Emerson ENV20G, ENV10G, 1.5 TO 10 TONS User Manual

Precision Cooling For Business-Critical Continuity
Liebert Envirosource
User Manual - 1.5 to 10 Tons, 60Hz
TABLE OF CONTENTS
2.0 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3.0 S
4.0 I
YSTEM COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
NSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
FIGURES
Figure 1 General piping arrangement—Envirosource standby pump and cooling module with
Process Fluid Chiller 1-1/2 to 5 ton air cooled models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2 General piping arrangement—Envirosource standby pump and cooling module with
Process Fluid Chiller 8-10 ton air cooled models with electronic hot gas bypass . . . . . . . . . . . 6
Figure 3 Physical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 4 Service clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 5 Equipment layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 6 Cabinet dimensions for Envirosource ENV05G and ENV10G. . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 7 Cabinet dimensions for Envirosource ENV20G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 8 Electrical schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
TABLES
Table 1 Model numbers for minimum application flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table 2 Time delay settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 3 Connection sizes (NPT male) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 4 Electrical data, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 5 Technical data—Envirosource module, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
i
ii

1.0 INTRODUCTION

The Envirosource Module is an accessory to the Process Chiller, for use on systems that circulate water and/or glycol solutions that require an isolated loop from the emergency water source. With the heat exchanger providing fluid separation, the Envirosource automatically switches to the emergency water source on a high fluid temperature alarm. Additionally, the module automatically switches to standby pump operation (with interlock to shut down the Process Chiller pump) on a loss of flow alarm.
The Envirosource Module is available in 208/230/460V, single-phase and three-phase, 60 Hz configu­rations. This module is a pre-piped and wired assembly that is encased in an almond colored, powder coated and baked cabinet. It consists of a copper brazed stainless steel heat exchanger, stainless steel pump, copper piping, RCM4 alarm monitor, adjustable time delay relays, high temperature thermo­stat, cooling solenoid valve, check valve and flow switch. It also includes a manual ball valve and dou­ble-check back-flow preventer on the city water line.
The integral RCM4 alarm monitor has a local display of normal operation, standby pump and standby cooling, “on” LED. Terminal strips are included for two optional alarms (customer supplied dry con­tacts) and for common alarm output (dry contacts, NC/NO/COM).

Table 1 Model numbers for minimum application flow

Model # Range (gpm)
ENV05G-_00 0.3 - 1.1
ENV10G-_00 3.7 - 13.3
ENV20G-_00 3.7 - 13.3
Introduction
The Process Chiller is modified with a bypass line to permit water to flow around the chiller’s pump when the standby pump in the Envirosource Module is operating. This bypass line runs from the pump suction line to the pump discharge line and includes a ball valve and check valve (see Figures 1 and 2).
1

2.0 SEQUENCE OF OPERATION

During normal operation, cold fluid flow from the chiller passes across the flow switch, through the heat exchanger, through the pump bypass check valve, past the supply temperature sensor and out to the load (see Figures 1 and 2). The standby cooling solenoid valve is closed (de-energized) and the standby pump is off.
If the flow switch senses loss of flow, a time delay is initiated to prevent nuisance switchovers. After the delay (see Table 2 below), the alarm panel indicates “standby pump on” and the common alarm contacts close, while the standby pump is brought on to resume flow and the chiller pump is locked out. This mode is locked in until the reset button is pressed.
Similarly, if the thermostat senses high fluid temperature, a time delay is initiated to prevent nuisance switchovers. After the delay (see Table 2 below), the alarm panel indicates “standby cooling on” and the common alarm contacts close, while the solenoid valve is energized to resume cooling. This mode is locked in until the reset button is pressed.

Table 2 Time delay settings

Condition Default
Loss of Flow 10 0 90
High Water Temp. 180 0 480
Minimum Maximum
Sequence of Operation
Delay (seconds)
Note that during normal operation, the auto/manual switches (see Figure 8) are set to “auto”. The switch can be set to “manual” to force switchovers to standby pump and/or standby cooling for trouble­shooting or maintenance.
Note that the “remote shutdown” function (see 4.0 - Installation) prevents emergency switchover operation regardless of the status of other controls.
2

3.0 SYSTEM COMPONENTS

RCM4 Monitor is configured to activate an LED and an audible alarm. The common alarm output contacts will close in response to a loss of flow or high supply fluid temperature. The silence/reset but­ton silences the alarm. The button also resets the LEDs and alarm contacts if the unit has returned to normal mode.
Thermostat monitors supply fluid temperature. The thermostat (switchover) setpoint is adjustable from 40°F to 90°F (4°C to 32°C). The setpoint has a differential of 3.0° to 12.0°. The recommended set­ting is 3.0°.
NOTE
Some applications may require different setpoints and differentials. Consult your local Liebert
representative or the factory for assistance.
Flow Switch monitors supply flow. The flow switch setpoint is adjustable. See Table 1 for minimum flow switch setpoint range.
Solenoid Valve is 24VAC, 2-way, pilot or direct operated, with brass body.
Manual Ball Valve is 1/4 turn, brass body for shutoff or trimming of emergency water source flow.
Back-Flow Preventer is of double-check design and is located at the emergency water source piping
connection point.
System Components
3

