Emerson EC3-P32 Operating Instructions Manual

EC3-P32 Superheat Controller with TCP/IP
• ECD-002 can be mounted in panels with
Turn Allen key until mounting lug barely touches
will break easily.
Commander
Operating condition
Digital input (I)
Compressor Compressor starts
Closed / 24 V (Start)
Compressor stops
Open / 0 V (Stop)
Thermostat Demand (compressor must be ON)
Closed / 24 V (Start)
No demand
Open / 0 V (Stop)
!
Non-explosiv environment
General information: EC3-P32 is the superheat controller for systems with flammable refrigerants
(A2L/A3) and able to drive EMERSON Valves EX4-7-…FLR via M12 Connector ECV05A.
Warning:
EC3-P32 has a potential ignition source and does not comply with ATEX
requirements. Installation only in non-explosive environment.
EX4-7…FL R are currently released for R 290 in term of compat ibility. Th e
other listed refrigerants are subject to qualification at later stage. No warranty or product liability if EX4-7…FLR to be used with other refrigerants stored in software of EC3-P32.
Safety instructions:
Read operatin g instru ctions th orough ly. Failu re to comp ly can result in device
failure, system damage or personal injury.
According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
Ensure that the system is correctly labeled with applied refrigerant type and
a warning for explosion ris k.
Do not exceed the specified maximum ratings for temperature (max. +60°C),
voltage and current.
Before installation or service disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Entire electrical connections have to comp ly wit h local regulations. Note: The E C3-P32 seri es conta ins a VRLA battery = valve regulated rechargeable
lead-acid battery. T he batte ry m ust NO T be dis pose d of w ith othe r comm erci al was te.
Instead, it is the use r’s responsi bility to pass it to a desig na te d col l ec tion po int f or t he safe recycling of batteries (harmonized directive 2012/19/EU). For further information contac t your local environmental recycling center.
Mounting positio n:
The EC3-P32 is desig ned to be mounted onto a standard DIN rail. Mounting position: on vertical walls, with stepper motor connector on top side only.
Mounting of ECD-002:
• ECD-002 can be installed at any time also during operation.
71x29 mm cutout.
• Push controller in to panel cut-out.(1)
• Make sure that mounting lugs are flush with
outside of controller housing
• Insert Allen key into front panel holes and turn
clockwise. Mounti ng lugs will turn and grad ually move towards panel (2)
panel. Then move other mounting lug to the same position (3)
• Tighten both sides very carefully until keypad is
secured. Do not over ti ghten as mounting lugs
Electrical Installation:
Refer to the electrical wiring diagram for electrical connections.
Do not apply voltage to the controller before completion of wiring.
Ground the metal housing with a 6.3 mm spade connector.
Keep controller and sensor wiring well separated from mains wiring.
Minimum recommended distance 30 mm.
Ensure that cables are not mounted near sharp edges.
• Use a class II category transformer for 24 VAC power supply. Do not ground the
24 VAC lines. We recommend using individual transformers for EC3 controller(s)
rd
and for 3
party contr ollers to avoi d pos sible in terferenc e or groun ding p roblems in the pow er suppl y. Connecting any EC3 inputs to mains voltage will permanently damage the EC3.
• The use of the relay is essential to protect the system in case of power failure if the
communications interface or the ECD-002 are not utilized.
• If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power failure.
• In order to pro v ide system pro tection in the event of power loss, it is recommended
to change the battery annually.
Installation in non explosive environment
Operating instruction
Digital input status is dependent to operation of compressor/t h e r mostat
Wiring:
2: White wire 4: Black wire 3: Blue wire 1: Brown wire G: Remote control pan el, s yst em controller. H: Alarm relay, dry contact. Relay coil is not energized at alarm or power off. I: Digital input (0 V/open = Stop; 24 V/closed = Start) J: Transformer Class II, 24 VAC secon dary / 25VA K: Third party controller (can use the analog output signal from EC3) O: Pump down relay, dry contact. Relay is energized during normal operation.
Preparation for Start -up:
• Vacuum the entire refrigeration system.
Note: EX4-7-…FLR are d elivered at half open position. Do not charge system
before closu r e of valve.
• Apply suppl y voltage 24 V to EC3 while the digital input is 0 V (open). The valve
will be driven to close position.
• After closure of valve, start to charge the system with refrigerant.
• Start the system and check the superheat and operating conditions.
