1.2.1 FCC Part 15 Information ...................................................................................................................................... 3
3.1.1 DIN Rail Mounting................................................................................................................................................. 5
UPPORTED SYSTEM TYPES........................................................................................................................................... 5
ONTROL POWER .......................................................................................................................................................... 9
6 NETWORK SETUP AND COMMISSIONING ....................................................................................................... 13
6.1 S
ET UP NETWORK PORTS ............................................................................................................................................ 13
6.2 A
DDINGAN ENERGY METER....................................................................................................................................... 14
6.3.1 Daisy-chaining Devices to the Energy Meter ...................................................................................................... 15
ET PULSE ................................................................................................................................................................... 18
8.2 S
ET PULSE ENERGY – WH/P ....................................................................................................................................... 18
8.3 M
INIMUM DURATION TIME – MILLISECONDSPER PULSE (MS/P)............................................................................... 18
8.4 M
ULTIFLEX I/O BOARD PULSE LIMITS - STANDALONE VERSION ONLY.................................................................... 19
9 UI MENU ABBREVIATIONS ................................................................................................................................... 20
10 USER INTERFACE FOR DATA CONFIGURATION ...................................................................................... 21
12 USER INTERFACE FOR SETUP ......................................................................................................................... 23
13 ENERGY METER STANDARD MODBUS DEFAULT SETTINGS ................................................................. 25
APPENDIX OF COMPATIBLE CURRENT TRANSDUCERS ................................................................................. 27
Contents • v
Page 6
1Introduction
The Energy Meter (P/N 250-5000) provides a solution for
measuring energy data with a single device. Inputs include
Control Power, CT, and 3-phase voltage. The Energy
Meter supports multiple output options, including solid
state relay contacts, Modbus, and pulse. The LCD screen
on the faceplate allows instant output viewing.
The meter is housed in a plastic enclosure suitable for
installation on T35 DIN rail according to EN50022. The
Energy Meter can be mounted with any orientation over
the entire ambient temperature range, either on a DIN rail
or in a panel. The meter is not sensitive to CT orientation
to reduce installation errors.
For use in a Pollution Degree 2 or better environment
only. A Pollution Degree 2 environment must control
conductive pollution and the possibility of condensation or
high humidity. Consider the enclosure, the correct use of
ventilation, thermal properties of the equipment, and the
relationship with the environment. Installation category:
CAT II or CAT III.
Provide a disconnect device to disconnect the Energy
Meter from the supply source. Place this device in close
proximity to the equipment and within easy reach of the
operator, and mark it as the disconnecting device. The
disconnecting device shall meet the relevant requirements
of IEC 60947-1 and IEC 60947-3 and shall be suitable for
the application. In the US and Canada, disconnecting fuse
holders can be used. Provide over-current protection and
disconnecting device for supply conductors with approved
current limiting devices suitable for protecting the wiring.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the device may
be impaired.
WARNING! HAZARD OF ELECTRIC
SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA
70E in the USA, or applicable local codes.
• This equipment must only be installed and
serviced by qualified electrical personnel.
• Read, understand and follow the instructions
before installing this product.
• Turn off all power supplying equipment before
working on or inside the equipment.
• Any covers that may be displaced during the
installation must be reinstalled before powering
the unit.
• Use a properly rated voltage sensing device to
confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR
VOLTAGE INDICATION.
Failure to follow these instructions will result in death
or serious injury.
Introduction • 1
Page 7
1.1Specifications
Measurement Accuracy
Real Power and
Energy
Reactive Power
and Energy
Current
Voltage
Sample Rate 2520 samples per second
Data Update Rate 1 sec
Type of
Measurement
Input Voltage Characteristics
Measured AC
Voltage
Metering OverRange
Impedance
Frequency Range 45 to 65 Hz
Input Current Characteristics
CT Scaling Primary: Adjustable from 5A to 32,000A
Measurement Input
Range
Impedance 10.6kΩ (1/3 V mode) or 32.1kΩ (1 V mode)
Control Power
AC
DC*3W max.; UL and CE: 125 to 300VDC
Ride Through Time 100 msec at 120VAC
Output
Alarm Contacts
(all models)
Table 1-1 - Energy Meter Specifications
IEC 62053-22 Class 0.5S, ANSI C12.20
0.5%
IEC 62053-23 Class 2, 2%
0.4% (+0.015% per °C deviation from
25°C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from
25°C) from 1% to 5% of range
0.4% (+0.015% per °C deviation from
25°C) from 90V
to 600VAC
L-L
L-L
True RMS up to the 21st harmonic 60 Hz
One to three phase AC system
Minimum 90V
L-N
(156V
) for stated
L-L
accuracy;
UL Maximums: 600V
CE Maximums: 300V
L-L
L-N
(347V
(520V
L-N
L-L
)
)
+20%
2.5 MΩ
L-N
/5 MΩ
L-L
0 to 0.333VAC or 0 to 1.0VAC (+20% overrange)
5VA max.; 90V min.
