Edco PC2-TEL
Two Line Telephone Protection (Modular)
The Edco PC2-TEL is a solid state, two-line telephone interface protector module.
This unit is specically designed to protect both phone lines required by commercial
re/security panels.
General Technical Specifications
Operating Voltage 250 VDC
Clamping Voltage 270 VDC
Operating Current 0.15 A
Peak Surge Current 160 A (10 x 1000 T & R to Ground)
Frequency Range 0 to 20 MHz
Insertion Loss < 0.1 dB at 20 MHz
SPD Technology Silicon Breakover Device w/Series PTC
Connection Type Terminal block w/ compression lugs
Terminals accept up to 10 AWG
Operating Temperature -40°C to +85°C
Dimensions (in / mm) 2.0˝ H x 1.0˝ W x 2.5˝ L
[50.8 x 25.4 x 63.5 mm]
(PC2TEL + PCB1B-WKEY Base)
Weight (oz / kg) 1 oz [0.03 kg]
Certications UL 497A, CUL
Warranty 5 years
EDCO PCB1B-WKEY BASE SOLD SEPARATELY
Features
■ Tip to ring protection
■ Tip and ring to ground protection
■ Over-current protection
■ Resettable solid state fuses — PTCs
■ UL Listed 497A
■ Requires PCB1B-WKEY base
Caution
Do not place this product in service on any signal line capable of continuously supplying
more than 150 mA.
Attention
Ne pas placer ce produit dans le service sur une ligne de signal capable de fournir en
permanence plus de 150 mA.
■ PC642PTU (Pass Thru Unit)
available for troubleshooting
■ 5 year warranty
Ordering Information
2 Line Telephone PC2-TEL
Installation Instructions
Terminal Assignments
PCB1B-WKEY
Even TerminalsOdd Terminals
9
Unprotected Pair 2
Field Side
Unprotected Pair 1
{
7
5
{
3
1
1.0”
• Connect ground terminals, positions 1 or 10 (internally
tied together) to Building Approved Ground. (See Edco
Tech Bulletin #2015) NOT intended for shield termination.
Install ground in accordance with all applicable codes.
• Edco PCB1B-WKEY accommodates 26 to 10 AWG wire.
10
8
Protected Pair 2
}
6
4
Protected Pair 1
}
2
Keying Pin
Electronics Side
2.125"
[53.98]
2.4"
DANGER!
V
Only qualied personnel should install or
service this system. Electrical safety precautions must be followed when installing
or servicing this equipment. To prevent risk
of electrical shock, turn off and lock out all
power sources to the unit before making
electrical connections or servicing.
Seulement le personnel qualié doit installer
ou maintenir ce systéme. Des précautions
de sécurité en électricité doivent être suivis
lors de l’installation ou de la maintenance
de cet equipement. Pour eviter tout risque
de choc électrique, débranchez et verouiller
toutes les sources d’alimentation de cet
equipement avant de.
• Disconnect telephone line at the network interface before
installing this secondary device.
• This product is intended for indoor use only.
Emerson Network Power Contact information
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
T: (607) 721-8840
T: (800) 288-6169
F: (607) 722-8713
E: SurgeTech@Emerson.com
IO-50117 12/14 Rev. 4 Printed in USA
While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages
resulting from use of this information or for any errors or omissions. Specications are subject to change without notice.
Emerson Network Power, the Emerson Network Power logo and Edco are trademarks
www.EmersonNetworkPower.com/Surge
and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.