DC Distribution Panel for NetSure™ Systems
Product Overview
Key Features
n Flexible mounting options —
allow for relay rack or wall
mounting
n Compact panel with front
access and top feed — fits in
23" relay rack with 6U height
n Field wiring provisions, 2 hole
lug terminations — to meet
code requirements
n Bullet-nose style breakers —
provide easy installation and
removal
n Isolated Form-C alarm output
n Return bar
The DC Distribution Panel for NetSure™
systems is designed to provide overcurrent protection or separation of a single
source into multiple feeds on the output
of a DC source. This panel can be populated with up to 20 breakers and can be
wall-mounted or mounted in a 23" relay
rack. The breaker panel accepts bullet-nose style breakers from 1A to 250A. The breakers
plug into one of (20) mounting positions. Each position has a localized return landing.
Application
The DC Distribution Panel is ideal for installations where overcurrent protection or separation of load circuits is required on the output of a rectifier or converter. This panel is
compatible with NetSure
™
DC power systems from Emerson or as standalone.
Additional Information
Reference spec. number 545277 for additional specification, engineering or installation
information.
LOAD
CONNECTIONS
LOAD RETURN
CONNECTIONS
INPUT
RETURN
1-1/4"
1-1/4"
1-1/4"
1-1/4"
INPUT
5/8"
5/8"
F1/
CB1
1/4-20 THREADED HOLE, 80 PLACES
LOAD CIRCUIT BREAKERS/FUSES
F20/
CB20
3/8-16 THREADED
HOLES, 12 PLACES
1"
1"
1087D-DistPanel / 0114
DC Distribution Panel for NetSure™ Systems
Technical Specifications
Input / Output
DC Voltage +24VDC, -24VDC, +48VDC, -48VDC
Input Current 600A*
Environmental
Operating Temp. -40°C to 40°C
Safety Compliance UL/cUL
General
Dimensions (H x W x D) 10.375" x 23.0" x 6.5" (263mm x 584mm x 165mm)
Approx. Weight (without breakers) 34 lbs. (15.5 Kg)
Input Connections (3) 3/8"D x 1" on center per polarity, right side of panel
Output Connections (20) 1/4"D x 5/8" on center, top access
* Not to exceed 80% of each circuit breaker rating. Steady state.
Bullet-Nose Type Circuit Breakers
Ampere Electrical/Mechanical Trip Electrical Trip Ampere Electrical/Mechanical Trip Electrical Trip
Rating (Black Handle) * (White Handle) ** Rating (Black Handle) * (White Handle) **
1 101596 102272 50 101606 102282
3 101597 102273 60 101607 102283
5 101598 102274 70 101608 102284
10 101599 102275 75 101609 102285
15 101600 102276 80 121995 121996
20 101601 102277 90 147555 147554
25 101602 102278 100 101610 102286
30 101603 102279 125 516838 516991
35 101604 102280 150 516839 516993
40 101605 102281 200 *** 121832 121831
45 121997 121998 250 *** 121836 121835
NOTE: Load should not exceed 80% of device rating; 125, 150 & 200 amp devices occupy two positions; 250 amp device occupies three positions.
* Provides an alarm during an electrical or manual trip condition.
** Provides an alarm during an electrical trip condition only.
*** Ratings greater than 150 amps REQUIRE an empty mounting position between the breaker and any other overcurrent protective device.
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2014.
Business-Critical Continuity™, Emerson Network Power™, the Emer son Net work Power l ogo, Emer son™ and Consi der it Solv ed are ser vice mark s and trade -
marks o f Emerson E lectri c Co. Energy Master
Power, Ener gy Systems, N orth Am erica, In c. Any other p roduct , brand, or co mpany names o r logos are t he proper ty of the r especti ve owner.
™
, eSure™, NetPerform™, NetReach™, NetSpan™, NetSu re™ and NetXtend™ are trad emarks of E merson Ne twork
While ev ery prec aution has b een taken to e nsure accur acy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disc laims all liab ility, for da mages resul ting from u se of this
information or for any errors or omissions. Specifications subject to
change without notice.
2
087D-DistPanel / 0114