Liebert has reinvented the
double-conversion
UPS. The Npower is
the result of an
international design
collaboration and
more than a decade
of advanced
research.
Every aspect of the
Npower shows
careful design and
attention to detail. The rugged
powertrain and advanced
ActiveStar™ controls were
subjected to computer simulations
and thermal analysis to ensure
reliable performance in every
environment.
Even the physical packaging is
uniquely efficient, to make fully
configured systems more compact
than other products on the market.
Best of all, it’s a Liebert product—
designed to give the same millionhour critical bus MTBF as its older
brothers.
• Unmatched heritage of
reliability and availability
• Smallest system footprint
• Excellent efficiency with nonlinear loads and partial loads
• Outstanding dynamic response
• All-digital ActiveStar™ controls
and graphical user interface
LIEBERT NPOWER™ 3-PHASE UPS: 30-130KVA, 60 HZ, 208 OR 480VAC
General Specifications
INPUT
Voltage
Voltage Range
Frequency Range 60 Hz, ±5
Current Distortion
Current Limit 115% of full load input current
Current Walk-in 20 seconds to full load
Power Factor
Surge Protection
ENVIRONMENTAL
Operating
Temperature
Non-Operating Temp. -4° to 158°F (-20° to 70°C)
Relative Humidity 0-95% non-condensing
Operating Altitude Up to 6600 ft. (2000m) without derating
Acoustical Noise
OUTPUT
Voltage
Voltage Adjustment
Range
Voltage Regulation
Dynamic Regulation
Transient Response
Time
Voltage Distortion
Phasing Balance
Frequency
Regulation
Load Power
Factor Range
Overload
STANDARDS
ETL listed to UL 1778 UPS standards and CSA certified. Meets current
requirements for safe high performance UPS operation.
208 or 480VAC, 60 Hz
3-phase, 3- or 4-wire plus ground
+10, -15%
(no battery discharge at -20%)
10% maximum reflected THD at full load with
optional input filter; 30% THD without filter
0.80 lagging minimum at full load; up to 0.96
lagging at full load with optional input filter
Sustains input surges without damage, per
criteria listed in ANSI C62.41-1980 (IEEE 587)
UPS: 32° to 104°F (0-40°C)
Battery: 68° to 86°F (20-30°C)
Less than 65 dBA typical, measured
3.3 ft. (1m) from the unit
208 or 480VAC
3-phase, 4-wire plus ground
±5%
±0.5% for balanced load
±1.0% for 100% unbalanced load
±5% deviation for 100% load step
±1% for loss or return of AC input
Recover to ±1% of steady state within 1 cycle
For linear loads, 1% THD; less than 2.5% THD
for 100% nonlinear loads w/o kVA/kW derating
120° ±0.5° for balanced load.
