Emerson Manual: Controlinc Network Master Model M124, Version 3.1 Manuals & Guides

Controlinc Network Master
Model M124 Version 3.1
Installation and Operations Manual
VCIOM-17039-EN Rev. 0
April 2022
Notes
April 2022
Installation and Operations Manual
This page intentionally left blank
Installation and Operations Manual
Table of Contents
Section 1: Introduction
1.1 Reference Documents ................................................................................... 1
1.2 System Conguration ................................................................................... 2
1.3 General System Specications ....................................................................... 4
1.3.1 Environmental .................................................................................... 4
1.3.2 Electrical ............................................................................................ 4
1.3.3 LCD Touch Panel Specications ........................................................... 4
1.3.4 M124 PLC Port 2 Setup for Database Exchange Link (DxL) ................... 5
1.4 Parts List ....................................................................................................... 7
Section 2: Installation
2.1 Mounting ...................................................................................................... 8
2.1.1 Rack Mount ...................................................................................... 10
2.2 Power Input ................................................................................................ 11
2.3 Field Network Wiring .................................................................................. 11
2.3.1 Network Grounding ......................................................................... 12
2.3.2 Network Termination ....................................................................... 13
2.4 Modbus Host Cables ................................................................................... 13
Table of Contents
April 2022
Section 3: Conguring the System
3.1 System Protection and Software Versions ................................................... 14
3.1.1 Password Protection ......................................................................... 14
3.1.2 CoProcessor Software Protection ..................................................... 14
3.1.3 Software Version Identication ........................................................14
3.2 Selecting Diagnostic/Programming Mode ................................................... 15
3.3 Chassis Identication and Hot Standby ........................................................ 15
3.4 Conguring Modbus Host Port Interface(s) ................................................. 15
3.5 Conguring the Field Network .................................................................... 15
3.5.1 Conguring the Number of Slaves .................................................... 15
3.5.2 Conguring Field Network Baud Rate ............................................... 15
3.5.3 Conguring Network Master Receiver Time-Out ............................... 16
3.5.4 Conguring Report-By-Exception (RBE) ............................................ 16
3.6 Conguring Network Address Sequence ..................................................... 16
3.7 Conguring Device Types ............................................................................ 17
Table of Contents
i
Table of Contents
April 2022
Section 4: Modbus Register Maps
Installation and Operations Manual
4.1 Valve Status and Command Registers per Modbus Function Code ............... 18
4.2 Valve Status Bit Data for Each Valve ............................................................. 19
4.2.1 Multiple Valve Status Locations Using Function Code 02 ................... 20
4.2.2 Multiple Valve Status Data Using Modbus Function Code 03 ............. 20
4.2.3 Multiple Valve Status Data Using Modbus Function Code 04 ............. 21
4.3 Reading Valve Position and Setpoint ............................................................ 21
4.4 Writing Analog Valve Position Setpoint (Function Codes 06 and 16) ............ 22
4.5 Writing Discrete Commands to Valve Actuators .......................................... 22
4.6 Reading Auxiliary Analog Inputs Using Function Code 03 ............................ 23
4.6.1 Reading Torque Analog Input Using Function Code 03 ...................... 23
4.7 Reading and Writing Auxiliary Analog Outputs ............................................ 23
4.8 Reading User Discrete Inputs ....................................................................... 23
4.9 Writing User Relay Outputs (MRTU Support) ............................................... 24
4.10 System Status Word .................................................................................... 25
4.11 Combined System Alarms ........................................................................... 26
4.12 Network Fault Location ............................................................................... 26
4.13 M124 Global Database and Modbus Holding Register Map .......................... 26
Section 5: Theory of Operation
5.1 Valve Actuator Network Connections .......................................................... 30
5.2 Power-up Initialization ................................................................................. 30
5.3 Hot Standby Fail-Over ................................................................................. 31
5.3.1 Modbus Host Link and Fail-Over ........................................................ 31
5.4 Network Fault Detection ............................................................................. 32
5.5 Polling Process ............................................................................................ 32
5.6 Report-by-Exception ................................................................................... 32
5.7 Priority Scan ................................................................................................ 33
5.8 Writing Discrete Commands to Valve Actuators .......................................... 33
5.9 Writing Position Setpoint ............................................................................ 33
5.10 Writing Analog Outputs .............................................................................. 33
