Emerson IS-WEB485ADPT User Manual

Monitoring For Business-Critical Continuity™
Liebert® IntelliSlot® Web Cards
Installation Manual – Liebert IntelliSlot Web Card, Liebert IntelliSlot Web Card-LB, Liebert IntelliSlot Web Card-LBDS, Liebert IntelliSlot Web/485 Card-ADPT
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.1 Compatibility With Liebert Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Web Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Password Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 SNMP Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Liebert Nform
1.6 Liebert MultiLink
1.7 Liebert SiteScan
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Install a Liebert IntelliSlot Web Card—Non-Adapter Version . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Install a Liebert IntelliSlot Web/485 Card With Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.0 CONFIGURATION OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.1 Guide to Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Open the Terminal Emulation Interface - Serial Connection . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Open the Terminal Emulation Interface - TCP/IP Connection . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Open the Telnet Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.5 Open the Web Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.6 Saving Changes and Reinitializing the Web Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
®
Web With Modbus Support - IS-WEB485ADPT only . . . . . . . . . . . . . . . . 3
4.0 SYSTEM INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.0 NETWORK SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.1 Boot/IP Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2 Domain Name Server (DNS) Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Management Protocol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4 Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.5 Telnet Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.6 Time (SNTP) Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.7 Change Username / Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.8 Reset Authentication to Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.0 MESSAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
6.1 E-Mail Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.2 SMS Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.3 Customize Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.0 FACTORY SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
7.1 Reset to Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2 Liebert DS - Local Node Settings for Multiple Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.0 MONITOR AND CONTROL FUNCTIONS - WEB ONLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.1 Monitoring Liebert Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.2 Controlling Liebert Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.3 Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9.0 SUPPORT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9.1 View Web Card Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9.2 Events and Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
APPENDIX A-FIRMWARE UPDATES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
FIGURES
Figure A1 Null connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A10
TABLES
Table 1 Liebert IntelliSlot card communication protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 2 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 3 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 4 Configuration interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 5 Guide to configuration details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 6 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 7 System information identifiers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 8 Network Settings menu guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 9 Boot/IP settings range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 10 Domain Name Server settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 11 Management protocol ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 12 SNMP communications menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 13 Web server settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 14 Time Server parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 15 Factory default passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 16 Username and password guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 17 Factory default passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 18 Messaging menu guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 19 E-mail configuration guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 20 SMS configuration guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 21 E-mail and SMS message guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 22 Factory default MAC addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 23 Control operations parameters—functions vary by Liebert unit . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table A1 Overview of the upgrade process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
Table A2 Estimated Time for downloads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
Table A3 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Table A4 Firmware update settings - TFTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6
Table A5 Firmware update settings - Web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A8
ii

IMPORTANT SAFETY INSTRUCTIONS

!
!
SAVE THESE INSTRUCTIONS
WARNING
Only a qualified service professional should install these products. Liebert recommends having an Emerson Network Power Liebert Services representative perform the installation in large UPSs. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).
WARNING
Risk of electric shock. Can cause equipment damage, injury or death. Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the electrical source.
Check the circuits with a voltmeter before beginning installation.
1

1.0 INTRODUCTION

Liebert IntelliSlot Web card
IS-WEBCARD, IS-WEBLB and IS-WEBLBDS
Liebert IntelliSlot Web/485 Card With Adapter
IS-WEB485ADPT
The Liebert® IntelliSlot® Web Card family delivers enhanced communications and control to Liebert AC Power and Precision Cooling systems.
Liebert IntelliSlot Web cards bring SNMP, Telnet and Web-management capability to many models of Liebert power and cooling equipment. The cards employ an Ethernet network to monitor and manage a wide range of operating parameters, alarms and notifications.

1.1 Compatibility With Liebert Equipment

Introduction
The Liebert IntelliSlot Web Card family, formerly the OpenComms line, includes:
Liebert IntelliSlot Web Card Compatible with these Liebert UPS models: Liebert PowerSure PSI
Liebert GXT
6kVA & Liebert GXT™ 10kVA, Liebert GXT2U™ and Liebert Nfinity
, Liebert GXT™,
®
Liebert IntelliSlot Web Card-LB Compatible with the Liebert NX
and Liebert Hinet™ UPS models
Liebert IntelliSlot Web Card-LBDS Compatible with the Liebert DS
Precision Cooling unit and the Liebert XDF
Liebert IntelliSlot Web/485 Card-ADPT Compatible with Liebert AC Power and Precision Cooling systems not equipped with a Liebert
IntelliSlot port

Table 1 Liebert IntelliSlot card communication protocols

Communication Protocol
Liebert IntelliSlot Card Part Number
Liebert IntelliSlot Web Card IS-WEBCARD ✔✔ ✔ — ✔✔✔
Liebert IntelliSlot Web Card-LB IS-WEBLB ✔✔ ✔ — ✔✔✔
Liebert IntelliSlot Web Card-LBDS IS-WEBLBDS ✔✔ ————
Liebert IntelliSlot Web/485 Card With Adapter
IS-WEB485ADPT ✔✔ ——
SNMP HTTP HTTPS Modbus E-mail SMS Telnet
Liebert IntelliSlot Web cards support both 10Mbit and 100Mbit communication speeds and either half or full duplex.
NOTE
See online demonstrations of Web cards installed in Liebert equipment at:
http://demos.liebert.com
2

1.2 Web Support

The Liebert IntelliSlot Web card delivers Web management and control to Liebert equipment. All authorized users on your network will be able to view status information.

1.3 Password Protection

Control and configuration capabilities are protected by a username and password combination. Optionally, status information can be password-protected. The default username is “Liebert” and the default password is also “Liebert.”
You can change the password using the terminal emulation, Telnet or Web interface. See 5.7 -
Change Username / Password for details.
NOTE
Change the username and password today to prevent unauthorized access.

1.4 SNMP Support

The Liebert IntelliSlot Web card enables SNMP management of Liebert equipment. To integrate the card into your SNMP implementation, compile the Liebert Global Products MIB on your network management station (NMS).
The Liebert Global Products MIB is included in this package on CD-ROM and supports both Windows and Unix file formats.
Introduction

1.5 Liebert Nform™ Support

Utilizing the SNMP and Web technologies built into each of the Liebert IntelliSlot Web cards, Liebert Nform will centrally manage alarm notifications to provide you with an easy interface to access criti­cal system information.
A downloadable edition is available online at:
nform.liebert.com

1.6 Liebert MultiLink™ Support

The Liebert IntelliSlot Web card integrates with Liebert’s MultiLink software to provide unattended, graceful operating system shutdown of PCs, servers and workstations. The card can be monitored by MultiLink over the network, eliminating the need for serial cables.
For more information on MultiLink and a downloadable version of MultiLink software, visit the MultiLink page at:
multilink.liebert.com

1.7 Liebert SiteScan® Web With Modbus Support - IS-WEB485ADPT only

The Liebert IntelliSlot Web/485 Card With Adapter integrates with Liebert’s SiteScan Web software using Modbus to monitor trends for analysis and maintenance to ensure high-availability operation of critical facilities.
For more information on SiteScan Web and Modbus integration, visit the SiteScan Web page at:
sitescan.liebert.com
3

2.0 INSTALLATION

!
WARNING
Only a qualified service professional should install these products. Liebert recommends having a Liebert Services representative perform the installation in large UPSs. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).
2.1 Install a Liebert IntelliSlot Web Card—Non-Adapter Version
Follow these steps to install a Liebert IntelliSlot Web card (non-adapter version—P/N IS-WEBCARD, IS-WEBLB and IS-WEBLBDS).
1. Locate the Liebert IntelliSlot option bay on your Liebert equipment—You might need to remove a plastic cover.
2. Insert the Liebert IntelliSlot Web Card into the Liebert IntelliSlot bay.
3. Secure the card with the supplied screws.
4. Connect an Ethernet cable. DHCP: The card ships with DHCP service enabled. The MAC address is on a
sticker on the top of the card.
OR
Static IP: To assign a static IP address or hostname, use terminal emulation software to configure the card, as described in Sections 2.1.1 and 2.1.2.
Installation

2.1.1 Connect the Cable

1. Locate the blue serial configuration cable (null modem) that shipped with the card.
2. Connect the configuration cable to the DB-9 port on the card and to a COM port on your PC.

2.1.2 Prepare the Card for Configuration

• Use terminal emulation software, such as Microsoft connection to the card with the settings in Table 2.
Table 2 Communication settings
• Press the Enter key for the Main Menu, above right.
• Select IP Network Settings, then Boot/IP Settings and follow the instructions to enter an IP ADDRESS, NETMASK and GATEWAY.
• Press Esc to return to the Main Menu.
• Choose Exit and Save to save your changes and reboot the card.
®
HyperTerminal, to open a
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
NOTE
When installing the card in a Liebert NX configure the communication port of NX to 2400 baud. See the NX user manual for details.
4
,

2.2 Install a Liebert IntelliSlot Web/485 Card With Adapter

!
TB2 (P1: +) (P2: -); P1 is at the right side of the terminal block.
Network Port for NMS and Web Access
TB3 (P1: +) (P2: -) (P3: NC) P1 is on left end of terminal block.
DB-9 Port
MAC Address
P1
TB1 (P1: +; P2: -); P1 is at the right side of the terminal block.
Table 3 Communication settings
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
WARNING
Risk of electric shock. Can cause equipment damage, injury or death. Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the electrical source.
Check the circuits with a voltmeter before beginning installation.
Follow these steps to install a Liebert IntelliSlot Web/485 Card With Adapter (P/N IS-WEB485ADPT).
• Locate the adapter mounting location in your Liebert equipment.
• Secure the Liebert IntelliSlot Web/485 Card With Adapter with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal block or P1 on the card (see the user manual for the Liebert power or cooling unit for details).
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal block; Pin 1 is at the far left, and Pin 2 is the middle pin.
Installation

2.2.1 Connect the Cable

1. Locate the blue serial configuration cable (null modem) that shipped with the card.
2. Connect the configuration cable to the DB-9 port on the card and to a COM port on your PC.

