Emerson EC3-X32 Operating Instruction

Operating instruction
• ECD-002 can be mounted in panels with 71x29
Turn Allen key until mounting lug barely touches panel. Then move other mounting lug to the same
will break easily.
Commander
Operating condition
Digital input (I)
Compressor Compressor starts
Closed / 24 V (Start)
Compressor stops
Open / 0 V (Stop)
Thermostat Demand (compressor must be ON)
Closed / 24 V (Start)
No demand
Open / 0 V (Stop)
!
EC3-X32 Superheat Controller with TCP/IP
EMERSON Electrical Control Valves EX4...EX8 and FX5…FX9.
Safety ins tructions:
Read operat ing i nstruct ions t horou ghly. Failu re to c omp ly can r esult in device
failure, system damage or personal injury.
According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
Do not exceed the specified maximum ratings for pressure, temperature,
voltage and current.
Before installation or service disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Entire elec t rical connections have to comply with local regulations. Note: The EC3 -X32 series contains a VRLA battery = valve regulated rec ha rg eab le
lead-acid battery. The batter y mus t NOT be dis posed o f with o ther comme rcial waste .
Instead, it is the us er ’s r e sponsi bil ity to pass it to a des ig nate d col l ectio n po int f or the safe recycling of batteries (harmonized directive 2012/19/EU). For further information contac t your local environmenta l recycling center.
Mounting positio n:
The EC3-X32 is designed to be mounted onto a standard DIN rail. Mounting position: on vertical walls, with stepper motor connector on top side only.
Mounting of ECD-002:
• ECD-002 can be installed at any time also during operation.
communication capability
Wiring:
mm cutout.
• Push controller in to panel cut-out.(1)
• Make sure that mounting lugs are flush with
outside of controller housing
• Insert Allen key into front panel holes and turn
clockwise. Mounti ng lugs will turn and graduall y move towards panel (2)
position (3)
• Tighten both sides very carefully until keypad is
secured. Do not over ti ghten as mounting lugs
Electrical Installation:
• Refer to the electrical wiring diagram for electrical connections.
• Do not apply voltage to the controller before completi on of wiring.
• Ground the metal housing with a 6.3 mm spade connector.
• Keep controller and sensor wiring well separated from mains wiring. Minimum
recommended distance 30 mm.
• Use a class II category transformer for 24VAC power supply. Do not ground the
24VAC lin es. We recommend using individual transformers for EC3 con troller(s)
rd
and for 3
party contr ollers to avoi d pos sible in terferenc e or groun ding p roblems in the pow er suppl y. Connecting any EC3 inputs to mains voltage will permanently damage the EC3.
• The use of the relay is essential to protect the system in case of power failure if the
communications interface or the ECD-002 are not ut ilized.
• If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power failure.
• In order to provide system protection in the event of power loss, it is recommended
to change the battery annually.
Digital input status is dependent to operation of compressor/th ermostat
A: White wire B: Black wire C: Blue wire D: Brown wi r e E: M12 Plug cable assembly EXV-Mxx for connection to EX4…EX8 and
FX5…FX9.
G: Remote control panel, system controller. H: Alarm relay, dry contact. Relay coil is not energized at alarm or power off. I: Digital input (0V/open = Stop; 24V/closed = Start) J: Transformer Class II, 24VAC secondary / 25VA K: Third party controller (can use the analog output signal from EC3) O: Pump down relay, dry contact. Relay is energized during normal operation.
Preparation for Start -up:
• Vacuum the entire refrigeration system.
Note: EMERSON Electrical Control Valves EX4…EX8 and FX5…FX9 are
delivered at half open position. Do not charge system b efore closure of v alve.
• Apply supply voltage 24V to EC3 while the digital input is 0V (open). The valve
will be driven to close position.
• After closure of valve, start to charge the system with refrigerant.
• Start the system and check the superheat and operating conditions.
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Operating instruction
Factory
setting
Field
setting
H5
Password
1
199
12 u0
System refrigerant
0
15 1
0 = R22 1 = R134a 2 = R50 7 3 = R40 4A 4 = R40 7C
12 = R449A 13 = R450A 14 = R513A 15 = R1234ze
uP
Installed pressure sensor type
0 3 0
0 = PT5-07x (for R22 / R134a / R507 / R404A / R407A / R407C /
3 = PT5-50x (for R744)
ut
Installed valve type
1
12 5
1 = EX4 2 = EX5 3 = EX6 4 = EX7 9 = FX7 10 = FX7.5 11 = FX8 12=FX9
uu
Start valve opening ( %)
0
100
50 u9
Start opening duration (second)
0
120 5
uL
Low superheat alarm function
0 2 1
0 = disable (for flooded eva porator)
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K
u5
Superhea t set-point (K)
If uL disabled
0.5
30
6
u2
MOP function
0 1 1
0 = disable 1 = enable
u3
MOP set-point (°C) saturation temperature
* * **
**) Factory setting is according to selected refrigerant (u0):
refrigerant
┌┘5
Units conversion
0 1 0
0 = °C, K, bar 1 = °F, R, psig (Psig values are divided by 10. Example: Display 12.5 is 125 psig)
1
Value to show
0 4 0
0 = Measured superheat (K) 1 = Measured evaporating pressure, (bar);
4 = Calculat ed evaporating temperature (°C) from the pressure
u4
Superheat control mode
0 2 0
0 = Standard, 1 = Slow, 2 = intermediate control
uH
High superheat alarm function 0 = disable, 1 = enable auto reset
1
uA
High superheat alarm setpoint
16
40
30
ud
High superheat alarm delay, min.
1
15 3
P2
Freeze protection cut -out, °C
-40
40 0
P3
Freeze protection cut -in , °C
-37
43 3
P4
Freeze protection alarm function
2 = enable manual r eset)
0 2 0
P5
Freeze protection alarm delay, sec.
5
199
30
P6
Pump-down function (0 = disable, 1 = enable auto-reset)
0 1 0
P7
Pump-down cut-out, barg
-0,5
18
0.5 P8
Pump-down time del ay, sec.
