Emerson Daniel 750, Daniel 711, Daniel 760, Daniel 710, Daniel 762, Daniel 770, Daniel 763, Daniel 766, Daniel 765, Daniel 767, Daniel 754, Daniel 710S750, Daniel 710P760, Daniel 788, Daniel 531, Daniel 535, Daniel 588, Daniel 536, Daniel 532, Daniel 578 Technical Manual
This brochure has been prepared to provide a thorough understanding of the principle of operation and typical applications of the
Daniel Control Valves.
The Daniel Valves operate on a basic hydraulic principle and are of the balanced-piston design, spring biased (loaded). The
valves are self contained, pilot operated for most applications (some exceptions) and use the line product as their power source.
The exceptions are valves with an external power operator that do not require line product to operate. (Ref. Models 531, 532, and
762 Series).
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Table of Contents
Section 1 - AN INTRODUCTION TO BASIC HYDRAULICS ..................................................................................3
Pressure Defined ...........................................................................................................................................................................5
Pressure Indicates Work Load ......................................................................................................................................................6
Force is Proportional to Pressure and Area ..................................................................................................................................6
Series Flow Paths .........................................................................................................................................................................7
Pressure Drop Through an Orifice ................................................................................................................................................8
Flow and Pressure Drop ...............................................................................................................................................................9
Fluid Seeks A Level .......................................................................................................................................................................9
Section 2 - PRESSURE VERSUS VARIABLE FORCE REQUIRED ....................................................................10
Section 3 - BASIC VALVE - NO CONTROLS .......................................................................................................12
Section 4 - 700 SERIES VALVES ..........................................................................................................................14
Typical 700 Series Valve .............................................................................................................................................................14
Model 710 (N.C.), Model 711 (N.O.) Solenoid on-off valves .......................................................................................................16
Model 750 Pressure Reducing Control Valve (N.O.) ..................................................................................................................18
Model 760 Back Pressure/761 Pressure Relief Control (N.C.) ...................................................................................................20
Model 770 Minimum Differential Pressure Control (N.C.) ...........................................................................................................22
Model 770 Differential Vapor Pressure Control (N.C.) ................................................................................................................25
Model 762, 763, 765, 766 and 767 Gas Loaded Pressure Relief/Back Pressure Control Valves ..............................................26
Model 754 Rate of Flow Control (N.O.).......................................................................................................................................28
Section 5 - MULTIPLE PILOTS (SERIES AND PARALLEL) ................................................................................30
Model 710S750 Combination Solenoid On-Off and Pressure Reducing Control in Series ........................................................30
Model 710P760 Combination Solenoid On-Off and Back Pressure Control in Parallel ..............................................................32
Section 6 - DIGITAL AND TWO-STAGE ELECTRIC SHUT-OFF VALVES ..........................................................34
Model 788 DVC Digital Control Electric Shut-off Valves .............................................................................................................34
Section 7 - POWER CYLINDER OPERATED VALVES ........................................................................................36
Model 531, 535, 578 and 588 (N.C.) Pressure to Open and Model 532 and 536 (N.O.) Pressure to Close .............................36
Model 588 (N.C.) Digital Control Electric Shut-off Valve .............................................................................................................38
Model 578 (N.C.) Two-stage Electric Shut-off Valve ...................................................................................................................40
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Section 1
AN INTRODUCTION TO BASIC HYDRAULICS
The study of hydraulics deals with the use and characteristics of liquids. Since the beginning of time, man has used fluids to ease
his burden. It is not hard to imagine a caveman floating down a river, astride a log with his wife, and towing his children and other
belongings aboard a second log with a rope made of twisted vines.
Earliest recorded history shows that devices such as pumps and water wheels were known in very ancient times. It was not,
however, until the 17th century that the branch of hydraulics with which we are to be concerned first came into use. Based upon a
principle discovered by the French scientist Pascal, it relates to the use of confined fluids in transmitting power, multiplying force
and modifying motions.
Pascal’s Law simply stated, says this:
Pressure applied on a confined fluid is transmitted undiminished in all directions, and acts with equal force on equal areas, and at
right angles to them.