2.2.2 Prepare the Card for Configuration

1. Use terminal emulation software, such as HyperTerminal, to open a direct connection to the card with the settings in Table 3.
2. Press the Enter key for the Main Menu.
3. Select 485 Network Settings to access the communications settings.
4. Select Enabled Application.
5. Select Modbus Server to enable the Modbus application.
6. At the next screen, select Server ID (the default Server ID is 1, but may be any number up to 255).
7. Press Esc to return to the Main Menu.
8. Select IP Network Settings, then Boot/IP Settings and follow the instructions to enter an IP ADDRESS, NETMASK and GATEWAY.
9. Press Esc to return to the Main Menu.
10. Choose Exit and Save to save your changes and reboot the card.
NOTE
When installing the card in a Liebert NX baud. See the NX user manual for details.
, configure the communication port of NX to 2400
5

3.0 CONFIGURATION OVERVIEW

You may use any of the following interfaces to configure the Web card:

Table 4 Configuration interfaces

Interface Icon Description
Terminal Emulation (Serial or TCP/IP)
Telnet
Web
Each configuration section provides instructions using the Terminal Emulation (Serial or TCP/IP Connection) / Telnet Interface, along with a brief description of how to access the same function through the Web Interface.
NOTE
The Terminal Emulation and Telnet interfaces present the same menus and choices.

3.1 Guide to Configuration

Use terminal emulation software —for example, HyperTerminal.
Use a command prompt—enter “telnet” and the IP address or hostname.
Use a Web browser—for example, Microsoft
®
Windows® Internet Explorer®.
Configuration Overview
Available
Functions
Configuration
Configuration TCP/IP
Configuration,
Monitoring, Control
Connection
Methods
Serial Cable
or TCP/IP
TCP/IP
Refer to the following guide for details on configuration functions. Sections 3.4 to 3.5 describe how to get started with each interface.

Table 5 Guide to configuration details

Topic Section
3.2 - Open the Terminal Emulation Interface - Serial Connection 7
Connecting to an interface
Saving configuration changes 3.6 - Saving Changes and Reinitializing the Web Card 10
Performing configuration functions
3.3 - Open the Terminal Emulation Interface - TCP/IP Connection 8
3.4 - Open the Telnet Interface 9
3.5 - Open the Web Interface 10
4.0 - System Information 11
5.0 - Network Settings 12
6.0 - Messaging 28
7.0 - Factory Settings 34
Appendix A - - Firmware Updates A1
Page:
6

3.2 Open the Terminal Emulation Interface - Serial Connection

Name
COM3
Connection settings
RTCS v2.96.00 Telnet server
Service Port Manager Active <Esc> Ends Session
Main Menu
---------­1: System Information 2: IP Network Settings 3: Messaging 4: Factory Settings 5: Firmware Updates
q: Quit and abort changes x: Exit and save
Please select a key ?>
To access configuration using terminal emulation software with a serial connection to the Web card:
1. Open a terminal emulation application, such as HyperTerminal.
To do this:
•Click the Start button, then Programs, Accessories, Communications and finally HyperTerminal.
2. In the Connection Description window, enter a name for the connection—for example, GXT2U—then click OK.
3. In the Connect To window:
• Choose COM3 from the Connect Using drop-down list.
•Click OK.
4. In the COM3 Properties window, enter the communication settings shown in Table 6.

Table 6 Communication settings

Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
Configuration Overview
5. When the message at right appears in the HyperTerminal window,
6. In the Main Menu, enter the number that corresponds to your choice.
7. After making changes, return to the Main Menu and choose Exit and
press the Enter key.
Refer to 3.1 - Guide to Configuration for details on each function.
Save to reboot the Web card and put your changes into effect (see
3.6 - Saving Changes and Reinitializing the Web Card).
7

3.3 Open the Terminal Emulation Interface - TCP/IP Connection

Name
TCP/IP (Winsock)
RTCS v2.96.00 Telnet server
Service Port Manager Active <Esc> Ends Session
Login: Liebert Password: ********
Main Menu
---------­1: System Information 2: IP Network Settings 3: Messaging 4: Factory Settings 5: Firmware Updates
q: Quit and abort changes x: Exit and save
Please select a key ?>
To access configuration using terminal emulation software with an Ethernet connection to the Web card:
1. Open a terminal emulation application, such as HyperTerminal.
To do this:
•Click the Start button, then Programs, Accessories, Communications and finally HyperTerminal.
2. In the Connection Description window, enter a name for the connection—for example, GXT2U—then click OK.
3. In the Connect To window:
• Choose TCP/IP (Winsock) from the Connect Using drop-down list.
• Enter the IP address or hostname of the Web card—for example, 192.168.0.125—in the Host Address box, then click OK.
4. When the message at right appears in the HyperTerminal window, press the Enter key.
5. Enter the Administrator username and password (both are case­sensitive):
a. Login (username—default is Liebert) b. Password (default is Liebert)
Configuration Overview
NOTE
For security, change the default username and password (see 5.7 - Change Username / Password).
6. In the Main Menu, enter the number that corresponds to your choice. Refer to 3.1 - Guide to Configuration for details on each function.
7. After making changes, return to the Main Menu and choose Exit and
Save to reboot the Web card and put your changes into effect (see
3.6 - Saving Changes and Reinitializing the Web Card).
8

3.4 Open the Telnet Interface

C:>telnet 192.168.0.125
RTCS v2.96.00 Telnet server
Service Port Manager Active <Esc> Ends Session
Login: Liebert Password: ********
Main Menu
---------­1: System Information 2: IP Network Settings 3: Messaging 4: Factory Settings 5: Firmware Updates
q: Quit and abort changes x: Exit and save
Please select a key ?>
To access configuration using Telnet:
1. Open a Telnet connection on a computer with an Ethernet connection to the Liebert unit.
To do this:
• Open a command prompt window—click the Start button, then Run.
• Enter cmd and click OK.
• In the command prompt window that opens, enter telnet followed by a space and the IP address or hostname of the Web card—for example:
telnet 192.168.0.125
2. When the message at right appears in the command prompt window, press the Enter key.
3. Enter the Administrator username and password (both are case­sensitive):
a. Login (username—default is Liebert)
b. Password (default is Liebert)
NOTE
For security, change the default username and password (see 5.7 - Change Username / Password).
Configuration Overview
4. In the Main Menu, enter the number that corresponds to your choice. Refer to 3.1 - Guide to Configuration for details on each function.
5. After making changes, return to the Main Menu and choose Exit and
Save to reboot the Web card and put your changes into effect (see
3.6 - Saving Changes and Reinitializing the Web Card).
9

3.5 Open the Web Interface

Configuration Categories
Configure tab
Connect To
Reinitialize (to save any changes)
New Settings will take effect
when saved
GO TO MAIN MENU AND DO 'EXIT AND
SAVE' TO SAVE YOUR CHANGES!
Exiting and saving...
Configuration saved successfully
First click Reinitialize at left
Then click Reinitialize button
Progress message window
To access configuration using the Web interface:
1. Open a Web browser such as Internet Explorer, then enter the IP address or hostname of the Web card in the address bar—e.g., http://192.168.0.125.
2. Click on the Configure tab, shown at right. Configuration Categories appear in the left panel, organized with folder icons.
3. Click on any configuration category, and the Connect To box opens.
4. Enter the Administrator username and password (both case-sensitive):
a. User Name (default is Liebert) b. Password (default is Liebert)
NOTE
For security, change the default username and password (see 5.7 - Change Username / Password).
5. Click OK.
6. Refer to 3.1 - Guide to Configuration for details on each function.
7. After making changes, click the Save button, then click on Reinitialize to reboot the Web card and put your changes into effect (see 3.6 - Saving Changes and Reinitializing the Web Card).
Configuration Overview

3.6 Saving Changes and Reinitializing the Web Card

Follow the applicable steps for your interface to save configuration changes and reinitialize the Web card. Changes will not take effect until these steps are completed.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

• After each change is made, a reminder appears (shown at right).
• Return to the Main Menu, then choose Exit and Save. A mes­sage appears and remains until the card is reinitialized, followed by a message that the process was successful.

Web Interface

• After making each change, click the Save button. A reminder appears each time you make a change (shown at right).
• Without leaving the Configure tab window (below left), click Reinitialize in the left panel, then click the Reinitialize button at right to reboot the Web card and put your changes into effect.
• A message window appears, shown above right, and remains until the card is reinitialized.
10

4.0 SYSTEM INFORMATION

System Information Menu
-----------------------­1: Name Uninitialized 2: Contact Uninitialized 3: Location Uninitialized 4: Description Uninitialized
<ESC>: Cancel menu level
Please select a key ?>
Agent Info
Edit
Configure tab
System Information is optional and identifies the Liebert unit, its location, a contact person and other information about the unit. The default value of each field is “Uninitialized.”
NOTE
This information also configures the SNMP parameters sysName, sysContact, sysDescr, and sysLocation available using RFC-1213 MIB II.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To edit any field in this category:
1. From the Main Menu, choose System Information.
2. Enter the number that corresponds to your choice, then enter the identifying information, using the following as a guide.

