Emerson EC2 User Manual

Infrared Remote Control for EC2
Operating Instructions
The EC2 series of electronic controls can be easily and quickly programmed by means of the remote control unit using single keypad operations.
Until now, in fact, programming the multi-function instruments dedicated to the refrigeration sector was a very complex procedure. This is why EMERSON has enhanced the EC2 series with the remote control unit, which may be used not only to program the controller from a remote position but also to allows the user to set the main working parameters easily and fast. Today, modifying any parameter of an EC2 unit is as easy as controlling the volume of your TV. An interesting feature of the EC2 series is the possibility of selecting the access code (H3) of each controller so as to further simplify the use of the remote control unit. In fact, if your control panel includes several controllers, selecting a specific access code will allow you to modify only the parameters of the unit the code refers to, without interfering with the other controllers.
Changing the value of a parameter requires a special procedure (see 'ENABLE' button). Further safety is also provided by the 'H2' parameter that allows you to protect your system from unwilling or unauthorised access or modification of all set data.
REMOTE CONTROL UNIT: KEYPAD
On the basis of the function performed, the buttons on the remote control unit have been grouped as follows:
Buttons to activate / deactivate the use of the remote control unit
Pre-programmed buttons for the modification of the values of the main
parameters
Buttons for the remote control of the EC2 keypad
BUTTONS USED TO ACTIVATE/DEACTIVATE THE USE OF THE REMOTE CONTROL UNIT
ENABLE (blue zone) enables the use of the remote control unit; PRG (blue zone) 1) ends the programming procedure and
2) silences the buzzer when programming the IR
ESC (orange zone) interrupts the transmission without memorizing the
0 … 9 BUTTONS: allow you to select the access code. We advise
For the correct use of the buttons see 'How to use the remote control unit' next page.
The buttons shown on the left are the remote control unit ON/OFF buttons. They also allow you to memorize any new parameter value.
Note: A red LED indicator will be displayed on the front panel of the controller to acknowledge that a signal is being received from the IR handset.
memorizes the new values given to the parameters;
controller via remote control unit;
modifications;
you to give each controller a specific access code, especially when your control panel includes several IR instruments or when all of them are exposed to the beam of the remote control unit. In this way you will be able to modify exactly the parameters you want to change, without interfering with the data of the other controllers.
(See also 'How to use the remote control unit' and 'How to select the password').
GB
Technical specifications
Power supply 2 x 1.5V alkaline batteries (type UM-4 AAA,
Case plastic Dimensions 60x160x18mm Storage -25/+70°C Operating temperature 0/50°C Transmission Infrared Weight 80 g (without batteries)
BUTTONS USED TO MODIFY THE MAIN PARAMETERS (DIRECTLY ACCESSIBLE BUTTONS)
THE EC2 CONTROLLER
The green zone of the remote control unit reproduces exactly the keypad of the EC2 instruments and allows you to perform the same operations, as if you were directly acting on the keypad.
Here are the main functions of the buttons:
2) increases the displayed data
Service
Service (grey) sends the Neuron ID
2) decreases the displayed value
IEC R03) Batteries are supplied.
The most frequent parameters are directly indicated on the remote control unit. They are grouped in three zones:
temperature parameters (grey zone);
defrost parameters (white zone);
superheat parameters (grey zone).
For the correct use of the buttons see 'How to use the remote control unit' next page.
BUTTONS FOR THE REMOTE CONTROL OF
SEL displays the value of the
1) goes to the next parameter
1) goes to the previous parameter
selected parameter
(parameters selection phase)
(parameters selection phase)
EC2-IR__65046__R01.doc Rev.: 01 Replacement for Rev.:00 1 / 4 20.07.2007
Infrared Remote Control for EC2
Operating Instructions
HOW TO USE THE REMOTE CONTROL UNIT
Access without code
1) HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE CONTROL UNIT TRANSMISSION
press the 'ENABLE' button to operate the remote control unit;
the controller's led indicator above the digits flashes and the first
parameter - '/C' - is immediately displayed. If the display shows a code different from /C, it is necessary to introduce the access code (see point 5 below).