This precept explains why a full glass bottle will break if a stopper is forced into the already full chamber. The liquid is practically
non-compressible and transmits the force applied at the stopper throughout the container (Figure 1-1). The result is an
exceedingly higher force on a larger area than the stopper. Thus, it is possible to break out the bottom by pushing on the stopper
with a moderate force.
Perhaps it was the very simplicity of Pascal’s Law that prevented men from realizing its tremendous potential for some two
centuries. Then, in the early stages of the industrial revolution, a British mechanic named Joseph Bramah utilized Pascal’s
discovery in developing a hydraulic press.
PRESSURE (FORCE PER UNIT AREA) IS TRANSMITTED THROUGHOUT A CONFINED FLUID
The bottle is lled with
a liquid, which is not
compressible.
A 10 pound force applied to a
stopper with a surface area of
one square in...
Results in 10 pounds of force
on every square in (pressure)
of the container wall.
If the bottom has an area of
20 square inches and each
square inch is pushed on by
10 pounds of force, the entire
bottom receives a 200 pound
push.
Figure 1-1
3
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Figure 1-2 shows how Bramah applied Pascal’s principle to the hydraulic press. The applied force is the same as on the stopper
in Figure 1-1, and the small piston has the same one square inch area. The larger piston, has an area of 10 square inches. The
large piston is pushed on with 10 pounds of force per square inch, so that it can support a total weight or force of 100 pounds.
It can easily be seen that the forces or weights which will balance with this apparatus are proportionate to the piston areas.
Thus, if the output piston area is 200 square inches, the output force will be 2000 pounds, (assuming the same 10 pounds of
push on each square inch). This is the operating principle of the hydraulic jack, as well as the hydraulic press.
It is interesting to note the similarity between this simple press and a mechanical lever (Figure 1-2). As Pascal had previously
stated, force is to force, as distance is to distance.
HYDRAULIC LEVERAGE
10 pounds here ...
10 lbs.
If this lever is 10 times as long as ...
An input force of 10 pounds on
a one aquare inch piston ...
... develops a pressure of 10 pounds
per square inch (psi) throughout the container.
10 lbs.
1 sq. in.
will balance 100 pounds here.
100 lbs.
... this arm.
This pressure will support a
100 pound weight if this is a
10 square inch piston.
100 lbs.
10 sq. in.
INPUT
The forces are proportional to the piston area.
10 lbs.
1 sq. in.
100 lbs.
=
10 sq. in.
Figure 1-2
4
OUTPUT
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Pressure Defined:
In order to determine the total force exerted on a surface, it is necessary to know the pressure or force on a unit of area. We
usually express this pressure in “Pounds per Square Inch”, abbreviated psi. Knowing the pressure and the number of square
inches of area on which it is being exerted, one can readily determine the total force.
(Force in Pounds = Pressure in psi x Area in Sq. In.)
How Pressure is Created:
Pressure results whenever the flow of a fluid is resisted. The resistance may come from (1) a load on an actuator, (2) a control
valve or, (3) a restriction (or orifice) in piping. See Figure 1-3.
PRESSURE CAUSED BY RESTRICTION AND LIMITED BY PRESSURE CONTROL VALVE.
When the manual valve is
wide open, all flow is
unrestricted.
5 gpm
PUMP
PUMP
PUMP
There is no pressure in this condition.
0 psi
As flow is restricted by
closing the manual valve...
... pressure builds up.
25 psi
With the manual valve
closed...
... the pressure gauge reads the
maximum pressure available.
50 psi
Figure 1-3
5
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Pressure Indicates Work Load:
Figure 1-4 illustrates how pressure is generated by resistance of a load. It was noted that the pressure equals the force of the
load divided by the piston area.
We can express this relationship by the general formula:
In this relationship:
P is pressure in psi
F is force in pounds
A is area in square inches
From this we can see that an increase or decrease in the load will result in a like increase or decrease in the operating pressure. In
other words - pressure is proportional to the load, and pressure gauge reading indicates the workload, in psi, at any given moment.
Pressure gauge readings normally ignore atmospheric pressure. That is, a standard gauge reads zero at atmospheric pressure.
An absolute gauge reads 14.7 psi at sea level atmospheric pressure. Absolute pressure is usually designated “psia”.