UL Maximums: 600V
CE Maximums: 300V
L-L
L-N
(347V
(520V
L-N
L-L
)
)
N.C., static output
(30VAC/DC, 100mA max. @ 25°C,
derate 0.56mA per °C above 25°C)
Real Energy Pulse
Contacts (all
N.O., static output
models) AND
Reactive Energy
Pulse Contacts
(30VAC/DC, 100mA max. @ 25°C,
derate 0.56mA per °C above 25°C)
RS-485 Port 2-wire, 1200 to 38400 baud, Modbus RTU
FCC part 15 Class B, EN55011/EN61000
Class B
(residential and light industrial)
EN61000 Class A (heavy industrial)
Safety
US and Canada
(cULus)
UL508 (open type device)/CSA 22.2 No.
14-05
Europe (CE) EN61010-1:2001
Table 1-1 - Energy Meter Specifications
*External DC current limiting is required,
see Section 4.2.1, Fuse Recommendations.
2 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 8
1.2Notice
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
1.2.1FCC Part 15 Information
NOTE: This equipment has been tested by the manufacturer and found to comply with the limits for a
class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a residential
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area may cause harmful interference in which case the user will be required to
correct the interference at his own expense. Modifications to this product without the express authorization of
Emerson nullify this statement.
NoticeIntroduction • 3
Page 9
2Overview
2.1Dimensions2.2Product Diagram
Figure 2-1 - Energy Meter Dimensions
Figure 2-2 - Bottom View (DIN Mount Option)
Figure 2-4 - Energy Meter Interface
Figure 2-5 - Four Output Options
Figure 2-3 - Bottom View (Screw Mount Option)
4 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 10
3Installation
WARNING! Disconnect power prior to
installation.
Any covers that may be displaced during the
installation must be reinstalled before powering the
unit.
Mount the Energy Meter in an appropriate electrical
enclosure near equipment to be monitored.
Exposure to VFD harmonics may cause permanent
damage to this device.
3.1Types of Mounting
The Energy Meter can be mounted in two ways: on
standard 35 mm DIN rail or screw-mounted to the
interior surface of the enclosure.
3.1.1DIN Rail Mounting
2.Use three #8 screws (not supplied) to mount the
Energy Meter to the inside of the enclosure. See
diagram of the underside of the Energy Meter
(below).
Figure 3-2 - Screw Mounting
1.Attach mounting clips to the underside of the
Energy Meter by sliding them into the slots from
the inside. The outside edge of the clip must be
flush with the outside edge of the Energy Meter.
2.Snap the clips onto the DIN rail. See diagram of
the underside of the Energy Meter (below).
Figure 3-1
- DIN Rail Mounting
3.To prevent horizontal shifting across the DIN
rail, use two AV02 end stop clips.
3.1.2Screw Mounting
3.2Supported System
Types
The Energy Meter Series has a number of different
possible system wiring configurations (see Section 4, Wiring). To configure the meter, set the System Type via
the User Interface or Modbus register 130 (if so equipped).
The System Type tells the meter which of its current and
voltage inputs are valid, which are to be ignored, and if
neutral is connected. Setting the correct System Type
prevents unwanted energy accumulation on unused
inputs, selects the formula to calculate the Theoretical
Maximum System Power, and determines which phase
loss algorithm is to be used. The phase loss algorithm is
configured as a percent of the Line-to-Line System
Voltage (except when in System Type 10) and also
calculates the expected Line to Neutral voltages for system
types that have Neutral (12 & 40).
1.Attach the mounting clips to the underside of the
Energy Meter by sliding them into the slots from
the outside. The screw hole must be exposed on
the outside of the housing.
