Emerson EC2-712 Operating Instructions Manual

EC2-712_65108_EN_R03.doc Replacement for Rev.:02 1 / 4 16.09.2009
EC2-712 Condenser Controller
Operating Instructions
GB
Note: This document contains short form instructions for experienced users. Use last column in List of Parameters to document your individual settings. More detailed information can be found in the User Manual.
The EC2-712 has been designed to control condensers with up to four fans. The purpose of the controller is to keep condensing pressure to a minimum by switching fans on or off.
The PT5 pressure transmitter (5) senses condensing pressure and feeds the signal into a condensing pressure dead band control loop. Condensing pressure is modulated by turning fan motors on and off. No change occurs as long as the condensing pressure remains within the dead band (P1) around the condensing pressure setpoint (P0). The controller will add/remove fan capacity when the condensing pressure goes beyond the limits of the condensing pressure dead band. For stable condenser operation, adjustable time delays for fan motor on and off are available. To avoid premature wear of individual fan motors, run time equalization is built into the controller.
remove capacity dead band add capacity
Condensing Pressure
A fast recovery procedure can be used to immediately switch off all fans when the condensing pressure falls below a set limit. Similarly an emergency routine can be activated automatically if the condensing pressure exceeds a definable limit.
!
Safety instructions:
Read installation instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
The product is intended for use by persons having the appropriate
knowledge and skills.
Ensure electrical ratings per technical data are not exceeded.
Disconnect all voltages from system before installation.
Keep temperatures within nominal limits.
Comply with local electrical regulations when wiring
Technical data:
Power supply 24VAC ±10%; 50/60 Hz; Class II Power consumption 4VA max. Communication TCP/IP Ethernet 10MBit/s Terminals Removable screw terminals
wire size 0.14 … 1.5 mm2 Temperature storage
operating
-20 … +65°C
0 … +60°C Pressure sensor input 24VDC, 4 … 20mA Fan output relays Inductive (AC15) 250V / 2A
Resistive (AC1) 250V / 6A; 12A total return current Digital inputs Volt free contacts 5V/0,1mA Humidity 0 … 80% rh. non condensing Protection class IP65 (front protection with gasket) Marking
Mounting
The EC2-712 can be mounted in panels with a 71 x 29 mm cutout. See dimensional drawing below for space requirements including rear connectors. Push controller into panel cutout.(1) Make sure that mounting clamps are flush with outside of controller housing Insert allen key into front panel holes and turn clockwise. Mounting clamp will turn and gradually move towards panel (2) Turn allen key until mounting clamp barely touches panel. Then move other mounting clamp to the same position (3) Tighten both sides very carefully until controller is secured. Do not over tighten as mounting clamps will break easily.
Electrical Installation
Refer to the electrical wiring diagram (right) for electrical connections. A copy of this diagram is labelled on the controller. Use connection wires/cables suitable for 90°C operation (EN 60730-1). EC2 analog inputs are for dedicated sensors only and should not be connected to any other devices. Volt free digital inputs should only be connected to serial control loops or relays with gold contacts. They should not be connected to any other devices
Important: Keep controller and sensor wiring well separated from mains wiring. Minimum recommended distance 30mm. Warning: Use a class II category transformer for 24VAC power supply (EN 60742). Do not ground the 24VAC lines. We recommend to use one transformer per EC2 controller and to use separate transformers for 3
rd
party controllers, to avoid possible interference or grounding problems in the power supply. Connecting any EC2 inputs to mains voltage will permanently damage the EC2.
Set-up and Parameter Modification Using the Keypad
For convenience, an infrared receiver for the optional IR remote control unit is build-in, enabling quick and easy modification of the system parameters when a computer interface is not available. Alternatively, the parameters can be accessed via the 4-button keypad. The configuration parameters are protected by a numerical password. The default password is “12”. To select the parameter configuration:
• Press the PRG button for more than 5 seconds
A flashing 0 is displayed
• Press
or until 12 is displayed; (password)
• Press SEL to confirm password
• The first modifiable parameter code is displayed (/1).
