4.4 to 102 psig,

 

15 to 73 psig

 

49/65 psig

87 to 464 psig

Fixed

 

290 psig

1 m (3 ft.) Cap Tube

PS2-Y7K

099009

0.3 to 7 bar

 

 

 

w/1/4" Flare Nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-4899_146_12.16.20

Loading...