PRESSURE CONTROLS PS2 SERIES
PS2 SERIES PRESSURE SWITCH
DUAL CONTROL
PS2 Dual Pressure Controls are designed for use on high and low pressure applications
in refrigeration, air conditioning, and heat pump systems. This control reacts to
changes in either low or high side pressures, providing single-device control of the
compressor or other electrical device.
PS2-Y7A
FEATURES
• Adjustable pressures and differentials
• Narrow adjustable differential depending on model
• Range and differential pointer in units bar and psig
• Range and differential individually lockable by tab
• High rated SPDT contacts for all versions
• Captive terminal and cover screws
• Manual toggle for system checkout and override
• Factory installed wire bridge for reduced installation effort
• High side convertible from manual to auto reset.
• Automatic and manual reset models available
SPECIFICATIONS
Electrical Ratings ................................. SPDT Switch Rated for 12 FLA and 72 LRA at 240 VAC
.........................................................................................and 16 FLA and 96 LRA at 120 VAC
UL/CUL File Number ................................................................................................. E85974
........................................................................................CE per (LVD) Low Voltage Directive
MODEL NUMBER NOMENCLATURE - Example: PS2-Y7A
SERIES FUNCTION PRESSURE RANGE CONNECTION TYPE
PS2
Dual Adjustable
Pressure Switch
X = Auto Reset
Y = Low Side: Auto Reset
High Side: Convertible Reset
-Y
Internal range and differential adjustments
External range and differential
adjustments
7 A
7 = Left Side: 9"Hg to 102 psig (-0.3 to 7 bar)
Right Side: 87 to 464 psig (6 to 32 bar)
A = 1/4"" SAE Male Flare
K = 1 m (3 ft.) Cap Tube, 1/4"" Flare Nut
L = 1 m (3 ft.) Cap Tube, 1/4"" ODM Solder Connection
PS2 PRESSURE SWITCH DUAL CONTROL
LOW PRESSURE SIDE HIGH PRESSURE SIDE
FUNCTION
Auto Reset
Manual Reset
PRESSURE
RANGE
4.4 to 102 psig,
0.3 to 7 bar
4.4 to 102 psig,
0.3 to 7 bar
DIFFERENTIAL
RANGE
15 to 73 psig 49/65 psig 87 to 464 psig Fixed 290 psig 1/4" SAE Male Flare PS2-Y7A 099008
15 to 73 psig 49/65 psig 87 to 464 psig Fixed 290 psig
FACTORY
SETTING
PRESSURE
RANGE DIFFERENTIAL
FACTORY
SETTING
CONNECTION
TYPE
1 m (3 ft.) Cap Tube
w/1/4" Flare Nut
MODEL
NUMBER
PS2-Y7K 099009
ITEM
NUMBER
R- 48 99_146 _12.16. 20