• To modify parameters see Parameters modification below.
EC2-712_65108_EN_R03.doc Replacement for Rev.:02 2 / 4 16.09.2009
EC2-712 Condenser Controller
Operating Instructions
GB
Parameter Modification: Procedure
Press or to show the code of the parameter that has to be changed;
Press SEL to display the selected parameter value;
Press
or to increase or decrease the value;
Press SEL to temporarily confirm the new value and display its code;
Repeat the procedure from the beginning "press
or to show..."
To exit and save the new settings:
Press PRG to confirm the new values and exit the parameters modification procedure.
To exit without modifying any parameter:
Do not press any button for at least 60 seconds (TIME OUT).
Press “ESC” on IR remote control.
Load Default Parameters:
The default parameter settings can be reloaded into the controller memory by using the special function described below.
Special Functions:
The Special Functions can be activated by:
Press
and together for more than 5 seconds, a flashing “0” is displayed.
Press
or until the password is displayed (default = 12). If password was
changed, select the new password.
Press SEL to confirm password, a “0” is displayed and the Special Function mode is activated.
Press
or to select the function. The number of special functions is dynamic
and controller dependent. See list below.
Press SEL to activate the function without leaving the special function mode.
Press PRG to activate the function and leave the special function mode.
Most of the Special Functions work in a toggle mode, the first call activates the function, and the second call deactivates the function. The indication of the function can only be displayed after exiting the special function mode.
0: Display test function
1: Displays the current TCP/IP address
2: Set the controller's TCP/IP address to 192.168.1.101 (default value). This
change is only temporary. A power down will reset the previous address
3: Resets all parameters to the factory default setting. The controller will
indicate “oF” during the reset and the valve will close.
Display of Data:
The data to be permanently shown on the display can be selected by the user (parameter /1). In case of an alarm, the alarm code is displayed alternately with the selected data. The user can inhibit the alarm code. It is possible to temporarily display these values. This is a useful feature when initially setting-up the system without the aid of the WebPages. Press the SEL button to scroll through all possible displayable data.. The display will show for one second the numerical identifier of the data (see /1 parameter) and then the selected data. After two minutes the display will return to the by parameter /1 selected data. This action is only valid when parameter H2 = 3.
Ethernet activity LED
(only active when service pin is pressed)
Display indicates condenser controller
Display indicates pressure in bar
Alarm condition
Fan 3 on
IR LED Fan 4 on
Fan 2 on Fan 1 on
Indications on The Display:
Condenser fan controller
State
Alarm in combination with alarm message and alarm LED
Condensing pressure or saturation temperature from condensing pressure
Parameter
Other display
Pressure: Pressure value in bar (g)
Alarm: Alarm condition
IR: IR communication enabled
Alarm Codes
hP High pressure alarm
Condensing pressure higher than the maximum limit
lP Low pressure alarm
Condensing pressure lower than the minimum limit
EP Error pressure
Condensing pressure sensor failure
Fr Fast recovery alarm
Fast recovery form low condensing pressure
hr High discharge pressure alarm
High condensing pressure recovery
E1 Feedback alarm 1
Digital input associated with fan 1 has changed into alarm state (safety chain)
E2 Feedback alarm 2
Digital input associated with fan 2 has changed into alarm state (safety chain)
E3 Feedback alarm 3
Digital input associated with fan 3 has changed into alarm state (safety chain)
E4 Feedback alarm 4
Digital input associated with fan 4 has changed into alarm state (safety chain)
n1 Service alarm 1
Fan 1 operating time higher than run limit
n2 Service alarm 2
Fan 2 operating time higher than run limit
n3 Service alarm 3
Fan 3 operating time higher than run limit
n4 Service alarm 4
Fan 4 operating time higher than run limit
Er Data error
Data send to the display is out of range
Messages
--- No data to display
The display will show an “---” at node start up and when no data is send to the
display.
