This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert MC. Read this manual thoroughly before attempting to install or
operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in
this manual. Follow all operating and user instructions.
WARNING
Risk of improper handling, installation, and service. Can cause property damage, injury, or
death.
Only trained and qualified personnel should work on this unit. Read all installation,
operation and safety alerts and instructions and wear appropriate protective headgear, safety
glasses, gloves and clothing before installing, operating or servicing this unit.
WARNING
Risk of arc flash and electric shock hazard. Disconnect all local and remote electric power
supplies and wear appropriate personal protective equipment per NFPA 70E before working
within the electric control enclosure or the fan motor connection box(es). Failure to comply can
cause serious injury or death.
This unit contains lethal voltage. The line side of the unit disconnect switch remains
energized when the unit disconnect switch is in the “Off” position. Use a voltmeter to verify
that the line side input electric power to the unit disconnect switch is off before working on
any electrical components or connections.
Important Safety Guidelines
WARNING
Risk of high-speed, rotating fan blades. Can cause serious personal injury or death.
Fan blades can automatically start rotating without warning at any time during a cooling
cycle or after power is restored after a power failure. Disconnect all local and remote electric
power supplies and verify with a voltmeter that the power is off and that the fan blades have
stopped rotating before working within the cabinet or servicing fan motors.
WARNING
Risk of electric shock. Can cause injury or death.
The variable speed control may contain a stored electrical charge. Disconnect all local and
remote electrical power supplies and wait 10 minutes before working within condenser main
electrical enclosure or fan electrical enclosure.
WARNING
Risk of heavy condenser falling or tipping over. Can cause property damage, serious injury or
death.
Confirm that all components of the lifting system are rated for the weight of the condenser by
an OSHA Certified rating organization before attempting to lift and/or move the condenser.
See 2.2 - Dimensions and Weights for the condenser weights.
CAUTION
Risk of hot surfaces. Can cause injury.
Fan motors, transformers, piping and other components may become extremely hot during
normal operation. Wear thermally insulated gloves and appropriate protective clothing and
allow time for components to cool when working within the cabinet or electric control
enclosure.
®
1Liebert
MC
™
Important Safety Guidelines
!
!
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes, and glasses should attempt to move, lift, remove packaging from or prepare unit for
installation.
CAUTION
Risk of explosive discharge of high-pressure gas. Can cause injury.
Relieve system pressure and verify that the indoor and outdoor units are Off before making
piping connections/disconnections.
NOTICE
Risk of overhead interference. Can cause unit and/or structure damage.
Refer to the installation plans before moving the unit to verify clearances.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep unit upright and protected from contact damage.
Liebert® MC
™
2
Liebert MC Nomenclature
LIEBERT MC NOMENCLATURE
Model Number – Part 1/2Model DetailsPart 2/2
12 345678910111213141516171819202122232425
MCM040E1AD0A0VU000000****
1-2. Unit Family; MC = Microchannel Condenser12. Panel Material
3. Platform SizeA = Bright Aluminum
S = Small13. Connection Pipe Unit of Measurement
M = Medium0 = Inches (Std. ACR Copper)
L = Large14. Legs Included
4-6. Nominal Condenser Capacity, kWV = 18" Tall Legs (Std.)
Example: 040 = 40kW @ 95°F(35°C) & 27°R (15°K) ITDX = 36" Tall Legs with Bracing
7. Control/Fan TypeY = 48" Tall Legs with Bracing
E = Premium & EC FanZ = 60" Tall Legs with Bracing
10. Packaging1 = Factory Set for Liebert Lee-Temp Kits
D = Domestic, Non-Stackable (Horizontal Airflow Orientation)18-21. Undefined - Reserved For Future Use
E = Export Crating - Non-Stackable (Horizontal Airflow Orientation) 22-25. Factory Configuration Number
11. Coil Coating
0 = None
E = E-Coat (Epoxy)
Configuration
®
3Liebert
MC
™
1.0INTRODUCTION
1.1 Product Description and Features
The Liebert MC condenser is a low-profile, direct-drive propeller fan-type air-cooled unit suitable for
mounting outdoors. It provides heat rejection for either one or two separate refrigeration circuits,
matches the heat rejection capacity corresponding with the outdoor ambient temperature, and with
each corresponding compressor heat rejection requirements. Constructed with an aluminum cabinet,
galvanized steel frame and microchannel coil, the unit is quiet and corrosion resistant. The condenser
is quickly and easily installed, because all internal wiring is completed at the factory with only
electrical connections to be made at the job site. All electrical connections and controls are enclosed in
an integral weatherproof section of the condenser.