Table 7 System information identifiers

Item Description Maximum Length
Name A name for the Liebert unit 255 characters*
Contact
Location The location of the Liebert unit 64 characters*
Description
* Valid characters include spaces and other printable characters except double quotes (").
A contact person or department responsible for maintenance and operation of the Liebert unit
Other useful information about the unit for quick reference
System Information
64 characters*
64 characters*

Web Interface

To access System Information through the Web interface:
• Click on the Configure tab, then Agent Info in the left panel and finally Edit in the right panel. After making changes, click Save.
11

5.0 NETWORK SETTINGS

IP Network Settings Menu
------------------------­1: Boot/IP Settings 2: Domain Name Server (DNS) Settings 3: Management Protocol 4: Web Server 5: Telnet Server 6: Time (SNTP)
7. Change Administrator Username/Password 8: Change General Username/Password 9: Reset Authentication to Factory
Defaults
<ESC>: Cancel menu level Please select a key ?>
The IP Network Settings Menu is used to enable network communications with the Web card.
Refer to the following sections for detailed step-by-step instructions on each item from this menu:

Table 8 Network Settings menu guide

Menu item Refer to:
5.1 - Boot/IP Settings page 13
5.2 - Domain Name Server (DNS) Settings page 14
5.3 - Management Protocol page 15
5.4 - Web Server page 19
5.5 - Telnet Server page 24
5.6 - Time (SNTP) Menu page 24
5.7 - Change Username / Password page 26
5.8 - Reset Authentication to Factory Defaults page 27
Network Settings
12

5.1 Boot/IP Settings

Boot/IP Settings Menu
---------------------­1: Speed/Duplex Auto 2: Boot mode Static 3: IP Address 192.168.0.125 4: Netmask 255.255.255.0 5: Default Gateway 192.168.0.1 6: DNS Server 0.0.0.0
<ESC>: Cancel menu level Please select a key ?>
Network Settings
Edit
Configure tab
The Boot/IP Settings Menu is used to set parameters for network access to the Web card. Consult your network administrator for these settings.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To change any parameter:
1. Choose IP Network Settings from the Main Menu, then Boot/IP Settings.
2. Select an option to change—for example, Speed/Duplex, then enter settings according to the following guide.
Table 9 Boot/IP settings range
Parameter Description & Valid Settings*
Speed/ Duplex
Boot Mode
IP address
Netmask
Default Gateway
DHCP/BootP Server
DNS Server
* Consult your network administrator for proper settings.
Network Settings
Speed and duplex configuration of the Ethernet port.
• Auto (default—use this setting if unknown)
• 10Mbs/Half Duplex • 100Mbs/Half Duplex
• 10Mbs/Full Duplex • 100Mbs/Full Duplex
Startup mode enabling the Web card to be a network-ready device.
Static - Fixed network addresses and other parameters
DHCP - Central management using dynamic network addresses
BootP - Older mechanism for central management of network addresses
Network address for the Liebert unit. Four numbers (0-255) separated by periods (.)—for example, 10.0.0.5
Network mask that divides your network into manageable segments. Four numbers (0-255) separated by periods (.)—e.g., 255.255.255.0
IP address of the gateway for network traffic to other networks or subnets. Four numbers (0-255) separated by periods (.)—e.g., 10.0.0.1
Device on a network that assigns IP addresses that are not static. Four numbers (0-255) separated by periods (.)—for example, 192.168.0.5
IP address of the Domain Name Server for the network. Four numbers (0-255) separated by periods (.)—e.g., 10.0.0.1

Web Interface

To access Boot/IP Settings through the Web interface:
• Click on the Configure tab, then Network Settings in the left panel and finally Edit beneath the table of parameters and descriptions. After making changes, click Save.
13

5.2 Domain Name Server (DNS) Settings

The Domain Name Server settings menu configures the servers the Web card will use for hostname resolution. When configured, host addresses for SNMP, Network Time and Email/SMS can be speci­fied in either full Domain Name format or in host-only format, provided that the appropriate Domain Name Suffix is used.
The DNS menu is used to set parameters for network access to the Web card. Consult your network administrator for these settings.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To change any parameter:
1. Choose IP Network Settings from the Main Menu, then Domain Name Server (DNS) Settings.
2. Select an option to change—for example, DNS Mode, then enter settings according to the following guide.
Table 10 Domain Name Server settings
Parameter Description & Valid Settings*
Obtain DNS server addresses automatically or use specified addresses.
DNS Mode
Primary DNS
Secondary DNS
DNS Resolve Interval Interval to resolve DNS addresses from a network name to an IP address.
Domain Name Suffix
DNS Test
* Consult your network administrator for proper settings.
Note: Automatic assignment option is available only if a DHCP server is used to assign IP information to the Web Card.
Primary IP address of the name server for network.* Four numbers (0-255) separated by periods (.)—e.g., 192.168.0.1
Secondary IP address of the name server for network.* Four numbers (0-255) separated by periods (.)—e.g., 192.168.0.1
This suffix is used for assembling a fully qualified domain name when a host-only name is specified.
Checks whether the Web card will resolve a hostname to an IP address. Provide a host­only name, a fully qualified domain name or an IP address, click on Query for the card to attempt a lookup with the provided information.
Network Settings
14
Network Settings
Obtain address automatically
Specify address
Options for how long card retains resolved addresses
Click Edit to change settings
Network Settings
Configure tab
Management Protocol Menu
------------------------­1: SNMP Agent enabled 2: SNMP Communications
<ESC>: Cancel menu level Please select a key ?>
Enable SNMP Agent? [y/n] ?>
SNMP Communications Menu
------------------------­1: Authentication Traps 'no' 2: RFC-1628 (UPS) MIB 'enabled' 3: - Traps 'enabled' 4: Liebert Global Products MIB 'enabled' 5: - Condition Traps 'enabled' 6: - System Notify Tra p 'enabled' 7: Heartbeat Trap Interval’’ 8: Display/Modify Communities 9: Display/Modify Trap Communities A: Support Information
<ESC>: Cancel menu level Please select a key ?> 1

Web Interface

To access the DNS menu through the Web interface:
• Click on the Configure tab, then Network Settings in the left panel and finally Edit beneath the table of parameters and descriptions. After making changes, click Save.

5.3 Management Protocol

The Management Protocol Menu allows you to enable or disable SNMP and configure management protocols. Consult your network administrator for these settings.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To change any parameter:
1. Choose IP Network Settings from the Main Menu, then Management Protocol.
2. Select an option to change, then use the following guide to make changes.
Table 11 Management protocol ranges
Parameter Description & Telnet Menus
SNMP Agent
SNMP Communications
Enable or disable SNMP for remote management.
Set up access privileges, configure the Web card to send traps, described in the next section, SNMP Communications Menu.
For details on viewing support information, see 9.2 - Events and Parameters.
15
Network Settings
Click on Edit to enable any options
List sets frequency of Heartbeat Traps
Management Protocol
Configure tab

Web Interface

To access Management Protocol settings through the Web interface:
• Click on the Configure tab, then Management Protocol in the left panel and finally Edit in the right panel. After making changes, click Save.
16
Network Settings
Communities - Example
------------------------­1:
10.0.0.5 write public1
2: 10.0.0.6 write public1
<a>dd <d>elete <e>dit Complex lines allowed. e.g. <a 198.1.1.1 write public> ?>
Entry
#
IP
address
Access
(read/write)
Community
string
Codes for editing
SNMP Communications Menu
Use the SNMP Communications Menu to enable authentication traps and view or change communi­ties and trap communities, events and parameters. For details on viewing support information, see
9.2 - Events and Parameters.
Table 12 SNMP communications menu
Parameter Description & Telnet Menus
Authentication Traps
RFC-1628 (UPS) MIB
Traps
Liebert Global Products MIB
Condition Traps
System Notify Trap Enabled
Heartbeat Trap Interval
Enables authentication traps to receive security alerts when the Web card detects a request with an invalid community string.
Enables the RFC-1628 (UPS specific information) MIB on the Web card for querying of information in that MIB. This can be enabled or disabled independently of the Liebert Global Products MIB.
This option enables the RFC-1628 traps to be sent when an alarm event occurs on the device. The parent option must be enabled for this to also be enabled.
Enables the Liebert Global Products MIB (Enterprise Specific) for querying of information in that MIB. This option can be enabled or disabled independently of the RFC-1628 MIB.
Enables event condition traps to be sent per the LGP MIB. The parent option must be enabled for this to also be enabled.
Enables system traps to be sent per the LGP MIB. The parent option must be also enabled for this to be enabled.
Specifies how often a heartbeat trap will be sent to show that the device is online and functioning normally.
Display/Modify Communities
View devices that have permission to access the Web card, identified by IP address or hostname, read/ write permission and community string. Up to 20 devices may be configured for access.
Each device is identified by:
Entry Number - use the entry number (1-20) to edit or delete an entry
IP address or Hostname - the address of the device with access (MultiLink server, Nform server, Network Management System)
Access (read/write) - read allows users to view but not change data; write allows full permission for configuration, control and viewing
Community string - the community string used by the IP host for this Entry Number (case-sensitive, up to 32 characters)
To make changes:
Add a device (see example at right to enter all parameters in one line):
• Enter a to add an entry, then press Enter.
• Enter the IP address or hostname of the device to be added, then press Enter.
• Enter 1 for read or 2 for write access for this device, then press Enter.
• Enter the community string, then press Enter.
Example
a 10.0.0.5 write public1
(then press Enter)
17
Network Settings
Trap Communities - Example
------------------------------­1:
10.0.0.5 162 public1
2: 10.0.0.6 162 public1
<a>dd <d>elete <e>dit Complex lines allowed. e.g. <a 198.1.1.1 162 public> ?>
Entry
#
IP
address
Port to
receive traps
Community
string
Codes for editing
Edit a device (see example at right to enter all parameters in one line):
• Enter e to edit an entry, then press Enter.
• Type the Entry Number, then press Enter.
Example
e 2 10.0.0.7 read public2
(then press Enter)
• Enter the new IP address or hostname, then press Enter.
• Enter 1 for read or 2 for write access for this device, then press Enter.
• Enter the new community string, then press Enter.
Delete a device (see example at right to enter parameters in one line):
• Enter d, then press Enter. No confirmation message will appear.
• Type the Entry Number, then press Enter.
Example
d2
(then press Enter)
NOTE
Avoid the following setting—it permits access by any host and may pose a security risk:
• IP address = 0.0.0.0
• Access = write
•Community = public
Display/Modify Trap Communities
View devices that are configured to receive notifications from the Web card, identified by IP address or hostname, trap listen port and community string. Up to 20 devices may be configured to receive traps.
Each device is identified by:
Entry Number - use the entry number (1-20) to edit or delete an entry
IP address or hostname - the address or name of the device to receive traps (MultiLink server, Nform server, Network Management System)
Port - the Trap Listen Port where traps will be sent; use 162 if the host computer uses standard ports (161/162)
Community string - the community string used by the IP host for this Entry Number (case-sensitive, up to 32 characters)
To make changes:
Add a device (see example at right to enter all parameters in one line):
• Enter a to add an entry, then press Enter.
• Enter the IP address or hostname of the device to be added, then press
Example
a 10.0.0.5 162 public1
(then press Enter)
Enter.
• Enter the port number (default is 162), then press Enter.
• Enter the community string, then press Enter.
Edit a device (see example at right to enter all parameters in one line):
• Enter e to edit an entry, then press Enter.
• Type the Entry Number, then press Enter.
Example
e 2 10.0.0.7 162 public2
(then press Enter)
• Enter the new IP address or hostname, then press Enter.
• Enter the port number (default is 162), then press Enter.
• Enter the new community string, then press Enter.
Delete a device (see example at right to enter parameters in one line):
• Enter d, then press Enter. No confirmation message will appear.
• Type the Entry Number, then press Enter.
Example
d2
(then press Enter)
18

5.4 Web Server

Web Server Menu
---------------­1: Web Server Mode HTTP (Not Secure) 2: HTTP Transport Port 80 3: Password Protect Site 'disabled' 4: Configuration/Control 'enabled' 5: Refresh Rate 30 seconds
<ESC>: Cancel menu level Please select a key ?>
Web
Edit
Configure tab
Use the Web Server Menu to configure access to the card through the Web interface. Consult your network adminis­trator if needed.