Force is Proportional to Pressure and Area:
When a hydraulic cylinder is used to clamp or press, its output force can be computed as follows: F = P x A
Again:
P is pressure in psi
F is force in pounds
A is area in square inches
PUMP
NO LEAK IN SYSTEM
500 lbs.
50 psi
10 sq. in.
The force is 500 pounds and ...
The area is 10 sq. in.
The pressure equals force divided by
area equals 500 pounds divided by
10 sq. in. equals 50 psi.
Figure 1-4
6
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Parallel Flow Paths
An inherent characteristic of liquids is that they will always take the path of least resistance. Thus, when two parallel flow paths
offer different resistances, the pressure will increase only to the amount required to take the easier path.
In Figure 1-5 the oil has three possible flow paths. Since valve A opens at 10 psi, the oil will go that way and pressure will build
up to only 10 psi. Should flow be blocked beyond A, pressure would build up to 20 psi, then oil would flow through B. There
would be no flow through C unless the path through valve B should also become blocked.
Series Flow Paths
When resistances to flow are connected in a series, the pressures add up. Figure 1-6 shows the same valves as Figure 1-5,
but connected in a series. Pressure gauges placed in the lines indicate the pressure normally required to open each valve
plus back pressure from the valves down-stream. The pressure at the pump is the sum of the pressures required to open the
individual valves.
The oil can choose 3 paths.
It first chooses path "A" because
only 10 psi is required . A pressure
gauge at the pump will read 10 psi.
PUMP
PARALLEL FLOW PATHS
A
10 psi opens valve A
B
20 psi opens valve B
C
30 psi opens valve C
Figure 1-5
7
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
SERIES RESISTANCES ADD PRESSURE
There is no resistance to
flow here, so ...
At this point, flow is resisted
by a spring equivalent to
10 psi.
Here, flow is resisted by a
20 psi spring PLUS a 10 psi
back pressure from valve A.
A
10 psi
B
20 psi
A
B
P4
0 psi
P3
10 psi
P2
30 psi
P4 gauge reads zero.
Therefore, P3 gauge
reads 10 psi.
The two pressures are added and
P2 gauge reads 30 psi
With a 30 psi back pressure
here...
C
30 psi
PUMP
C
P1
60 psi
And a 30 psi spring here...
There is 60 psi pressure
at the pump.
Figure 1-6
Pressure Drop Through an Orifice
An orifice is a restricted passage in a hydraulic line or component, used to control flow or create a pressure difference (pressure drop).
In order for oil to flow through an orifice, there must be a pressure difference or pressure drop through the orifice. The term
“drop” comes from the fact that the lower pressure is always downstream. Conversely, if there is no flow, there is no difference in
pressure across the orifice.
An increase in pressure drop across an orifice will always be accompanied by an increase in flow.
If the flow is blocked beyond an orifice, the pressure will immediately equalize on both sides of the orifice in accordance with
Pascal’s Law. This principle is essential to the operation of many control valves.
Note: A control valve is a variable orifice.
8
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Flow and Pressure Drop
Whenever a liquid is flowing, there must be a condition of unbalanced force to cause motion. Therefore, when a fluid flows
through a constant-diameter pipe, the pressure will always be slightly lower downstream than to any point upstream. The
difference in pressure or pressure drop is required to overcome friction in the line.
Figure 1-7 illustrates pressure drop due to friction. The succeeding pressure drops, from maximum pressure to zero pressure, are
shown as differences in head in succeeding vertical pipes.
Fluid Seeks A Level
When there is no pressure difference on a liquid (no flow) it is distributed equally in the pipes as shown in Figure 1-7. If the
pressure changes the liquid levels rise until the weight is sufficient to make up the difference in pressure. The difference in height
(head) in the case of oil is one foot per 0.4 psi. Thus, it can be seen that additional pressure difference will be required to cause
a liquid to flow up a pipe or to lift the fluid, since the force due to the weight of the liquid must be overcome. In circuit design,
naturally, the pressure required to move the oil mass and to overcome friction must be added to the pressure needed to move the
load. In most applications, good design minimizes these pressure “drops” to the point where they become almost negligible.
Pressure is maximum here
because of the head height
of liquid.
FRICTION IN PIPES RESULTS IN A PRESSURE DROP
The lower level
of liquid in these pipes is
a measure of reduced
pressure at points
downstream from the
source.