Figure 1Two-fan Liebert MC condenser
Introduction
1.1Control/Fan Types
1.1.1Premium Efficiency Control/EC Fan
Premium Efficiency Controls and EC fans are matched to provide superior system energy efficiency.
The premium control board allows CANbus communication with the indoor unit’s Liebert iCOM
control. This communication feature provides compressor run signals, condenser operating mode
changes, condenser alarm monitoring, simplified system charging procedures and outdoor ambient
temperature monitoring. The EC fan is an integral assembly of an electronically commutated motor,
quiet fan blade assembly and finger/hail guard. The fans are controlled by the premium control board
using pressure transducer signals from the refrigerant circuit and factory programming to control the
refrigerant head pressure.
The premium control board uses inputs from the indoor unit, condenser refrigerant pressures and
temperatures and ambient temperatures to modulate the EC fan motor speed from 0 to 100% RPM,
maintaining refrigerant head pressure setpoints. The control board, EC fan(s) and transducer(s) are
factory-wired. Dual refrigeration circuit condensers adjust fans of each circuit independently to match
each circuit’s head pressure conditions. Multiple fan single refrigeration circuit condensers adjust all
fans to the same RPM to maintain head pressure. The control system provides refrigerant head
pressure control for outdoor ambient temperatures as low as -30°F (-35°C), provided that the total
design range (from minimum to maximum) is 125°F (70°C) or less. Liebert Lee-Temp
required only when the design temperature ranges exceed 125°F (70°C) for standard match ups and
115°F (65°C) for Liebert Quiet-Line
Liebert® MC
™
™
match ups.
®
™
kits are
4
1.1.2Liebert Lee-Temp™ Refrigerant Control
The Liebert Lee-Temp head pressure control system utilizes head pressure control valve(s), extra
refrigerant and insulated refrigerant receiver(s) with heater pads to assist system starting and to
maintain proper operating head pressures in outdoor ambient temperatures below the rating point of
the Liebert MC control type. The system works by flooding the condenser coil with liquid refrigerant
to a level that balances the system condensing requirements with the condenser coil surface available
to reject the system heat. During the summer, the system requires the entire condenser coil surface
for heat rejection and most of the refrigerant is stored in the receiver. In the winter, the same amount
of heat can be rejected by only a fraction of the coil surface. As head pressure begins to fall, the control
valve restricts the flow of liquid refrigerant existing from the condenser. This extra liquid refrigerant
reduces the effective condenser surface area available for heat transfer. The head pressure control
valve also bypasses hot gas into the receiver to warm the liquid and maintain liquid pressure for
proper operation of the expansion valve. Liebert Lee-Temp kit is optional for condensers and is
field-installed. Condenser control boards are factory-configured for Liebert Lee-Temp if ordered with
Liebert Lee-Temp receivers. They can be field-configured if Liebert Lee-Temp system is added later.
1.2Sound Level
Liebert MC condensers utilize low air resistance coil(s) and slower speed fan motors to yield the
required heat rejection at significantly lower sound levels. EC fans are designed to yield the same
maximum sound levels at summer design conditions to help your facility meet noise codes with
moderate operating sound levels.
Introduction
1.2.1Liebert Quiet-Line Match Up
Special match ups of premium condensers are available for applications needing to meet even lower
governmental sound regulations. Lower sound levels are achieved by oversizing the condenser, which
will decrease the maximum airflow and sound level produced by the condenser at design outdoor air
temperatures. This feature requires special setup of the indoor unit. Liebert Lee-Temp may be
required for these applications.
1.3Surge Protection Device (Optional)
An optional surge protection device (SPD) can be field-wired to protect the condenser from surges that
threaten sensitive equipment. The condenser’s electrical panel provides a terminal block to allow the
SPD to be wired in parallel with the high-voltage power. An additional low-voltage terminal block is
provided on condensers with Premium Control Boards to allow monitoring of the SPD alarm circuit.
The Liebert PowerSure CM
protection. An illuminated green LED indicates the SPD is On and providing full protection. An
illuminated red LED indicates that the device’s protection may have been reduced and may require
replacement.
Both lights extinguished indicates there is no power to the condenser or the condenser disconnect is in
the Off position.
