Description: A DC-DC Converter Module Mounting Shelf designed to mount in a 19” or 23” (nominal) relay
rack or equipment mounting rack (configured for 19” mounting unless otherwise specified).
The Converter Module Mounting Shelf, when equipped with up to three separately ordered
Converter Modules (Spec. No. 486800127), provides a DC-DC Converter System that
operates from +24VDC to provide -48VDC load power.
Spec. No.: 584622000
Model: DCS4830
Input Voltage: +24 Volts DC
Output Voltage: -48 Volts DC
Output Capacity:
Mounting Type: 19” or 23” Relay Rack or Equipment Mounting Rack
Mounting Depth: 12.18”
Mounting Height 3.5” (2RU)
Access: Front for Installation, Operation, and Maintenance
Color: Textured Gray
Environment:
-20°C to +65°C (-4°F to +149°F).
Page 1 of 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SYSTEM OVERVIEW.................................................................................................................................................1
TABLE OF CONTENTS.............................................................................................................................................2
DC Input (+24V)...............................................................................................................................................4
DC Output (-48V) .............................................................................................................................................5
External Control and Alarms............................................................................................................................6
DC Input (+24V)...............................................................................................................................................7
DC Output (-48V) .............................................................................................................................................8
External Control and Alarms............................................................................................................................9
1.4 Standard Features.....................................................................................................................................13
RELATED DOCUMENTATION................................................................................................................................16
Page 2 of 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG584622000
Spec. No. 584622000 (Model DCS4830) Issue AB, November 18, 2009
ORDERING INFORMATION
Converter Module Mounting Shelf (Model DCS4830)
Features
♦ The Converter Module Mounting Shelf accepts up to three (3) DC-DC Converter Modules.
♦ Two (2) blank panels are provided to cover unused Converter Module mounting positions.
♦ 19” rack mounting angles factory installed,
23” rack mounting angles supplied loose
(can be adjusted for a 5” or 6” front projection).
Ordering Notes
1) For each DC-DC Converter System, specify (1) Spec. No. 584622000 Converter Module Mounting Shelf.
2) Also order one (1) to three (3) Converter Modules per Converter Module Mounting Shelf (as specified
next).
Converter Modules (Model MHSA10B)
Ordering Notes
1) Order one (1) to three (3) Spec. No. 486800127 DC-DC Converter Module for each Converter Module
Mounting Shelf ordered.
Home
Page 3 of 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Refer also to the next section, Wiring Illustrations.
DC Input (+24V)
Features
♦ Front accessed 1/4-20 x 5/8” studs on 5/8” centers are provided for installation of customer provided DC
input leads terminated in 2-hole lugs.
Ordering Notes
1) DC input lugs must be ordered separately. For lug selection, refer to the following table. Refer also to
the following table for recommended DC input wire size. For additional lug information, refer to drawings
031110100 through 031110300.
2) Customer must provide 1/4-20 hardware to secure lugs to DC input busbars.
Recm 90°C
Wire Size
(AWG)
Recommended
Loop
(feet)
2
Vendor Part No.
1
Length
Crimp Lug
3
T & B 54206
4 47
Burndy YA4CL-2TC14
Emerson 245346800
T & B 54207
2 74
Burndy YA2CL-2TC14
Emerson 245346900
T & B --
1/0 118.9
Burndy YA25L-2TC14
Emerson 245391400
1
Wire sizes based on recommendations of the American National
Standards Institute (ANSI) approved National Fire Protection
Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 90°C conductor temperature, operating
in ambient of 30°C was used. For other operating ambient
temperatures, refer to the NEC. For operation in countries
where the NEC is not recognized, follow applicable codes.
2
Wire sizes listed are sufficient to restrict voltage drop to 1.0 volt
or less at rated full load output current for the loop lengths
shown. Loop length is the sum of the lengths of the positive and
negative leads.
3
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to
drawing 031110100 for lug crimping information.
Page 4 of 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG584622000
Spec. No. 584622000 (Model DCS4830) Issue AB, November 18, 2009
DC Output (-48V)
Features
♦ Two (2) 6-position 0A to 15A GMT Fuse Modules (for a total of 12 fuse positions) are provided for load
distribution.
♦ Load and load return leads are connected to a screw-type terminal block located on the front of each
GMT Fuse Module.
♦ Each GMT Fuse Module is equipped with six (6) dummy fuses and safety fuse covers.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere
fuses, for which load should not exceed 70% of device rating.
Terminal block wire size capacity is 24 to 14 AWG.
Each GMT Fuse Module has a 30A @ +65°C (+149°F) maximum capacity (combined load of both GMT Fuse
Modules must not exceed shelf rating of 30A). Maximum GMT fuse size is 15A. Fuses are to be loaded from
bottom of the shelf to top of the shelf with highest value in the lowest position.
Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Home
Ordering Notes
1) Order GMT fuses as required per the following table.
Ampere Rating P/N Fuse Color
18/100 GMT-A 248610301 --
1/4 248610200 Violet
1/2 248610300 Red
3/4 248610500 Brown
1-1/3 248610700 White
2 248610800 Orange
3 248610900 Blue
5 248611000 Green
7-1/2 248611300 Black-White
10 248611200 Red-White
15 248611500 Red-Blue
Replacement
Dummy Fuse
Replacement Safety
Fuse Cover
248872600 ---
102774 --
Page 5 of 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
♦ An external control and alarm circuit card is located behind the shelf’s top front access panel. This circuit
card provides three sets of Form C relay contacts for external alarms, plus an ESTOP input. A terminal
block is provided on the circuit card for customer connections.
Restrictions
Terminal block wire size capacity is 14 to 26 AWG.
Relay contacts are rated for 1A at 30VDC or 0.3A at 60VDC.
Relays are energized for normal operating conditions and de-energized for an a larm condition.
Ordering Notes
1) Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Page 6 of 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Loading...