5.11 Writing User Relay Outputs ......................................................................... 34
5.12 Writing ESD Command ............................................................................... 34
Section 6: Software Source Code
6.1 Host Database Conguration Aid ................................................................ 35
Section 7: LCD Touch Panel Backup Terminal Operation
7.1 Home Screen ..............................................................................................36
7.1.1 Alarm Display ................................................................................... 37
7.1.2 Security Codes Screen ...................................................................... 37
7.1.3 ESD Screen ....................................................................................... 38
7.1.4 Switch Active Master to Standby Screen ...........................................39
7.2 Valve Control and Status Display ................................................................. 40
7.2.1 Valve Control .................................................................................... 41
7.2.2 Navigation Buttons ...........................................................................41
ii
Table of Contents
Installation and Operations Manual
VCIOM-17039-EN Rev. 0 April 2022
Section 1: Introduction
Section 1: Introduction
Emerson Controlinc Network Masters are the master of Emerson Controlinc valve actuator networks with Modbus RTU protocol. The system provides network management, data concentration, and protocol conversion, off-loading the host system of these tasks. This enhances overall system performance and minimizes software development and system conguration tasks by the system integrator. The Network Master serves as the master of a master/slave network. It manages the network by keeping an orderly cycle of data transfers to and from the slave devices (valve actuators). It handles error detection, alarming, and network recovery. The Network Master serves as a data concentrator for the host by providing a common database for all slave devices. The host is required to communicate with only one slave device (network master) for all data transfers to and from the eld. Data can be transferred between the network master and host in large blocks at a much higher
communications rate than would be possible if the host communicated with each slave device
(valve actuator) on the eld network. The Network Master acquires data from the valve actuators by polling or scanning each device in a sequence of slave address from a table called a scan list. Polling is a process of the Network Master sending to each slave address, a command to return its status information, including alarms, discrete and analog inputs and outputs. When control commands (valve open, stop, close, position setpoint, etc.) are generated by a host system up-line of the Network Master, it then sends the appropriate commands over the network to the addressed
slave device. A more detailed functional description of operation is provided in the Theory of Operation section of this manual.
1.1 Reference Documents
In addition to this Controlinc Network Master Operations Manual, the following references are required for proper installation, conguration, and operation of the Network Master. All reference documents are supplied with the system. Paragraph numbers, as listed below, are used for reference
to these documents in this manual.
1. EIM TEC2000 Installation and Operations Manual E2K-405-0703
2. Bettis XTE3000 Electric Actuator IOM
3. FACTS Engineering 205 Basic CoProcessor User’s Manual
4. FACTS Extended BASIC Reference Manual
5. Direct Logic DL205 User Manual
All manuals and software are provided in electronic format with the system on CD.
Introduction
1
Section 1: Introduction
April 2022
1.2 System Conguration
Controlinc Network Master Model M124 contains redundant valve actuator network masters in a single enclosure. M124 supports one Controlinc E>Net ring network with up to 124 valve actuators.
The system uses standard RS485 and Modbus RTU protocol.
Redundant systems consist of two identical chassis with identical software. One is the primary master and the other a hot standby master. The two chassis may switch roles of primary and hot standby at
any time. Figure 1 shows the specic system conguration of the supplied system. Version 1.0 and later communicate with DCM 320B valve actuators with Version 1.0 or later rmware that control both block valves (Open, Stop, Close) and modulating or positioner type valves. The system consists of two six-slot chassis with each chassis having a central processor located in Slot 0, which provides a global database for the CoProcessors installed the chassis. The central processor also performs such functions as watchdog timers and system alarm generation for the CoProcessors. It also provides
interrupt control for fast data transfers between processor modules.
Each chassis consists of two Modbus Slave modules located in Slots 3 and 4. These slave modules communicate with a redundant Modbus host systems up line. The CoProcessor installed in Slot 1 is
the Controlinc Network Master to a ring eld network. Two ports of the Network Master module are connected to Network Interface Module (NIM) Model M124I with redundant, isolated ports. Each NIM has connections to the redundant Network Master modules of the redundant chassis. Any one of the four ports may acquire data from and control all actuators in the eld in either direction around the network. Multiple M124 systems may be networked from a single host or redundant hosts to automate any size system form a few valves to thousands of valves covering a large network area. Ten (10) independent processors ensure full redundancy of all functions in a single unit. All components except display are redundant with double-redundant host links to redundant hosts and automatic processor hot swapping. Host equipment is not required to implement any fail-over logic. Full-time redundant Modbus host links are standard. Plug-in modular construction and DIN-rail mounting of components ensure minimum MTR, minimizing down time. LCD screen and keypad provide valve actuator monitor and control of all valves in case redundant host links fail.