™
surge protection device provides 50kA per mode of surge current
®
5Liebert
MC
™
2.0SITE PREPARATION
2.1Site Considerations
• Condensers should be installed in a location offering maximum security and access for
maintenance.
• Avoid ground-level sites with public access and areas prone to heavy snow or ice accumulations.
• To ensure adequate air supply, Emerson
with clean air, away from loose dirt and foreign matter that might clog the coil. In addition,
condensers should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.
• For roof installation, mount the condenser on suitable curbs or other supports in accordance with
local codes.
• Condensers must not be installed in a pit.
• Condensers must be installed on a level surface to ensure proper refrigerant flow.
• Use caution when installing condensers below the indoor unit. Condensers must not be installed
more than 15ft. (4.6m) below the indoor unit. Condensers with Liebert Lee-Temp
be installed at or above the level of the indoor units to maintain proper subcooling.
• Liebert Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation.
Contact Emerson Application Engineering Department for assistance with applications requiring
remote mounting of receivers.
• Condensers must be installed in vertical airflow orientation to maintain the electrical box’s
NEMA 3R rating.
Site Preparation
®
recommends that condensers be installed in an area
™
receivers must
2.2Dimensions and Weights
Table 1Condenser net weights, shipping weights, dimensions and volume, approximate
Domestic PackagingExport Packaging
Condenser
Number
Model #
MCS0281154 (70)335 (152)
MCM0401231 (105)410 (186)
MCM0802441 (200)750 (340)
MCM1203672 (305)1110 (503)
MCM1604860 (390)1425 (646)
MCL0551344 (156)525 (238)
MCL1102602 (273)910 (413)
MCL1653891 (404)1330 (603)
MCL22041186 (538)1755 (796)
Net and packaged weights will increase with factory options: legs taller than 18", coated coils and seismic options.
Field-installed receivers also add to net weights. Consult factory for additional information.
* 18" legs standard for all models. Cross-bracing required for legs longer than 18". Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths. Source: DPN002172, Rev. 3; and DPN002189, Rev. 4.
No.
FansAIn. (mm)
One-Fan
Condenser
39-5/16"
(999mm)
44-3/8"
B
In. (mm)
(1127mm)
Electric Box End
C
ANCHOR PLAN
E
Provided On
Four-Fan Models
C
In. (mm)
D
In. (mm)
E
In. (mm)
46"
(1168mm)
D
Leg supplied for
each Liebert
Lee-Temp kit on
2- & 4-fan models
39-5/16"
(999mm)
(1127mm)
Electric Box End
46-5/16"
(1177mm)
Leg
Height
F * In
(mm)GH
60 (1524) 73-5/8 (1870) 81-5/8 (2073)
44-3/8"
Liebert® MC
™
8
Figure 5Condenser planning dimensions–MCM120
A
Shown with typical 60" legs.
152-3/4"
(3880mm)
46-1/4"
1175mm
B
C
A
144-5/16"
(3666mm)
Liebert DSE receiver adds
8-1/2" (216mm) to the unit
width and may be mounted
on the right or left side.
DETAIL A
Electrical Box End
46"
(1169mm)
Fastener assembly,
fender washer and
hex nuts.
4 each required,
2 places
Spacer
2 each required,
2 places
Emerson recommends a clearance of
36" (915mm) on each end and each side
for proper operation and component access.
46-5/16" (1177mm)
39-5/16"
(999mm)
44-3/8"
(1127mm)
1-7/8"
(48mm)
94-7/16"
(2398mm)
Install two (2) each 1/8"(3.18mm)
leg spacers in each of these
locations (see note below)
NOTE:
Install (2) two condenser leg spacers, part number 304679P1, in two places where shown, between each pair of legs
that adjoin each other.
Use (4) four of part number: 301375G1 (fastener assembly), 301369P1 (washer fender) and 301392P1 (nut hex),
to secure each pair of legs and spacers together.
* 18" legs standard for all models. Cross-bracing required for legs longer than 18". Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths.
Source: DPN002555, Rev. 1
B
In. (mm)
In. (mm)
C
9Liebert
®
MC
™
Figure 6Condenser planning dimensions—MCL055, MCL110, MCL165 and MCL220
Emerson recommends a clearance of
36" (915mm) on each side for proper
operation and component access.
