Emerson DFA-0803, DFA-0802, DFA-1004, DFA-1206, DFA-2010 Instruction Manual

...
Instruction Manual D103810X012
January 2019
Enardo DFA Series
Enardo DFA Series Detonation Flame Arrestor (USCG/ATEX Approved)
Table of Contents
Introduction ..................................................................1
Specifications ..............................................................2
Principle of Operation .................................................. 4
Factors Affecting Flame Arrestor Performance ............4
Installation ...................................................................6
Maintenance ................................................................ 7
Recommended Spare Parts ...................................... 11
Parts Ordering ........................................................... 11
Figure 1. Typical Enardo DFA Series Detonation Flame Arrestor
WARNING
!
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion,
causing property damage and personal injury or death.
Fisher™ detonation ame arrestor must
be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies Tulsa, LLC instructions.
Failure to correct trouble could result in
a hazardous condition. Call a qualied
service person to service the unit. Installation, operation and maintenance
procedures performed by unqualied
person may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Only a
qualied person shall install or service the ame arrestor.
Introduction
Scope of the Manual
This Instruction Manual provides instructions for installation, startup, maintenance and parts ordering information for the Enardo DFA Series detonation
ame arrestor.
Product Description
The Enardo DFA Series detonation ame arrestor represents the best value in ame arrestor protection. The detonation ame arrestor provides protection against ame propagation in piping systems that are manifolded or have long run-up distances. These are typically used for extended pipe length or multiple pipe bend congurations to stop high pressures and ame velocities with detonations and overdriven detonations. It also stops conned and unconned, low and high pressure deagration. The design is unique in the ability to provide large ame channels which requires less frequent maintenance and greater ease in cleaning when service is required, translating to less down time. Enardo DFA Series detonation ame arrestors are bi-directional and proven to stop an ignited ammable
Outside North America Only
Enardo DFA Series
Specications
The Specications table lists the specications for the detonation ame arrestors. Some, or all, of the following information is stamped on the nameplate attached to the arrestor: model number, ange size and rating, maximum initial operating pressure, EN number (European Standard), EU type examination certicate, notied body number, gas group, date of manufacture and serial number; other identication and customer tag number are optional.
Available Constructions
See Table 1 and Figure 3
Temperature Rating of Gasket
Fiber Gaskets (standard): 450°F / 232°C Graphite/Metal (optional): 1600°F / 870°C
Gas Group
D (IIA), C (IIB3) and B(IIC)
Burning Rating
See Table 3
Flange Sizes and Rating
1 to 24 in. / 50 to 600 mm CL150
Housing Material
Carbon steel, 304 Stainless steel, 316 Stainless steel and Hastelloy
Housing Size
4 to 48 in. / 100 to 1200 mm
Element Material
304 Stainless steel, 316 Stainless steel
Maximum Experimental Safe Gap (MESG)
See Table 2
Maximum Initial Operating Pressure
(1)
See Table 3
and Hastelloy
Certication
(3)
EN 12874 ATEX Certied U.S. Coast Guard (USCG) Approved
Maximum Ambient Air Temperature
140°F / 60°C
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Hastelloy® housings and element material are not USCG approved.
3. Not all models are available with USCG and ATEX certications. Contact your local Sales Ofce for more information.
4. USCG and ATEX approval report(s) are available upon request.
5. Flow test data available upon request.
(1)
®(2)
®(2)
(4)(5)
(4)(5)
Table 1. Enardo DFA Series Detonation Flame Arrestor Available Construction (USCG/ATEX Approved)
(2)
MODEL
Enardo DFA-0401 1 25 4 100
Enardo DFA-0602
Enardo DFA-0802 2 50 8 200
Enardo DFA-0803 3 75 8 200
Enardo DFA-1004 4 100 10 250
Enardo DFA-1206 6 150 12 300
Enardo DFA-1608 8 200 16 400
Enardo DFA-2010 10 250 20 500
Enardo DFA-2412 12 300 24 600
Enardo DFA-2814 14 350 28 700
Enardo DFA-3016 16 400 30 750
Enardo DFA-3418 18 450 34 850
Enardo DFA-3620 20 500 36 900
Enardo DFA-4824
1. Not all models are available with USCG and ATEX certifications. Contact your local Sales Office for more information.
2. Includes eccentric construction.
3. Eccentric construction not USCG or ATEX certified.
®
Hastelloy
is a mark owned by Haynes International, Inc.