0
199
30
P9
Low pressure alarm function
2 = enable manual reset)
0 2 0
PA
Low pressure alarm cut-out, barg
-0,8
17,7 0
Pb
Low pressure alarm delay, sec.
5
199 5
Pd
Low pressure alarm cut-in, barg
-0,5
18
0.3 L2
Output logic
0 3 1
0: Alarm = normal, pump down. = normal
3: Alarm = inverse, pump down. = inverse
Blinking: valve is closing ON: valve is fully close
Blinking: valve is opening ON: valve is fully open
ON: demand
ON: alarm OFF: no alarm
Parameters setting/saving
Selecting/confirming
Next parameter/
Next parameter/ value (lower)
Prg&Sel (5 sec)
blinking alarm codes
EC3-X32 Superheat Controller with TCP/IP
ECD-002 displ ay/keypad unit: (LE Ds and button functions )
OFF: no demand Blinking: pump
down
Manual reset for
Procedure for parameter modifi cation using ECD-002:
Note: Some of the functions/parameters (manual control and TCP/IP
configuration) cannot be modified when using ECD-002 comparing to a set-up by PC via TCP/IP.
Warning:
All alarms are disabled during manual control. We do not recommend unattended operation of system during manual control.
• The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is “12”. To select the parameter configuration:
• Press the PRG button for more than 5 seconds, a flashing “0” is displayed
• Press or until “12” is displayed (password)
• Press SEL to confirm password
• Press or to show the code of the parameter that must be chan g ed;
• Press SEL to display the selected parameter value;
• Press or to increase or decrease the value;
• Press SEL to temporarily confirm the new value and display its code;
• Repeat the procedure from the beginning "press or to show..."
To exit and save the new settings: Press PRG to confirm the new values and exit
the parameters modification procedure.
To exit without modifying any parameters: Do not press any button for at least
60 seconds (TIME OUT).
Special Function s:
The Special F unctions can be act iv ated by:
• Press and together for more than 5 seconds, a flashing “0” is displayed.
• Press or until the password is displayed (default = “12”).
If password was changed, select the new password.
• Press SEL to confirm password
A “0” is displayed and the Special Function mode is activated.
• Press or to select the function. The number of special functions is dynamic
and controller dependent. See list below. 0: Reset controller to factory settings (this action is possible only when digital
input is 0V i.e . open). 1: Displays the current TCP/IP address. 2: Assign temporary 192.168.1.101 as TCP/IP address if EC3-X32 has different
Address.
• Press SEL to activate the function without leaving the special function mode.
• Press PRG to activate the functio n and leave the special function mode.
communication capability
value (higher)
Main parameters: (must be checked and modified if necessary)
Code Parameter description and choices Min Max
5 = R410A 6 = R124 7 = R744 (subcritical application) 8 = R407A 9 = R 4 07F 10 = R32* 11 = R448A
R407F / R124 / R448A /R449A / R450A / R513A / R1234ze) 1 = PT5-18x (for R410A/ R32) 2 = PT5-30x (for R410A / R744 / R32)
5 = EX8 6 = FX5 7 = FX6 8 = FX6.5
1 = enable auto reset 2 = enable manual reset
If uL enabled (auto or man ual)
+13°C - R22 +15°C - R134a +7°C - R507 +7°C - R404A +15°C - R407C +15°C - R410A +50°C - R124 -5°C - R744 +10°C - R407A +10°C - R407F +10°C - R32 +12°C - R448A +12°C - R449A +19°C - R450A +13°C - R513A +24°C - R1234ze
3
*) Min. and Max . setting values are dependent to select ed type of
┌┘
2 = Valve opening (%) 3 = Measured coil-out temperature (°C)
0 = disable, 1 = enable auto-reset,
(0 = disable, 1 = enable auto-reset,
30
6
1: Alarm = inverse, pump down. = normal 2: Alarm = normal, pump down. = inverse
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Operating instruction
Factory
setting
Field
setting
b1
Battery error management, when battery is defective, see below
0 3 2
value
Alarm
display
Alarm relay
Valve
Reset possibility after
recovery/replacement
0 - - Regulating
-
1 Ab - Regulating
-
2 Ab
Signaling
Fully close
Auto
3 Ab
(blinking)
Signaling
Fully close
Manual
When setting b1 to option 0 or 1, the user must ensure appropriate safety precautions are in p la ce to protect the system against damage c au sed by a power failure.
uF
Control range valve %
5
100
100
Digital input status
Alarm condition
24V (ON)
NO
Activate
0V (OFF)
NO
Deactivate when pressure drops below P7 and after elapsed time P8
0V or 24V
YES
Deactivate
!
Sec.
uu
u9
%
EC3-X3 BA.cdr
EC3-X32 Superheat Controller with TCP/IP
Code Parameter description and choices Min Max
*) Notes for R32: R32 is classified as low flamm able refrigera nt in Europe. EC3-
X32 is designed under consideration of European safety standards and directives for none flammable refrigeran ts. Th e use of EC3-X32 with R32 is for systems/regions which it does not require consideration of additional safety standards as for flammable refrigerant.
After selecting the parameters the EC3-X32 is f ul ly func tional witho ut con n ec ted P C or keypad/display unit ECD-002.
Control (valve) start-up behavio r: (Parameter uu and u9 )
communication capability
DHCP server from network/Router. Refer to the TCP/IP Controller-Readme file if a specific port is required.
• It is possible to identify the dynamic TCP/IP address assigned by DHCP of the
Router or network, refer t o the TCP/IP Controller-Readme file.
• After a few moments, the default monitoring page should be displayed. If the
browser d oes no t open t he defa ult pa ge or displa y activ e data , the us er sho uld c heck the Internet browser “Option” configuration. Refer to the TCP/IP Controller- Readme file.
