Avtron K875A-MV
Resistive Medium Voltage Permanent Load Bank - 500 to 3000 KW
Testing Your Emergency Standby
Generator with a Load Bank Means
Reliability When it Matters Most.
Key Features
• Outdoor Installation
• Fully Supported Load
Elements
• No Cool Down Period
Required
• Vertical Air Discharge
• Slide Out Resistor Cases
• Integral Step-Down Transformer
Superior Avtron quality combined with
simple operation and maintenance will
provide years of trouble free service.
Avtron’s extensive line of Load Bank and
Industrial Resis tor Products are solid
performers used throughout the world.
The Avtron Model K875A-MV Load Bank is used for
resistive testing medium voltage power sources.
The Avtron K875A-MV load bank system provides a convenient and economical means of
testing power sources at utility voltages. Incorporating an integrally mounted step-down
transformer, the K875A-MV provides resistive load testing for power sources at 2400, 4160,
12,470, or 13,800 volts (other voltages are available). The single skid mounted load bank
system makes it practical for transportation and set up with single point termination of diesel
or turbine generator sets.
The load bank features vertical air dis charge for installation in areas where space is at a premium
such as the rooftops of high-rise buildings. Weatherproof exhaust hoods provide maximum
protection to the resistor cases and blower assemblies.
The K875A-MV incorporates state-of-the-art load bank design features and manufacturing techniques to provide years of trouble free service. This model utilizes a modular design with common
parts shared throughout the product range. This assures quick delivery, easy installation, and
simple operation and maintenance.
The K875A-MV load bank is used for resistive testing medium voltage power sources in factory
production lines or in the field after installation.
For total technical support or additional
information, please contact Avtron at
(216) 573-7600 or LBsales@Emerson.com.
Quality System Certified to ISO 9001
K875A-MV 3000 KW
Skid-Mount Resistive
Medium Voltage
Avtron Load Bank
with Transformer.
Avtron K875A-MV
Resistive Medium Voltage Permanent Load Bank - 500 to 3000 KW
Specications subject to change without notice.
Construction
The load bank enclosure is constructed of
heavy gauge aluminized steel with stainless
steel ex terior fasteners. Vertical airflow provides a compact footprint for tight installations.
The structural skid base is designed to support
the step-down transformer as well as the load
bank and interconnecting wiring to provide for
a single point connection for medium voltage
(5 or 15 KV) applications. The skid is provided
with lifting provisions at each corner.
Resistor Elements
The resistive elements are manufactured of a
corrosion resistant chromium alloy wire and
are fully supported with stainless steel rods for
long life.
Control Power
The K875A-MV requires 120 VAC, single phase
power which is derived from an integral control
transformer.
Cooling
The resistive elements are air cooled by integrally mounted blower motors rated at 10 HP,
460 VAC, 3 phase, 60 Hz. No additional cooling
period is required when load is removed.
Controls
The control panel is provided as a 19" [482.6]
rack-mount panel for remote mounting.
Controls include OVERTEMPERATURE light,
MASTER LOAD ON-OFF switch, and load step
ON-OFF toggle switches. An optional digital
metering package with data logging software
is available.
Protection
Secondary fusing is provided on the load side
of the step-down transformer to protect the
load bank feeder cable. The K875A-MV features branch circuit fusing on all load steps and
overtemperature protection. Differential pressure air switches on the blowers are electrically
interlocked to remove load if the airflow is not
sufficient to provide proper cooling.
Transformer
Outdoor construction, Dry-Type designed for
150° C rise (220° C insulation system) with secondary fusing. Primary protection, disconnect,
or circuit breaker provided by others.
Options
• SIGMA™ Network Control
• ADMS™ Digital Metering (V, A, KW, Hz) with
Communicator EXT™ Data Logging Software
121.50
[3086.00]
12.60 [300.00]
81.00 [2057.00]
BASE MTG. HOLES
84.00
[2134.00]
1.50 [38.10]
4.00
[101.00]
Load Capacity Ratings
Available Load Step Resolution: 5 or 50 KW
Rated KW
500 2.4, 4.16, 12.47, or 13.8 KV
750 2.4, 4.16, 12.47, or 13.8 KV
1000 2.4, 4.16, 12.47, or 13.8 KV
1500 2.4, 4.16, 12.47, or 13.8 KV
2000 2.4, 4.16, 12.47, or 13.8 KV
3000 2.4, 4.16, 12.47, or 13.8 KV
NOTE Designs for international 50/60 Hz voltages or custom
DC designs are also available. Consult factory for exact
detailed weights and dimensions.
280.50 [7125.00]
BASE MTG HOLES
1.25 DIA 4 HOLES IN BOTTOM OF
FRAME AT 268.00 x 81.00
MOUNTING CENTERS
288.50 [7328.00]
All dimensions are in inches [millimeters].
Rated Voltages
(3 phase, 60 Hz)
3.50 [88.90] DIA
THRU FOR LIFTING
45.75
[1162.00]
92.14
[2340.00]
Emerson Network Power
Avtron • 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
EmersonNetworkPower.com/loadbank
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
ADMS™ is a trademark of Avtron. SIGMA™ is a trademark of NJ Froment & Co. Ltd.
Specications subject to change without notice.
©2015 Emerson Network Power Bulletin 423• Rev. C