Technical Note
00840-1300-4420, Rev AA
06/14
Connecting an Emerson® Wireless Gateway to
the ABB Totalflow XRC 6490
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
Emerson WirelessHART® Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
1.1 Purpose
This document describes how to connect an Emerson Smart Wireless Gateway to a ABB Totalflow
XRC6490using serial Modbus
®
.
1.2 Emerson WirelessHART® Gateway
ABB Totalflow XRC6490 with PCCU configuration software
Emerson Smart Wireless Gateway1420/1410
A computer setup to connect to the Gateway
1.3 Assumptions
1. The user of this document has a fundamental understanding of the ABB Totalflow PCCU
software.
2. A comm port has been added in the Totalflow configuration for Modbus communications.
3. The user of this document has a fundamental understanding of the Gateway.

Emerson WirelessHART Gateway
06/14
1.4 Wiring
1. Wire the modbus terminals.
Note
The Smart Wireless Gateway 1420 wiring diagram is shown below.
Figure 1-1. Standard Terminal Block
Technical Note
00840-1300-4420, Rev AA
2
Emerson WirelessHART Gateway

Technical Note
00840-1300-4420, Rev AA
2. Connect the modbus “A” wire to pin 6 and “B” wire to pin 8. In this case we are
Figure 1-2. Connecting to Comm Port 2
Emerson WirelessHART Gateway
06/14
connecting to Comm Port 2.
Emerson WirelessHART Gateway
3

Emerson WirelessHART Gateway
06/14
1.5 Configuration
1. Configure the 1420 for serial modbus communication. This can be done using the web
browser. In this case we are using the following communication settings, Baud Rate =
9600, Start Bit = 1, Data Bit = 8, Parity = None, Stop Bit = 1.
Figure 1-3. 1420 Settings for serial Modbus communications
Technical Note
00840-1300-4420, Rev AA
Figure 1-4. 1420 Settings for serial Modbus Register Map
4
Emerson WirelessHART Gateway

Technical Note
00840-1300-4420, Rev AA
2. Configure the Totalflow by starting the PCCU software. Click the Entry button to
Figure 1-5. Starting the PCCU software
Emerson WirelessHART Gateway
06/14
connect to the Totalflow XRC 6490 hardware.
3. In this case we have renamed Comm Port 2 to RSMT Modbus. Select the Comm Port
configured for modbus communications.
4. In the “Setup” tab, set the Baud Rate and the Register Format values. The Baud Rate
must match with the Gateway modbus parameter settings.
Note
The value entered in “Register Format” will depend on what modbus registers you are reading in
the Gateway.
5. Based on what you chose in the Gateway Modbus communication web page for “Use
swapped Floating Point format”, enter in correct Register Format value.
a. For Gateways not using swapped floating point format, select the “16 BIT Modicon”.
b. If using the swapped format, then choose “16 Bit Word Swapped” in the Totalflow.
Figure 1-6. Select the Comm Port configured for Modbus communications
Emerson WirelessHART Gateway
5