Operating instruction
24VAC ±10% ; 50/60Hz; Class I I
Removable screw terminals
0…80% r.h. non co ndensing
IP65 (front protection with gasket)
Pressure transmitter input
Resistive (AC1) 250V/8A; 12A total return current
The EC2-352 can be mounted in panels with a 71 x
29 mm cutout. See dimensional drawing below for
Make sure that mounting lugs are flush with outside
allen key into front panel holes and turn
clockwise. Mounting lugs will turn and gradually
Turn allen key until mounting lug barely touches
panel. Then move other mounting lug to the same
y until controller is
secured. Do not over ti ghten as mounting lugs will
break easi ly.
EC2-352 Display Case and Coldroom Controller
Note: This document contains short form instructions for experienced users.
Use last column in List of Parameters to document your individual settings.
More detailed information can be found in the User Manual.
Technical Data:
EC2 Series Controller
wire size 0.14 … 1.5 mm2
The EC2-352 is a dedicated refrigeration controller with superheat and a driver for
an Alco Controls El ect ric C ontrol Va lve E X2 . In ad di tion th e EC2-352 controls air
temperature and manages defrost and fan (s ).
A PT5 pressure transmitter (1) and an ECN-Pxx pipe temperature sensor (2)
measure saturated suction gas pressure and suction gas temperature at the
evaporator outlet and feed the signals into the superheat control loop. The
superheat controller output modulates the opening of the EX2 pulse width
modulated Elec trical Control Valve ( 6) thus optimizing the refrigerant mass flow
through the evaporator. The ECN-Sxx air temperature sensors (3) and (4) measure
air-in and out temperature of the evaporator and feed signals into the air
temperature thermostat. The ECN-Fxx fin sensor (5) is used for defrost
termination. The controller has 3 relay outputs to control the compressor (7),
defrost heater (9) and evaporator fan (8). Please consult the technical data (right)
for input and output ratings.
In case of power loss, due to the positive shut-off characteristics of the EX2
Electrical Control Valves, a liquid line solenoid valve is not needed to prevent
flooding of the compr essor.
storage
-20 … +65°C
Electrical Control Valve
Marking
Mounting:
space requirements including rear connectors.
Push controller in to panel cutout.(1)
of controller housing
Insert
move towards panel (2)
position (3)
Tighten both sides very carefull
Electrical Installation:
Refer to the electrical wiring diagram (below) for electrical connections. A copy of
this diagram is labeled on the controller. Use connection wires/ cables su itable for
90°C operation (EN 60730-1)
Safety instruc tions:
• Read installation instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
• The product is intended for use by persons having the appropriate
knowledge and skills.
• Ensure electrical ratings per technical data are not exceeded.
• D iscon nect all voltages from system bef o re ins ta llation.
• Keep temperatures wit h in n ominal limits.
• Comply with local electrical regulations when wiring
EC2 analog inputs are for dedicated sensors only and should not be connected to
any other devices. C onnecting any EC2 inpu ts to mains voltage will per manently
damage the EC2.
Important: Keep controller an d sensor wiring well separated from mains wiring.
Minimum re commended distance 30mm.
Warning: Use a class II category transformer for 24VAC power supply (EN
60742). Do not ground the 24VAC lines. We recommend to use one transformer
per EC2 controller an d to use separate transformers for 3
rd
party controllers, to
avoid possible interference or grounding problems in the power supply. Connecting
any EC2 inputs to main s voltage will permanently dam age the EC2.
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 15.06.2016 EC2-352_OI_EN_R07_864925.doc
Operating instruction
Ethernet activity LED
(only active when service pin is pressed)
EC2-352 Display Case and Coldroom Controller
Recommended Senso r Positi ons in Deta il:
(2) ECN-Pxx coil-out temp eratur e sensor: Posi tion di rectly aft er the evap orator on
the common suction line.
(3) ECN-Sxx air-in temperature sensor: Position in the middle of the cabinet as
high as possible.
(4) ECN-Sxx air-out temperature sensor: Position asymmetric closer to the
expansion valve as hi gh as possible.
(5) ECN-Fxx fin temperature sensor: Position on the evaporator, asymmetric closer
to the expansion va lve.
