Emerson ECD-002, EC3-P33 Operating Instructions Manual

Operating instruction
EC3-P33 Superheat Controller and
ECD-002 Keypad / Display Unit
Installation in non explosive environment
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 04.05.2017 EC3-P33_OI_ML_R01_865919.docx
General information: EC3-P33 is the superheat controller for systems with flammable refrigerants
(A2L/A3) and able to drive EMERSON Valves EX4-7-…FLR via M12 Conn ector ECV05A.
Note: This document contains short form instructions for experienced users.
Warning:
EC3-P33 has a potential ignition source and does not comply with ATEX
requirements. Installation only in non-explosive environment.
EX4-7…FL R are currently released for R29 0 in term of compat ibility. The
other listed refrigerants are subject to qualification at later stage. No warranty or product liability if EX4-7…FLR to be used with other refrigerants stored in software of EC3-P33.
Safety instruc tions:
Read operatin g instru ctions th oroughl y. Failu re to comp ly can result i n device
failure, system damage or personal injury.
According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
Ensure that the system is correctly labeled with applied refrigerant type and
a warning for ex p losion risk.
Do not exceed the specified maximum ratings for temperature (max.+60°C),
voltage and current.
Before installation or service disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Entire electrical connections have to comp ly wit h l o cal regulati on s . Note: The E C3-P33 series contains a VRLA battery = valve regulated rechargeable
lead-acid battery. The batte ry m ust NOT be dis posed of w ith othe r comme rcia l was te.
Instead, it is the use r’s re sponsi bility to pass it to a des igna te d co ll e ctio n po i nt fo r t he safe recycling of batteries (harmonized directive 2012/19/EU). For further information contact your local environmental recycling center.
Mounting position:
The EC3-P33 is designed to be mounted onto a standard DIN rail. Mounting position: on vertical walls, with stepper motor connector on top side only.
Mounting of ECD-002:
• ECD-002 can be installed at any time also during operation.
• ECD-002 can be mounted in panels with
71x29 mm cutout.
• Push controller into panel cut-out.(1)
• Make sure that mounting lugs are flush with
outside of controller h ousing
• Insert Allen key into front panel holes and turn
clockwise. Mounting lugs will turn and gradually move towards panel (2)
Turn Allen key until mounting lug barely touches
panel. Then move ot her mounting lug to the same position (3)
• Tighten both sides very carefully until keypad is
secured. Do not over tighten as mounting lugs
will break easily.
Electrical Installation:
Refer to the electrical wiring diagram for electrical connections.
Do not apply voltage to the controller before completion of wiring.
Ground the metal housing with a 6.3 mm spade connector.
Keep controller and sensor wiring well separated from mains wiring.
Minimum recommended distance 30 mm!
Ensure that cables are not mounted near sharp edges.
• Use a class II category transformer for 24 VAC power supply. Do not ground the
24 VAC lines. We recommend using individual transformers for EC3 controller(s) and for 3
rd
party controllers t o avoid poss ible in terference or grounding problems
in the power supply.
• Connecting any EC3 inputs to mains voltage will permanen tly damage the EC3.
• The use of the relay is essential to protect the system in case of power failure if the
communications interface or the ECD-002 are not utilized.
• If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power failure.
• In order to provide system protection in the event of power loss, it is recommended
to change the battery annually.
Digital input status is dependent to operation of compressor/th ermostat
Commander
Operating condition
Digital input (I)
Compressor Compressor starts
Closed / 24 V (Start)
Compressor stops
Open / 0 V (Stop)
Thermostat Demand (compressor must be ON)
Closed / 24 V (Start)
No demand
Open / 0 V (Stop)
Wiring:
v
2: White wire 4: Black wire 3: Blue wire 1: Brown wire G: Remote control panel, system controller H: Alarm relay, dry contact. Relay coil is not energized at alarm or power off. I: Digital input (0V/open = Stop; 24 V/closed = Start) J: Transformer Class II, 24 VAC secondary / 25 VA K: Third party controller (can use the analog output signal from EC3)
Preparation for Start-up:
• Vacuum the en tire refrigeration system
Note: EX4-7-…FLR are d elivered at half op en position. Do not ch arge system
before closur e of valve.
• Apply suppl y voltage 24 V to EC3 while the dig ital input is 0 V (open). The valve
will be driven to close position.
• After closure of valve, start to charge the system with refrigerant.
• Start the system and check the superheat and operating conditions.
!
Non-explosiv environment
Operating instruction
EC3-P33 Superheat Controller and
ECD-002 Keypad / Display Unit
Installation in non explosive environment
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 04.05.2017 EC3-P33_OI_ML_R01_865919.docx
ECD-002 display/keypad unit: (LE Ds and button functio ns)
Setup of main para meters u sing ECD-002: (need to be checked/modified before start-up)
• Make sure that digi tal input is 0 V (open). Turn the power supply ON.