(P1 minus P5) equals
maximum differential
pressure available.
P1
Friction in the pipe drops pressure
from maximum to zero.
P2
P3
P4
Figure 1-7
9
P5
Pressure is zero here as the liquid
flows out unrestricted.
Technical Guide
0 10 20 30 40 50 60 70 80 90 100
PERCENT STROKE
SPRING FORCE (lbs.)
DAN-LIQ-TG-44-rev0813
November 2013
Section 2
PRESSURE VERSUS VARIABLE FORCE REQUIRED
Pressure, force, and area were discussed in the Pressure Defined section. It was stated that pressure indicates work load, and
force is proportional to pressure and area.
The principle described for Figures 2-2 and 2-3 is the same for Figure 1-4, with the exception of the work load. It is, in this
instance, a variable force (linear spring). The spring exerts 100 pounds of force or resistance in the full position of the power
cylinder (Figure 2-2) and 50 pounds in the down position (Figure 2-3). The spring is linear in force; therefore, if the power cylinder
were at 50% of stroke, the spring force would be 75 pounds (Figure 2-1).
Also, if the spring force were divided by the area in square inches of power cylinder piston, the answer would be the equivalent
force of the spring in psi. Therefore, the force of the spring can be rated as 5 to 10 psi resistance.
Figure 2-1
10
Technical Guide
Spring force is 100
pounds (compressed).
The pump pressure required equals
the spring force divided by area, equals
100 pounds divided by 10 sq. in equals
10 psi for full stroke.
The area is 10 sq. in.
10 psi
PUMP
0 psi
10 sq. in.
DAN-LIQ-TG-44-rev0813
November 2013
Spring force is 50 pounds.
0 psi
5 psi
PUMP
Pump pressure is 5 psi.
Available force equals:
Area x Pressure equals 10 sq.
in. x 5 psi equals 50 pounds. The spring
force is equal to the pressure and area.
The power cylinder will not move.
Figure 2-2
10 sq. in.
Figure 2-3
The area is 10 sq. in.
To start the cylinder moving,
minimum pump pressure
required must be more than
5 psi.
11
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Section 3
BASIC VALVE - NO CONTROLS
The Introduction to Basic Hydraulics covered the subjects of pressure, force and area and how the three are combined to perform
various functions. Note the similarity between the spring loaded hydraulic cylinder in Figures 2-2 and 2-3 on Page 11, and the
basic control valve in Figures 3-1, 3-2, and 3-3. P1 is similar to pump pressure, P2 is similar to downstream pressure, and P3 is
similar to spring force. The Basic Control Valve uses the principles of hydraulics as described in Section 1, Introduction to Basic
Hydraulics, and performs the various control functions illustrated and described in the following pages.
The valve as shown serves no useful purpose because it does not have a pilot control loop to regulate the pressure at (P3).
The purpose of these illustrations is to show the effects and force of the main valve spring, which is the total control force of the
basic valve. All main valve springs are linear in force and are rated in psi.
The basic valve operates on a balanced piston principle and is spring biased (loaded). Since the area of the nose (P1 side) of the
main valve piston is exactly the same as the spring side (P3 side), it can be seen that the main valve spring now becomes the
differential force necessary to control the position of the main valve piston.
Three (3) different springs are applicable and selection is based on the intended service. These springs are:
Light - 4 to 6 psi force
Medium - 5 to 10 psi force
Heavy - 10 to 30 psi force
The first number given is seated force and the last is full open force.
CLOSED POSITION - The valve is closed because (P1) is less than the spring force in the seated
position or; (P2) is greater than (P1).
= Inlet Pressure
= Outlet Pressure
= Spring Force
Figure 3-1
12
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
50% OPEN - The pressure differential across the valve (P1 minus P2) is equal to the spring force in
the 50% open position.
P3
P1
P2
= Inlet Pressure
= Outlet Pressure
= Spring Force
Figure 3-2
FULLY OPEN - The pressure differential across the valve (P1 minus P2) is equal to the spring force
in the fully open position.
P3
= Inlet Pressure
= Outlet Pressure
= Spring Force
P1
P2
Figure 3-3
13
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Section 4
700 SERIES VALVES
Typical 700 Series Valve
This is the starting point for unlimited control applications. The basic valve now incorporates a pilot control loop, which is
mandatory for it to function.