All valve status and alarms may be displayed by the LCD terminal for maintenance purposes.
The LCD terminal is a valuable troubleshooting tool during system commissioning. A more detailed
description of operation is provided in the Theory of Operation section of this manual.
Installation and Operations Manual
2
Introduction
Installation and Operations Manual
VCIOM-17039-EN Rev. 0 April 2022
Figure 1 Model M124 Valve Control System
Section 1: Introduction
HOST 1
HOST 2
Host 1 NIM TCP Host 2
M124
Primary
Master
M124
Secondary
Master
A NIM 124I B
Controlinc
E>Net Ring
Network
Modbus TCP/IP Ethernet
Links 10/100 BaseT
RS232 Modbus RTU
Links at 115.2K baud
NEMA Enclosure
with LCD Touch Panel
124
Actuators
per Network
Introduction
3
Section 1: Introduction
April 2022
Installation and Operations Manual
1.3 General System Specications
1.3.1 Environmental
Storage temperature: -20 °C to 70 °C
Ambient operating temperature: 0 °C to 55 °C
Ambient humidity: 5 to 95% (non-condensing)
Vibration resistance: MIL STD 810C, Method 514.2
Shock resistance: MIL STD 810C, Method 516.2
1.3.2 Electrical
Standard input voltage: 117 V AC at 50/60 Hz (100 - 240 V AC) (other options available)
Total current at nominal voltage: 0.65 A (includes LCD panel)
Maximum inrush current: 60 A
Total power consumption: 25 VA nominal (includes LCD)
Isolation resistance: >10 MΩ at 500 V DC
Dielectric withstand voltage: 1500 V AC at 1 min.
1.3.3 LCD Touch Panel Specications
Display type: 5.7 in. diagonal color TFT
Enclosure: NEMA 4 (IP65)
Input voltage: 12 - 24 V DC
Power consumption: 16.0 W, 1.30 A at 12 V DC, 0.66 A at 24 V DC
Operating temp: 0 °C to 50 °C
4
Introduction
Installation and Operations Manual
VCIOM-17039-EN Rev. 0 April 2022
Section 1: Introduction
1.3.4 M124 PLC Port 2 Setup for Database Exchange Link (DxL)
Primary Master Secondary Master
DirectNet DirectNet
Base Timeout x 1 Base Timeout x 1
RTS/CTS 0 mS, 0 mS RTS/CTS 0 mS, 0 mS
Station Address 2 Station Address 1
38400, 1, Odd, Hex 38400, 1, Odd, Hex
PLC to PLC cable is RS232, 3-wire, rolled, with 15-pin D connectors
Primary Secondary
Pin/Wire Pin/Wire
2 Red 3 Red
3 Wht 2 Wht
7 Grn 7 Grn
8 Blk 8 Blk
Introduction
5
Section 1: Introduction
April 2022
Figure 2 M124 Internal Wiring
Installation and Operations Manual
Actuator
RS485
Network
Port A
Actuator
RS485
Network
Port B
6
Introduction
Installation and Operations Manual
Section 1: Introduction
VCIOM-17039-EN Rev. 0 April 2022
1.4 Parts List
Figure 3 is a list of materials supplied within each Network Master enclosure. This may be used as a
spare parts list.
Figure 3
Actuator RS485
Network
Port A
Actuator RS485
Network
Port A
Item Qty Model
Emerson Part
Number
Description
1 1 EA9-T6CL-R VA001-667-58 Color graphics LCD touch panel
2 1 2938730 VA2001803004 Power Supply, 24 V DC, 3 A
3 1 NIM124I VA84713 Network Interface Module, Iso. RS485 4 2 D2-06B-1 VA2001805050 Base, 6-slot with 110/220 V AC P/S 5 2 D2-250-1 VA2001805052 CPU, DL205-250 6 8 - VA37586-1 Cable, CoProcessor to NIM, 6x6, 11" 7 8 F2-CP128 VA2001805051 CoProcessor, Overdrive 8 1 NIM-TCP VA87065 Network Interface Module, Ethernet
9 1 - VA37587 Cable, CPU to CPU DxL 10 3 BK/MDA-1 VA7019900428 Fuse, 1 A, 250 V, Time Lag, CRM MDA 11 2 - VA37586-2 Cable, CoProcessor to LCD, 6x6, 46" 12 1 - VA84725 LCD com adapter
Introduction
7
Section 2: Installation
April 2022
Section 2: Installation
If the system is supplied from the factory in an NEMA enclosure, no internal wiring is required except for connecting power and eld network wiring. The next three Sections 2.1, 2.2 and 2.3 discuss mounting, power input and eld network wire connections to the NIM.