In Reset to default values activated
The display will show an “In” when the factory default configuration data set
is initialized.
Id Wink request received
The display will show a flashing “Id” when the wink request was received.
The flashing “Id” will be shown on the display until the service button will be pressed, or a 30 min delay timer will expire or a second wink request is received. This function is action only when using SNMP protocol
OF Node is offline
The node is offline and no application is running. This is the result of a
network management command and will happen for example during node installation.
EC2-712_65108_EN_R03.doc Replacement for Rev.:02 3 / 4 16.09.2009
EC2-712 Condenser Controller
Operating Instructions
GB
Fan controller
/ DISPLAY PARAMETERS Min Max Unit Def Individ.
/1 Value to be shown on display 0 2 - 0
0 = Fan states 1 = condensing pressure (bar) 2 = condensing temperature (°C)
r SENSOR PARAMETERS
r0 Condensing pressure sensor
minimum value
-1.0 50 bar 0.0
r1 Condensing pressure sensor
maximum value
-1.0 50 bar 30
r2 Pressure offset for condensing
pressure
-1.0 1.0 bar 0.0
r3 Refrigerant type 0 5 - 4
0 = no temperature conversion;
1 = R22; 2 = R134a; 3 = R507; 4 = R404A; 5 = R407C
P SET-POINT PARAMETERS
P0 Pressure set-point (condensing) for
fan circuit
-1.0 50 bar 14.0
P1 Pressure band (dead band for dead
band control mode)
0.0 50 bar 4.0
P3 Fast recovery from low pressure -9.9 50.0 bar 9 P4 Enable set-point compensation
0 = disabled; 1 = enabled
0 1 - 0
P5 Maximum pressure compensation -3.0 3.0 bar -3.0 P6 Temperature at minimal shift value
(0)
-50.0 50 °C 30
P7 Temperature at maximal shift value
(Shift Max)
-50.0 50 °C 15.0
P8 High discharge pressure recovery. -9.9 50 bar 20
t TIME PARAMETERS
t1
(1)
Time delay before adding capacity 0 99 10sec 3
t2
(1)
Time delay before removing capacity 0 99 10sec 3
A ALARM PARAMETERS
A2 Minimum condensing pressure
alarm limit
-1.0 50 bar 10.0
A3 Maximum condensing pressure
alarm limit
-1.0 50 bar 27
A4
(1)
Delay time for minimum pressure
alarm limit
0 99 10sec 0
A5
(1)
Delay time for maximum pressure
alarm limit
0 99 10sec 0
A8
(1)
Fan serial alarm delay 0 99 10sec 0
A9
(2)
Fan run limit 0 99 10000hr 0
u STEP ENABLE PARAMETERS Min Max Unit Def Individ.
u0 Reset operating time
0 = do nothing 1 = reset operating time fan 1 2 = reset operating time fan 2 3 = reset operating time fan 3 4 = reset operating time fan 4 5 = reset operating time all fans
0 5 - 0
u1 Enable/disable fan 1 0 1 flag 1 u2 Enable/disable fan 2 0 1 flag 1 u3 Enable/disable fan 3 0 1 flag 1 u4 Enable/disable fan 4 0 1 flag 1
C
APPLICATION PARAMETERS
C1 Number of fans 1 4 - 4 C4 Fan 1 (0 = standard control loop
1 = fan 1 act as base load)
0 1 - 0
C5 Fan switch logic (Rotation) 0 1 flag 1
0 = FILO logic (First In, Last Out)
Capacity demand
: Adds first fan.
Capacity excess
: Removes last fan.
1 = Rotation enabled
Capacity demand
: Adds fan with lowest runtime out of available fans. Capacity excess
: Removes fan with highest runtime out of
available fans.