EX4/5/6 ≤ 1.5 seconds EX7 ≤ 3.2 second s EX8 ≤ 7.2 seconds FX5-8 ≤ 7.3 seconds FX9 ≤ 9.7 seconds
Pump down functio n: (if P6=1 and L2=1)
Pump down relay
Possibilities of connecting EC3-X32 to a network or PC:
• A TCP/IP Controller Readme file is available on the www.emersonclimate.eu
website to provide detailed information about TCP/IP Ethernet connectivity. Please refer to this file if you need information beyond the contents of this instruction sheet.
• Connect t he E C3-X32 using the optional ECC-Nxx cable assembly or a standard
CAT5 netw or k cabl e w ith RJ4 5 plug s as se mbl y to a ne two rk o r route r tha t e na ble s the controller to receive a dynamic TCP/IP address or
• Connect the EC3-X32 to a computer using a crossover cab le plugged directly into
the Ethernet port. In this case, the TCP/IP address of the computer must be manually modifi ed to be compatible with the default address of the controller. Refer to the TCP/IP Controller-Readme file for more details.
Setting and visualizing Data: WebPages (recommended method)
Make sure that digital input is 0V (open), turn the power supply ON.
• Four parameters i.e. refrigerant type (u0), pressure sensor type (uP), valve type (ut)
and control mode can be set only when digital input is open (0V) while the power supply is ON (24V). This feature is for added safety to prevent accidental damage of compressors and other system components. All other parameters can be modified at any time.
• The EC3-X32 has a TCP/IP Ethernet communication interface enabling the
controller t o be di rec tly conn ect ed to a net work or a PC via th e stand ar d Ethern et port. The EC3-X32 controller has embedded WebPages to enable the user to visualize t he parameter lists using r eal text labels.
• To view WebPages on the PC, a standard Web Browser like Internet Explor e r® or
Mozilla Firefox and JRE Java Runtime Environment is needed. JRE can be downloaded at no charge from the www.java.com website.
• Open the Internet browser program on the co m puter and, if EC3-X32 is connected
directly to PC with a crossover cable enter the default TCP/IP address of the controller (192.168.1.101) into the address line, or the dynamic address from the
• The Monitoring and Alarm WebPages are read only and therefore it is not
necessary to enter a username or password. A username and password will be requested upon the initi al re quest to any of the other WebPages. The factory default settings are: Username: “EmersonID”, Password: “12”
• The default settings may be modified on the Display configuration page.
• Press the ta bs at the top of t he Mo nitor ing page with a le ft cl ick o f the mouse bu tton
to enter the respective Web page.
• The paramet ers will b e visualized in real text together with the program code as
defined in the parameter list below.
• After the parameters have been modified, the complete list of settings can be saved
to the memory of the computer a nd used later t o upload into a nother controller. This can save a considerable amount of time when using multiple controllers and over a period of time, a library can be created containing the parameter lists for equipment for different applications.
• It is also possible to display live graphical data from the controller. Superheat,
evaporating pressure, coil-out temperature and evaporating temperature are available on a 15 minutes rolli ng chart. R efer to the TCP/IP C ontroller-Readme file for a complete des cription of th e features av ailable for the TC P/IP series o f controllers.
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Pressure transmitter error
Temperature sensor error
EXV electrical connection error
Ab
b1: 1
-
Regulating
Battery potentially does not have enough charge to close valve in
replaced. (Replacement kit: 807 790).
-
Ab
b1: 2
Signaling
Fully close
-
Pump down action
accomplished
AF
P4: 1
Signaling
Fully close
No
AF blinking
P4: 2
Signaling
Fully close
Yes
AL
uL: 1
Signaling
Fully close
No
AL blinking
P9: 1
Signaling
Fully close
No
AP blinking
P9: 2
Signaling
Fully close
Yes
Data error display ­out of range
Data send to the display is out of range. Check temperature and pressure sensor.
Check Cable and plug conn ection between EC3-X… and ECD-002.
Operating superheat is several degrees higher or lower than
Incorrect signal from pressure or
1- Check the sensors.
high voltage c ables
Operating superheat is too low i.e. compressor wet runn ing
1- Incorrect wiring of ECVs 2- Defective sensors
1- Check the wiring 2- Check the sensor
Valve is not fully closed
1- The digital input is ON (24 V) 2- Wrong setting of parameter ut.
1- Valve is shut off only when the digital input is turned off (0 V). 2- Check the setting of parameter ut.
Instable superheat (hunting)
Evaporator is designed to operate at higher superheat
Increase the superheat set-point.
Valve opens when EC3 comm ands to close and vice versa
Wrong wiring between EC3-X3... and valve
Correct the wiring.
EX8 is not able to open at hi gh differential pressu r e
Wrong setting of para m eter ut
Check the parameter ut. (Larger valve requires higher torque and higher current)
Superhea t set-point is shifting after several months of
digital input
Stepper motor driven valv es require
Do not apply permanent 24 V digital input. Interrupt digital input
Error/Alarm handling:
Alarm
code
Description
Related
parameter
Operating instruction
EC3-X32 Superheat Controller with TCP/IP
communication capability
Alarm
relay
Valve What to do?
Requires manual
reset after resolvin g
alarm
E0
E1
- Signaling Fully close Check wiring connection and measure the signal 4…20 mA. No
- Signaling Fully close Check wiring connection and measure the res istance of sensor. No
- Signaling - Check wiring connection and measure the resistance of winding. No
case of main power supply interruption. May occur temporarily with new controllers or after long storage but should disappear when batter y i s charged sufficiently. I f Ab remains active even when battery is charged, battery may be defective and should be
Allocate the source, which does not let suction pressure drops below desired set-point.
Check the system for cause of low pressure such as insufficient load on evaporator.
Check wiring connection and operation of valve.
Check the system for cause of low pressure such as refrigerant loss.