2) MODIFYING THE MAIN PARAMETERS
press either the + or - key relative to the parameter you want to
modify. The display will show the code of the selected parameter (see the codes of the parameters listed in the
Instruction Sheet of the instrument). Press the button again to display the value associated to the selected parameter and
press + to increase it;
press - to decrease it.
The section including directly accessible buttons also comprises 3 buttons
that activate/deactivate the function they represent:
DEFROSTING SECTION:
START activates/deactivates a manual defrosting cycle; evap.tmp displays the temperature value measured by the evaporator
Important: This function is always active. Consequently the
CONTINUOUS CYCLE SECTION:
C.cycle. activates a continuous cycle;
see point 4 below to exit the programming procedure.
3) HOW TO MODIFY THE PARAMETERS NOT DIRECTLY INDICATED BY A SPECIFIC BUTTON
The other parameters - not directly associated to a specific button on the remote control unit - can be easily modified as follows:
3.1 press either
4) HOW TO EXIT THE PROGRAMMING PROCEDURE
probe (if present) or the value measured by the second probe (Thermometer EC2-000).
temperature measured by the second probe will be always displayed without having to press the 'START' button or select the access code (see point 5 below).
perform the same operations described in point 1 above until the
first parameter '/C' appears on the display;
or until the display shows the parameter you
want to modify;
press SEL to display the value of the selected parameter;
press either or to increase/decrease its value;
press SEL to confirm temporarily the new value and display again
the code of the parameter;
to modify another parameter repeat the operations described
above starting from point 3.1;
see point 4 below to exit the programming procedure.
press PRG to exit and memorize all modifications;
press ESC to exit without memorizing the previous
modifications;
do not press any button for at least 60 seconds (TIME OUT).
In this way the previous modifications will be cancelled.
GB
Access with code
5) HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE CONTROL UNIT TRANSMISSION
press 'ENABLE' to operate the remote control unit;
all the controllers exposed to the beam of the remote control unit
will display their own access code;
select the access code of the controller whose parameter you
intend to modify using the numeric section on the remote control unit. Select the code correctly (if the code of the controller is 05, press 0 and 5).
the controller's led indicator above the digits flashes and,
simultaneously, the code of the first parameter '/C' appears on the display.
perform the same operations described in point 2) or 3)
above.
HOW TO SELECT THE ACCESS CODE
SETTING THE ACCESS CODE All EC2 controllers have no factory-set access codes. The User can
choose and set his own access codes by simply modifying the H3 parameter as follows:
press 'ENABLE' to operate the remote control unit;
the controller's led indicator above the digits flashes and the first
parameter ('/C) appears immediately.
press to display the H3 parameter;
press SEL to display its value (default 00);
press to select the desired value (from 01 to 199);
press SEL to confirm the new value and display again the H3
code;
press PRG to memorize the access code and exit the
procedure.
REMOVING THE CODE
repeat the operations described above and give the H3 parameter
the value 00 (H3=00). In this way you can program your controller/s without selecting the access code.
WHAT TO DO IF THE REMOTE CONTROL DOESN'T WORK
check that the remote control is equipped with batteries aligned
correctly;
replace spent or weak batteries;
check that there are no obstacles between controller and
transmitter;
periodically clean the transmitter and the controller with a soft cloth;
remember that the remote control's usable range is within 3 meters
away from the controller.
in case parameters are accessible but the user is not allowed to
change values, verify "H2" parameter (refer to the USER manual)
MODELS
There are several versions available, in different languages:
Language Type Order Nr.
English EC2- IRE 804 345 German EC2- IRD 804 346 French EC2- IRF 804 347 Spanish EC2- IRS 804 348 Italian EC2- IRI 804 349
Emerson Electric GmbH & Co.OHG is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information given herein is based on technical data and tests which ALCO CONTROLS believes to be reliable and which are in compliance with technical knowledge of today. It is intended only for use by persons having the
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - D-71332 Waiblingen - Germany - Phone .49-(0)7151-509-0 - Fax .49-(0)7151-509-200 www.eCopeland.com/alcoliterature.cfm
EC2-IR__65046__R01.doc Rev.: 01 Replacement for Rev.:00 2 / 4 20.07.2007
appropriate technical knowledge and skills, at their own discretion and risk. Since conditions of use are outside of ALCO'S control we cannot assume any liability for results obtained or damages occurred due to improper application.