Recommendations for mounting the pipe sensor: Insure proper thermal contact by
using a metallic pipe clamp or temperature resistant plastic straps. Do not use
standard plastic tie wraps (as used for electrical wiring) as they may become loose
over time, which could result in faulty temperature measurements and poor
superheat control performance. It is recommended to insulate the pipe temperature
sensor with ARMAFLEX™ or equivalent. The recommended position of the pipe
sensors is between 9 and 3 o’clock as shown in the picture.
(1) PT5-07M suction pressure transmitter: Position on the common suction line
close to coil-out temperature sensor (2)
Both air tem perature s ensors shou ld be mount ed on spacers i n the air duct so that
there is airflow around.
Caution: The sensor cables can be extended if necessary. The connection must be
protected against water and dust.
The evaporator outlet temperature sensor should be mounted on the common
suction header of the eva porator.
A calibration correction can be made using the parameter u1 (see procedure
below).
Setup and Paramete r Modifi cation Usi ng the Keypad
For convenience, an infrared receiver for the optional IR remote control unit is
build-in, enab ling quick and eas y modification of th e system parameters wh en a
computer interface is not available.
Alternatively, the parameters can be accessed via the 4-button keypad. The
configuration parameters are protected by a numerical password. The default
password is “12”. To select the parameter configuration:
• Press the PRG button for more than 5 seconds, a flashing “0” is displayed
• Press
or until “12” is displayed (password)
• Press SEL to confirm password
The first mo d ifiable pa r ameter code is displayed (/1).
To modify parameters see Parameters mo dification below.
Parameter Modification: Procedure:
• Press
or to show the code of the parameter that has to be changed;
• Press SEL to display the selected parameter value;
• Press
or to increase or decr ease the value;
• Press SEL to temporarily confirm the new value and display its code;
• Repeat the procedure from the beginning "press
or to show..."
To exit and save the new settings :
• Press PRG to confirm the new values and exit the parameters modification
procedure.
To exit without modifying any parameter:
• Do not press any button for at least 60 seconds (TIME OUT).
• Press “ESC” on IR remote control.
Defrost Activation:
A defrost cyc le can be activated locally from the keypad:
• Press the
• Press
button for more than 5 sec onds, a flashing “0” is displaye d
or until “12” is displayed (password)
• Press SEL to confirm password
The defrost cycle is activated.
Special Function s:
The Special F unctions can be ac tivated by:
• Press
• Press
and together f or m or e than 5 seconds, a flashing “0” is displayed.
or until the password is displayed (default = 12). If password was
changed, s elect the new pa ssword.
• Press SEL to confirm password, a “0” is displayed and the Special Function
mode is activated.
• Press
or to select the function. The number of special functions is dynamic
and controller dependent. See list below.
• Press SEL to activate the function without leaving the special functi on mode.
• Press PRG to activate the fu nction and leave the speci al function m o de.
Most of the Special Functions work in a toggle mode, the first call activates the
function , and the second call deactivates the function.
The indication of the function can only be displayed after exiting the special
function mode.
• 0: Display test function
• 1: Clear alarm messages
• 2: Cleaning mode. The cleaning mode is effectively a manual defrost with the
option of the fans on/off. The cleaning mode should not be used in order to
isolate the applicatio n for maintenance purposes.
• 3: Fans only
• 4: Set the electronic control valve to 100% open
• 5: Displays the current TCP/IP address
• 6: Set the controller's TCP/IP address to 192.168.1.101 (default value). This
change is only temporary. A power down will reset the previous address.
• 7: Resets all parameters to the factory default setting. The controller will
indicate “oF” during the reset and the va lv e will close.
Display of Data:
The data to be permanently shown on the display can be selected by the user
(parameter /1). In case of an alarm, the alarm code is displayed alternately with the
selected data. The user can inhibit the alarm code.
It is possible to temporarily display these values. This is a useful feature when
initially setting-up the system without the aid of the WebPages. Press the SEL
button to scroll through all possible displayable data.. The display will show for
one second the numerical identifier of the data (see /1 parameter) and then the
selected data. After two minutes the display will return to the by parameter /1
selected data. This action is only valid when parameter H2 = 3.