2
(3)
(3)
FLANGE SIZE HOUSING SIZE USCG ATEX
In. mm In. mm D C B IIA IIB3
2 50 6 150
24 600 48 1200
(1)
Outside North America Only
Figure 2. Cut-away view of Enardo DFA Series Detonation Flame Arrestor
/ - -
Detonation
Flame
Arrestor
Enardo DFA =
Concentric
Enardo DFAE =
Eccentric
Note: Not all models are available with USCG and ATEX certifications. Contact your local Sales Office for more information.
Housing
Size
04 = 4 in.
through
48 = 48 in.
Connection
Size
01 = 1 in.
through
24 = 24 in.
NEC
Gas
Group
D (IIA) C (IIB3) B (IIC)
Housing
Material
C = Carbon steel 4 = 304 SST 6 = 316 SST
H = Hastelloy
®(1)
Element Material
4 = 304 SST 6 = 316 SST
H = Hastelloy
Enardo DFA Series
Connection
F = Flat face
®(2)
R = Raised face
Type
flange
flange
Options
1 = Drain Plug 2 = Pressure Tap 3 = Temperature Probe Tap 4 = Miscellaneous
5 = Protective coating
6 = Special feature
Figure 3. Enardo DFA Series Detonation Flame Arrestor Available Constructions and Model Numbering System
Markings
Nameplate Information
A nameplate will be attached to the arrestor and will contain the following information:
Model Number: Ex. DFA 1206/D (see model
information above)
Flange Size and Rating: Ex. 6 in. CL150
Maximum Initial Operating Pressure, P
EN Number: Ex. ISO EN 16852 (if applicable) or
EN 12874
EU Type Examination Certificate (if applicable)
Notified Body Number (if applicable): Ex. 0518
Gas Group: Ex. IIA or IIB3, D, C
Date of Manufacture
Serial Number
Other Identification (Optional)
Customer Tag Number (Optional)
O
Outside North America Only
HAZARDOUS LOCATIONS
Figure 4. Product Identification and Marking for ATEX Units
®
is a mark owned by Haynes International, Inc.
Hastelloy
1. Hastelloy® housings are not USCG approved.
2. Hastelloy® element material is not USCG approved.
3
Enardo DFA Series
Table 2. Maximum Experimental Safe Gap (MESG)
NATIONAL ELECTRIC
CODE (NEC)
Group D Group IIA 0.035 >0.90 Propane
Group C Group IIB3 0.026 ≥0.65 Ethylene
Group B Group IIC 0.020 <0.50 Hydrogen
DETONATION
FLAME ARRESTOR
MODEL
Enardo DFA***/D 2 to 12 50 to 300 D (IIA) 22.7 1.56 Unstable Stabilized Type 1 (2 hours)
Enardo DFA***/D 14 to 20 350 to 500 D (IIA) 20.7 1.43 Unstable Stabilized Type 1 (2 hours)
Enardo DFA***/D 24 600 D (IIA) 16.0 1.1 Unstable N/A Type 2 (15 minutes)
Enardo DFAE***/D 2 to 20 50 to 500 D (IIA) 20.7 1.43 Unstable 1 minute Type 2 (15 minutes)
Enardo DFA***/C 2 to 20 50 to 500 C (IIB3) 20.7 1.43 Unstable Stabilized Type 1 (2 hours)
Enardo DFAE***/C 2 to 20 50 to 500 C (IIB3) 20.7 1.43 Unstable 1 minute Type 2 (15 minutes)
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION (IEC)
GROUP
Table 3. Detonation Arrestor Size Ranges and Rating, Maximum Initial Pressure and Burn Rating
DETONATION
FLAME ARRESTOR
SIZE RANGE
In. mm psia bar a ATEX (EN 12874) USCG
GAS GROUP
In. mm
MESG
MAXIMUM INITIAL
PRESSURE
DETONATION
RATING
TEST GAS LIST
BURN RATING
vapor mixture approaching from either direction that can be travelling at subsonic or supersonic velocities. The patented element offers maximum ow to pressure drop characteristics enhancing the value of the ame arrestor in any system.