The basic valve operates on a balanced piston principle, spring biased (loaded). The term balanced piston means that the
exposed area on the spring side (P3) of the piston and the bottom side (P1) are equal in area. The spring is the differential force
that closes the piston when (P1) and (P3) pressures are equal.
By design, the valve serves as a check valve because there can be no reverse flow. It is possible, in some applications, to reverse
flow through the pilot control loop, but this can be eliminated by installing a check valve in the X-port. To open the valve, the
pressure against the bottom of the piston (P1) must exceed the pressure on the spring side of the piston (P3) plus spring force.
CLOSED POSITION - Pilot is closed. Y-port (P3) to Z-port (P2) is closed. X-port (P1) and Y-port (P3)
pressures are balanced. The differential force created by the main valve spring, closes the piston
and keeps it seated.
Therefore, total pressure equals 40 psi @ (P1) and 45 psi @ (P3) or (P3 minus P1) - 5 psid.
The needle valve incorporated with the strainer controls the speed of the closure by controlling the
flow through the X-port.
Needle Valve/Strainer
P3
Y
Manual Pilot Control
X
P1
Z
P2
= Inlet Pressure
= Outlet Pressure
Figure 4-1
14
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
FULLY OPEN - NO CONTROL - Pilot is fully open. Y-port (P3) is open to Z-port (P2). The pressure
on the bottom of the piston (P1) is greater than the pressure at (P3) plus spring force. The valve
will not open unless the pressure drop across the valve (P1 minus P2) is slightly greater than
the force applied by the main valve spring. In a non-control state, the main valve is opened in a
percentage directly proportional to (P1 minus P2).
Manual Pilot Control Needle Valve/Strainer
P3
Y
X
P1
= Inlet Pressure
= Outlet Pressure
Figure 4-2
OPEN CONTROLLED POSITION - Pilot is partially open. Y-port (P3) is open to Z-port (P2) but
is being restricted by the control pilot. The pilot control is a variable orifice that regulates the
pressure at Y-port (P3) by controlling the flow through Z-port. By increasing or decreasing the
Y-port pressure (P3) causes the piston to change positions.
Z
P2
Manual Pilot Control Needle Valve/Strainer
= Inlet Pressure
= Outlet Pressure
= Controlled Pressure
P1
X
P3
Figure 4-3
15
Y
Z
P2
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Solenoid Operated On-Off Valves - Model 710 (N.C.) and Model 711 (N.O)
N.C. = Normally closed, energize to open
N.O. = Normally open, energize to close
A solenoid valve is either open or closed. It does not perform any control functions unless the other controls have been
incorporated. It is an on-off block valve, and is inherently a check valve.
As a line block valve, it is used for remote on-off control to start or stop a flowing stream such as:
1. Batching operation by preset
2. Tank filling high level control
3. Line block valve
CLOSED POSITION - The solenoid pilot is closed (N.C. illustrated). Y-port (P3) to Z-port (P2) is
closed. X-port (P1) and Y-port (P3) pressures are balanced. The main valve spring, being the
differential force, closes the piston and keeps it seated. The needle valve controls the speed of
closure.
MODEL 710 - (N.C.) ILLUSTRATED - Opens when energized.
MODEL 711 - (N.C.) - Closes when energized.
OPEN POSITION - The solenoid pilot is open. Y-port (P3) is open to Z-port (P2). The pressure on
the bottom of the piston (P1) is greater than the pressure at (P3) plus the spring force. (P1 minus
P2) is equal to or greater than the spring force.
= Inlet Pressure
= Outlet Pressure
P1
X
P3
Figure 4-5
Y
Z
P2
17
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Model 750 Pressure Reducing Control Valve (N.O.)
Closes on increasing Outlet Pressure
A pressure reducing valve is normally open and throttles toward a closed position on increasing outlet pressure. It is a regulating
or positioning type valve that does not require any outside power source to operate.
The pilot control is normally open. It is an adjustable spring loaded variable orifice in the Z-port. The pilot is piston operated,
spring biased (loaded) with a pressure sensing chamber connected on the downstream (P2) side.
