Surge Protection
For Business-Critical Continuity
TCS-T1 Series
T1 Line Protection Against Damaging Transients
Protection of your vital T1 lines should be part of the overall power protection plan for your facility.
The T1 Series provides you state-of-the-art protection in a small package.
T1 lines need protection from direct and indirect lightning, as well as power disturbances from
nearby AC lines. The TCS-T1 Series prevents T1 line disturbances by providing a level of protection
typically not provided by the telephone company.
The TCS-T1 Series devices combine highly reliable, nondegrading Silicon Avalanche Diode (SAD)
technology, along with high energy gas tube protection. This technology combination leverages the
best aspects of each protection method in a single, reliable design to ensure optimal performance.
The TCS-T1 Series features two models with different clamping voltages. Both the TCS-T1S and the TCS-T1DS
support in-line connections via hardwire lugs or standard RJ-45 ports.
Features
■
Uses bipolar Silicon Avalanche Diode to provide
nondegrading protection
■
Provides unparalleled performance in a
compact, modular design
■
Offers RJ or hardwire connection capabilities to
provide installation flexibility
■
Comes complete with ring terminals
and a male/male RJ-45 cable to make
installation easy
TM
General Technical Specifications
Enclosure Dimensions†
Inches 3H x 2W x 1.5D
Centimeters 7.6H x 5W x 3.8D
Weight 0.313 lb; 140 k
Primary Technology Silicon Avalanche Diode
Interface Hardwire or RJ-45
3' (0.9m) Male to Male Supplied
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
Emerson Network Power Contact information
Headquarters
Surge Protection
328 Water Street 1805 N.E. 19th Avenue 10020 E. Knox Avenue, Suite 50
Binghamton, NY 13901 Ocala, FL 34470 Spokane Valley, WA 99206
T: (607) 724-2484 T: (352) 732-3029 T: (509) 777-2300
T: (800) 288-6169 T: (800) 648-4076 T: (800) 953-3701
F: (607) 722-8713 F: (352) 867-1237 F: (509) 927-0435
E: surgeprotection@
emersonnetworkpower.com
SL-60102 3/07 Rev. 0 Printed in USA
TM
.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Performance Technical Specifications
Operating Frequency Up to 55 MHz Up to 55 MHz
Signal Line Voltage Up to 170 Vpk Up to 8 Vpk
Clamping Voltage 211 Vpk 13 Vpk
Response Time 5 ns or less 5 ns or less
Peak Pulse Current* 40,000 Amp 40,000 Amp
Leak Capacitance 55 Picofarad 55 Picofarad
Protection Modes:
Hardwire: L1-Gnd – L3-Gnd L1-Gnd – L3-Gnd
RJ-48C Standard (RJ-45) Pin 1-Gnd – Pin 4-Gnd Pin 1-Gnd – Pin 4-Gnd
†
Does not include mounting tabs.
*Based on component specifications for all T1 lines.
Outside Plant
Power Switching & Control
Precision Cooling
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power
logo are trademarks and service marks of Emerson Electric Co. ©2007 Emerson Electric Co.
Pin 2-Gnd – Pin 5-Gnd Pin 2-Gnd – Pin 5-Gnd
Pin 1-Pin 2 – Pin 4-Pin 5 Pin 1-Pin2 – Pin 4-Pin 5
TCS -T1S TCS -T1DS
L2-Gnd –L4-Gnd L2-Gnd –L4-Gnd
L1-L2 – L3-L4 L1-L2 – L3-L4