Yes
No
No
Ab blinkin g
AE blinking
AH AP
Er
---
Battery error
b1: 3 Signaling Fully close Yes
cannot
P6: 1 Signaling -
Freeze protection
Low superheat (<0,5K)
uL: 2 Signaling Fully close Yes
High superheat uH: 1 Signaling Fully close Check the system. No Low pressure
- - -
No data to display - - -
Note: When multiple a larms occur, the highest prio r ity alarm is displ ayed until being cleared, then the next highest al ar m is displayed until all alarms are cleared . Only then will parameters be shown again.
Checking system operating conditions using local display/keypad ECD-002:
The data to be permanently shown on the display can be selected by the user (parameter ┌┘1). It is possible to temporarily display these values. However this function is not availa bl e i n a n a lar m condition. Th e dis pla y w ill sho w for one s eco nd the n ume ric al identifier of the data (see ┌┘1 parameter) and then the selected data. After 5 minutes, the display will return to the value selected by parameter ┌┘1.
Service / Troubleshooting:
Symptom Cause Action
set-point
temperature sensors
2- Make sure ECN-N60 temperature sensor is us ed. 3- For optimum accuracy, please use:
PT5-07x (for R22 / R134a / R507 / R404A / R407A / R407C / R407F / R124 / R448A /R449A / R450A / R513A / R1234ze) PT5-18x (for R410A/ R32) PT5-30x (for R410A / R744 / R32) PT5-50x (for R744)
4- Make sure the sensor cables are not installed along with other
uninterrupted operation or permanent jump er of 24 V
synchronization
once every week for 5 seconds if compressor never stops .
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
EC3-X32 Superheat Controller with TCP/IP
Power supply
24 VAC ±10% ; 5 0/60 Hz; 1 A
Power consumption
25 VA max. including EX4…EX8, FX5…FX9.
Removable screw terminals wire size 0.14…1.5 mm2
Grounding
6.3 mm spade earth connector
COM, TCP/IP connection
RJ45 Ether ne t
Connection to optional ECD-002
ECC-Nxx or CAT5 cable with RJ45 connectors
Digital Inputs
0/24 VAC/DC for stop/start function
NTC input
EMERSON temperature sensor ECN-Nxx
4-20 mA Analog input
EMERSON PT5 Press ure Transmitter
4-20 mA Analog output
Deviation from input signal
For connection to an y 3rd party contro l ler with 12/24 VDC power supply and appropriate burden
±8% max
Output alarm relay
SPDT contacts 24 VAC/DC, 2 A inductive load
Output pump down relay
Deactivated
SPDT contact 24 VAC/DC, 2 Amp inductive load
All other conditions
Stepper motor output for EX4…EX8, FX5…FX9
Maximum cur r ent 0.8 A with nominal 24 VDC operating voltage
0…+60°C
> 35°C battery life time < 2 year s
Technical data
Plug-in connector
Protection class IP20
Operating instruction
communication capability
(If L2 = 1) Activated: During normal operation (no alarm condition) Deactivated: During alarm condition or power supply is OFF
(If L2 = 1) Activated:
Ambient t emperature range
Marking
During normal operation
+1…+25°C (for best battery life time)
,
Dimensions [mm]:
EC3-X32 ECD-002
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Betriebsanleitung
• Die Anzeigeeinheit ECD-002 wird in Frontplatten
ichtig mit eingefahrenen
Beiliegenden Imbusschlüssel in die Löcher auf der Frontseite einstecken und im Uhrzeigersinn drehen. Die Halterungen treten aus dem Gehäuse hervor und
drehen bis die erste Halterung die
Halterungen abbrechen.
Befehlsgeber
Betriebszustand
Digitaleingang
Verdichter startet
geschlossen / 24 V (Start)
Verdichter stoppt
offen / 0 V (Stopp)
Anforderung (Verdichter Ein)
geschlossen / 24 V (Start)
Keine Anforderung
offen / 0 V (Stopp)
!
EC3-X32 Überhitzungsregler
Beschreibung: EC3-X32 ist der Überhitzungsregler mit TCP/IP – Schnittstelle zur Steuerung der
schrittmotorgesteuerten elektrischen Regelventile EX4…EX8 und FX5 …FX9.
Sicherheitshinweise:
Lesen Sie die Betriebsanleitung gründlich. Nichtbeachtung kann zum
Versagen oder zur Zerstörung des Gerätes und zu Verletzungen führen.
Der Einbau darf gemäß EN 13313 nur von Fachkräften vorgenommen
werden.
Die angegebenen Grenzwerte für Druck, Temperatur, Strom und Spannung
nicht überschreiten.
Vor Installation oder Wartung sind die Anlage und das Bauteil spannungsfrei
zu schalten.
Das Ventil nicht betreiben, wenn der Kompressor nicht läuft.
Für den gesamten elektrischen Anschluss sind die länderspezifischen
Vorschriften einzu halten.
Hinweis: EC3-X32 Regler en thalten einen wied er aufladba ren Blei-Gel-Akku, der
nicht im normalen Haus- oder Gewerbem üll entsor gt werden dar f. Er muss gemäß Batterieverordnung dem hierfür vorgesehe nen Entsorgu ngssystem z ugeführt we rden (Umsetzun g der 2012/19/EU in nat ionales Recht ). Weitere Inf ormation en erhalten Sie beim für Ihre Stadt zuständigen Recyclinghof.
Einbauort:
EC3-X32 sind für die Montage auf Standard DIN-Schienen geeignet. Montageposition: Auf senkrechten Flächen, mit dem Motoranschluss nach oben.
Dauerhafte Montage der Anzeigeeinheit ECD-002:
• ECD-002 kann jeder zeit montiert werden, auch während dem Betrieb.
mit TCP/IP Schnittstelle
Verdrahtung:
mit einem Ausschnitt von 71x29mm montiert.
Anzeigeeinheit vors
Halterungen in den Frontplattenausschnitt ein­schieben (1).
bewegen sich in Richtung Frontplatte (2).
Imbusschraube
Frontplat te leicht berühr t. Dann zweite Halt erung in diese Position br ingen (3).
• Beide Seiten gleichmäß ig und nicht zu f est
anziehen.