Eyebolts for lifting condenser
provided on 3&4 fan models
55-5/8"
(1413mm)
55-1/2"
(1409mm)
53-7/8"
(1368mm)
Electric Box End
48-3/4"
(1239mm)
Height to Top
of Fan Guard
DPN002416
Rev. 2
ANCHOR PLAN
Provided on
3- & 4- Fan Models
D
E
For typical footprint
dimensions, see Figure 2
See Table 3 for
dimensions F, G and H
Site Preparation
Table 3Condenser leg height and additional weight, MCL055, MCL110, MCL165 and MCK220
# of
Model #
MCL0551
MCL1102
MCL1653
MCL2204
* 18" legs standard for all models. Cross-bracing required for legs longer than 18" (457mm). Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths.
Source: DPN002416, Rev. 2
FansAin. (mm)Bin. (mm)Cin. (mm)Din. (mm)Ein. (mm)
68
(1727)
124-1/8
(3152)
180-1/4
(4578)
236-5/16
(6003)
—
—
73-7/16
(1866)
129-9/16
(3291)
56
(1423)
112-1/8
(2848)
168-1/4
(4274)
224-3/8
(5699)
54-3/8
(1381)
110-1/2
(2806)
110-1/2
(2806)
110-1/2
(2806)
—18 (457)
—36 (914)
56-1/8
(1425)
112-1/4
(2851)
Leg Height
F * In. (mm)GIn. (mm)HIn. (mm)
35-7/8
(911)
53-7/8
(1368)
48 (1219)
60 (1524)
65-7/8
(1673)
77-7/8
(1978)
43-5/8
(1108)
61-5/8
(1565)
73-5/8
(1870)
85-5/8
(2175)
Liebert® MC
™
10
Site Preparation
Emerson recommends a clearance of
36" (915mm) on each side for proper
operation and component access.
Eyebolts for lifting condenser
provided on 3&4 fan models
55-1/2"
(1409mm)
53-7/8"
(1368mm)
55-5/8"
(1413mm)
Height
to Top
of Fan
Guard
54-3/8"
(1381mm)
Electric Box End
48-3/4"
(1239mm)
ANCHOR PLAN
(1) leg supplied for
each Liebert
Lee-Temp
kit on 2, 3, & 4
fan models
Provided on
3- & 4- Fan
Models
D
E
DPN002415
Rev. 3
For typical footprint
dimensions, see Figure 2
Figure 7Cabinet and anchor dimensions—MCL055, MCL110, MCL165 and MCL220 with Liebert
Lee-Temp
™
receiver
# of
Model #
MCL0551
MCL1102
MCL1653
FansAin. (mm)Bin. (mm)Cin. (mm)Din. (mm)Ein. (mm)
MCL2204
* 18" legs standard for all models. Cross-bracing required for legs longer than 18" (457mm). Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths.
Source: DPN002415, Rev. 3
68
(1727)
124-1/8
(3152)
180-1/4
(4578)
236-5/16
(6003)
73-7/16
(1866)
129-9/16
(3291)
—
—
56
(1423)
112-1/8
(2848)
168-1/4
(4274)
224-3/8
(5699)
Leg Height
F *
In. (mm)GIn. (mm)HIn. (mm)
54-3/8
(1381)
110-1/2
(2806)
110-1/2
(2806)
110-1/2
(2806)
11Liebert® MC
—18 (457)
—36 (914)
56-1/8
(1425)
112-1/4
(2851)
48 (1219)
60 (1524)
35-7/8
(911)
53-7/8
(1368)
65-7/8
(1673)
77-7/8
(1978)
43-5/8
(1108
61-5/8
(1565)
73-5/8
(1870)
85-5/8
(2175)
™
3.0INSPECTIONAND INSTALLATION
!
!
!
3.1Equipment Inspection
Before unpacking the condenser, verify that the labeled equipment matches the bill of lading.
Carefully inspect all items for damage, either visible or concealed. Report any damage immediately to
the carrier and your local Emerson representative. File a damage claim with the carrier and send a
copy to your local Emerson representative.
3.1.1Packing Material
All material used to package this unit is recyclable. Save it for future use or dispose of the material
appropriately.
SAFETY INFORMATION
WARNING
Risk of improper handling. Can cause equipment damage, injury or death.
Read all of the following instructions before attempting to move, lift, remove packaging from
or preparing unit for installation.
WARNING
Risk of heavy condenser falling or tipping over. Can cause property damage, serious injury or
death.
Confirm that all components of the lifting system are rated for the weight of the condenser by
an OSHA Certified rating organization before attempting to lift and/or move the condenser.