Emerson Climate Technologies GmbH www.emersonclimate.eu
Operating instruction
Factory setting
Field setting
H5
Password
1
199
12 u0
System refrigerant
0 6 0
0 = R290; 1 = R32; 2 = R1234ze;
5 = R227; 6 = R600a
uP
Installed pressure sensor type
PT5-30L-FLR
ut
Installed valve type
0 3 1
0=EX4-…FLR; 1=EX5-…FLR; 2=EX6-…FLR; 3=EX7-…FLR
uu
Start valve opening ( %)
5
100
10 u9
Start opening duration (second)
1
120 5
uL
Low superheat alarm function
0 2 1
0 = disable (for flooded eva porator)
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K
Superhea t set-point (K)
If uL disabled
0.5
30
6
u2
MOP function
0 1 1
0 = disable 1 = enable
u3
MOP set-point (°C) saturation tempe r atur e
* * X
Factory setting is according to selected refrigerant (u0):
+15°C for R600a
┌┘5
Units conversion
0 1 0
0 = °C, K, bar 1 = °F, R, psig (Psig values are divided by 10. Example: Display 12.5 is 125 psig)
Value to show
0 4 0
0 = Measured superheat (K) 1 = Measured evaporating pressure, (bar);
4 = Calculat ed evaporating temperature (°C) from the pressure
Superheat control mode 0 = Standard, 1 = Slow
0 1 0
High superheat alarm function
1 = enable auto reset
1
uA
High superheat alarm setpoint
16
40
30 ud
High superheat alarm delay, min.
1
15 3
P2
Freeze protection cut-out, °C
-40
40 0
P3
Freeze protection cut-in, °C
-37
43 3
Freeze protection alarm function
2 = enable man ual reset)
0 2 0
P5
Freeze protection alarm delay, sec.
5
199
30
Pump-down function 0 = disable, 1 = ena ble auto-reset
0 1 0
P7
Pump-down cut-out, barg
-0,5
18
0.5 P8
Pump-down time del ay, sec.
0
199
30
Low pressure alarm function
2 = enable man ual reset
0 2 0
PA
Low pressure alarm cut-out, barg
-0,8
17,7 0
Pb
Low pressure alarm delay, sec.
5
199 5
Pd
Low pressure alarm cut-in, barg
-0,5
18
0.3
L2
Output logic
0 3 1
0: Alarm = normal, pump down. = normal
3: Alarm = inverse, pump down. = inverse
Blinking: valve is closing ON: valve is fully close
Blinking: valve is opening ON: valve is fully open
ON: demand
ON: alarm OFF: no alarm
Parameters setting/saving
Selecting/confirming
Next parameter/
Next parameter/ value (lower)
Prg&Sel (5 sec)
blinking alarm codes
EC3-P32 Superheat Controller with TCP/IP
ECD-002 display/keypad u nit: (LEDs and button fu nctions)
OFF: no demand Blinking: pump
down
Manual reset for
Procedure for parameter modification using ECD-002:
Note: Some of the functions/parameters (manual control and TCP/IP
configuration) cannot be modified when using ECD-002 comparing to a set-up by PC via TCP/IP.
Warning:
All alarms are disabled during manual control. We do not recommend unattended operation of system during manual contro l.
• The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is “12”. To select the parameter configuration:
• Press the PRG button for more than 5 seconds, a flashing “0” is displayed
• Press or until “12” is displayed (password)
• Press SEL to confirm passw ord
• Press or to show the code of the parameter that has to be changed;
• Press SEL to display t he selected parameter value;
• Press or to increas e o r decrease the value;
• Press SEL to temporarily confirm the new value and display its code;
• Repeat the procedure from the beginning "press or to show..."
To exit and save the new settings: Press PRG to confirm the new values and exit
the parameters modification procedure.
To exit without modifying any parameters: Do not press any button for at least
60 seconds (TIME OUT).
Special Function s:
The Special F unctions can be ac ti v ated by:
• Press and together for more tha n 5 seconds, a flashing “0” is displayed.
• Press or until the pass word is displayed (defaul t = “12”).
If password was changed, select the new password.
• Press SEL to confirm passw ord
A “0” is displayed and the Special Function mode is activated.
• Press or to select the function. The number of special functions is dynamic
and controller dependent. See list below. 0: Reset controller to factory settings (this action is possible only when digital
input is 0V i.e . open). 1: Displays the current TCP/IP address. 2: Assign temporary 192.168 .1.101 as TCP/IP address if EC3-P32 has different
Address.
• Press SEL to activate the function without leaving the special function mode.
• Press PRG to activate the function and leave the special function mode.