Types of MountingInstallation • 5
Page 11
Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the
Modbus registers.
CTsVoltage ConnectionsSystem TypePhase Loss Measurements
Number
of wires
Single-Phase Wiring
21A2A,NL-N101L+1nAN1
21A2A,BL-L112LAB2
32A,B3A,B,NL-L with N122L+1nABAN,BNAN-BN3
Three-Phase Wiring
33A,B,C 3A,B,CDelta313L
43A,B,C 4A,B,C,N
Qty IDQtyIDType
Grounded
Wye
Modbus
Register
130
403L+1n
User
Interface:
SETUP>S
SYS
VLLVLNBalance
AB, BC,
CA
AB, BC, CAAN, BN,
CN
AB-BC-CA 4
AN-BN-CN
&
AB-BC-CA
Table 3-1 - System Types
Wiring
Diagram
Diagram
number
5, 6
6 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 12
4Wiring
To avoid distortion, use parallel wires for control power
and voltage inputs.
The following symbols are used in the wiring diagrams on
the following pages.
SymbolDescription
Voltage Disconnect Switch
Fuse (installer is responsible for
ensuring compliance with
local requirements. No fuses are
included with the Energy Meter.)
Earth ground
Current Transducer
4.1Wiring Diagrams
Potential Transformer
Protection containing a voltage
disconnect switch with a fuse or
disconnect circuit breaker. The
protection device must be rated for
the available short-circuit current at
the connection point.
Table 4-1 -Diagram Symbols
WARNING! This product is designed only for
use with 1V or 0.33V current transformers
(CTs).
DO NOT USE CURRENT OUTPUT
(For example, 5A) CTs ON THIS PRODUCT.
Failure to follow these instructions can result in
overheating and permanent equipment damage.
Figure 4-1 - 1-Phase Line-to-Neutral 2- Wire System 1 CT
Figure 4-2 - 1-Phase Line-to-Line 2-Wire System 1 CT
Wiring DiagramsWiring • 7
Page 13
Figure 4-3 - 1-Phase Direct Voltage Connection 2 CT
Figure 4-5 - 3-Phase 4-Wire Wye Direct Voltage Input
WARNING! CTs are referenced to the meter’s
neutral (N).
8 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 14
4.2Control Power
Figure 4-7
Figure 4-8 - Direct Connect Control Power (Phase to Neutral)
- Direct Connect Control Power (Phase to Phase)
Figure 4-10 - Control Power Transformer (CPT) Connection
4.2.1Fuse Recommendations
Keep the fuses close to the power source (obey local and
national code requirements).
For selecting fuses and circuit breakers, use the following
criteria:
• Current interrupt capacity should be selected based
on the installation category and fault current
capability.
• Over-current protection should be selected with a
time delay.
• The voltage rating should be sufficient for the input
voltage applied.
• Provide over-current protection and disconnecting
devices appropriate for the wiring.
• The earth connection is required for
electromagnetic compatibility (EMC) and is not a
protective earth ground.
Figure 4-9 - Control Power Transformer (CPT) Connection
Control PowerWiring • 9
Page 15
4.3Wiring Connection to Site Supervisor
Figure 4-11 - Site Supervisor Wiring
10 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 16
4.4Wiring Connection to E2
RS
485 MODBUS
CON
NECTORS
E2 Power Interface
Board (PIB)
+485
-485
0V
ECT MODBUS
CONNECTOR on the
Energ y Meter
BLACK
WHITE
SHIELD
+485-4850V
W
H
I
T
E
B
LA
C
K
S
H
I
E
L
D
+ - S
REVERSE POLARITY
Energy Meter +Data to the E2 RS485 Energy Meter -D ata to the E2 RS485 +
Figure 4-12 - E2 MODBUS connection
Connect the network cable to the three-terminal connector on the COM port that has been configured for the
Energy Meter. The Energy Meter polarity markings are the inverse of E2; connect the Energy Meter +Data wire
to the E2 RS485 - terminal and connect the Energy Meter -Data wire to the E2 RS485 + terminal. The shield
cable should be connected to the right most terminal.
When the E2 is at one end of the daisy chain, terminate the E2 with all three jumpers in the terminated (UP)
position.