This document replaces all former versions.
r
Infrarot Fernsteuerung für EC2
Bedienungsanleitung
Die elektronischen Temperaturregler der Serie EC2 können mit der Fern­steuerung schnell und bequem programmiert werden.
In der Vergangenheit war die Programmierung elektronischer Temperatur­regler eine sehr komplexe Prozedur. Aus diesem Grund bietet EMERSON zur EC2 Serie die passende Infrarot-Fernsteuerung an. Sie erlaubt die Programmierung der Kühlstellenregler in bequemer Lage, vereinfacht aber auch die Eingabe, weil die wichtigsten Parameter mit Funktionstasten direkt und schnell abrufbar sind. Parameteränderungen an EC2 sind
heutzutage so einfach wie die Lautstärkeregelung am Fernsehapparat. Eine wichtige Eigenschaft der EC2 Baureihe ist die
Möglichkeit, mit dem Parameter H3 einen Zugangscode vergeben zu können. Bei einer Schalttafel mit mehreren Reglern wählen Sie über den Zugangscode das gewünschte Gerät aus und modifizieren nur seine Werte, ohne andere Regler zu stören. Zusätzliche Sicherheit bietet Ihnen der Parameter ‘H2’, der versehentliche oder unerlaubte Eingabemöglichkeiten weitgehend einschränkt.
FERNSTEUERUNG : TASTATUR
Die Tasten der Fernsteuerung sind in folgende Funktionsblöcke eingeteilt:
Tasten, die den EC2 auf Empfang der Fernsteuerung schalten.
Vorprogrammierte Tasten für die Änderung der Hauptparameter.
Tasten, die den vier Bedienungsknöpfen des EC2 entsprechen.
TASTEN DIE DEN EC2 AUF EMPFANG DER FERNSTEUERUNG SCHALTEN
PRG
PRG (blauer Bereich) 1. Beendet die Parametereingabe und speichert
2. Schaltet den Alarmsummer aus. Vor einer
ESC (orangefarbiger Bereich) beendet die Parametereingabe ohne geänderte
0 … 9 Ziffernblock: für die Eingabe des Zugangscodes. Wenn sich
Weitere Informationen siehe Bedienungsanleitung nächste Seite.
ES C Parameter
Die links dargestellten Tasten starten oder beenden einen Programmierzyklus des EC2 von der Fernsteuerung und speichern die geänderten Werte ab.
Bemerkung: die blinkende LED am oberen Rand des Anzeigefeldes weist darauf hin, daß der EC2 von der Fernsteuerung angesprochen wird und auf weitere Eingaben wartet.
Parameter (blauer Bereich) Starte t die
Parametereingabe durch die Fernsteuerung
alle neueingegebenen Werte
Parametereingabe muß der Alarmsummer aus­geschaltet werden
Werte zu speichern
mehrere EC2 im Empfangsbereich der Fern­steuerung befinden, muß jedem EC2 ein separater Zugangscode vergeben werden (Parameter H3). Auf diese Weise kann jedes Gerät einzeln konfiguriert werden, ohne andere Geräte zu stören (siehe auch “Zugang mit Code” und “Eingabe des Zugangscodes” auf der nächsten Seite).
D
Technische Daten
Versorgungsspannung 2 x 1.5V Alkaline Batterien (Typ UM-4 AAA,
Gehäuse Kunststoff Abmessungen 60 x 160 x 18 mm Lagertemperatur -25 / +70°C Betriebstemperatur 0 / 50°C Signalübertragung Infrarot Gewicht 80 g (ohne Batterien)
VORPROGRAMMIERTE TASTEN FÜR DIE ÄNDERUNG DER HAUPTPARAMETER
Temperatur
Sollwert
Schaltdifferenz
Fühlerabgleich
Alarmtemp. hoch
Alarmtemp. tief
Alarmverzögerung
Abtauen
Start C° Kühle
Abtauintervall
C° Abtauende
Abtaudauer
Abtropfzeit
Verzög. Lüfter
Überh. Mode
Überh. Sollwert
TASTEN, DIE DEN VIER BEDIENUNGSKNÖPFEN DES EC2 ENTSPRECHEN
Die drei Tasten im grünen Bereich der Fernsteuerung sowie die graue Service-Taste entsprechen den vier blauen Tasten des EC2 und ermöglichen im Wesentlichen die gleichen Eingaben.