2.1 Mounting
The enclosure is rated for NEMA 4/12 and IP65/IP55. Dimensions of the enclosure are shown in Figure 4. Mounting dimensions are shown in Figure 5. The enclosure may be bulkhead mounted using the internal mounting holes. External mounting brackets may be used if desired. When mounting using the internal mounting holes, caution must be used to ensure the holes are sealed to maintain the NEMA/IP rating. The enclosure is supplied with ve 1/2" compression type cable entry hubs. These may be tted with conduit type ttings if desired. If the system includes backup LCD keypad terminal, some planning is required to allow for proper height above the oor to view the display and properly operate the keypad.
Installation and Operations Manual
Figure 4
(5) Cable entries are provided for: (1) Power Cable (2) Field RS485 Network Cables (2) Host RS485 Network Cables
NOTE
Allow 1 in. clearance on left side for ventilation and room for the door to swing open to left.
8
Installation
Installation and Operations Manual
VCIOM-17039-EN Rev. 0 April 2022
Section 2: Installation
Figure 5 NEMA Box Mounting
Installation
9
Section 2: Installation
April 2022
2.1.1 Rack Mount
The enclosure is designed for standard EIA 19" DIN rail rack mounting. Dimensions of the enclosure are shown in Figure 6. The enclosure conforms to EIA RS310, IEC 297-1, and DIN 41 494, Part 1 standards. The rack in which the enclosure(s) are mounted must allow a minimum of 20" (508 mm) depth, allowing space for cable connections. If the system includes backup LCD keypad terminals, some planning is required to allow for proper height above the oor to view the display and operate the keypad properly.
Figure 6
Installation and Operations Manual
Enclosure Depth = 15.0" (381 mm)
Allow a total depth of 20" (508 mm)
for rear panel cable connections.
Figure 7 Rear Panel View
PORT A PORT B PORT C PORT D HOST 1 HOST 2
10
Installation
Installation and Operations Manual
VCIOM-17039-EN Rev. 0 April 2022
Section 2: Installation
2.2 Power Input
The system operates from 120 V AC or 220 V AC, 50/60 Hz single-phase power with internal three-wire power terminals. Ensure that a good safety ground is provided to the electrical supply to which the power input is connected. The system contains three main fuses (6.3x32 mm, 1 A) in the DIN-rail mounted fuse blocks. Each chassis and the LCD terminal are independently fused. Each NIM
is powered from redundant 24 V DC power supplies from the two chassis power supplies. The LCD terminal is powered from an independent 24 V DC power supply. All other modules within the unit are powered over the base back plane from the associated main chassis power supply.
2.3 Field Network Wiring
The eld network is wired in a ring conguration from Port A around a loop to Port B of the network master. Beginning at Port A, the network is wired to Port A of the rst actuator and then from Port B of the rst actuator to Port A of the second actuator and so on until the network returns from Port B of the last actuator to Port B of the network master. Networks may have parallel wired (BUS wired) actuators between series wired actuators. Always wire parallel actuators to Port A
and remove termination and bias. Do not connect more than 15 actuators in parallel between any
two series connected actuators. Networks are polarized with (+) and (-) symbols on all drawings. Proper operation requires that polarity be observed at all connections. Connect the eld networks to the Port A and B connectors on the NIM in the network master as shown in Figure 8. The networks must be connected to Port A and Port B of the valve actuators as shown in the wiring diagram of the DCM 320B manual, and XTE manual. DCM 320B with Controlinc supports many different network topologies. This manual supports only a single ring E>Net network topology that allows a combination of parallel (BUS) and series E>Net connections on the same network.
Installation
11
Loading...
+ 33 hidden pages