The Enardo DFA Series is designed with anged
connections, the arrestor provides the option of the
removal of the ame cell element for easy cleaning and replacement without disconnecting the pipe connection.
Principle of Operation
Detonation ame arrestor prevents ame propagation as it enters the exposed side of the unit to the protected side by absorbing and dissipating heat using spiral wound crimped ribbon ame cells. This detonation ame arrestor utilizes an element assembly that dampens the high velocities and pressures associated with deagration and detonations while quenching the ame front. These cells allow maximum ow with maximum protection.
Detonation ame arrestor has the heat capacity and structural design to withstand all dynamic conditions of ame propagation and still stop the ame. Detonation ame arrestor is used when the ame can be in any of the detonation states.
Limits of Use for Detonation/Deagration
Flame Arrestors:
The following vapors are not within the scope of the products covered by this IOM:
- Explosive mixtures of vapors and gases, which tend to self-decompose (e.g. Acetylene) or which are chemically unstable
- Carbon Disulphide, due to its special properties;
- Mixtures other than gas-air or vapor-air mixtures
(e.g. higher oxygen-nitrogen ratio, chlorine as oxidant, etc.)
Minimum distance between flame arrestor connection and a restriction on the protected side is 10 L/D, but not less than 3 m.
• Arrestors shall only be installed into piping with a nominal size that is smaller than or equal to the nominal size of the flame arrestor connection.
Factors A󰀨ecting Flame
Arrestor Performance
Gas Group
WARNING
!
Methanol is classied as a Group-D (IIA)
vapor. However, our lab tests indicate that methanol exhibits characteristics unlike other Group-D (IIA) vapors under certain conditions. We therefore recommend that an arrestor rated for
Group-C (IIB3) vapors be specied for
methanol service.
Outside North America Only
4
Enardo DFA Series
The type of gas in the system determines its gas grouping and therefore predetermines the type of arrestor element required. The element must be designed to accommodate the specic gas group that could possibly ignite and propagate in the system. The more explosive gases require the ame cell to absorb the heat more quickly and efciently. The International
Electrotechnical Commission (IEC) groups gases
and vapors into Groups IIA through IIC categories
depending on a number of factors including the
Maximum Experimental Safe Gap (MESG) of the gas.
The National Electrical Code (NEC) groups gases into
A, B, C, D and G.M. categories.
Maximum Experimental Safe Gap (MESG)
WARNING
!
Verify that the detonation ame arrestor
being installed has the appropriate gas group rating for your process. This information is included in the nameplate attached to the element housing. Do not remove or alter this nameplate.
The Maximum Experimetal Safe Gap (MESG) is the measurement of the maximum gap between two equatorial anges on a metal sphere that prevents a ame from being transmitted from the sphere to the surrounding ammable mixture. MESG is dependent on gas composition. The stoichiometric mixture (the ideal air/fuel ratio for the most efcient combustion) is used to determine the minimum MESG for a given gas. See Table 2 for MESG information.
Turbulence in Piping System
Elbows, tees, pipe expansions and/or contractions, spiral wound vapor hoses, valves, orice plates and similar devices will contribute to turbulent ow. Turbulent ow enhances mixing of the combustible gases, greatly increasing the combustion intensity. This can result in increased ame speeds, higher ame temperatures and higher ame front pressures than would occur in normal ow conditions. The likelihood for developing detonations via Deagration to Detonation Transition (DDT) is enhanced by turbulent ow conditions.
Pipe Length
Extended lengths of pipe allow the ame to advance into more severe states of ame propagation such as high pressure deagration and detonations. Enardo Detonation Flame Arrestors are not limited by pipe length.