IEC R03) Das Gerät wird mit Batterien ausgeliefert.
Die wichtigsten Parameter können auf der Tastatur direkt angesprochen werden. Sie sind in drei Bereiche eingeteilt:
Temperaturparameter (grauer Bereich)
Abtauparameter (weißer Bereich)
Überhitzungs-Parameter
(grauer Bereich)
Weitere Informationen siehe Bedienungs- anleitung nächste Seite.
Die wichtigsten Funktionen der Tasten:
sel zeigt den Wert des gewählten
Parameters an
1. weiter zum nächsten Parameter
2. vergrößert den angezeigten Parameter um 1
1. zurück zum vorhergehenden Parameter
2. verkleinert den angezeigten
Parameter um 1
Service sendet die Neuron-ID
EC2-IR__65046__R01.doc Rev.: 01 Replacement for Rev.:00 3 / 4 20.07.2007
Infrarot Fernsteuerung für EC2
Bedienungsanleitung
BEDIENUNGSANLEITUNG DER FERNSTEUERUNG
Zugang ohne Code
1. EC2 FÜR DEN EMPFANG VON DER FERNSTEUERUNG AKTIVIEREN
Taste “Parameter” drücken
Die LED am oberen Rand des Anzeigefeldes blinkt, der erste
Parameter ‘/C’ wird angezeigt. Wird etwas anderes angezeigt, muß zuerst der Zugangscode (siehe unter 5.) eingegeben werden.
2. HAUPTPARAMETER ÄNDERN (Temperatur- und Abtauparameter, Dauerbetrieb)
+’ oder ‘-‘ Taste des betreffenden Parameters drücken. Auf der
Anzeige erscheint der Code des gewählten Parameters (siehe PARAMETERTABELLE der Bedienungsanleitung des EC2). Taste nochmal drücken um den aktuellen Wert des gewählten Parameters anzuzeigen.
+’ Taste erhöht den angezeigten Wert um 1
‘-‘ Taste vermindert den Wert um 1
Im Bereich der Hauptparameter befinden sich auch drei Tasten, mit denen Funktionen ein- oder ausgeschaltet werden können.
Bereich “ABTAUEN”: START schaltet einen manuellen Abtauzyklus EIN oder AUS °C Kühler zeigt die Temperatur am Abtaufühler an (wenn vorhanden)
Bereich “DAUERBETRIEB”: Dauerbetr. startet den Dauerbetrieb ein.
Ende der Parametereingabe siehe Punkt 4.
3. ALLE SONSTIGEN PARAMETER ÄNDERN
Alle anderen Parameter, ohne Funktionstasten auf der Fernbedienung, werden folgendermaßen geändert:
Parameter” drücken (siehe Punkt 1); der erste Parameter ‘/C
3.1 Mit den
sel” drücken; der aktuelle Parameterwert wird angezeigt.
Mit den
sel” drücken; der aktuelle Parameter wird temporär gespeichert;
Zur Änderung weiterer Parameter weiter mit Punkt 3.1.
Ende der Parametereingabe siehe Punkt 4.
4. ENDE DER PARAMETEREINGABE
PRG” speichert die geänderten Werte und beendet die
ESC” beendet die Parametereingabe ohne geänderte Werte zu
60 Sekunden lang keine Taste drücken (TIME OUT) beendet die
oder die Temperatur am Sensor 2 Bemerkung: Diese Funktion kann sofort aufgerufen werden.
Taste “Parameter” oder die Eingabe des Zugangscodes ist nicht erforderlich.
wird angezeigt.
oder Tasten gewünschten Parametercode aus-
wählen (siehe PARAMETERTABELLE in der Bedienungs- anleitung des EC2).
oder Tasten Wert vergrößern oder verkleinern.
der Parametercode wird wieder angezeigt.