120° ±1° for 100% unbalanced load
±0.1%
1.0 to 0.7 lagging without derating
125% of full load for 10 minutes
150% for 1 minute w/ true sinusoidal waveform
Npower Matching Battery Cabinet
Run Time (minutes) for kVA: Dimensions Weight
Model
1PJ(130) ------7
2PJ(130) ------20
3PJ(130) ------35
4PJ(130) ------50
30 40 50 65 80 100 130 WxDxH, in. (mm) lb. (kg)
1FJ 127----1HJ 21 14 10 7 5 - - 1,800 (815)
1LJ 28 20 14 8 5 - - 2,350 (1,065)
1MJ 36 25 18 12 8 5 - 2,350 (1,065)
1PJ 53 38 28 20 15 10 - 3,000 (1,360)
1RJ 62 45 34 25 19 13 9 3,700 (1,680)
1UJ 72523930231712 4,000 (1,815)
1WJ 104 74 55 40 33 25 16 5,050 (2,290)
2PJ 126 83 67 50 38 28 -
2RJ 144 104 76 55 45 35 25 7,400 (3,360)
2UJ 156 111 90 67 52 40 30 8,000 (3,630)
2WJ - - - 97 74 55 40 10,100 (4,580)
3PJ 204 145 108 78 63 48 -
3RJ 223 161 129 94 72 54 39 11,100 (5,040)
3UJ 265 187 142 105 81 65 48 12,000 (5,445)
3WJ 421 302 217 157 124 94 69 15,150 (6,870)
4PJ 301 206 154 111 90 68 -
4RJ 329 224 182 134 102 77 55 14,800 (6,720)
4UJ 377 266 201 147 111 91 67 16,000 (7,260)
4WJ 480 423 320 222 180 135 97 20,200 (9,160)
25x32.5x71
(635x825x1800)
49x32.5x71
(1250x825x1800)
(2) 25x32.5x71
635x825x1800)
(2) 49x32.5x71
(1250x825x1800)
(3) 25x32.5x71
635x825x1800)
(3) 49x32.5x71
(1250x825x1800)
(4) 25x32.5x71
(635x825x1800)
(4) 49x32.5x71
1250x825x1800
Maintenance Bypass Cabinets
Dimensions Weight, lb. (kg) for kVA:
Model
L or N
P or Q
WxDxH, in. (mm) 30-50 65-80 100-130
25x32.5x71
(635x825x1800)
31.7x32.5x71
(805x825x1800)
660 (299) 750 (340) 800 (363)
1,210 (549) 1,320 (599) 1,540 (699)
Slim-Line Distribution Cabinet
Dimensions Weight
kVA
All
WxDxH, in. (mm) lb. (kg)
10x32.5x71
(254x825x1800)
250 (113)
1,600 (725)
3,350 (1,520)
6,000 (2,720)
6,700 (3,040)
9,000 (4,080)
10,050 (4,560)
12,000 (5,440)
13,400 (6,080)
Site Planning Data, Liebert Npower: 30-130kVA, 60 Hz, 208 or 480VAC
UPS
Rating Voltage
kVA kW Input Output Nom. Max. Nom. Max. Nom OCPD
30 24 208 208 92 114 150 80 99 125 480 26 66A 83 125
30 24 480 480 38 48 60 33 41 50 480 26 66A 36 50 259 (1265) 7,500 (2.2)
40 32 208 208 122 153 200 106 133 175 480 34 88A 111 150
40 32 480 480 51 64 80 44 55 70 480 34 88A 48 60 266 (1299) 10,000 (2.9)
50 40 208 208 153 191 250 133 166 200 480 43 109A 139 175
50 40 480 480 64 80 100 55 69 100 480 43 109A 60 80 266 (1299) 12,000 (3.5)
65 52 208 208 193 242 300 171 213 300 480 55 141A 180 225
65 52 480 480 80 99 125 70 88 125 480 55 141A 78 10 242 (1182) 15,000 (4.4)
80 64 208 208 238 298 400 210 262 350 480 68 174A 222 300
80 64 480 480 98 122 150 87 108 150 480 68 174A 96 125 242 (1182) 18,000 (5.3)
100 80 208 208 296 370 450 261 326 400 480 85 218A 278 350
100 80 480 480 122 152 200 108 135 175 480 85 218A 120 150 252 (1230) 21,000 (6.1)
130 104 208 208 385 481 600 336 420 500 480 111 283A 361 450
130 104 480 480 158 198 250 140 175 225 480 111 283A 156 200 252 (1230) 27,000 (7.9)
See Notes for Table (below): 1 2,3,8,12 6,14 1 2,3,8,12 6 4 — 1,3,5,8,12 1,3,8,12 6 13 13, 14 — — —
Standard AC Input AC Input w/Filter Opt. Battery AC Output Mechanical Data
Current (A)
Rec.
OCPD
Current (A)
Rec.
OCPD
Nom.
BatterykWMax.