Wiring Connection to E2Wiring • 11
Page 17
5Display Screen Diagram
5.1LCD Screen
Figure 5-1 - Energy Meter Screen
5.2Buttons
Figure 5-2 - Energy Meter Buttons
12 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 18
6Network Setup and Commissioning
E2 PIB COM PORT ASSOCIATIONS
COM1
COM4
COM6
COM2
Serial Device
RS485 COM Port
(2 Connectors)
RS485 COM Card
(2 Connectors)
Serial Device
RS232 Port
POWER INTERFACE BOARD
(PIB)
E2 Modem/Expansion
COM Card Mounted
Above PIB
Plug-In
Modem
Card
COM3
E2 Enclosure (Right Side)
RS485
RS232
6.1Set Up Network Ports
Before communicating to an Energy Meter, the port on the
E2 that has the cable connected to the Energy Meter must
be configured to use the Energy Meter.
1.Log in to the E2 with Level 4 access.
Figure 6-1
- Location of E2 COM Ports
Connecting an Energy Meter to an E2 requires the E2 to
be version 3.0 or above. Contact Emerson for upgrade
information if the controller is a version before 3.0.
An E2 has up to three COM ports that can be assigned for
MODBUS communication: COM2, an RS485 port on the
E2 power interface board, and COM4 and COM6, which
are optional ports requiring expansion cards.
COM ports can only be used for one function; in other
words, if COM2 is set up as the I/O network, you
cannot connect MODBUS devices to COM2. Ensure your
E2 is equipped with an RS485 COM Card (P/N 637-4890)
and configured in E2 General Services (731, Serial tab) to
enable COM4 or an E2 Expansion COM Card
(P/N 637-4871) to enable COM6.
Connect the MODBUS network cable to the
three-terminal connector on the COM port you wish to
assign as MODBUS. Reverse polarity of +/- on RS485
cable from E2 to device.
2.Press
( followed by 731 - General Controller
Info.
3.Press
c+3 to open the Serial tab of the General
Controller Info setup screens:
Figure 6-2 - Serial Communications Manager Screen
4.This screen will have a “Connection” field for all
COM ports on the E2. Highlight the COM port
connection field that will be used for MODBUS,
and press $ - LOOK UP. From the list of
network types, select MODBUS (1-3).
5.Four fields will become visible underneath the
COM port connection field, which pertain to the
way the device communicates:
6.Baud - Default setting is 19.2k. The baud rate
setting should be set to match the baud rate dip
switch settings of all Energy Meter devices. (All
devices connected to the same COM port should
be set to the same baud rate.)
Set Up Network PortsNetwork Setup and Commissioning • 13
Page 19
• Data Size - Leave this field at the default value (8).
• Parity - Leave this field at the default value (None).
The parity settings should be set to match the parity
dip switch settings of all Energy Meter devices.
Refer to Table 2.
• Stop Bits - Leave this field at the default value (1).
7.Press ) to save changes and exit.
6.2Adding an Energy
Meter
To enable communications between E2 and the Energy
Meter units, the devices must be added and addressed in
E2.
1.Log in to the E2 with Level 4 access.
2.Press
(772 - Connected I/O Boards and
Controllers.
6.
Figure 6-4 - Network Summary Screen
7.By default, each Energy Meter’s board number in
the network list is indicated by a - (dash). To set
the address and begin communication, press
Commission. (If you have more than one
MODBUS network, specify which network you
want the device to belong to.) A screen will open
that will allow you set the address:
$ to
Figure 6-3
14 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
- Connected I/O Screen
3.In the Connected I/O screen, under the ECT tab,
Enter the number of devices in the Energy Meter
number field.
4.Press
5.Locate the Energy Meter units you added to the
) to return to the Network Setup menu, then
select
1 - Network Summary.
network list (press
list). The default name for an Energy Meter
increments up starting with Energy001. The two
and three-letter designator does not apply here.
kandjto scroll through the
Figure 6-5
- Set the Address of the Energy Meter
8.In the list of MODBUS devices, choose the
address number corresponding to the Energy
Meter’s dip switch/jumper setting, and press
select it. If a network ID has already been
selected, its name will be shown next to the
network ID in this list. If the network ID you are
trying to assign has already been used, you must
set the network ID dip switch/jumper on this
device to a different number that is not being
used.
eto
Page 20
Figure 6-6
E2
MODBUS
device
#1#3
REVERSE POLARITY
Energy Meter +Data to the E2 RS485 Energy Meter -Data to the E2 RS485 +
MODBUS
device
MODBUS
device
- List of MODBUS Devices
9.Repeat Steps 5 and 6 until each Energy Meter
device has been commissioned.