Hinweis: durch zu festes Anziehen können di e
Elektrischer Anschluss:
• Den elektrischen Anschluss gem. Verdrahtungsschema durchführen!
• Versorgungsspannung erst nach kompletter Insta lla tion anlegen!
• Gehäuse mit einem 6.3 mm Fla chstecker erden!
• Signalleitungen und Leit ungen mit Netzspannung in getrennten Kabelschächten
verlegen, Mindestabstand 30 mm!
• Für die 24V Stromversorgung sind ausschließlich Transformatoren der Klasse II
zu verwe nden. Die 24V L ei tunge n dür fe n nic ht ge erde t w erde n. W ir em pfehl en d ie Verwendun g jeweils sepa rater EMERSO N Transform atoren fü r EC3 Regler und die Regler anderer Hersteller, weil unter Umständen über die Erdleitungen Kurzschl üs s e entstehen kön ne n .
• Vor der Inbetriebnahm e des EC3 müssen die Haupt-Parameter eingestellt und der
24V-Digital eingang darf ni c h t a m E C3 angeschlos s en werden.
• Das Alarmrelais dient zum Schutz des Systems bei Stromausfall, wenn
Kommunikations-Schnittstelle oder ECD-002 ni cht verwendet werden!
• Wird das Alarmrelais nicht verwendet, muss das System auf andere Weise vor
Schäden durch Stromausfall geschützt werden.
• Um das System vor Schäden durch Stromausfall zu schützen empfehlen wir einen
jährlichen Austausch des Akkus.
Funktion des Digitaleingangs bei Verdichter- oder Thermostat-Betrieb
Verdichter
Kabelfarben: A: Wei ß B: Schwarz C: Blau D: Braun E: M12 Kabel-Stec kereinheit EXV-Mxx zur Verbindung mit EX4…EX8 und
FX5…FX9.
G: Schaltschrank, Anlagenregler H: Alarmrelais, Wechsler. Inaktiv bei Alarm oder fehlender Stromversorgung I: Digitaleingang (0V = Aus; 24V = Ein) J Trafo Klasse II, 24VAC Sekundär/ 25VA K Anlagenregler (kann analoges Ausgangssignal von EC3 nutzen) O: Relais für Abpump-Betrieb, potentialfreier Kontakt. Relais ist im Normal -
betrieb unter Spannung.
Vorbereitungen für Inbetriebnahme:
• Den gesamten Kältekreislauf vakuumi er en.
Hinweis: Elekt rische Regelventi le von EMERSON EX4…EX8 und FX5…FX9
werden halbgeöffnet ausgeliefert. Den Kältekreislauf nur bei geschlossenem Ventil mit Kältemittel füllen.
• Versorgungsspannung 24V zu EC3 einschalten, der Digitaleingang bleibt bei 0V.
Das Ventil wird zugefahren.
• Bei geschlo ssenem Ventil System mit Kält emittel füllen.
• System starten, Überhitzung und Betriebsbedingungen überprüfen.
Thermostat
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Betriebsanleitung
Blinkt: Ventil schließt
Blinkt: Ventil öffnet
Parameter Eingabe/Speicherung
Nächster Parameter/Wert (höher)
AN: Anforderung AUS Blinkt: arbeitet
AN: Alarm AUS: kein Alarm
auswählen/bestätigen
Nächster
Manuelle Rückstellung für
H5
Passwort
1
199
12 u0
Kältemittel
0
15 1
0 = R22 1 = R134a 2 = R507 3 = R404A
13 = R450A 14 = R513A 15 = R1234ze
uP
Installierter Drucktransmitter
0 3 0
0 = PT5-07x
3 = PT5-50x (für R744)
ut
Installier tes EMERSON Rege lv e ntil
1
12 5
1 = EX4 2 = EX5 3 = EX6 4 = EX7
9 = FX7 10 = FX7.5 11 = FX8 12=FX9
uu
Startöffnung des Regelventils (%)
0
100
50
u9
Startzeit für Ventilöffnung (Sekunden)
0
120
5 uL
Alarm bei zu niedriger Überhitzung
0 2 1
0 = deaktiviert (für überfluteten Verdam pfer)
Alarm Aus bei 3K (ohne Zeitverzug)
u5
Überhitzungseinstellung (K)
wenn uL deakt iv iert
0.5
30
6
u2
MOP Funktion
0 1 1
0 = deaktiviert 1 = aktiviert
u3
MOP (°C) Sättigungstemperatur
* * **
**) Werkseinstellun g abhängig vom gewählten Kältemittel (u0):
abhängig
┌┘5
Einheiten
0 1 0
0 = °C, K, bar 1 = °F, R , psig (Psig Werte geteilt durch 10. Bsp: Display 12.5 bedeutet 125 psig)
┌┘1
Angezeigter Wert
0 4 0
0 = gemess. Überhitzung (K) 1 = gemessener Verdampfungsdruck (bar)
4 = aus gemessenem Druck errechnete Verdampfungstem peratur (°C)
u4
Regelverhalten der Überhitzung
2 = Zwischeneinstellung
0 2 0
uH
Alarm hohe Überhitzung 0 = abgescha l tet 1 = ein mit Auto Reset
1
uA
Alarm Überhitzung Einstellwert
16
40
30 ud
Alarmverzögerung Ü berhitzung, min.
1
15 3
P2
Frostschutz Ausschaltpunkt, °C
-40
40 0
P3
Frostschutz Ein schaltpunkt, °C
-37
43 3
P4
Frostschutz Alarmfunktion
2 = ein mit Hand Reset
0 2 0
P5
Alarmverzögerung Frostschutz, sec.
5
199
30
P6
Abpumpen Einstellung 0 = aus 1 = ein mit Auto Reset
0 1 0
P7
Abpumpen A us s c h al tpunkt, barg
-0,5
18
0.5 P8
Abpumpen Zeitverzögerung, sek.