Flow Restrictions at Protected Side of the Arrestor; Pressure Piling
When ame propagation occurs, unburned and pressurized ammable vapors are forced through the detonation ame arrestor into the protected (cold) side piping. Restrictions close to the protected (cold)
side of the arrestor will restrict the passage of the
unburned ammable vapors causing pressurization to
occur inside the crimped passages of the detonation
ame arrestor element assembly. This pressurization can result in ame passage through the arrestor to the protected side during a ame propagation event.
WARNING
!
For maximum safety, avoid bends
and ow obstructions within 10 pipe
diameters but not less than 3 meters on the protected (cold) side of the
detonation ame arrestor.
Maximum Initial Operating Pressure and Fundamental Burning Velocity
The Maximum Initial Operating Pressure of the
detonation arrestor is indicated on the product
nameplate in absolute pressure units. This is the maximum allowable pressure that is allowed at the instant the owing velocity of the process vapors drops
to a value to or less than the fundamental burning
velocity of that particular ammable vapor stream. When the owing velocity drops to this level, any ame in the system can propagate back toward the fuel source. High pressure deagrations and detonations can occur more easily at higher system operating pressures than at pressures near atmospheric. Elevated pressures compress the system vapors and can cause the ame propagation to become more intense.
Outside North America Only
5
Enardo DFA Series
WARNING
!
If ame propagation occurs when the
system pressure is higher than the Maximum Initial Operating Pressure, the
ame arrestor could be ine󰀨ective in stopping the ame propagation.
Detonation State
Unstable (overdriven) detonations exist during a deagration to detonation transition (DDT) before a stable detonation is reached. An unstable detonation is the most severe condition where pressure and velocity are at maximum values. Detonation arrestors rated for unstable detonations may be placed in any location in a piping system, provided installation is in accordance with all sections of this manual.
Stabilized Burning
Refer to Table 3 and 6 for stabilized burning limitations
for the Detonation Flame Arrestors covered within the
scope of this document.
WARNING
!
Unlimited burning should not be allowed in any flame arrestor, regardless of its rating. In installations where there is a potential for stabilized burning, it is recommended that a temperature sensor, alarm and shutdown system be installed. Stabilized burning after ignition creates additional hazards in applications where there could be a continuous flow of the flammable mixture towards the unprotected side of the flame arrestor. An overheated Detonation Flame Arrestor will fail and allow flame propagation to move into the protected side of the process.
WARNING
!
Scorched, discolored paint or discolored metal on unprotected (hot) side end section and/or adjacent piping is possible indication of a stabilized flame inside the Detonation Flame Arrestor. This is an abnormal condition that must be corrected. Do not operate any system where indications of stabilized burning are observed. Effective corrective measures must be taken to correct this
condition. Any Detonation Flame Arrestor with indications of stabilized burning must be removed from service and thoroughly inspected by personnel with appropriate training and qualifications.
WARNING
!
Temperature sensors must be used with flame arrestors having 1 minute ATEX burn ratings. Never disconnect or remove these devices.
Installation
WARNING
!
Always make sure that the system is at atmospheric pressure and there is
no ignitable gas that could ash when
either installing or maintaining the unit.
Connection
Enardo DFA Series are normally provided with CL150 raised or at faced anges. Other anges such as CL300 are sometimes provided on special request. Make sure the companion anges installed in adjacent piping match the anges on the detonation ame arrestor.
Standard compressed ber gaskets that withstands temperatures of 450°F / 232°C or higher are normally used, but other materials of equal or higher temperature capability may be used at the customer’s discretion.
For proper torquing of the detonation arrestor to the process piping, please refer to Tables 6, 7 and 8.
Positioning
CAUTION
The detonation ame arrestor is tted with lugs for lifting the element
assembly during servicing operations. These lugs are not intended for lifting the entire unit during installation.
Damage to the detonation ame arrestor
may result from improper lifting. The unit should be lifted using appropriately rated Nylon (PA) straps rigged on the outside of the tension studs. Detonation
ame arrestors tted with temperature
sensors are directional dependant. The sensor must be located on the unprotected side of the arrestor.