5.4.1 Specify Web Server Settings

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To change any parameters:
1. Choose IP Network Settings from the Main Menu, then Web Server.
2. Select an option to change, then use the following guide to make changes.
Table 13 Web server settings
Parameter Description & Valid Settings
Select the operation mode of the Web server.
Web Server Mode
HTTP Transport Port
Password Protect Site
Configuration/ Control
Refresh Interval
Disabled - Web server is disabled
HTTP - Standard Web port, not encrypted
HTTPS - Standard secure Web port, all communication is encrypted
Web Server listening port number.
• For HTTP mode (non-encrypted communications), the default port is 80.
• For HTTPS mode (encrypted communications), the default port is 443. For HTTPS, you must also install a security certificate for Internet Explorer. Refer to the appro-
priate section for your version of Internet Explorer:
5.4.2 - Install Security Certificates - Internet Explorer 6 or earlier
5.4.3 - Install Security Certificates - Internet Explorer 7 or later
When enabled, the entire site is password-protected. (If disabled, all pages are accessible without a password except configure and control functions.)
Enable or disable the use of a Web browser to perform configuration and control operations. Note: This feature affects configuration and control operations from the Web interface only. If disabled, these functions may still be available using other system interfaces.
The interval in seconds (10 to 600 seconds) between automatic updates of dynamic Web pages—parametric data and device status in the right panel.
RECOMMENDATION: Consider whether frequent updates will slow down the system. If many users will access the device simultaneously, select a larger value to best serve all users. Recommended values range from 20 to 60 seconds.
Network Settings

Web Interface

To access Web Server settings through the Web interface:
• Click on the Configure tab, then Web in the left panel and finally Edit in the right panel. After making changes, click Save.
19

5.4.2 Install Security Certificates - Internet Explorer 6 or earlier

Click on View Certificate
View Certificate
Certificate Path tab
If you use Internet Explorer 6 or an earlier version and select HTTPS as the operation mode of the Web server (see 5.4.1 - Specify Web Server Settings), follow these instructions to install a security certificate.
• Open Internet Explorer and enter https:// followed by the IP address or hostname of the Web card—for example, https://192.168.0.125—in the address bar. The following message appears.
Network Settings
•Click the View Certificate button. This opens the Certificate window.
• In the Certificate window, above left, click the Certificate Path tab.
• In the Certificate Path tab, above right, click on Allegro Root CA, then on View Certificate.
20
• In the Certificate window, click the Install Certificate button, as shown below.
Install Certificate
Automatically select...
• The Certificate Import Wizard opens. Click Next.
Network Settings
• Click on Automatically select the certificate store based on the type of certificate, then click Next.
• The final Wizard window appears with a message that the process is complete. Click Finish.
• A confirmation box appears with a message that the import was successful. Click OK.
21

5.4.3 Install Security Certificates - Internet Explorer 7 or later

Continue to this website
Certificate Error
View Certificates
View Certificate
Certificate Path tab
If you use Internet Explorer 7 or later and select HTTPS as the operation mode of the Web server (see
5.4.1 - Specify Web Server Settings), follow these instructions to install a security certificate.
To do this:
• Open Internet Explorer and enter https:// followed by the IP address or hostname of the Web card—for example, https://192.168.0.125—in the address bar. The following message appears.
• Click on Continue to this website (not recommended) to open a connection to the Web card.
Network Settings
•Click the Certificate Error box next to the address bar, shown above left.
• In the window that pops up, shown above right, click the View Certificates link. This opens the Certificate window.
• In the Certificate window, above left, click the Certificate Path tab.
• In the Certificate Path tab, above right, click on Allegro Root CA, then on View Certificate.
22
• In the Certificate window, click the Install Certificate button, as shown below.
Install Certificate
Automatically select...
• The Certificate Import Wizard opens. Click Next.
Network Settings
• Click on Automatically select the certificate store based on the type of certificate, then click Next.
• The final Wizard window appears with a message that the process is complete. Click Finish.
• A confirmation box appears with a message that the import was successful. Click OK.
23

5.5 Telnet Server

Telnet Server Menu
------------------­1: Telnet Server 'enabled'
<ESC>: Cancel menu level Please select a key ?>
Telne t
Edit
Configure tab
Time Server Menu
------------------­1: SNTP Time Sync Rate Hourly 2: Time Server time.nist.gov 3: Time Zone (GMT) UTC
<ESC>: Cancel menu level Please select a key ?>
Use the Telnet Server Menu to enable or disable access to the Web card through a Telnet interface.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To change this setting:
1. Choose IP Network Settings from the Main Menu, then Telnet Server.
2. Choose Telnet Server, then specify:
Enabled to permit Telnet access
Disabled to block access via Telnet

Web Interface

To access Telnet settings through the Web interface:
• Click on the Configure tab, then Telnet in the left panel and finally Edit in the right panel. After making changes, click Save.
Network Settings

5.6 Time (SNTP) Menu

This permits setting time options—how often the Web card synchronizes with the Time Server, which Time Server to use for synchronization and which the Time Zone the Web card is operating in.
24

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

Click on Edit to choose options
Time zones available from list
Configure tab
Time Server list
Time Servers must be entered manually
To change this setting:
1. Choose IP Network Settings from the Main Menu, then Time (SNTP).
2. Choose SNTP Time Synch Rate, then specify:
• Hourly
•Daily
3. Choose Time Server, then specify the new time server, if desired.
4. Choose Time Zone, select a region from the list and then select a time zone.
Table 14 Time Server parameters
Parameter Description & Telnet Menus
SNTP Time Sync Rate
Time Server
Time Zone
This is how often the card will attempt to synchronize its internal clock with the specified time server.
This is the server that will be used for synchronization. This can be either an IP address or a hostname, provided that the DNS options are configured.
This is the local Time Zone that will be used to correctly adjust the time provided by the server for the locale where the Web Card is being used.

Web Interface

To access Time (SNTP) settings through the Web interface:
Network Settings
Click on the Configure tab, then Network Settings in the left panel and finally Edit in the right panel. After making changes, click Save.
25

5.7 Change Username / Password

Users
Edit
Configure tab
The Web card is designed for two types of access, each with a default user name and password. For security, be sure to change the default password.

Table 15 Factory default passwords

Type of User Factory Default Description
Administrator
General User
Follow these guidelines to change the user name and password.

Table 16 Username and password guidelines

Maximum length 32 characters (6 or more characters recommended)
Valid characters Any printable character EXCEPT colon, tab, double quote, question mark
Upper/lowercase Case-sensitive—letters must be uppercase or lowercase as entered
Tips Avoid common names, words and phrases as passwords

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

Username Liebert
Password Liebert
Username User
Password User
Network Settings
Full access to configuration and control functions, as well as viewing privileges
Viewing privileges only—no access to configuration or control functions
To change the Administrator or General user name or password:
1. Choose IP Network Settings from the Main Menu, then choose either:
Change Administrator Username/Password or
Change General Username/Password
2. Enter a user name—the current user name is shown in brackets.
Enter Administrator Username, press enter for [Liebert]: (Max 32 chars) ?>
3. Enter a password, then verify by typing the password again.
Enter New Password: (Max 32 chars) ?> ******** Verify Password: ?> ********

Web Interface

To access usernames and passwords through the Web interface:
• Click on the Configure tab, then Users in the left panel and finally Edit in the right panel. After making changes, click Save.
26

5.8 Reset Authentication to Factory Defaults

You may reset the Administrator and General User usernames and passwords to the factory defaults.
If you forget your username or password, you may reset them using a serial configuration cable connection (see Section 2.1.1 or 2.2.1 - Connect the Cable), which provides direct access to the card without a username or password. To enter a new username and password, see 5.7 - Change Username / Password.

Table 17 Factory default passwords

Type of User Factory Default Description
Administrator
General User
Username Liebert
Password Liebert
Username User
Password User

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To reset the usernames and passwords to the factory defaults:
1. Choose IP Network Settings from the Main Menu, then Reset Authentication to Factory Defaults.
Reset authentication to factory Defaults? [y/n] ?>
2. Enter y to reset the Administrator and General User usernames and passwords to the default settings.
Full access to configuration and control functions, as well as viewing privileges
Viewing privileges only—no access to configuration or control functions
Network Settings
NOTE
This feature is not available through the Web interface
27

6.0 MESSAGING

Messaging Menu
--------------­1: Email 'disabled' 2: SMS 'disabled' 3: Email Configuration 4: SMS Configuration
<ESC>: Cancel menu level
Please select a key ?>
Messaging
Configure tab
Edit
The Messaging menu is used to set up e-mail and text message notifications from the Web card.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To access these options:
1. Choose Messaging from the Main Menu.
2. Select an option, then use the following guide to make changes.