Pressure reducing valves are used for:
1. Precise pressure control in process streams.
2. Over-pressure protection of meters, pipe line manifold systems, etc.
FULLY OPEN - NO CONTROL - The pilot is fully open. Open pressure (P2) is less than the pilot
spring setting. Y-port (P3) is open to Z-port (P2). The valve is floating the stream and is not
required to control.
OPEN - CONTROLLED POSITION - The pilot is partially open. Outlet pressure has slightly
exceeded the pilot spring. Z-port (P2) is being squeezed off by the throttling of the pilot, placing
higher pressure on Y-port (P3). The increasing pressure at Y-port (P3) plus the main valve spring
force, establishes a position of the valve piston so it balances outlet pressure equal to the pilot
setting (plus or minus 2 psi).
Model 760 Back Pressure/Pressure Relief Control (N.C.)
Opens on increasing inlet pressure
A back pressure/pressure relief valve is normally closed and throttles open on increasing inlet pressure. This valve is used to
maintain minimum pressure for more efficient operating conditions or to relieve excess pressure. It is a regulating or positioning
type valve that does not require any outside power source to operate.
The pilot control is normally closed. It is an adjustable spring loaded variable orifice in the Z-port. The pilot is piston operated,
spring biased (loaded) with a pressure sensing chamber connected to upstream (P1).
Back pressure/pressure relief valves are used for:
1. Back pressure against a pump, meter, hill pressure, etc.
2. Pressure relief and surge control
CLOSED POSITION - The pilot is closed. Inlet pressure (P1) is less than the pilot spring setting,
indicating the main line upstream (P1) is closed, or pressure is not sufficient to overcome the pilot spring
setting. Pilot is closed. Y-port (P3) to Z-port (P2) is closed. X-port (P-1) and Y-port (P3) pressures are
balanced. The main valve spring, being the differential force, closes the valve and keeps the piston seated.
= Inlet Pressure
= Outlet Pressure
= Pilot Spring Force
P1
P3
Figure 4-9
P2
20
Technical Guide
X
Z
Y
X
Z
Y
DAN-LIQ-TG-44-rev0813
November 2013
OPEN - CONTROLLED POSITION - The pilot is partially open. Inlet pressure (P1) has slightly
exceeded the pilot spring setting. Z-port (P2) is being opened by the throttling of the pilot,
reducing the pressure on Y-port (P3). The decreasing pressure at Y-port (P3) plus the main valve
spring force establishes a position of the valve piston such that it balances inlet (P1) pressure
equal to the pilot setting (Plus or minus 2 psi).
Model 770 Minimum Differential Pressure Control (N.C.)
Opens on increasing differential pressure
The Model 770 valve is normally closed and throttles toward an open position on increasing differential pressure. It is a regulating
or positioning type valve that does not require any outside power source to operate.
The pilot control is normally closed. It is an adjustable spring loaded variable orifice in the Z-port. The pilot is piston operated,
spring biased (loaded) with a differential pressure sensing chamber connected to the high and low pressure sources.
The Model 770 valve is used for:
1. Pump differential pressure control
2. Bypass differential pressure control for pumps, strainers, filters, etc.
3. Vapor pressure control on LPG, NH3 and similar products.
CLOSED POSITION - The pilot is closed. The differential pressure between (P1) and (P4) is less
than the pilot spring setting, indicating the pump is not running or sufficient differential pressure
(P1 minus P4) is not available to overcome the pilot spring setting. Pilot is closed. Y-port (P3) to
Z-port (P2) is closed. X-port (P1) and Y-port (P3) pressures are balanced. The main valve spring,
being the differential force, closes the piston and keeps it seated.
OPEN - CONTROLLED POSITION - The pilot is partially open. Differential pressure (P1 minus P4)
has slightly exceeded the pilot spring setting. Z-port (P2) is being opened by the throttling of
the pilot, reducing the pressure on Y-port (P3). The decreasing pressure at Y-port (P3) plus the
main valve spring force establishes a position of the valve piston such that is balances the pump
differential pressure (P1 minus P4) equal to the pilot setting (Plus or minus 2 psid).
P3
Y
P1
P4
= Inlet Pressure
= Outlet Pressure
= Controlled Pressure
= Pilot Spring Force
FULL OPEN - NO CONTROL - The pilot is full open. Differential pressure (P1 minus P4) has
exceeded the pilot spring setting. Y-port (P3) is open to Z-port (P2). The valve is floating the
stream and is not required to control.