0
199
30
P9
Niederdruck-Alarm
2 = ein mit Hand Reset
0 2 0
PA
Niederdruck-Alarm Ausschaltpu nk t, barg
-0,8
17,7 0
Pb
Niederdruck-Alarm Zeitverzögerung, sek.
5
199 5
Pd
Niederdruck-Alarm Einschaltpunkt, barg
-0,5
18
0.3
EC3-X32 Überhitzungsregler
ECD-002 Anzei geeinheit: (Funktio n der LEDs und Tasten)
AN: Ventil ist offen
AN: Ventil ist geschlossen
: keine Anford.
alle blinkenden Alarme
(PRG & SEL) 5s drücken
Parametereinstellung mit der Anzeigeeinheit ECD-002:
Hinweis: Einige der Funktionen/Parameter (Handbetrieb und TCP/IP
Konfiguration) sind nicht mit der Anzeigeeinheit einstellbar.
Warnung:
während des Handbetriebs sind alle Alarme blockiert. Wir empfehlen daher das System während des Handbetriebs nicht unkontrolliert zu lassen.
• Parameteränderungen sind mit der Gerätetastatur möglich. Die Konfigurations-
parameter sin d pa s swort ges c h ü tzt . D as wer k ss ei t ig ein g est ellt e Pa s swo rt i st “1 2 ” . Zur Auswahl der Parametereinstellungen:
PRG Taste länger als 5 Sek. gedrückt halt en , eine blink en de "0" erscheint
• oder Taste drücken bis Passwort (Standardwert 12) angezeigt wird
SEL drücken - Passwort wird bestätigt
• oder Taste drücken bis der gewünschte Parameter erscheint;
SEL drücken - der aktuell eingestellte Wert wird angezeigt
• oder Taste drücken - der Wert wird vergrößert oder verkleinert
SEL drücken - der eingestellte W ert wird vorläufig beh alten, muss aber noc h
gespeichert werden. Di e P arameterkennung wird wieder angezeigt.
• Zur Änderung weiterer Parameter wird dieser Ablauf wiederholt:
• oder Taste drücken - nächste Parameterkenn ung a u s wählen.
Parameter speichern und Konfigurationsmodus beenden: PRG Taste drücken
Parameter nicht speichern und Konfigurationsmodus ohne Parameter-
änderung beenden: Mindestens 60 Sekunden lang keine Taste drücken (Zeitsperre)
Spezialfunktionen:
• und Taste länger als 5 Sek. gedrückt halten bis blinkende "0" erscheint
• oder Taste drücken bis das Passwort (Standardwert 12) angezeigt wird
SEL drücken - Passwort wird bestätigt
“0” wird angezeigt und der Modus für Spezialfunktionen ist aktiviert
• oder Taste drücken und den Code der Funktion auswählen. Die Anzahl der
Sonderfun ktionen ist dy na m is c h u nd reglerabhä ng i g : 0: Reg ler auf Werkseinstellung zurücksetzen (Reset).
(nur bei offenem Digi taleingang (O V) möglich) 1: Aktuelle TCP/ IP Adresse anzeigen. 2: Dem Regler vorübergehend die Standard TCP/IP-Adresse 192.168.1.101
zuweisen, falls dieser ei ne andere Ad resse besi tzt. Nac h dem Abscha lten wird
die zuvor ei ngestellte Adr esse wieder aktiviert.
SEL drücken - alle Parameter werden auf Werkseins tellung zurückgesetzt.
PRG drücken - die gewählte Funktion wird aktiviert und die Betriebsart Spezial-
funktionen verlassen.
mit TCP/IP Schnittstelle
Parameter/Wert (tiefer)
Parametertabelle: (im Regler hinterlegte Reihenfolge)
Code Beschreibung und Wahlmöglichkeiten Min Max Werk Kunde
4 = R407C 5 = R410A 6 = R124 7 = R744 (unterkritische Anwendung) 8 = R407A; 9 = R407F 10 = R32* 11 = R448A 12 = R449A
(für R22 / R134a / R5 07 / R404A / R407A / R407C / R407F / R124 / R448A /R449A / R450A / R513A / R1234ze) 1 = PT5-18x (für R410A/ R32) 2 = PT5-30x (für R410A / R744 / R32)
5 = EX8 6 = FX5 7 = FX6 8 = FX6.5
1 = automat. Rückstellung 2 = manueller Rückstellung Alarm Ein bei 0.5K (wenn länger als 1 Minute unterschritten);
wenn uL aktiviert (autom. oder manuell)
+13°C - R22 +15°C - R134a +7°C - R507 +7°C - R404A +15°C - R407C +15°C - R410A +50°C - R124 -5°C - R744 +10°C - R407A +10°C - R407F +10°C - R32 +12°C - R448A +12°C - R449A +19°C - R450A +13°C - R513A +24°C - R1234ze *) Min. und Ma x. Einstellungen sind vom gewählten Kältemittel
3
30
6
2 = Ventilöffnungsgrad (%) 3 = gemessen e Sauggas-Temperatur (°C )
0 = Standard 1 = langsam
0 = abgeschaltet 1 = ein mit Auto Reset
0 = aus 1 = ein mit Auto Reset
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Betriebsanleitung
L2
Ausgabe Logik
0 3 1
0: Alarm = normal, Abpumpen = normal
3: Alarm = invers, Abpumpen = invers
b1
Batterie-Fehlermanagement bei defekter Batterie:
0 3 2
Anzeige
Möglichkeit zur
Erholung/Austausch
0 - - regelt
-
1 Ab - regelt
-
2 Ab
signalisierend
geschlossen
automatisch
3 Ab (blinkt)
signalisierend
geschlossen
manuell
Wird das Alarmrelais nicht verwendet (b1 = 0 oder = 1), muss das
urch Stromausfall geschützt
werden.
uF
Regelbereich Ventil %
5
100
100
FX9 ≤ 9,77 Sekunden
Digitaleingang

Alarm

Relais für Abpumpen
24V (AN)
NEIN
aktiviert
0V (AUS)
NEIN
deaktiviert, wenn der Druck unter P7 abfällt und die für P8 eingestellte Zeit vergangen ist
0V oder 24V
JA
deaktiviert
!
