Emerson K580, K575A Brochures and Data Sheets

Avtron K580
Resistive Trailer Mounted Load Bank - 500 to 1250 KW
Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most.
Key Features
• High Capacity in a Compact Package
• Heavy Duty Dual Axle Trailer
• Optional Cable Reels or Cable Storage Box
• Convenient Operator Controls with Digital Metering and Data Logging Software Included
• Load Bank is available as “Trailer-Ready”
• Optional SIGMA™ Control for Networking of Multiple Load Banks
The Avtron Model K580 Load Bank is trailer mounted and ideal for high power mobile testing.
The Avtron K580 load bank contains resistive elements and a blower motor in a rigid structure of formed heavy gauge aluminized steel. Designed for outdoor operation and storage, this load bank utilizes a screened air inlet and exhaust to protect the motor and resistive assemblies. The K580 trailer mounted load bank is ideal for high power mobile testing of AC generating systems at multiple sites.
Carefully engineered and manufactured Helidyne™ resistor elements are designed to operate at a fraction of their maximum temperature rating. This ensures more stable loading, extends element operating life, and eliminates the need for a cool down period after each loading session.
The K580 features the Avtron Advanced Digital Monitoring System (ADMS™). The ADMS meter provides faceplate digital display of Volts, Amps, Frequency, and KW. The Communicator EXT™ Data Logging Software allows Real Time Data Acquisition and trending of all meter parameters from your Laptop PC or PDA. An Infrared/USB interface cable is included for “Plug and Play” con­venience.
Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service.
Avtron’s extensive line of Load Bank and Industrial Resis tor Products are solid performers used throughout the world.
For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com.
Quality System Certified to ISO 9001
K580 1000 KW Resistive Trailer Mounted Avtron Load Bank, shown with optional cable storage reel and quick connect receptacles.
Avtron K580
Resistive Trailer Mounted Load Bank - 500 to 1250 KW
Specications subject to change without notice.
Construction
The load bank enclosure is made of heavy gauge aluminized steel with a powder coat paint finish. Side panels have gaskets to pro­tect contactors from the weather. Horizontal airflow provides a low profile and maximum reliability in an outdoor environment. The trailer features heavy duty welded construc­tion with steel deck, dual axles, radial tires, 7000 lbs. GVW, DOT, and ICC road legal.
Electric brakes, 3" adjustable lunette eye, and stabilizer jacks are provided.
Resistor Elements
The resistive elements are designed by Avtron and manufactured of a corrosion resistant chromium alloy wire. Resistive elements are fully supported over their entire length for maximum reliability.
Controls
The controls and digital metering are housed in a single NEMA enclosure includ­ing a POWER ON-OFF switch, a POWER ON light, BLOWER ON-OFF push buttons with a BLOWER FAILURE light, OVERTEMPERATURE light, MASTER LOAD ON-OFF switch, and load step switches.
Cooling
The resistive elements are air cooled by a self-contained 15 HP blower rated 208/230 or 460 volts, 3 phase, 60 Hz power. No additional cooling period is required when load is removed.
Digital Metering
Avtron Advanced Digital Monitoring System (ADMS™) is provided for display of Volts, Amps, Frequency, and KW. ADMS™ also includes Communicator EXT™ Data Logging Software.
Protection
The K580 differential pressure air switch is electrically interlocked to remove the load if the air flow is not sufficient to produce proper cooling. Overtemperature protection and branch circuit fusing is also provided.
Load Capacity Ratings: (3 Phase, 60Hz)
Available Load Step Resolution: 5 KW
Rated KW Load Capacity KW
500
1000
1250
NOTE Refer to Operation and Maintenance Manual for safe towing instructions.
Avtron K580 1250 KW load bank shown with optional cable storage reels.
CABLE STORAGE REELS (optional)
LOAD CONNECTION ACCESS BOTH SIDES
500 KW @ 480 VAC, 500 KW @ 240 VAC,
375 KW @ 208 VAC
1000 KW @ 480 VAC, 1000 KW @ 240 VAC,
750 KW @ 208 VAC
1250 KW @ 480 VAC, 1250 KW @ 240 VAC,
500 KW @ 208 VAC
AIR INTAKE
150.00 [3810.00]
208.00 [5283.00]
OVERALL LENGTH
DANGER
BED LENGTH
Load Bank Weight (approx.)
Load Bank/Trailer without cables: 3500 lbs. [1587 kg] Load Bank only: 1000-2200 lbs. [453-997 kg]
Standard Features
• Local Meter and Control Panel Enclosure
• Dual Voltage Blower rated 208/230 or 460 Volts, 3 Phase, 60 Hz
• Control Power Transformer rated 240/480 Volts to 120 Volts, single phase, 60 Hz
Optional Features
• SIGMA™ Network Control
• Cable Reels or Cable Storage Box
• Load Cable (1800 lbs. [816 kg] max.)
• Quick Connect Cable Receptacles
• Hydraulic Surge Brakes
• Cable Reel Covers
LOCAL CONTROLS/ METERING
HOT AIR EXHAUST
DANGER
33.00 [838.00] DECK HEIGHT
72.00 [1829.00] BED WIDTH
All dimensions are in inches [millimeters].
50.50
[1283.00]
83.50
[2121.00]
93.00 [2362.00] MAX
Emerson Network Power
Avtron 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
EmersonNetworkPower.com/loadbank
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
Communicator EXT™ is a trademark of Electro Industries/GaugeTech. ADMS™ and Helidyne™ are trademarks of Avtron. SIGMA™ is a trademark of NJ Froment & Co. Ltd. Specications subject to change without notice.
©2015 Emerson Network Power Bulletin 418• Rev. D