Table 18 Messaging menu guide

Menu item Refer to:
E-Mail Configuration page 29
SMS Configuration page 30
Customize Messages (E-Mail and SMS) page 32

Web Interface

To access Messaging settings through the Web interface:
• Click on the Configure tab, then Messaging in the left panel and finally Edit in the right panel. After making changes, click Save.
Messaging
28

6.1 E-Mail Configuration

Email Configuration Menu
------------------------­1: Email From 'Uninitialized' 2: Email Message Recipients 3: Email Subject 4: Email Customize Message 5: SMTP Server 'Uninitialized' 6: Port 25 7: Test Email 8: View Test Email Log File
<ESC>: Cancel menu level
Please select a key ?>
Setting up event notifications to be sent via e-mail involves two steps: enabling the function, then specifying the parameters.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To activate and set up e-mail messages:
1. Choose Messaging from the Main Menu, then Email.
Enable Email? [y/n] ?>
2. To enable the e-mail feature, enter y (yes) at the prompt.
3. Choose Email Configuration from the Messaging Menu, then select an option and use the following guide to make changes.
Table 19 E-mail configuration guide
Parameter Description Maximum
Email From
Email Message Recipients
Email Subject
Email Customize Message
SMTP Server
Port SMTP server port—typically the default port, 25.
Test Email
View Test Email Log File
The e-mail address of the sender—for example, support@company.com— typically, the address where replies should be sent.
The e-mail will be sent to this list of addresses. To add an e-mail address, use the format a jsmith@abc.com. Multiple addresses must be added individually. Changes may be made by entering d to delete an entry or e to edit an entry. NOTE: To specify multiple recipients of the e-mail message in the Web interface, use a semicolon (;) to separate addresses in the Email To box.
The subject line of the e-mail. By default, this is the event description—e.g., AlarmOnBypass—but it may be customized.
The text of the message sent to e-mail recipients. Choose from a list of items to include in the message. For details, see 6.3 - Customize Messages.
The IP address or domain name of the SMTP e-mail server that sends messages.
After saving changes to e-mail parameters, send a test e-mail message to verify the settings are correct. The message status will be displayed.
Choose this option to display a log showing the results of test e-mails.
Messaging
64
characters
64
characters
120
characters
32
characters
29

Web Interface

Email
Configure tab
Edit
SMS Configuration Menu
----------------------­1: SMS From 'Uninitialized' 2: SMS Message Recipients 3: SMS Subject 4: SMS Customize Message 5: SMTP Server 'Uninitialized' 6: Port 25 7: Test SMS 8: View Test SMS Log File
<ESC>: Cancel menu level Please select a key ?>
To access E-Mail Configuration through the Web interface:
• Click on the Configure tab, then Email in the left panel and finally Edit in the right panel. After making changes, click Save.
Messaging

6.2 SMS Configuration

Setting up event notifications for SMS text messages involves two steps: enabling the function, then specifying the parameters.
30
Messaging
SMS
Configure tab
Edit

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To activate and set up SMS messages:
1. Choose Messaging from the Main Menu, then SMS.
Enable SMS [y/n] ?>
2. To enable the SMS feature, enter y (yes) at the prompt.
3. Choose SMS Configuration from the Messaging Menu, then select an option and use the following guide to make changes.
Table 20 SMS configuration guide
Parameter Description Maximum
SMS From
SMS Message Recipients
SMS Subject
SMS Customize Message
SMTP Server The IP address or domain name of the SMTP e-mail server that sends messages.
Port SMTP server port—typically the default port, 25.
Test SMS
View Test SMS Log File
The e-mail address of the sender—for example, support@company.com— typically, the address where replies should be sent.
The message will be sent to this list of addresses. The SMS/Text Message address is usually a 10-digit phone number followed by @____.com (where ____ might be a company name). To add an SMS address, use the format a 1112223333@abc.com. Multiple addresses must be added individually. Changes may be made by entering d to delete an entry or e to edit an entry. NOTE: To specify multiple recipients of the SMS message in the Web interface, use a semicolon (;) to separate addresses in the SMS To box.
The subject line of the message. By default, this is the event description—e.g., AlarmOnBypass—but it may be customized.
The text of the message sent to e-mail recipients. Choose from a list of items to include in the message. For details, see 6.3 - Customize Messages.
After saving changes to SMS parameters, send a test SMS message to verify the settings are correct. The message status will be displayed.
Choose this option to display a log showing the results of test messages.
characters
characters
characters
characters
64
64
120
32

Web Interface

To access SMS Configuration through the Web interface:
• Click on the Configure tab, then SMS in the left panel and finally Edit in the right panel. After making changes, click Save.
31

6.3 Customize Messages

Email/SMS Customize Message Menu
-------------------------------­1: IP Address 'enabled' 2: Event 'enabled' 3: Event Date & Time 'disabled' 4: Name 'enabled' 5: Contact 'enabled' 6: Location 'enabled' 7: Description 'enabled' 8: Web link & Port 'disabled' 9: Event Consolidation 'enabled' A: Consolidation Time Limit (seconds) 60 B: Consolidation Event Limit 30
<ESC>: Cancel menu level Please select a key ?>
Both e-mail and SMS text messages may be custom­ized to include items such as the IP address or host­name, event name and a link to the Web card in the body of the message.
Terminal Emulation (Serial or TCP/IP Connec-
tion) / Telnet
1. Choose Messaging from the Main Menu, then Email Configuration (or SMS Configuration).
2. Choose Email (or SMS) Customize Message from the Configuration menu.
3. Choose an option from the Email (or SMS) Customize Message Menu, then enter y (yes) at the prompt to confirm your choice. Repeat for each item to be included in messages. Refer to the following guidelines to make changes:
Table 21 E-mail and SMS message guidelines
Parameter Description—if enabled, outgoing messages will include: Defined in:
IP address or hostname
Event Description of the SNMP event 9.0 - Support Information
Event Date & Time
Name The name for the Liebert unit 4.0 - System Information
Contact The contact person or department 4.0 - System Information
Location The location of the Liebert unit 4.0 - System Information
Description Other information about the Liebert unit 4.0 - System Information
Web Link & Port
Event Consolidation
Consolidation Time Limit (seconds)
Consolidation Event Limit
The IP Address or Hostname of the Web card 5.1 - Boot/IP Settings
The date & time when the SNMP event occurred
A clickable link to the Web card through the Web interface 5.1 - Boot/IP Settings
The port number of the SMTP server port
Enable or disable consolidation of events for e-mail/SMS notification
Duration (in seconds) to consolidate events before sending a notification. Notification will be sent when this threshold is reached, regardless of event limit. Range: 10 to 120.
Number of events to consolidate before sending a notification. Notification will be sent when this threshold is reached, regardless of time limit. Range: 1 to 50.
Messaging
6.1 - E-Mail Configuration
6.2 - SMS Configuration
6.1 - E-Mail Configuration
6.2 - SMS Configuration
Message Consolidation Time Limit on page 33
Message Consolidation Time Limit on page 33
32

Web Interface

Customize Message
Configure tab
Edit
To access Customize Message settings through the Web interface:
• Click on the Configure tab, then Customize Messages in the left panel and finally Edit in the right panel. Choose the items to include in each type of message in the Email and SMS columns.
• After making changes, click Save.
Messaging
Message Consolidation Time Limit
Message Consolidation Time Limit allows adjusting the duration the card will wait for additional events before sending a notification E-mail. Consolidation event limit allows adjusting the number of events each E-mail will contain.
33

7.0 FACTORY SETTINGS

Factory Settings Menu
---------------------­1: Reset to Factory Defaults 2: Agent Card Information
<ESC>: Cancel menu level
Please select a key ?>
Factory Defaults
Configure tab
Reset to Factory Defaults
Factory default values may be restored for all configuration settings. This step:
• Replaces all user-defined settings described in this manual (see 3.0 - Configuration Overview through 6.0 - Messaging)
• Restores DHCP service, the factory default, replacing a static IP address or hostname, if config­ured during installation (see 2.0 - Installation)

7.1 Reset to Factory Defaults

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To restore the factory default settings:
1. Choose Factory Settings from the Main Menu, then choose Reset to Factory Defaults.
Reset to factory Defaults? [y/n] ?>
2. Enter y (yes) at the prompt to confirm your choice. To cancel, enter n (no).
3. A message appears until the process is complete.
Resetting card to factory defaults...

Web Interface

Factory Settings
To restore the factory default settings through the Web interface:
• Click on the Configure tab, then Factory Defaults in the left panel and finally Reset to Fac- tory Defaults in the right panel.
34

7.2 Liebert DS - Local Node Settings for Multiple Cards

Liebert DS
Factory Settings Menu
---------------------­1: Advanced Communication
Settings
2: Reset to Factory Defaults
<ESC>: Cancel menu level
Please select a key ?>
Liebert DS
Advanced Communication Settings Menu
-------------------------------­1: Local Node Settings 2: Managed Device Settings 2: Reset to Default
<ESC>: Cancel menu level
Please select a key ?>
Liebert DS
Local Node Settings Menu
------------------------­1: Node ID: 1 2: Communication Rate: 38400 3: Maximum Master Address: 3 4: Maximum Retry Count: 5 5: Retry Interval(sec): 5
<ESC>: Cancel menu level
Please select a key ?>
If you use two cards of the same type with the Liebert DS, you will need to change the local node set­ting of one card. These steps apply only when both cards are the same type, either:
• Two Liebert IntelliSlot Web cards (P/N IS-WEBLBDS)
or
• Two Liebert IntelliSlot 485 cards (P/N IS-485LBDS)

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To access local node settings:
1. Choose Factory Settings from the Main Menu.
2. Choose Advanced Communication Settings from the Factory Settings Menu.
3. Choose Local Node Settings from the Advanced Communication Settings Menu.
4. Choose Node 1 from the Local Node Settings Menu, then use the following guide to make changes.
If there are two Liebert IntelliSlot Web cards or two Liebert IntelliSlot 485 cards, you must change the address of one card (see Table 22):
• For the Liebert IntelliSlot Web card, the default address is 1. For two Web cards, set the address of the second card to 2.
• For the Liebert IntelliSlot 485 card, the default address is 2. For two 485 cards, set the address of the second card to 1.
Table 22 Factory default MAC addresses
Factory Settings
Liebert IntelliSlot Card Part Number
Liebert IntelliSlot Web Card-LBDS IS-WEBLBDS 0x01 2
Liebert IntelliSlot 485 Card-LBDS IS-485LBDS 0x02 1
Factory Default
MAC Address
35
Set Node 1 Address
of Second Card to:

8.0 MONITOR AND CONTROL FUNCTIONS - WEB ONLY

Monitor tab
Monitor Categories
Click to view in right panel
Agent Information
Device Status

Web Interface Only

The Web interface allows you to monitor and control the Liebert equipment where the Web card is installed, in addition to configuration capabilities presented in previous sections.