See 2.2 - Dimensions and Weights for the condenser weights.
Inspection and Installation
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes, and glasses should attempt to move, lift, remove packaging from or prepare unit for
installation.
NOTICE
Risk of overhead interference. Can cause unit and/or structure damage.
Refer to the installation plans before moving the unit to verify clearances.
NOTICE
Risk of improper forklift handling. Can cause unit damage.
Keep the forklift tines level and at a height that will fit under the skid.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep unit upright and protected from contact damage.
Liebert® MC
™
12
Figure 8Equipment recommended for handling a Liebert condenser
ForkliftCrane
Lift Beam, Slings
and Spreader Bars
308111
Pg. 1, Rev. 1
308111
Pg. 1, Rev. 1
3.2Handling Unit on the Skid
Transport unit using a forklift or a crane with sling and spreader bars.
• If using a fork lift, make sure the forks (if adjustable) are spread to the widest allowable distance
to still fit under the skid.
• Type of fork lift used will be dependent on the terrain the unit to be moved across during
handling.
• Minimum fork lift fork length for use on 1 and 2 fan units to be 48" (1219mm).
• When moving the packaged unit, do not lift the unit any higher than 6"(152mm) off the ground. If
circumstances require the unit to be lifted higher than 6" (152mm), great care must be exercised
and all personnel not involved in moving the unit must be at least 20' (5m) from the lift point of
the unit.
Inspection and Installation
Figure 9Forklift position with one-fan or two-fan condensers
• When using a forklift to off-load or move for installation, it is recommended to lift one narrow end
off the ground no more than 6" (152mm). Use the forklift to push or pull the unit.
• When using a crane to lift the unit from a flat bed or to move for installation, using slings rated
for the unit weight is recommended.
• Spreader bars are to be used for sling stability and to prevent unit pinching. Make sure spreader
bars are wider than the unit.
• Slings are to be placed near the ends of the unit, under the top deck boards of the skid.
3.3Unit Storage
• Store the fan in the original shipping packaging in a dry area protected from the weather, or
protect it from dirt and weather until final installation.
• Avoid temperatures below -30°F (-34°C) and above 150°F (65°C).
• Avoid storing the Liebert MC condenser for longer than one year.
13Liebert® MC
™
3.4Unpacking the Condenser—All Unit Sizes
Step 5
Step 1-DomesticStep 1 - Export
Step 2
Detail Area
Unit Legs
(Fasteners in bag
attached to legs)
308111
Rev. 1
Steps 3 and 4
Step 6
To unpack a condenser with one to two fans:
1. Remove the fence for domestic packaging (for export packaging, remove the crate).
2. Remove corner and side foam planks from around the unit.
3. Remove the steel band holding the unit to the skid.
4. Set unit legs aside for use later.
5. Remove corrugated panels covering the Liebert MC’s coil(s).
6. Remove the bolts securing unit to the skid.
Figure 10 Removing protective material
Inspection and Installation
Liebert® MC
™
14
Inspection and Installation
308111
Rev. 1
308111
Pg. 2, Rev. 1
Straps go against
legs on one-fan and
two-fan units
Straps or chains go against
eyebolts on three-fan and
four-fan units
3.5Preparing a Condenser for Moving and Installation—Units with One or Two Fans
The following procedure is one recommended method for removing a Liebert condenser from its
shipping skid. Other methods may be used, provided that they are safe for personnel, the condenser
and equipment.
3.5.1Attaching Legs, Removing the Skid and Attaching Slings-Units with One or Two Fans
1. Attach legs to the unit at indicated locations.
Use the fasteners provided with the legs.
Recommended tools for attachment is a 5/8" socket and ratchet.
More legs may be available for installation than shown. This will depend on the unit type and
number of fans.
Figure 11 Attaching legs to one-fan or two fan condensers
B
Detail B
2. Place slings around the unit between the unit and the top deck boards of the skid:
• One-fan and two-fan units: against the inside of the attached legs.
• Three-fan and four-fan units: against the outside of the attached eye bolts.
3. Use spreader bars, a lift beam and a crane to lift the unit off the skid.
NOTICE
Risk of improper lifting. Can cause equipment damage.
Make sure that the spreader bars wider are than the unit. If the spreader bars are too short,
the slings may crush the unit.
Figure 12 Securing slings to condensers for lifting off skid
15Liebert® MC
™
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.