Outside North America Only
6
Enardo DFA Series
The arrestor should be positioned such that the entire
arrestor is accessible for removal. Install the unit such that the ow arrow located on the unit points in the direction travelling with the product ow. Models that have drain plugs are designed for horizontal
installation and should be installed with the drain plugs
aligned at the bottom of the unit. Models that have
pressure taps are designed to allow pressure gauges
to be installed on both sides of the ame cell assembly to determine blockage. The pressure taps should be aligned at the top to allow easy viewing of the gauges. Units that are equipped with optional internal cleaning systems should be connected to a source of
cleaning media such as water, steam or other suitable
solvent. Observe recommended installation practice as detailed bends and/or ow obstruction section.
Flow Direction
The Enardo DFA Series is not bi-directional when
temperature sensors are required unless a sensor
is installed on both sides of the arrestor element
assembly. However, detonation arrestors are rated for stabilized burning and bi-directional. All arrestors covered in this manual can be installed either vertically or horizontally. Consideration should be given to non­symmetrical assemblies that include features such
as clean-out ports, temperature monitoring device or other options that might have a preferred installation
direction to suit the needs of the customer.
Piping Expansions and Reductions Adjacent to Detonation Flame Arrestor
WARNING
!
No instrument, tubing or other device whatsoever shall circumvent the
detonation ame arrestor in such a manner to allow a ame path to exist around the ame element of the arrestor.
When instrumentation is installed in such a manner that it creates a path
circumventing the ame element of an
arrestor, measures must be taken to
prevent passage of ame through the
instrumentation device and/or system. Instrumentation must be capable of withstanding the maximum and minimum pressures and temperatures to
which the device may be exposed and at a minimum be capable of withstanding
a hydrostatic pressure test of 350 psig /
24 bar.
The Enardo DFA Series detonation ame arrestor may be installed in any vapor control line that is smaller than or equal to the nominal pipe diameter of the arrestor’s connection anges. When it is necessary to
increase the diameter of the piping on the downstream
side (unprotected) of the detonation ame arrestor, a length of pipe at least 120 pipe diameters must be installed between the detonation ame arrestor and the expansion. A pipe diameter is considered as the inside diameter of pipe having a nominal size equal to the detonation ame arrestor’s connecting anges.
Maintenance
Detonation Flame Arrestor Element Assembly Cleaning
1. Keep the element openings clean to prevent
loss of efciency in absorbing heat. Remove the element assembly and clean the elements to
prevent the clogging of particulates and other
contaminants on the openings. Clean the element
with a suitable cleaning media (solvent, soap,
water or steam) then blow dry using compressed air. Be careful not to damage or dent the cell
openings as this would hamper the effectiveness
of the unit. Do not clean the arrestor elements by rodding with wire or other hard objects to remove blockages. Cleaning the elements with wire or other hard objects could damage the elements and seriously impair the arrestor’s performance. If the arrestor element cannot be cleaned satisfactorily, replace it.
2. For best cleaning results, use a high pressure
sprayer with spray wand (1500 psig to 3000 psig / 103 to 207 bar) to clean the entire element surface. Hold the spray nozzle perpendicular to the surface being cleaned to maximize spray media penetration into the element. Alternately spray each side of the element surface until clean.
3. The cleaning interval should be governed by the
amount and type of particulate in the system to which it is installed and must be determined by the user. To determine the maintenance interval, the user should check the element in the rst few months of operation to nd how quickly particulate accumulates in the cells.
Outside North America Only
7
Enardo DFA Series
4. Thoroughly clean the gasket sealing faces being careful not to damage the sealing surface. For reassembly, use new gaskets and place them in the machined recess of each interior ange on the two conical sections.
5. Replace the ame element assembly with a new assembly or properly cleaned and inspected existing unit.
6. Locate the ame cell assembly such that it seats onto the gaskets.
7. Replace all tensioning studs and tighten the outer nuts hand tight only.
8. Torque the bolts in sequence as shown in the Torquing Instruction section. Refer to Figure 5 and Tables 4 and 5.
Note
Cleaning of units equipped with a cleaning system may be accomplished in several ways including periodic cleaning using manually operated valves, by use of an automated cycle timing method or by having the cleaning operation initiated whenever the pressure loss across the arrestor element exceeds a predetermined value.