8.1 Monitoring Liebert Equipment

To view monitoring data through the Web interface:
• Open the Web interface (if needed, see 3.5 - Open the Web Interface).
• Click on the Monitor tab if needed. This is always the opening view after connecting to the Web interface, as shown in the following example.
Monitor and Control Functions - Web Only
• The top portion of the left panel displays information that appears on all pages:
Agent Information - name, contact, location and description of the Liebert unit (as defined in 4.0 - System Information)
Device Status - current status of the Liebert unit and whether any alarms are active (if so, the most recent alarm is listed)
Monitor Categories appear at bottom left, organized with folder icons and showing the avail­able Monitoring functions.
• Click on a category to view parametric data in the right panel. The example above shows a graphic representation of the current state of a Liebert UPS. Other categories show data in table format. The information will vary according to the type of Liebert unit.
NOTE
If any alarms are currently active, they are listed below the graphic in the opening window. Click on the Active Alarms category to view more details about any alarms that are active.
36

8.2 Controlling Liebert Equipment

Control tab
Control Operations
Click to view in right panel
Output
Setpoints
Liebert GXT2U example
Liebert DS example
To perform Control operations through the Web interface:
• Open the Web interface (if needed, see 3.5 - Open the Web Interface).
• Click on the Control tab, as shown in the following example.
Control Operations categories appear at bottom left, organized with folder icons and showing the available Control functions. Clicking on a category changes the view in the right panel. The example above shows the summary page.
The following guide is a partial list of Control operations—these vary by the type of Liebert unit.
Table 23 Control operations parameters—functions vary by Liebert unit
Command Description
Abort Commands Prevent any pending commands from being completed.
Alarm Silence / Alarms Temporarily silence an audible alarm that is active. Reset or acknowledge alarms
Output / System Turn the Liebert unit On or Off; reboot the unit.
Statistics Reset statistics—for example, battery or power statistics
Tests Initiate diagnostic tests on the Liebert unit.
Setpoints Change setpoints for the Liebert unit.
Monitor and Control Functions - Web Only
• To perform an operation, click on a Control Operations category at left, then click on the appropri­ate button in the right panel. The example below shows control operations for two Liebert units.
37

8.3 Event Log

Scroll through Event Log
Event Log tab
The Event Log tab allows viewing events stored in the Web card’s history. This history is gathered only when the Web card is installed and communicating properly with the device. The history is stored in descending chronological order; Page 1 Item 1 contains the most recent event.
The list of events includes:
1. The time and date of the event—This is either the local time and date (if the network time synchronization is working properly) or the time-delta from when the card was first powered on (if no network time synchronization has taken place).
2. The event ID—This is the index number given to events since the start of the history.
3. The event text—Text stating the type of event and how the card reacted.

Event Log Controls

<<-: Scroll immediately to Page 1 of the history
<-: Scroll left one page in the history
->: Scroll right one page in the history
->>: Scroll immediately to the last page of the history

Links

Agent Event Log at the top of the page includes two links, (.txt) and (.csv). The Txt link will download the entire event history in unformatted text. The CSV link will download the entire event history in comma-separated format, which can then be imported into an application such as Microsoft Excel
Monitor and Control Functions - Web Only
®
.
38

9.0 SUPPORT INFORMATION

Factory Settings Menu
---------------------­1: Reset to Factory Defaults 2: Agent Card Information
<ESC>: Cancel menu level
Please select a key ?>
Summary
Support tab
Listing in right panel
Support data includes identifying information for the Web card, as well as events and parameters available for the Liebert equipment.

9.1 View Web Card Information

Identifying information for the Web card may be viewed through any interface and includes the MAC address, model and part number, serial number and firmware version.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To view Web card information:
1. Choose Factory Settings from the Main Menu, then choose Agent Card Information.
2. The Web card information appears, as shown in the following example. Press the Enter key to return to the previous menu.
MAC Address 00-00-68-16-82-C1 Network Card Model IntelliSlot Web Card Network Card Part # OCWEBCARD Manufacture Date APR 28,2004 Serial Number 416701G105T2004APR280074 Boot Version 2.300.0 Boot Label OCWEBCARD_HID3_2.300.0_034380 App Version 2.300.0 App Label OCWEBCARD_HID3_2.300.0_035191 Hardware Version 3 CPU Speed 50 MHz Flash Usage 4327 Out Of 8388 KByte
Hit Enter to Exit
Support Information

Web Interface

To view Web card information through the Web interface:
• Click on the Support tab, then Summary in the left panel. The Web card information appears in the right panel.
39

9.2 Events and Parameters

Support Information Menu
------------------------­1: Display Events 2: Display Parameters Total Events: 40 Total Parameters: 141 Total Objects: 181
<ESC>: Cancel menu level Please select a key ?>
SNMP Communications Menu
------------------------­1: Authentication Traps 'no' 2: Display/Modify Communities 3: Display/Modify Trap
Communities
4: Support Information
<ESC>: Cancel menu level Please select a key ?>
Display Events
(Example)
----------------­AlarmOnBypass,1.3.6.1.2.1.33.
1.6.3.9
lgpAgentDeviceCommunicationLost,
1.3.6.1.4.1.476.1.42.2.3.0.1
Hit any key to continue...
Display Parameters
(Example)
---------------------­sysDescr,1.3.6.1.2.1.1.1.0 sysObjectID,1.3.6.1.2.1.1.2.0 Hit any key to continue...
Events (or Parameters)
Listing in right panel
Support tab
You may view a list of all supported events and parameters for the Liebert equipment through any interface. Depending on the Liebert IntelliSlot Web card, the list might include SNMP and Modbus.

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To view this data:
• Choose IP Network Settings from the Main Menu.
• Choose Management Protocol, then SNMP Communica- tions.
• Choose Support Information from the SNMP Communica­tions Menu to display the menu at right.
The menu displays:
• the number of events
• the number of parameters
• the total number of objects (sum of events and parameters)
• Choose Display Events to view a list of supported events for the Liebert unit, as shown in the example at right.
These events may vary according to the Liebert unit where the card is installed.
• Choose Display Parameters to view a list of supported param­eters for the Liebert unit, as in the example at right.
These parameters vary according to the Liebert unit where the card is installed.
Support Information

Web Interface

To view events and parameters through the Web interface:
• Click on the Support tab, then Events (or Parameters) in the left panel. The events or parame­ters are listed in the right panel. The example below shows a list of Events.
40

APPENDIX A-FIRMWARE UPDATES

A.1 INTRODUCTION

Liebert’s IntelliSlot® cards may be updated to take advantage of the latest release of the firmware with enhanced features, compatibility with new units or service patches. Upgraded firmware may be downloaded with a browser, such as Internet Explorer. Liebert maintains firmware upgrades on its Web site, www.liebert.com/downloads
Liebert manufactures various types of network cards for Liebert products. Before beginning any upgrade, determine the type of Liebert IntelliSlot card to be upgraded.
This identifying information—the type of card and firmware version currently installed—may be found in the documentation shipped with the card or by reading the card’s support information through a terminal emulation, Telnet or Web interface, as described in A.3.2 - Determine the Lie-
bert IntelliSlot Card Type and Firmware Version.
NOTE
Liebert recommends that users read all the instructions prior to attempting a firmware upgrade.

A.1.1 Overview

The firmware upgrade involves these steps:
Table A1 Overview of the upgrade process
Step For details, see:
1. Decide which interface to use to connect to the Liebert IntelliSlot card
2. Prepare for the upgrade
• Make sure you have everything needed to
perform the upgrade
• Check the type of card and firmware version
currently installed
• Download the upgrade file from Liebert’s Web
site
• Decide which method to use for the upgrade
3. Follow the step-by-step instructions to upgrade the firmware with the chosen method:
• HTTP (Web) Method A.4 - Updating the Firmware - HTTP (Web) Method
• TFTP (HyperTerminal, Telnet, Web) Method
• Xmodem (Serial) Method A.6 - Updating the Firmware - Xmodem (Serial) Method
Introduction
.
A.2 - Connect to the Card - Terminal Emulation, Telnet
or Web Interface
A.3.1 - Requirements to Update the Liebert IntelliSlot
Card’s Firmware
A.3.2 - Determine the Liebert IntelliSlot Card Type and
Firmware Version
A.3.3 - Download the Firmware Upgrade File to the
Computer
A.3.4 - Choose a Method to Install the Firmware
Upgrade
A.5 - Updating the Firmware - TFTP (HyperTerminal,
Telnet, Web) Method

A.1.2 Estimated Time to Download the Firmware Upgrade File

The amount of time required to download the firmware upgrade file depends on the upgrade method used. Refer to Table A2 for estimated times for each method.
Table A2 Estimated Time for downloads
Upgrade Method Expected Speed
HTTP (Web) Method (.bin file)
TFTP (HyperTerminal, Telnet, Web) Method (.bin file)
Xmodem (Serial) Method Xmodem 1K 115,200 bps
6-7 minutes
(subject to network traffic)
5-6 minutes
(subject to network traffic)
1st file 2 minutes
2nd file 2 minutes
3rd file 3-5 minutes
A1
Connect to the Card - Terminal Emulation, Telnet or Web Interface
Name
COM3
Connection settings
Table A3 Communication settings
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
Name
TCP/IP (Winsock)
RTCS v2.96.00 Telnet server
Service Port Manager Active <Esc> Ends Session
Login: Liebert Password: ********

A.2 CONNECT TO THE CARD - TERMINAL EMULATION, TELNET OR WEB INTERFACE

Upgrading the firmware requires connecting to the card with one of these interfaces.