Important: Three ma in pa r am et ers i.e. r efri g era n t t yp e (u0 ) , p ress u re s en sor t ype
(uP) and valve type (ut) can be set only when digital input is open (0 V) while the power supply is ON (24 V). This feature i s for added safet y to p revent acc iden tal damage of compressors and other system components.
• For easy sett ing of main parameters, fo llow the pictorial pr ocedure of “Quick
start-up” on the attached individual p a pe r.
Once the main parameters have been selected/saved the EC3 is ready for
startup. All other parameters can be modified at any time during operation or standby if it is necessary.
Procedure for parameters modification using ECD-002:
• The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is “12”. To select the parameter configuration:
• Press the PRG button for more than 5 seconds. A flashing “0” i s displaye d
• Press or until “12” is displayed; (password)
• Press SEL to confirm password
• Press or to show the code of the param eter that has to b e changed;
• Press SEL to display the selected param eter value;
• Press or to increas e o r decrease the value;
• Press SEL to temporarily confirm the new value and display its code;
• Repeat the procedure from the beginning "press or to show..."
To exit and save the new settings: P
ress PRG to confirm the new values and exit
the parameters modification procedure.
To exit without modifying any parameters: Do not press any button for at least
60 seconds (TIME OUT).
Reset all parameters to factory setting:
• Make sure that digi tal input is 0 V (open).
• Press and together for more than 5 seconds. A fl a sh ing “ 0 ” i s di splayed.
• Press or until the passw o rd is displayed (Factory setting = 12).
If password was changed, select the new password.
• Press SEL to confirm password
“0” is displayed.
• Press SEL to reset all parameters to factory setting
• Press PRG to activat e the function and leave the special function mod e.
Control (valve) start-up behavior: (Parameter uu and u9)
EX4/5/6-…FLR ≤ 1.5 seconds EX7-…FLR ≤ 3.2 seconds
Main parameters: (must be checked and modified if necessary)
Code Parameter description and choices Min Max
Factory setting
Field setting
H5
Password
1
199
12 u0
System refrigerant
0 6 0
0 = R290; 1 = R32; 2 = R1234ze;
3 = R1234yf; 4 = R1270;
5 = R227; 6 = R600a
uP
Installed pressure sensor type
PT5-30L-FLR ut
Installed valve type
0 3 1
0=EX4-…FLR; 1=EX5-…FLR; 2=EX6-…FLR; 3=EX7-…FLR
Optional paramete rs: (recomm e n d ed factory setting fo r majority of app l i c at ions)
After selecting the parameters the EC3-P33 is fully functional without keypad/display unit. ECD-002 may be removed or connected at any time.
Code Parameter description and choices Min Max
Factory setting
Field setting
uu
Start valve opening (%)
5
100
10 u9
Start opening duration (second)
1
120 5
uL
Low superheat alarm function
0 2 1
0 = disable (for flooded evaporator)
1 = enable aut o reset 2 = enable manual reset
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K
u5
Superheat set-point (K)
If uL enabled (auto or manual)
If uL disabled
3
0.5
30
30
6
6
u2
MOP function
0 1 1
0 = disable 1 = enable
u3
MOP set-point (°C) saturation temper atur e
* * X
Factory setting is ac cording to selected refrigerant (u0):
+13°C for R290 +15 °C for R32 +15°C for R1234ze +15°C for R1234 yf +13°C for R1270 +15°C for R227
+15°C for R600a
┌┘5
Units conversion (only for u3, u5, ┌┘1)
0 1 0
0 = °C, K, bar
1 = °F, R, psig
(Psig values are divided by 10. Example: Display 12.5 is 125 psig)
┌┘
1
Value to show
0 4 0
0 = Measuredsuperheat (K)
1 = Measured evaporating pressure, (bar); 2 = Valve opening (%) 3 = Measured coil-out temperature (°C)
4 = Calculated evaporating temperature (°C) from the pressure
u4
Superheat control mod e
0 1 0
0 = Standard, 1 = Slow
b1
Battery error management, when battery is defective, see below
0 3 2
value
Alarm
display
Alarm relay Valve
Reset possibility after recovery/replacement
0 - - Regulating
-
1
Ab - Regulating
-
2
Ab
Signalling
Fully close
Auto
3 Ab
(blinking)
Signalling
Fully close
Manual
When setting b1 to option 0 or 1, the user must ensure appropriate safety
precautions are in place to protect the system against damage c
aused by
a power failure.
!