Inspecting Enardo DFA Element Assembly Following Flame Propagation Event
1. Inspect the outboard ame cells for damage immediately following a deagration, detonation and/or stabilized burn.
2. Carefully remove the element assembly from the arrestor.
3. Inspect the ame cells and the screens visually for any signs of corrosion or other damage and inspect the ame cells with a calibrated pin gauge to ensure maximum crimp size openings do not exceed the following values for their respective gas group. Use the following pin gauges as
no-go gauges:
• Model Enardo DFA(E)***/D Explosion
Group D (IIA) – 0.063 in. / 1.6 mm
• Model Enardo DFA(E)***/C Explosion
Group C (IIB3) – 0.039 in. / 1 mm
4. If any damage is noted or crimp openings exceed maximum size allowable as indicated by the entry of the no-go gauge, replace the element assembly.
Note
Under no circumstance shall any element assembly not provided by Emerson be used in this assembly. Failure to use the correct screens may lead to arrestor failure.
Element Assembly, Disassembly and Reassembly Instructions
WARNING
!
Isolate gas supply and bring system to atmospheric pressure to prevent
ignitable gas from ashing while
performing maintenance.
CAUTION
Element assemblies are heavy and require the use of adequate equipment and manpower to prevent injury.
Note
Element assemblies are provided with hinges and jacking nuts to facilitate
in-site cleaning of the ame cells or
removal of the element assembly without the need for removal of the end sections from the piping system. This method is intended for use with detonation arrestors installed in horizontal piping
congurations where adjacent piping is
fully supported such that no loads are applied to the detonation arrestor.
CAUTION
Removal and installation of the detonation arrestor and associated piping require the use of adequate equipment and manpower to prevent injury. Detonation arrestors installed in inclined or vertical orientations should be entirely removed from the system for servicing.
Outside North America Only
8
4
2
1
3
1 2
1
16
5
12
8
4
14
10
6
9
13
3
7
11
15
2
4
1
32
24
20
16
12
8
4
30
26
22
18
14
10
5
27
6
31
2
7
4
18
9
13
17
15
19
23
8
4 5
6
2
1
20
16
12
8
14
10
6
19
2
5
21
25
29
3
7
11
Enardo DFA Series
1
3
7
5
9
13
17
3
7
11
15
32
28
24
20
16
12
8
4
42
38
34
30
26
22
18
14
16
12
8
4
26
22
18
14
1
44
5
40
36
10
39
6
43
2
8
1
12
8
4
10
6
5
9
3
7
2
11
3
28281
5
24
20
10
6
9
13
17
21
25
3
7
11
15
19
23
27
2
6
9
13
17
21
25
29
33
37
41
3
7
11
15
19
23
27
31
35
Figure 5. Flange Pattern Tightening Sequence
Table 4. Tightening Steps and Torque Values for Internal Flanges
MODEL PATTERN
(2)
BOLT SIZE
1 2 3 4 5 6
Enardo DFA-300.5 1 5/8-11 Snug 20 / 27 40 / 54 60 / 81
Enardo DFA-0401 2 5/8-11 Snug 25 / 34 50 / 68 80 / 108
Enardo DFA-0602 2 3/4-10 Snug 40 / 54 85 / 115 125 / 169
Enardo DFA-0803 2 3/4-10 Snug 50 / 68 100 / 136 160 / 217
Enardo DFA-1004 3 7/8-9 Snug 50 / 68 90 / 122 145 / 197
Enardo DFA-1206 3 1-1/8-8 Snug 50 / 68 100 / 136 165 / 224
Enardo DFA-1608 4 1-1/4-8 Snug 50 / 68 120 / 163 190 / 258
Enardo DFA-2010 5 1-1/4-8 Snug 50 / 68 100 / 136 180 / 244 260 / 353
Enardo DFA-2412 5 1-1/2-8 Snug 75 / 102 150 / 203 280 / 380 400 / 542 500 / 678
Enardo DFA-2814 6 1-5/8-8 Snug 75 / 102 150 / 203 320 / 434 450 / 610 550 / 746
Enardo DFA-3016 6 1-3/4-8 Snug 80 / 108 200 / 271 350 / 475 500 / 678 700 / 949
Enardo DFA-3418 6 1-7/8-8 Snug 80 / 108 250 / 339 400 / 542 750 / 1017 1200 / 1627
Enardo DFA-3620 7 2-8 Snug 80 / 108 250 / 339 450 / 610 800 / 1085 1100 / 1491
Enardo DFA-4824 8 1-1/2-8 Snug 100 / 136 200 / 270 380 / 515 540 / 732 680 / 922
1. Using machine oil as lubricant. See Bolt Lubrication section on page 11 and torque correction factors for other lubricants in Table 5.