Figure 4-13
X
Z
P2
P4
= Inlet Pressure
= Outlet Pressure
= Pilot Spring Force
P1
Figure 4-14
X
23
P3
Y
Z
P2
Technical Guide
CLOSED POSITION
OPEN POSITION
DAN-LIQ-TG-44-rev0813
November 2013
CLOSED POSITION - Nitrogen gas pressure is higher that the valve inlet pressure, therefore the force of the
nitrogen gas plus the spring keep the valve in the closed postition.
Pressure
Sensor
= Inlet Pressure
Gas Pressure
Gas Pressure
Oil Reservoir
Gas Tank
= Outlet Pressure
= Gas Pressure
= Oil Reservoir and Main Valve Piston Pressure
Figure 4-15
OPEN POSITION - The pressure at the inlet of the valve has exceeded the combined force of the nitrogen gas
plus the spring, thereby causing the piston to become unbalanced, opening the valve and removing the surge
from the pipeline.
= Inlet Pressure
= Outlet Pressure
= Gas Pressure
= Oil Reservoir and Main Valve Piston Pressure
Gas Pressure
Oil Reservoir
Figure 4-16
24
Gas Pressure
Pressure
Sensor
Gas Tank
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Model 770 Differential Vapor Pressure Control (N.C.)
Opens on increasing differential pressure
Typical for LPG, NH3 or similar products
The Model 770 as illustrated is identical to the previously described 770 valve except it is shown as a vapor pressure
control valve for products having high flash points such as: butane, propane, anhydrous ammonia or other products with
similar characteristics.
When metering these products, the pressure at the meter must be higher than the vapor pressure of the product, otherwise it
turns into a gaseous state resulting in meter damage due to overspeed plus inaccurate measurement and possible pump
damage. The differential pressure between the meter inlet pressure and the vapor pressure (P4) is generally 10 to 30 psid, to
assure the product is in a liquid state when it passes through the meter.
CLOSED POSITION - The pilot is closed. Vapor pressure (P4) plus pilot spring setting is greater
than the line pressure (P1), indicating the pump is not running or sufficient differential pressure
(P1 minus P4) is not available to overcome the pilot spring setting. Pilot is closed. Y-port (P3)
to Z-port (P2) is closed. X-port (P1) and Y-port (P3) pressures become balanced. The main valve
spring being the differential force, closes the piston and keeps it sealed.
Model 762, 763, 764, 765, 766 and 767 Gas Loaded Pressure Relief / Back Pressure Control Valves (N.C.) Open on
increasing inlet pressure
These valves are normally closed and open upon increasing inlet pressure. They are used to relieve excess surge pressures
that may occur during a pipeline upset and can also be used to maintain a minimum back pressure for more efcient operating
conditions. These valves are direct acting and do not utilize pilots to operate. They incorporate an integral oil reservoir mounted
on the external surface of the valve cylinder head, which upon installation is partially lled with a light oil. Gas under pressure is
applied to the reservoir. The oil is a moveable barrier between the gas and the valve piston.
Principle of Operation
The valve is normally closed and opens upon increasing inlet pressure. Pressure applied to the nose of the piston is equally
transmitted to the spring side of the piston. When the line pressure on the nose of the piston exceeds the gas pressure, the
moveable barrier of oil compresses the gas and the valve opens.
As line pressure falls below the set point, the gas pressure, added to the spring pressure closes the valve and it remains closed
as long as gas pressure is higher than line pressure. Opening and closing speeds are controlled by a check valve mounted to the
internal surface of the cylinder head. Opening speed is relatively unrestricted which results in very fast opening response. Closing
speed is controlled by a xed orice in the check valve.
Typical Applications
A) Pipeline Pressure and Surge Relief (models 765, 766, 767)
Product movement by pipeline requires over-pressure protection. Response time to pressure rise is critical. These valves will
respond very quickly and only relieve the necessary volume of liquid to decrease pipeline pressure back to or below set-point.
B) Back Pressure Control (models 762, 763)
These valves are ideally suited for back pressure control and minimum pressure drop. When line pressure exceeds the gas
pressure, the valve will open and follow the CV curve for pressure loss.