Logical status of compressor relay
Logical status of fan relay
Logical status of defrost heater relay
Alarm condition
Am Borsigturm 31 I 13507 Berlin I Germany Date: 15.06.2016 EC2-352_OI_EN_R07_864925.doc
Emerson Climate Technologies GmbH www.emersonclimate.eu
DISPLAY PARAMETERS
0 = Thermostat control temperature with Temp. alignment /C
9 = Displays defrost status
Alarm suppression 0 = off, 1 = on
Temperature Unit 0 = °C, 1 = °F
Decimal point 0 = yes, 1 = no
0 = dF (= defrost mode); 1 = dF + defrost termination temp.
2 = dF + control temperature
Temperature alignment for /1=0
ALARM PARAMETERS
Mean factor alarm temperature
Alarm delay after defrost
0=absolu te temperatur es °C; 1= relative temperatures K to setpoint
THERMOSTAT PARAMETERS
Day/night control 0 = off, 1 = on
0 = off, no thermostat function, continues cooli ng air in sensor
sensor monitoring off. Temp. alarm s wil l be generated
Mean factor, day operat ion
Mean factor, night operation
DEFROST PARAMETERS
0 = natural defrost, defrost heater not activated
defrost termin a t io n us i ng nv iS t a r tU p v ia SN MP
0 = termination by tem perature,
3 = last, by time and temperature, no alarm
Defrost terminati on sensor
0 = Dedicated defrost sensor must be installed
1 = Air-out sensor used for defrost termination
0 = off, no pulsed defrost, heaters switched off at defrost termination
dH and switched on again at dH – dd
Defrost at startup 0 = no, 1 = yes
Compressor will run during pump down delay while valve is closed
sec 0 Valve is open during injection delay while compressor is not running
Pulsed defrost differential
Defrost termination temperature
Start up delay after synch
FAN PARAMETERS
1 = delayed by time Fd, error on temperature
4 = last, time and tempera t ure must come, no alarm
0 = on; 1 = off; 2 = delayed by F4; 3 = off, when door open
During defrost 0 = on, 1 = off
During cle aning 0 = off, 1 = on
COMPRESSOR PARAMETERS
Delay first start after power up
SUPERHEAT PARAMETERS
u0 Refrigerant 0 = R22 1 = R134a
5 = R410A 6 = R124 7 = R744
Pressure dr op = negativ e v alues
MOP control
0 = MOP of f, 1 = MOP on
ANALOG SENSOR PARAMETERS
Pressure sensor type sel ection
0 2 - 0 0 = PT5-07M; 1 = PT5-18M; 2 = PT5-30M
0 = all disabled (Caution, access to controller only via the TCP/IP Ethernet
Control setpoint with SEL key and manual defrost enabled.
List Of Parameters
EC2-352 Display Case and Coldroom Controller
1 = Air-in temperature °C
2 = Air-out temperature °C
3 = Alarm temp er ature °C
4 = Defrost termination temperature °C
5 = Coil-in temperature °C calculated from the pressure
6 = Coil-out temperature °C
7 = Calculated superheat °K
8 = Valve opening in %
Operating instruction
temperature dt or max. time dP whatever is selected
1 = on, pulsed defrost, dd and dH in use, heaters are switched off at
0 = off, 1 = on, 2 = on together with
2 = by temperature Ft, error on time
3 = first, whatever comes first time or temperature, no alarm
monitoring off, no t emp. alarms generated
1 = cooling, deadband control
cut in = set-point + difference
cut out = set-point
2 = cooling, modulating thermostat
cut in = set-p oint
cut out = set-point – difference /2
3 = heating, deadband control
2 = R507 3 = R404A 4 = R407C
cut in = set-point – difference
cut out = set-point
4 = on, external control using nvi Valve via SNMP. Air in and air out
Glide = positive values
1 = fixed superheat
pulsed defrost not possible
1 = forced defrost, defro st heater activated, pulsed
defrost possible
2 = forced defrost, defro st heater activated, pulsed defrost possible,
termination by time will generate an alarm
1 = termination by time ,
terminat ion by temperature will generate an ala r m
2 = first, what ever comes first time or temperature, no alarm
network possible)
1 = Keyboard enabled
2 = IR remote control enabled
3 = Keyboard and IR remote control; Temporary data display and manual
defrost enabled.
4 = Keyboard and IR remote control; Temporary data display disabled.
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 15.06.2016 EC2-352_OI_EN_R07_864925.doc