A.2.1 Open the Terminal Emulation Interface - Serial Connection

To connect to the card using terminal emulation software with a serial connection to the Web card:
1. Open a terminal emulation application, such as HyperTerminal.
To do this:
•Click the Start button, then Programs, Accessories, Communications and finally HyperTerminal.
2. In the Connection Description window, enter a name for the connection—for example, GXT2U—then click OK.
3. In the Connect To window:
• Choose COM3 from the Connect Using drop-down list.
•Click OK.
4. In the COM3 Properties window, enter the communication settings shown in Table A3.
5. When the message at right appears in the HyperTerminal window, press the Enter key.

A.2.2 Open the Terminal Emulation Interface - TCP/IP Connection

To connect to the card using terminal emulation software with an Ethernet connection to the Web card:
1. Open a terminal emulation application, such as HyperTerminal.
To do this:
•Click the Start button, then Programs, Accessories, Communications and finally HyperTerminal.
2. In the Connection Description window, enter a name for the connection—for example, GXT2U—then click OK.
3. In the Connect To window:
• Choose TCP/IP (Winsock) from the Connect Using drop-down list.
• Enter the IP address of the Web card—for example,
192.168.0.125—in the Host Address box, then click OK.
4. When the message at right appears in the HyperTerminal window, press the Enter key.
5. Enter the Administrator username and password (both are case­sensitive):
a. Login (username—default is Liebert) b. Password (default is Liebert)
A2

A.2.3 Open the Telnet Interface

C:>telnet 192.168.0.125
RTCS v2.96.00 Telnet server
Service Port Manager Active <Esc> Ends Session
Login: Liebert Password: ********
Configure and Support Tabs
To connect to the card using Telnet:
1. Open a Telnet connection on a computer with an Ethernet connection to the Liebert unit. To do this:
• Open a command prompt window—click the Start button, then Run.
• Enter cmd and click OK.
• In the command prompt window that opens, enter telnet fol­lowed by a space and the IP address of the Web card—for exam­ple:
telnet 192.168.0.125
2. When the message at right appears in the command prompt window, press the Enter key.
3. Enter the Administrator username and password (both are case­sensitive):
a. Login (username—default is Liebert) b. Password (default is Liebert)

A.2.4 Open the Web Interface

To connect to the card using the Web interface:
Preparing to Update Liebert IntelliSlot Firmware
1. Open a Web browser such as Internet Explorer.
2. Enter the IP address of the Web card in the address bar—e.g., 192.168.0.125.
3. Click on a tab at the top of the window.

A.3 PREPARING TO UPDATE LIEBERT INTELLISLOT FIRMWARE

A.3.1 Requirements to Update the Liebert IntelliSlot Card’s Firmware

Make sure you have the following before starting the update:
• Firmware upgrade downloaded from Liebert’s Web site (see A.3.3 - Download the Firmware Upgrade File to the Computer)
• A computer running Internet Explorer 5.5 or newer
• A Liebert IntelliSlot card
• A connection to the Liebert IntelliSlot card
• Null modem cable—serial upgrade method
• Ethernet connection—TFTP or HTTP upgrade method
• An Internet connection
A3
Preparing to Update Liebert IntelliSlot Firmware
Factory Settings Menu
---------------------­1: Reset to Factory Defaults 2: Agent Card Information
<ESC>: Cancel menu level
Please select a key ?>
MAC Address 00-00-68-16-82-C1 Network Card Model IntelliSlot Web Card Network Card Part # OCWEBCARD Manufacture Date APR 28,2004 Serial Number 416701G105T2004APR280074 Boot Version 2.300.0 Boot Label OCWEBCARD_HID3_2.300.0_034380 App Version 2.300.0 App Label OCWEBCARD_HID3_2.300.0_035191 Hardware Version 3 CPU Speed 50 MHz Flash Usage 4327 Out Of 8388 KByte
Hit Enter to Exit
Model and Part Number
Firmware Ver sio n
Summary
Support tab
Model, Part Number and Firmware Version

A.3.2 Determine the Liebert IntelliSlot Card Type and Firmware Version

Each type of Liebert IntelliSlot card uses different firmware. Attempting to upgrade a card with the firmware for another type of card will fail and may damage the card.
To determine the type of card in your Liebert equipment:

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To view Web card information using terminal emulation or Telnet:
1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.1 - Open the Terminal Emulation Interface
- Serial Connection, A.2.2 - Open the Terminal Emulation Interface - TCP/IP Connection or A.2.3 - Open the Telnet Interface).
2. Choose Factory Settings from the Main Menu, then choose Agent Card Information.
3. The Liebert IntelliSlot card model, part number and firmware version appear in the following example. Press the Enter key to return to the previous menu

Web Interface

To view Web card information using a Web browser:
1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the Web Interface).
2. Click on the Support tab, then Summary in the left panel. The Liebert IntelliSlot card model, part number and firmware version appear in the right panel.

A.3.3 Download the Firmware Upgrade File to the Computer

NOTE
Turn off the power management on your PC or laptop before beginning the update to ensure that communication will not be disrupted during the process.
To download the upgrade file:
1. Open a Web browser, such as Internet Explorer (5.5 or newer).
2. Navigate to Liebert’s Web site, www.liebert.com/downloads
3. Choose the firmware upgrade for your card from the selections on the Web page (see A.3.2 - Determine the Liebert IntelliSlot Card Type and Firmware Version).
4. Click on the link to download the file.
5. Save the file to your computer’s hard drive. Be sure to make a note of the location where the file is saved.
A4
.
Updating the Firmware - HTTP (Web) Method
Web
Configure tab
Browse
Filename
Update Firmware
Connect To

A.3.4 Choose a Method to Install the Firmware Upgrade

To install the firmware upgrade, choose one of these three methods and refer to the associated step­by-step directions:
• HTTP (Web) - see A.4 - Updating the Firmware - HTTP (Web) Method
• TFTP - see A.5 - Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
• Xmodem (Serial) - see A.6 - Updating the Firmware - Xmodem (Serial) Method

A.4 UPDATING THE FIRMWARE - HTTP (WEB) METHOD

Follow these steps to install the firmware upgrade using the HTTP (Web) method. This method is available through the Web interface only and requires an Ethernet connection to the Web card.

A.4.1 Install the Firmware Upgrade

NOTE
Turn off the power management on your PC or laptop before beginning the update to ensure that communication will not be disrupted during the process.
To update the Liebert IntelliSlot card firmware using the HTTP (Web) method:
1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the Web Interface).
2. Click on the Configure tab, then click on Web (under Firmware Update) in the left panel. The Connect To box opens for you to enter the username and password.
3. Enter the Administrator username and password (both case-sensitive): a. User Name (default is Liebert) b. Password (default is Liebert)
4. Click OK. The Web (HTTP) Firmware Update window opens, as shown at right below.
5. Click on the Browse button to locate the upgrade file. This is the file with the extension “.bin” downloaded in A.3.3 - Download the Firmware Upgrade File to the Computer. Then click Open to return to the update screen.
6. When ready to begin the update, click the Update Firmware button. A screen will appear, showing the firmware update progress.
NOTE
Do not refresh your browser or open another browser window. Wait until the firmware update has been completed before opening other applications or using the computer for other tasks.
7. A message appears indicating whether the update was successful.
After the firmware update is completed, the card will reinitialize and you may return to the Liebert IntelliSlot card’s Web interface.
Check the new firmware version if you wish (see A.3.2 - Determine the Liebert IntelliSlot Card Type and Firmware Version).
A5
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
Firmware Updates Menu
---------------------­1: TFTP Update
TFTP Update Menu
----------------­1: IP Address 0.0.0.0 2: Port 69 3: Filename Uninitialized 4: Initiate TFTP Firmware Update
<ESC>: Cancel menu level
Please select a key ?>
Firmware Updates Menu
---------------------­1: TFTP Update

A.5 UPDATING THE FIRMWARE - TFTP (HYPERTERMINAL, TELNET, WEB) METHOD

Follow these steps to update the firmware using the TFTP method. This method is available through the terminal emulation, Telnet and Web interfaces with an Ethernet connection to the Web card.
NOTE
This method includes a time-sensitive operation requiring expeditious location of the upgrade files downloaded in A.3.3 - Download the Firmware Upgrade File to the Computer. Read through this entire section before beginning the upgrade.