Blinking: valve is closing ON: valve is fully close
Blinking: valve is opening ON: valve is fully open
ON: demand
OFF: no demand
ON: alarm OFF: no alarm
Parameters setting/saving
Selecting/confirming
Next param eter/ value (higher)
Next param eter/ value (lower)
Prg&Sel (5 sec)
Manual reset f o r
blinking alarm codes
Sec.
uu
u9
%
EC3-X3 BA.cdr
Operating instruction
EC3-P33 Superheat Controller and
ECD-002 Keypad / Display Unit
Installation in non explosive environment
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 04.05.2017 EC3-P33_OI_ML_R01_865919.docx
Error/Alarm handling:
Alarm code Description
Related
parameter
Alarm
relay
Valve What to do?
Requires manual
reset after resolvin g
alarm
E0
Pressure transmitter error
- Signalling Fully close Check wiring connection and measure the signal 4…20 mA No
E1
Temperature sensor error
- Signalling Fully close Check wiring connection and measur e the resistance of sensor No
EXV electrical connection error
- Signalling - Check wiring connection and measure the resistance of winding No
AL
Low superheat (<0,5K)
uL: 1
Signalling
Fully close
Check wiring connect ion and operation of valve
No
AL blinking
uL: 2
Signalling
Fully close
Yes
Ab
Battery error
b1: 1 - Regulating
Battery potentia lly does not have enough charge to close valve in case of main power supply interruption. May occur temporarily with
new controllers or after lon g s torage but should disap pear when battery is charged sufficiently. If Ab remains active even when battery is c harged, battery may be defective and should be replaced.
(Replacement kit: 807790).
-
Ab
b1: 2 Signalling Fully close -
Ab blinking
b1: 3 Signalling Fully close Yes
Er
Data error display
- out of range
- - -
Data send to the display is out of range. Check temperature and pressure sensor.
No
---
No data to display
- - -
Check Cable and plug connection between EC3-X33 and ECD-002.
No
Note: When multiple alarms occ ur , the highest prio r ity alarm is displ a yed until being cleared, then the next highest a l ar m is displayed until all alarms are cleared. Only then will parameters be shown again.
Checking system ope rating conditions:
The data to be permanently shown on the display can be selected by the user
(parameter ┌┘1). It is possible to temporarily display other values. However this
function is not avail a bl e in an ala r m condition. The dis play wil l s how for one s econd the numerical identifier of the data (see ┌┘1 parameter) and then the selected data. After 5 minutes, the display will return to the value selected by parameter┌┘1.
Service / Troubleshooting:
Symptom Cause Action
Operating superheat is several degrees higher or lower
than set-point
Incorrect signal from pressure or
temperature sensors
1- Check the sensors
2- Make sure EC N -N6 0 temperature sensor is used 3- For optimum accuracy, please use: PT5-30L-FLR 4- Make sure the s ensor cables are not installed along with other
high voltage cables
Operating superhea t is too low i.e. compressor wet running
1- Incorrect wiring of ECV05A 2- Defective sensors
1- Check the wiring 2- Check the sensor
Valve is not full y clo sed
1- The digital input is ON (24 V) 2- Wrong setting of paramet er ut.
1- Valve is shut off only when the digital input is turned off (0 V) 2- Check the set t ing of paramet er ut
Instable superheat (hunting)
Evaporator is designed to operate at higher superheat
Increase th e superheat set-point
Valve opens when EC3 commands to close and vice versa
Wrong wiring between EC3-P33 and valve
Correct the wiring
Superheat set-point is shifting after severa l m onths of
uninterrupted op eration or permanent jumper of 24 V
digital input
Stepper motor driven valves require
synchronization
Do not apply permanent 24V digital input. Interrupt digital input once every week for 5 seconds if compressor never stops.
Technical data Dimensions [mm]:
Power supply
24 VAC ±10%; 50/60 Hz; 1 A
EC3-P3
3
Power consumption
25 VA max. including EX4-7-…FLR.
Plug-in connector
Removable screw terminals wire size 0.14…1.5 mm2
Grounding
6.3 mm spade earth connector
Protection class
IP20 Connection to ECD-002
ECC-Nxx or CAT5 cable with RJ45 connectors
Digital Inputs
0/24VAC/DC for stop/start function
NTC input
EMERSON temperature sensor ECN-N60
4…20 mA Analog input EMERSON PT5-30L-FLR Pressure Tran smitter
4-20 mA Analog output
Deviation from input
signal
For connection to any 3rd party controller with
12/24 VDC power suppl y and appropria te burden
±8% max
ECD-002
Output alarm relay
SPDT contacts 24 VAC/DC, 2 Amp inductive load
Activated:
During normal operation (no alarm condition)
Deactivated:
During alarm condition or power supply is OFF
Stepper motor output for EX4-7
Maximum cur r ent 0.8 A with nominal 24 VDC operating voltage
Ambient temperature range
0…+60°C
+1…+25°C (for best battery life t ime)
> 35°C battery life time < 2 years
Marking
Loading...
+ 4 hidden pages