Sec.
uu
u9
%
EC3-X3 BA.cdr
EC3-X32 Überhitzungsregler
Code Beschreibung und Wahlmöglichkeiten Min Max Werk Kunde
1: Alarm = invers, Abpumpen = normal 2: Alarm = normal, Abpumpen = invers
Wert Display-
System auf andere Weise vor Schäden d
Alarmrelais Ventilzustand
*) Hinw eis für R32: R32 ist in Europa als entflammbares Kältemittel eingestuft. EC3-X32 ist nach den Richtlinien für nicht brennbare Kältemittel entwickelt. Die Verwendung des EC3-X32 für R32 ist nur in Regionen zulässig in denen keine zusätzlichen Sicherheitsvorschriften für R32 bestehen bzw. Anzuwenden sind.
EC3-X32 sind auch ohne Anzeigeeinheit ECD-002 betriebsbereit, diese kann auch während d es Betriebs ein- oder ausgesteckt werden.
Startverhalten der Regelventile: (Parameter uu und u9)
mit TCP/IP Schnittstelle
Rückstellung nach
• Zur Darstellung der Internetseiten auf dem PC genügt ein Standard
InternetB rowser wie Intern et Ex plore r® od er Mozi lla Fi refo x und zusä tzli ch ein e installierte Version der JRE Java Runtime Environment. JRE kann kostenlos von der www.java.com
. Internetseite herunterg el aden werden.
• Am PC wird d er WebBrowser gestart et und entweder die St andardadresse des
Reglers eingegebe n ( 192.168.1.1 01) , oder die dynamische Adresse, d ie der DHCP Server vergeb en ha t. Weitere Hi nwei se sind in der "TC P/IP Cont roller-Readme" Datei zu fin den, falls ein spezieller Po rt vergeben w erden muss oder die DHCP Adresse au sgelesen werden soll
• Nach wenigen Sekunden erscheint die Monitorseite des Reglers (Homepage). Falls
diese Seit e n icht erscheint, oder falls keine dynamischen Werte angezeigt werden, müssen die "Op tionen" des WebBrowsers ü berprüft werden. Weit ere Hinweise dazu stehen i n der "TCP/IP Controller -Readme" Datei.
EX4/5/6 ≤ 1,5 Sekunden EX7 ≤ 3,2 Sekunden EX8 ≤ 7,2 Sekunden FX5-8 ≤ 7,3 Sekunden
Abpump-Fun ktion (wenn P6=1 und L2=1)
Vernetzung von EC3 -X32 und PC-Anbindung:
• Ausführlichere Informationen als hier beschrieben zur Einrichtung eines Ethernet
Netzwerkes stehen in der "TCP/IP Controller-Readme" Datei, die im Internet unter www.emersonclimate.eu abgerufen werden kann.
• EC3-X32 mit dem o ptio nale n K abel ECC-Nx x o der ha nde lsübl iche m CA T 5 Kabe l
mit RJ45 St eckern am Netzwerk od er Router ansch ließen, d amit der R egler ein e dynamische TCP/IP-Adresse erhält, oder
• EC3-X32 mit einem Crossover-Kabel direkt am Ethernet Anschluss des
Computers einst ecken . In di esem Fa ll mu ss di e TCP/ IP Adress e des PCs manu ell auf die Standardadresse des Reglers umgestellt werden. Einzelheiten hierzu entnehmen Sie bitte der "TCP/IP Controller-Readme" Datei.
Parametereinstellung und Datenanzeige auf Webseiten: (empfohlene Methode)
Während am Digitaleingang 0V anliegen Versorgungsspannung anschalten.
• Die vier Para meter Kältemittel (u0), Drucksensor-Typ (uP), Ventil-Typ (ut) und
Kontroll mo de könne n nur e ing e ste ll t w er de n, w e nn der D ig ita le ing ang o ff en ( 0 V) und die Versorgungsspannung AN (24 V) ist. Diese Siche rheits funkt ion v erhin dert die Beschädigung des Verdichters oder anderer Systemkomponenten. Alle anderen Parameter können jederzeit verändert werden.
• Der EC3-X32 kann mit seiner TCP/IP Ethernet-Schnittstelle direkt an den
Ethernetanschluss eines PCs oder an ein lokales Netzwerk angeschlossen werden. Übersicht liche Web seit en, auf den en die Par ameter listen angezei gt oder geändert werden können sind bereits eingebaut.
• Die Monitor- und Alarmseite lässt sich nicht ändern und ist daher nicht geschützt.
Beim erstmaligen Zugriff auf eine der anderen Seiten werden die Benutzerkennung und ein Passwort abgefragt. Ab Werk sind folgende Wert e eingestellt:
Username: EmersonID Password : 12
• Auf der Seite " Display Konf igurat ion" lass en sich dies e Werte änd ern. Zu dies er
Seite gelangt man, indem man mit dem Mauszeiger über die entsprechende Schalt­fläche oben a n der Monitorse ite fährt und dan n die linke Mausta s te drückt.
• Die Parameter werden sowohl in Textform, als auch mit dem Code aus der
Parametertabelle oben angezeigt.
• Alle Einstellungen können auf dem PC gesichert und gegebenenfalls in einen
weiteren Controller geladen werden. Dies spart viel Zeit, wenn mehrere Regler mit den gleich en Einstellungen eingesetzt werden . Im Laufe der Zei t lässt sich eine kleine Bibliothek aufbauen, in der die Reglereinstellungen für unterschiedliche Anwendungen gespeichert sind.
• Der zeitl iche Ve r lauf vo n Ü be rhi tzu ng , V e rdam pf ung sdr uc k und T e mpe r atur ka nn
grafisch in einem rollieren den 15 Minuten Zei traster da rgestel lt werden . Weitere Einzelhei ten siehe "TCP/IP Controller-Readme" Datei.