2. See Figure 5.
TIGHTENING STEPS AND TORQUE (FT-LBS / N•m)
(1)
Table 5. Torque Correction Factors for Common Lubricant
DESCRIPTION COEFFICIENT OF FRICTION MULTIPLY TORQUE VALUE IN TABLE 4 BY
Machine Oil f = 0.15 1.00
API SA2 Grease f = 0.12 0.80
Nickel-based Lubricant f = 0.11 0.73
Copper-based Lubricant f = 0.10 0.67
Heavy-Duty Lubricating Paste f = 0.06 0.40
Outside North America Only
9
Enardo DFA Series
Table 6. Torque Values for Raised Face Connection Flange (Steel Only)
NOMINAL PIPE
DIAMETER
1 4 0.50 12.70 9 12.20 1-1/4 4 0.50 12.70 13 17.63 1-1/2 4 0.50 12.70 18 24.40
2 4 0.63 16.00 35 47.45 2-1/2 4 0.63 16.00 41 55.59
3 4 0.63 16.00 60 81.35 3-1/2 8 0.63 16.00 34 46.10
4 8 0.63 16.00 43 58.30
6 8 0.75 19.05 80 108.5
8 8 0.75 19.05 109 147.8
10 12 0.88 22.4 101 136.9 12 12 0.88 22.4 135 183.0 14 12 1.00 25.0 168 227.8 16 16 1.00 25.0 159 215.6 18 16 1.13 28.7 244 330.8
20 20 1.13 28.7 214 290.2
Assumptions: Use of SAE grade 5 bolts or studs or stronger.
Notes: If lubricant is used on bolts, apply torque reduction factor listed in Lubricant Table.
24 24 1.25 31.8 253 343.0
No lubricant. Compressed mineral ber material or similar.
For best results hardened steel washers should be used on all cast ange bolted connections.
NUMBER OF BOLTS
Table 7. Torque Values for Flat Face Connection Flange (Steel or Aluminum)
NOMINAL PIPE DIAMETER NUMBER OF BOLTS
1 4 0.50 12.70 14 18.98 1-1/4 4 0.50 12.70 16 21.69 1-1/2 4 0.50 12.70 18 24.41
2 4 0.63 16.00 32 43.39 2-1/2 4 0.63 16.00 43 58.30
3 4 0.63 16.00 47 63.72 3-1/2 8 0.63 16.00 26 35.25
4 8 0.63 16.00 32 43.39
6 8 0.75 19.05 49 66.44
8 8 0.75 19.05 68 92.20
10 12 0.88 22.4 69 93.55 12 12 0.88 22.4 98 132.9 14 12 1.00 25.0 138 187.1 16 16 1.00 25.0 125 169.5 18 16 1.13 28.7 142 192.5
20 20 1.13 28.7 135 183.0
24 24 1.25 31.8 156 211.5
8 API 16 0.50 12.70 20 27.12
20 API 16 0.63 16.00 75 101.7
Assumptions: Use of SAE grade 5 bolts or studs or stronger.
Notes: Flat faced anges should never be mated to a raised face ange for installation.
24 API 20 0.63 16.00 75 101.7
No lubricant. Elastomer <70 Durometer Shore A.
If lubricant is used on bolts, apply torque reduction factor listed in Lubricant Table. For best results hardened steel washers should be used on all cast ange bolted connections.