Installation in non explosive environment
value (higher)
Main parameters: (must be checked and modified if necessary)
Code Parameter description and choices Min Max
3 = R1234yf; 4 = R1270;
1 = enable auto reset 2 = enable man ual reset
u5
If uL enabled (auto or man ual)
3
30
+13°C for R290 +15°C for R32 +15°C for R1234ze +15°C for R1234yf +13°C for R1270 +15°C for R227
┌┘1
2 = Valve opening (%) 3 = Measured coil-out te mp e r a t ure (°C)
u4
uH
0 = disable,
0 = disable,
P4
1 = enable auto-reset,
P6
0 = disable,
P9
1 = enable auto-reset,
6
1: Alarm = inverse, pump down. = normal 2: Alarm = normal, pump down. = inverse
Emerson Climate Technologies GmbH www.emersonclimate.eu
Operating instruction
Factory setting
Field setting
b1
Battery error management, when battery is defective, see below
0 3 2
value
Alarm
display
Alarm relay
Valve
Reset poss ibility after recovery/replacement
0 - - Regulating
-
1
Ab - Regulating
-
2 Ab
Signalling
Fully close
Auto
3 Ab
(blinking)
Signalling
Fully close
Manual
When setting b1 to option 0 or 1, the user must ensure appropriate safety
to protect the system against damage caused by
a power failure.
Digital input status
Alarm condition
Pump down relay
24 V (ON)
NO
Activate
0 V (OFF)
NO
Deactivate when pressure drops below P7 and after elapsed time P8
0 V or 24 V
YES
Deactivate
!
Sec.
uu
u9
%
EC3-X3 BA.cdr
EC3-P32 Superheat Controller with TCP/IP
Code Parameter description and choices Min Max
precautions are in p la ce
After selecting the parameters the EC3-P32 is fully functional without connected PC or keypad/display unit ECD-002.
Control (valve) start-up behavior: (Parameter u u and u9)
EX4/5/6-…FLR ≤ 1.5 seconds EX7-…FLR ≤ 3.2 seconds
Pump down functio n: (if P6=1 and L2=1)
Possibilities of connecting EC3-X32 to a network or PC:
• A TCP/IP Controller Readme file is available on the www.emersonclimate.eu
website to provide detailed information about TCP/IP Ethernet connectivity. Please refer to this file if you need information beyond the contents of this instruction sheet.
• Connect t he EC3 -P32 using the optional ECC-Nxx cable assembly or a standard
CAT5 netw or k cabl e w ith RJ4 5 plug s as se mbl y to a ne two rk o r ro ute r th at enables the controller to receive a dynamic TCP/IP address or
• Connect the EC3-P32 to a computer using a crossover cab le plu gged di rect ly into
the Ethernet port. In this case, the TCP/IP address of the computer must be manually modified to be compatible with the default address of the controller. Refer to the TCP/IP Controller-Readme file for more details.
Setting and visualizing Data: WebPages (recommended method)
Make sure that digital input is 0 V (open), turn the power supply ON.
• Four parameters i.e. refrigerant ty pe (u0), pressure sensor type (uP), valve type (ut)
and control mode can be set only when digital input is open (0V) while the power supply is O N (24 V). This feature is for added safety to prevent accidental damage of compressors and other system components. All other parameters can be modified at any time.
• The EC3-P32 has a TCP/IP Ethernet communication interface enabling the
controller t o be di rec tly conn ect ed to a net work or a PC via th e stand ard Eth ern et port. The EC3-P32 controller has embedded WebPages to enable the user to visualize t he parameter lists using real text labels.
• To view W ebPages on the PC, a standard Web Browser like Internet Explorer ® or
Mozilla Firefox and JRE Java Runtime Environment is needed. JRE can be downloaded at no charge from the www.java.com website.
• Open the Internet browser program on the computer and, if EC3-P32 is connected
directly to PC with a crossover cable enter the default TCP/IP address of the controller (192.168.1.101) into the address line, or the dynamic address from the DHCP server from network/Router. R efer to the TCP/IP Controller-Readme file if a specific port is required.
• It is possible to identify the dynamic TCP/IP address assigned by DHCP of the
Router or network, refer to the TCP/IP Controller-Readme file.
Installation in non explosive environment
• After a few moments, the default monitoring page should be displayed. If the
browser d oes no t open t he defa ult pa ge or displa y activ e data , the us er sho uld c heck the Internet browser “Option” configuration. Refer to th e TCP/IP Controller- Readme file.
• The Monitoring and Alarm WebPages are read only and therefore it is not
necessary to enter a username or password. A username and password will be requested upon the initi al re quest to any of the o ther We bPage s. The factory defa ult settings are: Username: “EmersonID”, Password: “12”
• The default settings may be modified on the Display configuration page.
• Press the ta bs at the top of t he Mo nitor ing page with a le ft cl ick o f the mouse bu tton
to enter the respective Webpage.
• The paramet ers will b e visualized in real text together with the program code as
defined in the parameter list below.
• After the parameters have been modified, the complete list of settings can be saved
to the memory of the computer and used later to upload into another controll er. This can save a considerab le amount of ti me when using multiple controllers and over a period of time, a library can be created containing the parameter lists for equipment for different applications.