Figure 6-7 - Network Summary Screen
10. When finished, press ) to return to the Network
Setup menu, then press
1 - Network Summary
(Figure 6-4). Locate the Energy Meters you set
up, and look at each device’s status in the Status
field. You will see one of the following
messages:
11. Online - The Energy Meter is communicating
normally.
12. Offline - The Energy Meter is not
communicating, has not been commissioned, is
not functional, or is not powered up. Verify the
Energy Meter is powered up, wired correctly, and
has the proper network
address, baud rate, and parity.
13. Unknown - The Energy Meter is not
communicating or has not been commissioned.
Verify the Energy Meter is powered up, wired
correctly, and has the proper network address,
baud rate, and parity.
14. No Port - No port is set up in the E2 Serial
Configuration Manager to be a MODBUS port.
15. Wrong FW Rev - This message is likely caused
by the Energy Meter having a firmware version
older than the minimum revision required by E2
for
communication. Replace the Energy Meter with a
new controller that has the latest version of
firmware.
6.3RS-485
Communications
6.3.1Daisy-chaining Devices to
the Energy Meter
The RS-485 slave port allows the Energy Meter to be
connected in a daisy chain with up to 63 two-wire
devices. In this manual, communications link refers to
a chain of devices that are connected by a
communications cable.
Figure 6-8
NOTES:
- Energy Meter Daisy Chain
• The Energy Meter polarity markings are the inverse
of E2; connect the Energy Meter +Data wire to the
E2 RS485 - terminal and connect the Energy Meter
-Data wire to the E2 RS485 + terminal. The shield
cable should be connected to the right most
terminal.
• The terminal’s voltage and current ratings are
compliant with the requirements of the EIA RS-485
communications standard.
RS-485 CommunicationsNetwork Setup and Commissioning • 15
Page 21
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 kOhm pull up to +5V, and RS-485- has a 47 kOhm pull down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use a 150 ohm termination resistor
at the end of the bus between the Energy Meter’s + and
termination block P/N 535-2711).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.
• When tightening terminals, ensure that the correct torque is applied: 0.37-0.44 ft·lb (0.5-0.6 N·m).
- terminals (not included, or use Emerson MODBUS
Figure 6-9
- Energy Meter Wiring
16 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 22
7Quick Setup Instructions
These instructions assume the meter is set to factory
defaults. If it has been previously configured, all
optional values should be checked.
1.Press the + or - button repeatedly until
SETUP screen appears.
2. to the PASWD screen.
3. through the digits. Use the + or - buttons
to select the password (the default is 00000). Exit
the screen to the right.
4.Use the + or - buttons to select the parameter
to configure ( - works best).
5.If the unit has an RS-485 interface, the first Setup
screen is S COM (set communications).
a. to the ADDR screen and through the
address digits. Use the + or - buttons to select
the Modbus address.
b. to the BAUD screen. Use the + or -
buttons to select the baud rate.
c. to the PAR screen. Use the + or -
buttons to select the parity.
d. back to the S COM screen.
6.- to the S CT (Set Current Transducer) screen.
If this unit does not have an RS-485 port, this will
be the first screen.
a. to the CT V screen. Use the + or -
buttons to select the voltage mode Current
Transducer output voltage.
9.- to the S V (Set System Voltage) screen.
a. to the VLL (or VLN if system is 1L-1n)
screen and through the digits. Use the + or buttons to select the Line to Line System Voltage.
b. back to the S V screen.
10. Use the to exit the setup screen and then
SETUP.
11. Check that the wrench is not displayed on the
LCD.
a. If the wrench is displayed, use the + or -
buttons to find the ALERT screen.
b. through the screens to see which alert is on.
For full setup instructions, see the configuration
instructions in Section 10, User Interface for Data
Configuration, Section 11, Alert/Reset Information, and
Section 12, User Interface for Setup.
b. to the CT SZ screen and through the digits.
Use the + or – buttons to select the CT size in
amps.
c. back to the S CT screen.