C6 Number of fans to switch on in case
of sensor failure
0 4 - 0
H OTHER PARAMETERS
H2 Keyboard and IR remote control 0 3 - 3
0 = all disabled
(Caution, access to controller only via network possible) 1 = Keyboard enabled 2 = IR remote control enabled
3 = Keyboard and IR remote control enabled H3 IR remote control access code 0 199 - 0 H5 Password 0 199 - 12
(1)
These values have a resolution of 10 sec, on the local display. Ex. A value 1 means 10 sec.
(2)
These values have a resolution of 10.000 hours, on the local display. Ex. A value 1 means 10.000 hours.
Note: Concerning the indicated parameters, it is recommended to check, before installing, if the factory value is suitable for the required use
EC2-712_65108_EN_R03.doc Replacement for Rev.:02 4 / 4 16.09.2009
EC2-712 Condenser Controller
Operating Instructions
GB
Visualising Data: WebPages
A TCP/IP Controller-Readme file is available on the www.emersonclimate.eu website to provide detailed information about TCP/IP Ethernet connectivity. Please refer to this file if you need information beyond the contents of this instruction sheet. The EC2-712 has a TCP/IP Ethernet communication interface enabling the controller to be directly connected to a PC or network via the standard Ethernet port. The EC2-712 controller has embedded WebPages to enable the user to easily visualise the parameter lists using real text labels. No special software or hardware is required. Connect the EC2-712 using the optional ECX-N60 cable assembly to a network or hub that enables the controller to receive a dynamic TCP/IP address. If a DHCP server is not available, the controller can be connected to a computer using a crossover cable plugged directly into the Ethernet port. In this case, the TCP/IP address of the computer must be manually modified to be compatible with the default address of the controller. Refer to the TCP/IP Controller-Readme file for more details. Open the Internet browser program on the computer and enter the default TCP/IP address of the controller into the address line of the Internet browser:
192.168.1.101 or the dynamic address from the DHCP server. The default communication port is 1030. Refer to the TCP/IP Controller-Readme file if a specific port is required After a few moments, the default monitoring page should be displayed. If the browser does not open the default page or display active data, the user should check the Internet browser “Option” configuration. Refer to the TCP/IP Controller-Readme file.
In addition, for those customers wishing to connect the controllers into a larger system, it is also possible to trap network variables using the SNMP protocol. Refer to the User Manual for further details. The Monitoring and Alarm WebPages are read only and therefore it is not necessary to enter a username or password. A username and password will be requested upon the initial request to any of the other WebPages. The factory default settings are :
Username: EmersonID Password: 12
The default settings may be modified in the Display configuration page. Press the tabs at the top of the Monitoring page with a left click of the mouse button to enter the respective Webpage. The parameters will be visualised in real text together with the program code as defined in the parameter list below. After the parameters have been modified, the complete list of settings can be saved to the memory of the computer and used later to upload into another controller. This can save a considerable amount of time when using multiple controllers and over a period of time, a library can be created containing the parameter lists for equipment for different applications. It is also possible to display live graphical data from the controller. In addition, a permanent 30 days log file containing the control temperature at 15 minutes intervals is stored in the non-volatile memory to be later transferred using FTP to the computer. The log file can be imported into a standard spreadsheet program such as Excel. Refer to the TCP/IP Controller-Readme file for a complete description of the features available for the TCP/IP series of controllers.
Emerson Electric GmbH & Co OHG is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information given herein is based on technical data and tests which EMERSON believes to be reliable and which are in compliance with technical
knowledge of today. It is intended only for use by persons having the appropriate technical knowledge and skills, at their own discretion and risk. Since conditions of use are outside of EMERSON’s control we cannot assume any liability for results obtained or damages occurred due to improper application. This document replaces all former versions
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - D-71332 Waiblingen - Germany - Phone .49-(0)7151-509-0 - Fax .49-(0)7151-509-200 www.emersonclimate.eu
Loading...