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Drucktransmitter Fehler
Temperatursensor Fehler
EXV Fehler
Anschluss
Batterieladung zu schwach für Schließen des Ventils bei
(Austauschkit Best.-Nr. 807 790).
Ab
Abpumpen kann
werden
AF
P4: 1
signalisierend
geschlossen
Nein
AF blinkt
P4: 2
signalisierend
geschlossen
Ja
AL
Überhitzung zu
(<0,5K)
uL: 1
signalisierend
geschlossen
Nein
AH
Hohe Überhitzung
uH: 1
signalisierend
geschlossen
System auf Fehler überprüfen.
Nein
AP
P9: 1
signalisierend
geschlossen
Nein
Daten außer ha l b des Anzeigebereichs
Display kann Daten nich t d arstellen, E instellwert der Paramet er verändern.
Kable- und Steckerverbindungen zwischen EC3-X3.. und ECD-002 prüfen.
Überhitzung ist einige Grad höher oder niedriger als der
Fehlerhaftes Signal von Druck- oder
1- Sensor überprüfen
verlegen
Überhitzung ist zu niedrig, Verdichter läuft nass
1- Ventile fals ch angesch l o ssen 2- Defekter Sen sor
1- Verdraht ung überprüfe n. 2- Sensor überprüfen.
Ventil ist nicht vollst ändig geschlossen
1- Digitaleingang ist EIN (24 V) 2- Falsche Einstellung für Parameter ut
1- Ventil schließt nur, wenn der Digitaleing ang A US ist ( 0 V). Schwankende Überhitzung
eingesetzter Verdamp f er ist für höhere Überhitzung ausgelegt
Einstellwert für Überhitzung vergrößern.
Ventil öffnet, wenn EC3 Befehl zum schließen gibt und umgekehrt
Fehlerhafte Verdrahtung zwischen EC3-X3.. und Ventil
Verdrahtung gem. Verdrahtungsschema durchführen.
EX8 öffnet bei hohem Differenzdruck nicht
Falsche Einstellung für Parameter ut
Parameter ut überprüfen. (Größere Ventil e er fordern ein größeres Drehmoment und eine höhere Stromstärke).
Überhitzungseinstellung verändert sich nach einigen
Überbrückung des 24 V Digitaleingangs
Ventile mit Schrittmotor erfordern
Am 24 V Digitaleingang nicht dauerhaft Spannung anlegen; wenn
für 5 Sekunden unterbrechen.
Alarmanzeigen und Fehlerbehebung:
Alarm
Code
Fehler
Beschreibung
Abhängiger
Parameter
Betriebsanleitung
EC3-X32 Überhitzungsregler
mit TCP/IP Schnittstelle
Alarm
Relais
Ventil-
zustand
Fehlerlösung
Manuelle Rückstellung
nach Fehlerbehebung
notwendig
E0
E1
Ab
Ab blinkt
AE blinkt
AL blinkt
AP blinkt Er
---
elektrischer
Batteriefehler
nicht vollendet
Frostschutz
niedrig
Niedriger Druck
Keine Daten - - -
- signalisierend geschlossen Verdraht ung prüfen und 4 bis 20 mA Signal messen. Nein
- signalisierend geschlossen Verdraht ung prüfen und Widerstand des Sensors messen. Nein
- signalisierend unbekannt
Verdrahtung prüfen und Widerstand der Wicklung messen.
Nein
b1: 1 - regelt b1: 2 signalisierend geschlossen -
b1: 3 signalisierend geschlossen Ja
P6: 1 signalisierend -
Stromausfall. Kann bei neuen Reglern oder langer Lagerzeit auftreten und sollte nach ausreichender Aufladung der Batterie verschwinden. Ansonsten defekte Batterie ersetzen
Herausfin den weshalb der Saugdruck nicht unter den eingestellten Wert abs i nkt.
Ja
Ursache für zu niedrigen Druck wie z.B. un zureichend e Verdampferfüllung ermitteln.
Verdrahtung prüfen und Funktionsprüfung des Ventils
uL: 2 signalisierend geschlossen Ja
durchführen.
Ursache für zu niedrigen Druck wie z.B. Kältemittelv erlust
P9: 2 signalisierend geschlossen Ja
- - -
ermitteln.
Nein
Nein
-
Hinweis: Bei mehreren Alarmen gleichzeitig wird der Alarm m it der höchst en Priorität angezeigt, nach dessen Beseitigung wird der nächsthöhere angezeigt usw., bis alle Alarme beseitigt sind. Danach werden wi eder die Parameter angezei g t.
Überprüfung der Be triebsbedingungen mit E CD-002:
Die am Display permanent angezeigten Daten werden vom Anwender durch Parameter ┌┘1 bestimmt. Gleichzeitig können andere Daten vorübergehend am Display angezeigt wer den, sofern k ein Alar m vorli egt. Da s Display zeigt nach Drücken von SEL zuerst für 1 Sekunde den Code für den jeweiligen Wert (s. Parameter ┌┘1) und dann die Daten. Nach 5 Minuten werden wieder die permanenten Daten angezeigt.
Service/Fehlersuche:
Fehlerbeschreibung Ursache Aktion
eingestellte Sollwert
Temperatursensoren
2- ECN-N60 Temperatursensor einsetzen 3- EMERSON Drucktransmitter verwenden:
PT5-07x (für R22 / R134a / R507 / R404A / R407A / R407C / R407F / R12 4 / R 4 4 8A /R449A / R45 0A / R513A / R1234ze) PT5-18x (für R410A/ R32) PT5-30x (für R410A / R744 / R32) PT5-50x (für R744)
4- Sensorkabel nicht zusammen mit stromführenden Leitungen
2- Einstellung für Parameter ut überprüfen.
Monaten ununterbrochenen Betriebs oder bei permanenter
Synchronisation
Verdichter ununterbrochen läuft, D igitaleingang einmal je Woc he
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx
Loading...
+ 21 hidden pages