7.- to the S SYS (Set System) screen.
a. to the SYSTM screen. Use the + or -
buttons to select the System Type (see wiring
diagrams).
b. back to the S SYS screen.
8.(Optional) - to the S PT (Set Potential
Transformer) screen. If PTs are not used, then
skip this step.
a. to the RATIO screen and through the
digits. Use the + or – buttons to select the
Potential Transformer step down ratio.
The Energy Meter has one normally open (NO) KZ Form
A output and one normally closed (NC) KY solid-state
output. One is dedicated to energy (Wh), and the other to
Alarm. The Energy Meter also provides an additional NO
reactive energy (VARh) contact. See the Setup section for
configuration information.
Figure 8-2 - Setting Pulse Energy
8.2Set Pulse Energy –
Wh/P
In Watt Hour (and VAR Hours, if present) per pulse.
When moving down to a smaller energy, the meter will not
allow the selection if it cannot find a pulse duration that
Figure 8-1
The solid state pulse outputs are rated for 24VAC/DC
max.
Maximum load current is 100mA at 25°C. Derate 0.56mA
per °C above 25°C.
* The over-current protective device must be rated for the
short circuit current at the connection point.
** All pulse outputs and communication circuits are only
intended to be connected to nonhazardous voltage circuits
(SELV or Class 2). Do not connect to hazardous voltages.
- Solid-State Pulse Output
8.1Set Pulse
The System Type, CT size, PT Ratio and System Voltage
must all be configured before setting the Pulse Energy. If
any of these parameters are changed, the meter will hunt
for a new Pulse Duration, but will not change the Pulse
Energy. If it cannot find a solution, the meter will display
the wrench icon, show “ConF” in the ALARM -> PULSE
screen, and enable Energy pulse output configuration error
bit in the Modbus Diagnostic Alert Bitmap (if equipped).
will allow the pulse output to keep up with Theoretical
Maximum System Power. When moving up to a larger
energy, the meter will jump to the first value where it can
find a valid solution.
8.3Minimum Duration
Time – Milliseconds
per Pulse (mS/P)
This read-only value is set by the meter to the slowest
duration (in mS per closure) that will keep up with the
Theoretical Maximum System Power. The open time is
greater than or equal to the closure time. The maximum
Pulses Per Second (PPS) is shown in yellow.
18 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 24
8.4MultiFlex I/O Board Pulse Limits - Standalone Version
Only
The MultiFlex board can read pulses at a maximum of 5HZ or 5PPS. The Energy Meter is capable of pulsing faster than
the 5PPS maximum that the MultiFlex board can read.
Pulses should be greater than 80mS in length at a maximum rate of 5HZ: Do not exceed 5PPS.
For Example:
• Values of 100, 250, or 500 will be read by the MultiFlex board.
• Values of 50, 25, or 10 will not be read by the MultiFlex board.
_PHASE _PHASE Summary Data for 1, 2, or 3 active phases
ALERT ALERT Diagnostic Alert Status
INFO INFO Unit Information
MODEL MODEL Model Number
OS OS Operating System
RS RS Reset System
SN SN Serial Number
RESET RESET Reset Data
PASWD PASWD Enter Reset or Setup Password
ENERG ENERG Reset Energy Accumulators
DEMND DEMND Reset Demand Maximums
Table 9-1 - UI Abbreviations
20 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 26
10User Interface for Data Configuration
MultiFlex I/O Board Pulse Limits - Standalone Version OnlyUser Interface for Data Configuration • 21
Page 27
11Alert/Reset Information
22 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 28
12User Interface for Setup
MultiFlex I/O Board Pulse Limits - Standalone Version OnlyUser Interface for Setup • 23
Page 29
24 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 30
13Energy Meter Standard MODBUS
Default Settings
SettingValue
Setup Password 00000–
Reset Password 00000–
System Type 40 (3 + N) Wye 130
CT Primary Ratio (if CTs are not included) 100A 131
CT Secondary Ratio 1V 132
PT Ratio 1:1 (none) 133
System Voltage 600 V LL 134
Max. Theoretical Power (Analog Output: full
scale (20mA or 5V))
Display Mode 1 (IEEE)137
Phase Loss 10% of System Voltage (60V), 25% Phase to Phase Imbalance 142, 143
Pulse Energy 1kWh/pulse 144
Demand: number of sub-intervals per interval 1 (block mode) 149
Demand: sub-interval length 900 sec (15 min) 150
Modbus Address 001–
Modbus Baud Rate 19200 baud –
Modbus Parity None–
Log Read Page 0158
Logging Configuration Register 0159
Log Register Pointer 1 1 (Real Energy MSR) 169
Log Register Pointer 2 2 (Real Energy LSR) 170
Log Register Pointer 3 29 (Reactive Energy MSR) 171
Log Register Pointer 4 30 (Reactive Energy LSR) 172
Log Register Pointer 5 37 (Real Demand) 173
Log Register Pointer 6 38 (Reactive Demand) 174
Log Register Pointer 7 39 (Apparent Demand) 175
Log Register Pointer 8 155 (Month/Day) 176
Log Register Pointer 9 156 (Year/Hour) 177
Log Register Pointer 10 157 (Minutes/Seconds) 178
104 kW 135
Modbus
Register
Table 13-1 -MODBUS Default Settings
MultiFlex I/O Board Pulse Limits - Standalone Version OnlyEnergy Meter Standard MODBUS Default Settings • 25
Page 31
14Troubleshooting
ProblemCauseSolution
The maintenance wrench icon
appears in the Energy Meter
display.