BOLT DIAMETER TORQUE
In. mm Ft-lbs N•m
BOLT DIAMETER TORQUE
In. mm Ft-lbs N•m
Outside North America Only
10
Table 8. Torque Correction Factors for Common Lubricants Applied on Flanges
DESCRIPTION COEFFICIENT OF FRICTION MULTIPLY TORQUE VALUE IN TABLE 6 BY
Machine Oil f = 0.15 0.75
API SA2 Grease f = 0.12 0.60
Nickel-based Lubricant f = 0.11 0.55
Copper-based Lubricant f = 0.10 0.50
Heavy-Duty Lubricating Paste f = 0.06 0.30
Enardo DFA Series
1. Loosen all outermost nuts on tension studs.
2. Tighten the inside jacking nuts on the tension studs forcing the two conical sections apart. When the two ange faces have separated, remove the tension studs that do not have inside jacking nuts, so that the element assembly can be removed. The inside jacking nuts are installed on all tension studs that facilitate jacking the unit apart. The inside jacking nuts are not installed on tension studs that are taken out, for ease of removal.
3. Thoroughly clean the gasket sealing faces being careful not to damage the sealing surface. For reassembly, lightly grease one side of a new
gasket and place it in the machined recess of each
interior ange on the two conical sections.
4. Replace the ame element assembly with a new assembly or properly cleaned and inspected existing unit.
5. Loosen the jacking nuts on the tension rods until the ame cell assembly seats onto the gaskets.
6. Replace all tensioning studs and tighten the outer nuts hand tight only. Check to be sure that all the jacking nuts are completely loose and not making contact with the ange face.
7. Torque the bolts in sequence as shown in the Torquing Instruction section.
Torquing Instructions
CAUTION
Excessive or uneven torque can cause permanent damage to gaskets and housing.
Procedure
1. Use studs and nuts that are free of visible contamination and corrosion.
2. Apply lubricant to the threads of the stud protruding outboard of the interior anges and to the face of the hex nuts which will contact the ange.
3. Assemble the nuts to the studs such that the amount of thread extending outboard beyond the nut is approximately equal on both ends.
4. Tighten the nuts to the torque values shown in Table 4 following the designated sequence, repeating the sequence as shown. Flange pattern tightening sequences are shown in Figure 5.
Bolt Lubrication
Lubrication affects required torque of clean fasteners in good condition more than any other factor. In fact, 90% of applied torque goes to overcome friction while only 10% actually stretches the bolt. Table 4 assumes that only machine oil is used as a lubricant. Table 5
shows a list of several common lubricants and their
effect on torque required to stretch bolts to 50% of their yield strength. Most are available from local bearing distributors.
Recommended Spare Parts
For installations that require frequent maintenance
and minimum downtime, it is recommended that the
user purchase a spare element assembly and several spare element gaskets. The spare element assembly can be installed immediately and the dirty assembly can then be cleaned and stored as a spare for the next maintenance interval.
Outside North America Only
Tools/Supplies Required
• Hand operated conventional torque wrench or power assisted torque wrench appropriate for the specied torque.
• Socket wrenches of the proper size to t the hex nuts being tightened.
• Molydisulde based lubricating paste. Molykote® G-n or equivalent.
• Brush suitable for applying lubricant to the studs.
• Wiping rags necessary for the clean up of excessive lubricant.
Molykote® G-n is a mark owned by Dow Corning Corporation.
Note
Element gaskets must be replaced each time the cell assembly is loosened and removed to ensure a gas tight seal.
Parts Ordering
When corresponding with your local Sales Ofce about this equipment, always reference the equipment serial number stamped on the nameplate.
11
Enardo DFA Series
Webadmin.Regulators@emerson.com
Enardo.com
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA T +1 800 558 5853
+1 972 548 3574
Tulsa, OK 74146 USA T +1 918 662 6161
Europe Bologna 40013, Italy T +39 051 419 0611
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
Asia Pacic
Singapore 128461, Singapore T +65 6777 8211
Middle East and Africa
Dubai, United Arab Emirates T +971 4 811 8100
D103810X012 © 2015, 2019 Emerson Process Management Regulator Technologies, Inc. All rights reserved. 01/19. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher™ is a mark owned by Fisher Controls International LLC, a business of Emerson Automation Solutions.
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies Tulsa, LLC does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies Tulsa, LLC product remains solely with the purchaser.
Outside North America Only
Loading...