Emerson K975A Brochures and Data Sheets

Avtron K975A
Resistive Permanent Load Bank - 1500 to 2500 KW
Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most.
Key Features
• Outdoor Installation
• Temperature Controlled Weather-proof Contactor Enclosure
• No Cool Down Period Required
• Optional DC Designs
• Standard 19" Remote Control Panel with Optional Enclosure
• Fully Supported Load Elements
Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service.
The Avtron Model K975A Load Bank is designed for testing AC generating systems and UPS.
The Avtron K975A load bank can be utilized independently or as a modular building block for larger systems to meet a variety of requirements. Standard units are designed for 480 volt oper ation, 3 phase, and are available in 1500 to 2500 KW load capacity models. This load bank series incorporates the latest state-of-the-art load bank design features and manufacturing techniques. The K975A is designed for testing AC generating systems, Uninterruptible Power Supplies (UPS), in production line and laboratory environments.
The contactors are enclosed in a thermostatically controlled heated enclosure to help prevent problems caused by condensation. This enclosure is sealed with a rubber gasket to protect the components from environmental contamination.
The K975A load bank contains resistive elements and blower motors in a rigid structure of formed heavy gauge steel. Designed for outdoor installation, the K975A utilizes a screened air inlet and exhaust louver to protect the motors and resistive assemblies.
Carefully engineered and manufactured resistive elements are designed to operate at a fraction of their maximum temperature rating. This ensures more stable loading, extends their operating life and eliminates the need for a cool down period after each loading session.
Avtron’s extensive line of Load Bank and Industrial Resis tor Products are solid performers used throughout the world.
For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com.
Quality System Certified to ISO 9001
K975A 1500 KW Permanent Resistive Avtron Load Bank.
Avtron K975A
Resistive Permanent Load Bank - 1500 to 2500 KW
Specications subject to change without notice.
Construction
Heavy gauge steel structure provides a rigid enclosure. Removable panels with rubber gaskets protect contactors from weather. Screened air inlet and louvered exhaust opening protect the load bank from foreign objects and weather. Horizontal airflow pro­vides maximum protection and reliability in an outdoor environment. Upright construc­tion minimizes footprint. Permanent base is designed for mounting on floor, roof, or cement pad and is equipped with built-in forklift channels.
Resistor Elements
The resistive elements are designed by Avtron and manufactured of a corrosion resistant chromium alloy wire. Resistive elements are fully supported over their entire length for improved operating life.
Control Power
The K975A requires control power of 120 volts, single phase, 60 Hz, 15 amps (control transformer optional).
Cooling
The resistive elements are air cooled by dual self-contained 5, 10, or 15 HP blowers requiring 460 volts, 3 phase, 60 Hz. No additional cooling period is required when load is removed from the elements. Optional voltages available.
Controls
Contactors are protected in a thermostati­cally controlled, heated enclosure. The 19" [482.6] rack-mounted control panel includes a POWER ON-OFF switch, a POWER ON light, BLOWER ON-OFF push buttons with a BLOWER FAILURE light, MASTER LOAD ON­OFF switch, and load step switches.
Protection
The K975A differential pressure air switch is electrically interlocked to remove load if the airflow is not sufficient to provide proper cooling. Overtemperature protection and branch circuit fusing is also provided.
Load Capacity Ratings: (3 phase, 60 Hz)
Available Load Step Resolution: 5 or 50 KW
Rated KW 240/480 VAC 480 VAC
1500
2000
2250
2500
GUARD
SCREENS
CUSTOMER CONTROL AND FAN CONNECTION
LOAD INPUT CONNECTIONS
93.12
[2365.00]
AIR IN SCREENED
32.50
[825.00]
REMOVABLE COVER
A
B
C
C L
21.50 [546.00] REF
75.25 [1911.00]
33.00 [838.00]
89.69 [2278.00]
84.00 [2134.00]
4.75 [120.00]
4.75 [120.00]
Load Bank Weight (approx.)
A
C
2.50 [63.00]
3600 lbs. [1633 kg]
Options
• SIGMA™ Network Control
• ADMS™ Digital Metering (V, A, KW, Hz) with Communicator EXT™ Data Logging Software
• Meter and Control Panel Enclosure
• 230/460, 208, 230, or 575 V Blower
• Control Transformer for 208, 230, 460, 230/460, or 575 V Power
36.00
[914.00] MIN
ALLOW CLEARANCE
FOR MAINTENANCE
2.50 [63.00]
2.50 [63.00]
B
FORKLIFT ACCESS
3.00 x 9.00 [76.00 x 229.00] TYP 2 PLACES
5.69 [144.00]
REMOVABLE ACCESS PANELS BOTH SIDES
AIR OUT SCREENED
LOUVERED PANELS
REMOVABLE ACCESS PANELS BOTH SIDES
All dimensions are in inches [millimeters].
Emerson Network Power
Avtron 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
EmersonNetworkPower.com/loadbank
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
Communicator EXT™ is a trademark of Electro Industries/GaugeTech. ADMS™ is a trademark of Avtron. SIGMA™ is a trademark of NJ Froment & Co. Ltd. Specications subject to change without notice.