The display is blank after
applying control power to the
meter.
The data displayed is
inaccurate.
Cannot communicate with
Energy Meter from a remote
personal computer.
There is a problem with the inputs
to the Energy Meter.
The meter is not receiving
adequate power.
Incorrect setup values
Incorrect voltage inputs
Energy Meter is wired improperly.
Energy Meter address is incorrect.
Energy Meter baud rate is
incorrect.
Communications lines are
improperly connected.
See the Alert sub-menu or the Diagnostic Alert Modbus Register
146
Verify that the meter control power is receiving the required
voltage. Verify that the heart icon is blinking. Check the fuse.
Verify the values entered for Energy Meter setup parameters (CT
and PT ratings, system type, etc.). See the
Quick Setup Instructions section.
Check Energy Meter voltage input terminals to verify adequate
voltage.
Check all CTs and PTs to verify correct connection to the same
service, PT polarity, and adequate powering. See the Wiring
section for more information.
Verify that the meter is correctly addressed. See the
User Interface for Setup section.
Verify that the baud rate of the meter matches that of all other
devices on its communications link. See the
Quick Setup Instructions section.
Verify the Energy Meter communications connections
(see Network Setup and Commissioning).
Verify the terminating resistors are properly installed on both ends
of a chain of units. Units in the middle of a chain should not have
a terminator. Verify the shield ground is connected between all
units.
Table 14-1 - Troubleshooting
26 • Energy Meter Installation and Operation Manual 026-1726 Rev 2
Page 32
Appendix of Compatible Current Transducers
Split Core Current Transducers
Part NumberInside DiameterAmperage
251-70100.75"100 AMP
251-70201.25"200 AMP
251-7021 0.75"200 AMP
251-70301.25"300 AMP
251-70402.00"400 AMP
251-70802.00"800 AMP
251-71202.00"1200 AMP
251-10000.75"5 AMP
251-10010.75"15 AMP
251-10020.75"30 AMP
251-10030.75"50 AMP
251-10041.25"70 AMP
251-10051.25"100 AMP
251-10061.25"150 AMP
251-10071.25"250 AMP
251-10081.25"300 AMP
251-10091.25"400 AMP
Solid Core Current Transducers
Part NumberInside DiameterAmperage
251-10200.30"5 AMP
251-10210.50"15 AMP
251-10220.50" 30 AMP
251-10230.75"50 AMP
251-10240.75"70 AMP
251-10251.00"50 AMP
251-10261.00"70 AMP
251-10271.00"100 AMP
251-10281.00"150 AMP
251-10291.00"200 AMP
251-10301.25"70 AMP
251-10311.25"100 AMP
251-10321.25"200 AMP
251-10331.25"250 AMP
251-10341.25"300 AMP
Table 14-2 - Compatible Transducers
MultiFlex I/O Board Pulse Limits - Standalone Version OnlyAppendix of Compatible Current Transducers • 27
Page 33
Page 34
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicab ility. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or
specifications of such products at a ny time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any prod uct. Responsibility for proper selection, use
and maintenance of any product remains solely with the purchaser and end-user.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.