4.0 INSTALLATION

Prepare the location(s) for the unit (see Figure 4). Allow adequate clearance for convenient mainte­nance. Anchor the unit to the floor or bolt it securely to the wall using appropriate anchors (supplied by others).
WARNING
!
Failure to fasten unit securely to wall studs or structural members with appropriate
anchors (supplied by others) may result in product failure and personal injury.
Connect the unit piping to the chiller, load, emergency water supply and drain (or recirculator). Pip­ing connections are labeled on the unit. Be sure to bleed all air out of the fluid system. Note that the pressure limit of the Envirosource Module is 100 psig.
CAUTION
!
To prevent leaks within the Envirosource Module, the fluid pressure should not exceed
100 psig. For installations using an Envirosource above this rating, a pressure-reducing
valve (supplied by others) is required.
Connect unit to the required AC power source through a remote on/off switch (field supplied) as indi­cated on the unit nameplate. Electrical service shall conform to national and local electrical codes. Refer to unit nameplate for full load amps (FLA), wire size amps (WSA) and overcurrent protection device (OPD) requirements. Refer to Figure 8 when making connections.
Installation
Connect pump interlock to Process Chiller. Connect optional control wiring for remote shutdown, remote indication of loss of flow, remote indication of high temperature and common alarm, as required.
4

5.0 MAINTENANCE

Periodic preventive maintenance should include a monthly manual switchover to ensure that the sys­tem operates properly.
Figure 1 General piping arrangement—Envirosource standby pump and cooling module with
Process Fluid Chiller 1-1/2 to 5 ton air cooled models
Maintenance
5
Figure 2 General piping arrangement—Envirosource standby pump and cooling module with
Process Fluid Chiller 8-10 ton air cooled models with electronic hot gas bypass
Maintenance
6

Figure 3 Physical data

City Water Supply
Supply from Chiller
To D r a in
Maintenance
Supply to Load
Supply from Chiller
Heat Exchanger
Pump
ENV05G-_00 / ENV10G-_00
Supply to Load
To Drain
City Water Supply
Heat
Exchanger
Pump
ENV20G-_00
7
Maintenance
Table 3 Technical data—Envirosource module, 60 Hz
Process Fluid Chiller PS018A PS024A PS036A PS048A PS060A PS096A PS120A
Model Number ENV05G ENV05G ENV10G ENV10G ENV10G ENV20G ENV20G
Circulating Fluid—Water
Flow Rate, gpm (l/s)
Pressure Drop, feet (kPa)
Emergency Fluid—Water
Flow Rate, gpm (l/s)
Pressure Drop, feet (kPa)
To prevent leaks within the Envirosource Module, the water pressure should not exceed 100 psig.
2.4
(.151)
13.6
(40.65)
3.6
(.227)
21
(62.77)
3.3
(.208)
24.9
(74.43)
4.9
(.312)
27.7
(82.80)
5.3
(.334)
11.7
(34.97)
8.0
(.502)
31.4
(93.85)
7.9
(.498)
18.6
(55.60)
11.9
(.751)
51.1
(152.74)
10.2
(.644)
30.7
(91.76)
15.3
(.965)
74.4
(222.38)
16.0
(1.009)
14.2
(42.44)
24.0
(1.51)
65.1
(194.58)
20.0
(1.262)
23.7
(70.84)
30.0
(1.89)
73.7
(220.29)

Table 4 Connection sizes (NPT male)

Model ENV05G ENV10G ENV20G
Supply from Chiller 3/4" 1" 1-1/4"
From Emergency Water Supply 1/2" 3/4" 1"
To Drain or Recirculator 1/2" 3/4" 1"
Supply to Load 3/4" 1" 1-1/4"

Table 5 Electrical data, 60 Hz

ENV05G ENV10G ENV20G
Electrical
Requirements
FLA 7.6 3.5 1.6 8.8 4.6 2.1 -- 10.6 4.8
WSA 9.9 4.4 2.0 11.0 5.8 2.6 -- 13.6 6.0
OPD 15.0 15.0 15.0 15.0 15.0 15.0 -- 15.0 15.0
*Electrical data based on standard pump selection for 40% E.G.
208/230 460 208/230 460 208/230 460
1 Ph 3 Ph 3 Ph 1 Ph 3 Ph 3 Ph 1 Ph 3 Ph 3 Ph
8

Figure 4 Service clearances

Maintenance
Shaded areas indicate recommended clearance for component access and removal.
ENV05G / ENV10G / ENV20G
9

Figure 5 Equipment layout

City Water
Maintenance
Envirosource
(ENV05G or ENV10G)
Load
Outdoor (Glycol) Application
Drain
Process
Chiller
10

Figure 6 Cabinet dimensions for Envirosource ENV05G and ENV10G

Maintenance
11

Figure 7 Cabinet dimensions for Envirosource ENV20G

Maintenance
12

Figure 8 Electrical schematic

Maintenance
13
Maintenance
14
Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-15700_REV1_08-06
Emerson Network Power.
The global leader in enabling Business-Critical Continuity
AC Power Systems Connectivity DC Power Systems
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2006 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Control Integrated Cabinet Solutions
.
Precision Cooling
EmersonNetworkPower.com
ServicesOutside Plant Site Monitoring Surge Protection
Loading...