Parametereingabe.
speichern.
Parametereingabe ohne geändertere Werte zu speichern.
D
Zugang mit Code
5. EC2 FÜR DEN EMPFANG VON DER FERNSTEUERUNG AKTIVIEREN
Taste “Parameter” drücken
Alle EC2 im Bereich der Fernsteuerung zeigen ihre Zugangscodes
an.
Zugangscode des gewünschten EC2 eingeben. Führende Null mit eingeben (z.B. Zugangscode = 05: Taste “0”, dann “5” drücken)
Die LED am oberen Rand des Anzeigefeldes blinkt, der erste Parameter ‘/C’ wird angezeigt. Alle nicht gewählten Regler zeigen wieder die Temperatur am Raumsensor an.
Weiter wie in den Punkten 2 bis 4 beschrieben.
ZUGANGSCODE EINSTELLEN
ZUGANGSCODE FESTSETZEN Der Zugangscode wird über den Parameter “H3” eingestellt:
Parameter” drücken um die Fernsteuerung zu aktivieren.
Die LED am oberen Rand des Anzeigefeldes blinkt, der erste
Parameter ‘/C’ wird angezeigt.
Taste mehrmals drücken bis H3 angezeigt wird.
SEL” drücken; aktueller Zugangscode wird angezeigt (Standard-
wert = 00)
Mit den oder
mit “SEL” wird der eingestellte Code fixiert; auf der Anzeige
erscheint wieder H3.
PRG” speichert den eingegebenen Code und beendet die
Parametereingabe.
ZUGANGSCODE LÖSCHEN
Vorgehensweise wie bei Zugangscode setzen, jedoch den
Parameter H3 auf 00 setzen. Der EC2 Regler zeigt bei der Aktivierung durch die Fernsteuerung keinen Zugangscode mehr an.
FEHLERBEHANDLUNG: FERNSTEUERUNG ARBEITET NICHT
Sind die Batterien korrekt eingelegt?
Tauschen Sie verbrauchte Batterien sofort aus.
Zwischen dem EC2 und der Fernbedienung dürfen sich keine
Gegenstände befinden.
Der Abstand zwischen EC2 und Fernbedienung darf nicht mehr
als 3 m betragen.
EC2 Regler und die Fernbedienung müssen sauber sein. Regel-
mäßig mit weichem Tuch reinigen.
Falls Parameter angezeigt aber nicht geändert werden können, ist
die Eingabe gesperrt. In diesem Fall muß der Parameter ‘H2’ geändert werden (siehe Bedienungsanleitung EC2).
MODELLÜBERSICHT
Die Fernbedienung ist in folgenden Sprachen verfügbar:
Sprache Typ Bestell Nr.
Englisch EC2- IRE 804 345 Deutsch EC2- IRD 804 346 Französisch EC2- IRF 804 347 Spanisch EC2- IRS 804 348 Italienisch EC2- IRI 804 349
Tasten gewünschten Code eingeben
Die in dieser Dokumentation enthaltenen Informationen basieren auf technischen Daten und Versuchen, die ALCO CONTROLS als zuverlässig ansieht und die den Regeln der heutigen Technik entsprechen. Da die genauen Umstände der Anwendung ALCO CONTROLS nicht bekannt sind, können wir für Ergebnisse bzw. Schäden, die auf unsachgemäße Anwendung zurückzuführen sind, keine Verantwortung übernehmen. Bei allen Leistungs-
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - D-71332 Waiblingen - Germany - Phone .49-(0)7151-509-0 - Fax .49-(0)7151-509-200 www.eCopeland.com/alcoliterature.cfm
EC2-IR__65046__R01.doc Rev.: 01 Replacement for Rev.:00 4 / 4 20.07.2007
und Maßangaben ist Irrtum ausdrücklich vorbehalten. Typen-, Modell-, Maß- und Konstruktionsänderungen können ohne Vorankündigung erfolgen.
Dieses Dokument ersetzt alle Vorgängerversionen. .
Loading...