Emerson K875A, MV Brochures and Data Sheets

Avtron K875A-MV
Resistive Medium Voltage Permanent Load Bank - 500 to 3000 KW
Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most.
Key Features
• Outdoor Installation
• Fully Supported Load Elements
• Vertical Air Discharge
• Slide Out Resistor Cases
• Integral Step-Down Transformer
Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service.
Avtron’s extensive line of Load Bank and Industrial Resis tor Products are solid performers used throughout the world.
The Avtron Model K875A-MV Load Bank is used for resistive testing medium voltage power sources.
The Avtron K875A-MV load bank system provides a convenient and economical means of testing power sources at utility voltages. Incorporating an integrally mounted step-down transformer, the K875A-MV provides resistive load testing for power sources at 2400, 4160, 12,470, or 13,800 volts (other voltages are available). The single skid mounted load bank system makes it practical for transportation and set up with single point termination of diesel or turbine generator sets.
The load bank features vertical air dis charge for installation in areas where space is at a premium such as the rooftops of high-rise buildings. Weatherproof exhaust hoods provide maximum protection to the resistor cases and blower assemblies.
The K875A-MV incorporates state-of-the-art load bank design features and manufacturing tech­niques to provide years of trouble free service. This model utilizes a modular design with common parts shared throughout the product range. This assures quick delivery, easy installation, and simple operation and maintenance.
The K875A-MV load bank is used for resistive testing medium voltage power sources in factory production lines or in the field after installation.
For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com.
Quality System Certified to ISO 9001
K875A-MV 3000 KW Skid-Mount Resistive Medium Voltage Avtron Load Bank with Transformer.
Avtron K875A-MV
Resistive Medium Voltage Permanent Load Bank - 500 to 3000 KW
Specications subject to change without notice.
Construction
The load bank enclosure is constructed of heavy gauge aluminized steel with stainless steel ex terior fasteners. Vertical airflow pro­vides a compact footprint for tight installations. The structural skid base is designed to support the step-down transformer as well as the load bank and interconnecting wiring to provide for a single point connection for medium voltage (5 or 15 KV) applications. The skid is provided with lifting provisions at each corner.
Resistor Elements
The resistive elements are manufactured of a corrosion resistant chromium alloy wire and are fully supported with stainless steel rods for long life.
Control Power
The K875A-MV requires 120 VAC, single phase power which is derived from an integral control transformer.
Cooling
The resistive elements are air cooled by inte­grally mounted blower motors rated at 10 HP, 460 VAC, 3 phase, 60 Hz. No additional cooling period is required when load is removed.
Controls
The control panel is provided as a 19" [482.6] rack-mount panel for remote mounting. Controls include OVERTEMPERATURE light, MASTER LOAD ON-OFF switch, and load step ON-OFF toggle switches. An optional digital metering package with data logging software is available.
Protection
Secondary fusing is provided on the load side of the step-down transformer to protect the load bank feeder cable. The K875A-MV fea­tures branch circuit fusing on all load steps and overtemperature protection. Differential pres­sure air switches on the blowers are electrically interlocked to remove load if the airflow is not sufficient to provide proper cooling.
Transformer
Outdoor construction, Dry-Type designed for 150° C rise (220° C insulation system) with sec­ondary fusing. Primary protection, disconnect, or circuit breaker provided by others.
Options
• SIGMA™ Network Control
• ADMS™ Digital Metering (V, A, KW, Hz) with Communicator EXT™ Data Logging Software
121.50
[3086.00]
12.60 [300.00]
81.00 [2057.00]
BASE MTG. HOLES
84.00
[2134.00]
1.50 [38.10]
4.00
[101.00]
Load Capacity Ratings
Available Load Step Resolution: 5 or 50 KW
Rated KW
500 2.4, 4.16, 12.47, or 13.8 KV
750 2.4, 4.16, 12.47, or 13.8 KV
1000 2.4, 4.16, 12.47, or 13.8 KV
1500 2.4, 4.16, 12.47, or 13.8 KV
2000 2.4, 4.16, 12.47, or 13.8 KV
3000 2.4, 4.16, 12.47, or 13.8 KV
NOTE Designs for international 50/60 Hz voltages or custom DC designs are also available. Consult factory for exact detailed weights and dimensions.
280.50 [7125.00]
BASE MTG HOLES
1.25 DIA 4 HOLES IN BOTTOM OF FRAME AT 268.00 x 81.00 MOUNTING CENTERS
288.50 [7328.00]
All dimensions are in inches [millimeters].
Rated Voltages
(3 phase, 60 Hz)
3.50 [88.90] DIA THRU FOR LIFTING
45.75
[1162.00]
92.14
[2340.00]
Emerson Network Power
Avtron 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
EmersonNetworkPower.com/loadbank
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
ADMS™ is a trademark of Avtron. SIGMA™ is a trademark of NJ Froment & Co. Ltd.
Specications subject to change without notice.
©2015 Emerson Network Power Bulletin 423• Rev. C