VDC
Discharge
Current
Dimensions
WxDxH, in. (mm)
31.7x32.5x71
(805x825x1800)
31.7x32.5x71
(805x825x1800)
31.7x32.5x71
(805x825x1800)
39.4x32.5x71
(1001x825x1800)
39.4x32.5x71
(1001x825x1800)
49.2x32.5x71
(1250x825x1800)
49.2x32.5x71
(1250x825x1800)
Weight
lb. (kg)
Floor Loading
2
(kg/m2)
lb./ft
2100 (953) 294 (1435) 8,500 (
1850 (839)
259 (1265) 7,500 (2.2)
2200 (998) 307 (1499) 11,000 (
1900 (862)
266 (1299) 10,000 (2.9)
2200 (998) 307 (1499) 14,000
1900 (862)
266 (1299) 12,000 (3.5)
2500 (1134) 281 (1372) 18,000
2150 (975)
242 (1182) 15,000 (4.4)
2500 (1134) 281 (1372) 22,000
2150 (975)
242 (1182) 18,000 (5.3)
3350 (1520) 302 (1474) 26,000 (7.6))
2800 (1270)
252 (1230) 21,000 (6.1)
3350 (1520) 302 (1474) 33,000
2800 (1270)
252 (1230) 27,000 (7.9)
Heat Dis.
BTU/h (kWH)
2.5)
(3.2)
(4.1)
(5.3)
(6.4)
(9.7)
Cooling Air
CFM (m
720
720 (1223)40 32 480 208 51 64 80 44 55 70 480 34 88A 111 150
720 (1223)50 40 480 208 64 80 100 55 69 100 480 43 109A 139 175
960 (1631)65 52 480 208 80 99 125 70 88 125 480 55 141A 180 225
960 (1631)80 64 480 208 98 122 150 87 108 150 480 68 174A 222 300
1440
1440 (2447)130 104 480 208 158 198 250 140 175 225 480 111 283A 361 450
3
/h)
(1223)30 24 480 208 38 48 60 33 41 50 480 26 66A 83 125
(2447100 80 480 208 122 152 200 108 135 175 480 85 218A 278 350
Notes for Table
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge
conditions.
3. UPS input and bypass cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. Power cables from UPS DC link to batteries should be sized for a total maximum 2.0V line
drop (measured at the UPS) at maximum discharge current.
6. OCPD=Overcurrent Protection Device. Recommended AC input and AC output overcurrent
protection represents 125% of nominal full load current (continuous) per NEC 215.
7. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground
conductors are recommended. Neutral conductors to be sized for full capacity per
NEC 310-15(b)(4). References are per NEC 1999.
8. Wiring requirements:
AC Input and Output: 3-phase, 3- or-4-wire plus ground, depending on UPS configuration.
See Installation Manual and submittal drawings for specific instructions.
DC Input: 2-wire (positive and negative), plus ground.
9. All wiring is to be in accordance with national and local electrical codes.
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
10. Minimum access clearance is 3 ft. (0.9m) front and 1 ft. (0.3m) above UPS.
11. Top or bottom cable entry through removable access plates. Punch plate to suit conduit
size, then replace.
12. Control wiring and power wiring must be run in separate conduit.
13. Weights and dimensions shown do not include battery cabinet, Slim-Line distribution
cabinet or other options.
14. Add 560 lb. (254kg) for 100-130kVA unit with dual input and isolated 208VAC output.
15. Backup emergency generator must be properly sized and equipped with an isochronous
governor (generator frequency regulation) and a UPS-compatible voltage regulator.
16. An on-site automatic transfer switch should be equipped with auxiliary contacts for UPS
“on generator” current limit. Refer to Liebert publication 91K-PLT-48-02.
17. An external isolated maintenance bypass circuit might cause utility AC input to be out of
phase with the UPS AC output.
© 2004 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names
referred to are trademarks or registered trademarks of their respective owners.
SL-24531 (11/04) Rev. 4