A.5.1 TFTP Method - Terminal Emulation / Telnet Interface

To update the Liebert IntelliSlot card firmware using the TFTP method with a terminal emulation or Telnet interface:
Open a Connection to the Card
1. Open a terminal emulation or Telnet connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.2 - Open the Terminal Emulation Interface - TCP/IP Connection or A.2.3 - Open the Telnet Interface).
2. Choose Firmware Updates from the Main Menu.
3. Choose TFTP Update from the Firmware Updates menu, shown at right.
Specify TFTP Server and Upgrade Filename
4. The TFTP Update Menu, shown at right, displays the TFTP server’s IP address and listening port, along with the name of the firmware update file.
5. Select options as needed and refer to the following guide to change any settings.
Table A4 Firmware update settings - TFTP
Parameter Description
Server The IP address of the TFTP server—for example, 192.168.0.125.
Port Port that the TFTP server is using, typically 69.
Filename
Name of the firmware update file—128 characters maximum, including spaces and punctuation. This is the file with the extension “.bin” downloaded in A.3.3 - Download the Firmware Upgrade File to the Computer.
6. After making changes, press the Escape key twice to return to the Main Menu.
7. Choose Exit and Save to save your changes and reboot the card.
Reconnect to the Card
8. Connect to the Liebert IntelliSlot card again (if needed, see A.2.3 - Open the Telnet Interface or A.2.1 - Open the Terminal Emulation Interface - Serial Connection).
9. Choose Firmware Updates from the Main Menu.
10. Choose TFTP Update from the Firmware Updates menu, shown at right.
A6
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
TFTP Update Menu
----------------­1: IP Address 192.168.0.125 2: Port 69 3: Filename OCWEBCARD_HID3_2.300.0_035780_AppFwUpdt.bin 4: Initiate TFTP Firmware Update
<ESC>: Cancel menu level
Please select a key ?>
All Code In Flash Will Be Rewritten, Confirm? [y/n]
TFTP Update initiated
The firmware on this card is currently being updated. This operation may take 6 or more minutes depending on network traffic and other factors. The card will be rebooted upon successful completion of the process OR control will be returned to this terminal session upon failure so another firmware update attempt can be made.
Firmware update in process... Percent Complete(0%)
Main Menu
---------­1: System Information 2: IP Network Settings 3: Messaging 4: Factory Settings 5: Firmware Updates
q: Quit and abort changes x: Exit and save
Please select a key ?>
TFTP
Configure tab
Edit
Begin the Upgrade Process
11. When ready to begin the update, choose Initiate TFTP Firmware Update.
12. Open the TFTP application and start TFTP. Ensure that all settings are ready to transfer the file, including the location of the upgrade file. Refer to your TFTP user manual for more details.
13. Return to the terminal emulation/Telnet screen. At the confirmation message prompt, enter y (yes) to confirm your choice. (To cancel, enter n for no.)
14. A message appears, as shown at right, showing the progress by percent complete.
15. When the progress screen shows 100% complete, the card will be rebooted. Press Enter when this is finished.
16. Press the Escape key to return to the Main Menu, then choose Exit and Save.
The upgrade is now complete.
Check the new firmware version if you wish (see A.3.2 - Determine the Liebert
IntelliSlot Card Type and Firmware Version).

A.5.2 TFTP Method - Web Interface

To update the Liebert IntelliSlot card firmware using the TFTP method with a Web interface:
Open a Connection to the Card
1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the Web Interface).
2. Click on the Configure tab, then TFTP in the left panel.
3. Enter the Administrator username and password (both are case-sensitive): a. Login (username—default is Liebert) b. Password (default is Liebert)
A7
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
TFTP
Configure tab
Save
Reinitialize
Update Firmware
Specify TFTP Server and Upgrade Filename
4. Click the Edit button in the right panel.
5. Select options as needed and refer to the following guide to change any settings.
Table A5 Firmware update settings - Web
Parameter Description
Server The IP address of the TFTP server—for example, 192.168.0.125.
Port Port that the TFTP server is using, typically 69.
Name of the firmware update file—128 characters maximum, including spaces and punctuation.
Filename
6. After making changes, click Save, then click Reinitialize in the left panel to reboot the card.
This is the file with the extension “.bin” downloaded in A.3.3 - Download the Firmware Upgrade File to the Computer.
Reconnect to the Card
7. Click the Configure tab, then TFTP and enter the username and password (Steps 2 and 3) to return to the TFTP screen as shown above.
Begin the Upgrade Process
8. Open the TFTP application and start TFTP. Ensure that all settings are ready to transfer the file, including the location of the upgrade file. Refer to your TFTP user manual for more details.
9. Return to the Web interface.
10. When ready to begin the download, click the Update Firmware button.
A8
Updating the Firmware - Xmodem (Serial) Method
Progress of update
11. During the update, the window displays a progress bar, as shown below left.
NOTE
Do not close the Web browser during this process or the update will abort.
After the firmware update is completed, the card will reinitialize automatically. A reboot mes­sage, as shown below right, remains until the rebooting is finished.
When the rebooting is complete, the Web browser window returns to the default opening view. The upgrade is now complete.
Check the new firmware version if you wish (see A.3.2 - Determine the Liebert IntelliSlot Card Type and Firmware Version).

A.6 UPDATING THE FIRMWARE - XMODEM (SERIAL) METHOD

Follow these steps to update the firmware using the Xmodem (serial) method. This method works through the Web card’s serial port, employing terminal emulation software, such as HyperTerminal.
NOTE
This method includes a time-sensitive operation requiring expeditious location of the upgrade files downloaded in A.3.3 - Download the Firmware Upgrade File to the Computer. Read through this entire section before beginning the upgrade.
A9

Connect a Cable to the Serial Ports

DTE Device
Receive Rx (Pin 2)
Transmit Tx (Pin 3)
DTE Device
Receive Rx (Pin 2)
Transmit Tx (Pin 3)
Firmware Updates Menu
---------------------­1: XMODEM Update 2: TFTP Update
Firmware Update (Step 1/3)
-------------------------­Select Firmware Update Protocol
------------------------------­1: XmodemCrc 2: Xmodem1K x: Exit/Cancel
Please select a key ?> Current Communications Rate is 9600 bps.
Call menu
Configure button
115200 bps
115200 bps
1. Connect one end of a DB-9 null modem or file transfer cable to the Web card’s serial port and the other to the computer’s serial port. The correct cable will have at a minimum, Pins 2 and 3 crossed at the ends, as shown in Figure A1.
Figure A1 Null connection

Open a Terminal Emulation Connection

2. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.1 - Open the Terminal Emulation Interface - Serial Connection).
3. Choose Firmware Updates from the Main Menu.
4. Choose XMODEM Update from the Firmware Updates menu, seen at right, and enter y (yes) to confirm your choice.
5. Choose Xmodem1K from the Select Firmware Update Protocol, as shown at right.

Change the Baud Rate to 115200

6. Choose 115200 bps from the menu, shown below left.
7. From the HyperTerminal menu, click on Call, then choose Disconnect (this will not close the HyperTerminal connection to the card).
8. In the HyperTerminal menu bar, click on File, then choose Properties.
9. Click on the Connect To tab and click the Configure button. This opens Port Settings tab in the COM1 Properties window, as shown below right.
10. Choose 115200 from the Bits Per Second drop-down list and click OK, then click OK to close the Properties window.
11. In the HyperTerminal menu bar, click on Call, then choose Call from the drop-down menu and press the Enter key.
Updating the Firmware - Xmodem (Serial) Method
A10
Updating the Firmware - Xmodem (Serial) Method
Press Enter to start firmware update
Choose 1K Xmodem
Progress window shows elapsed time...
... and remaining time
Browse to locate upgrade file
Would You Like to Continue (Y or N)? Firmware Update (Step 2/3)
-------------------------­Select Firmware Update Protocol
------------------------------­1: XmodemCrc 2: Xmodem1K x: Exit/Cancel
Please select a key ?> Current Communications Rate is 115200 bps. Press a number to Change Communications Rate.
------------------------------­1: 9600 bps 2: 19200 bps 3: 38400 bps 4: 57600 bps 5: 115200 bps Enter: Accept/Start Firmware Update
Please select a key > Press Enter to Start Firmware Update.

Download the First Firmware Update File

12. After changing the communication rate to 115200 bps, press Enter to resume the firmware update.
After you press Enter, HyperTerminal displays Cs as it counts down the time remaining to locate and begin transferring the upgrade files.
NOTE
After you begin the initialization process in Step 12, you must complete Steps 13 through 15 within 60 seconds. Before beginning, check to ensure that you know the location of the firmware files and read through the following steps to understand what needs to be done.
This 60-second limit also applies to downloading the second and third upgrade files.
13. In the HyperTerminal menu, click on Transfer, then Send File.
14. Click the Browse button to locate an upgrade file. Select the files in order—the filename ending in FILE1 for the first download, then FILE2, and finally FILE3—then click Open.
15. In the Send File window, choose 1K Xmodem from the Protocol drop-down list and click Send. A progress window opens, showing the elapsed time and amount of time remaining for the first
file to be downloaded to the Liebert IntelliSlot card. The window closes after the first file is down­loaded.
NOTE
Do not press any keys while the progress window remains open or the download will abort.

Download the Second and Third Firmware Update Files

16. When the progress window closes, enter y (yes) in HyperTerminal to continue the upgrade.
17. Choose Xmodem1K in the Select Firmware Update Protocol menu.
18. The screen shows that the communication rate is
115200. This does not need to be changed.
19. Press Enter to continue.
20. Repeat Steps 12 through 15 within the 60-second limit to browse to the second upgrade file and download it to the Liebert IntelliSlot card.
21. Wait for the Progress window to close after the second file is downloaded.
Then repeat Steps 16 through 20 to download the third upgrade file. This file is the largest and may take 30 minutes or longer to download.
A11
Updating the Firmware - Xmodem (Serial) Method
Call menu
Configure button
9600 bps
Main Menu
---------­1: System Information 2: IP Network Settings 3: Messaging 4: Factory Settings 5: Firmware Updates
q: Quit and abort changes x: Exit and save
Please select a key ?> 5

Complete the Upgrade and Restore Communication Rate

22. Choose 9600 bps from the menu, shown below left.
23. From the HyperTerminal menu, click on Call, then choose Disconnect (this will not close the HyperTerminal connection to the card).
24. In the HyperTerminal menu bar, click on File, then choose Properties.
25. Click on the Connect To tab and click the Configure button. This opens Port Settings tab in the COM1 Properties window, as shown below right.
26. Choose 9600 from the Bits Per Second drop-down list and click OK, then click OK to close the Properties window.
27. In the HyperTerminal menu bar, click on Call, then choose Call from the drop-down menu.
28. Press the Enter key.
29. Choose Exit and Save from the Main Menu to reboot the card. When rebooting is complete, the upgrade is finished.
Check the new firmware version if you wish (see A.3.2 - Determine the Liebert IntelliSlot Card Type and Firmware Version).
A12
Notes
Updating the Firmware - Xmodem (Serial) Method
A13
Updating the Firmware - Xmodem (Serial) Method
A14
Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Liebert.monitoring@emerson.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-52615_REV02_08-08
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power Connectivity DC Power
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Controls
Monitoring
Outside Plant
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...