26
Technical Guide
X
Z
Y
X
Z
Y
Z
Y
X
DAN-LIQ-TG-44-rev0813
November 2013
OPEN - CONTROLLED POSITION - The pilot is partially open. Differential pressure (P1 minus P4)
has slightly exceeded the pilot spring setting. Z-port (P2) is being opened by the throttling of the
pilot, reducing the pressure on Y-port (P3). The decreasing pressure at Y-port (P3) plus the main
valve spring force establishes a position of the valve piston such that it balances inlet pressure
(P1) equal to the pilot setting plus vapor pressure (P4) (Plus or minus 2 psid).
P4
Vapor Pressure
Liquid
= Inlet Pressure
= Outlet Pressure
= Controlled Pressure
= Pilot Spring Force plus P4
= Product Pressure
FULL OPEN - NO CONTROL - The pilot is full open. Differential pressure (P1 minus P4) has
exceeded the pilot spring setting. Y-port (P3) is open to Z-port (P2). The valve is floating the stream
and is not required to control.
A rate of flow or flow limiting valve is normally open and throttles toward a closed position on increasing differential pressure (P4
minus P1). It is a regulating or positioning type valve that does not require any outside power source to operate.
The pilot control is normally open. It is an adjustable spring loaded variable orifice in the Z-port. The pilot is piston operated,
spring biased (loaded) with a differential pressure sensing chamber connected to two separate pressure sources.
Rate of flow valves are used for:
1. Limiting the maximum flow through meters.
2. Limiting the maximum flow through pumps, process streams, etc.
FULL OPEN - NO CONTROL - The pilot is full open. Differential pressure (P4 minus P1) is less than
the pilot spring setting. Y-port (P3) is open to Z-port (P2). The valve is floating the stream and is
not required to control.
OPEN - CONTROLLED POSITION - The pilot is partially open. Differential pressure (P4 minus P1)
has slightly exceeded the pilot spring setting. Z-port (P2) is being squeezed off by the throttling
of the pilot, placing higher pressure on Y-port (P3). The increasing pressure at Y-port (P3) plus the
main valve spring force establishes a position of the valve piston such that it balances differential
pressure (P4 minus P1) equal to the pilot setting (plus or minus 2 psid), which is proportional to
the flow rate.
Sense Line (LO)
Needle Valve/Strainer
Sense Line (HI)
P4
Flow Meter
(Closing/Sensitivity Control)
P1
Note: Minimum of 5 psid required for Control
= Inlet Pressure and Pilot Spring Force plus P1
= Outlet Pressure
= Controlled Pressure
= Product Pressure
Figure 4-21
X
P3
Differential
Pilot (N.C.)
Y
Z
P2
29
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Section 5
MULTIPLE PILOTS (SERIES AND PARALLEL)
Model 710S750 Combination Solenoid On-Off and Pressure Reducing Control in Series
Both pilots have been illustrated as separate functions on a basic valve (Models 710 and 750). Now the pilots are combined on a
single valve. This is the starting point for multiple control functions on one basic valve.
When pilots are in a series, all pilots must be open for the main valve to open, but should one pilot close, the main valve
will also close.
The advantage of multiple controls is to incorporate various functions on a single valve.
CLOSED POSITION - The solenoid pilot is closed (de-energized). Y-port (3) to Z-port (P2) is closed.
X-port (P1) and Y-port (P3) pressures are balanced. The main valve spring being the differential
force, closes the piston and keeps it seated.
OPEN CONTROLLED POSITION - The solenoid pilot is energized. The pressure reducing pilot is
partially open. Outlet pressure has slightly exceeded the pressure reducing pilots spring setting.
A-port (P2) is being squeezed off by the throttling of the pressure reducing pilot, placing higher
pressure on Y-port (P3). The increasing pressure at Y-port (P3) plus the main valve spring forces
establishes a position of the valve piston such that it balances outlet pressure (P2) equal to the
pilot setting (Plus or minus 2 psi).
FULL OPEN - NO CONTROL - Both pilots are full open. The solenoid pilot is energized. Outlet
pressure P2 is less than the pressure reducing pilot spring setting. Y-port (P3) is open to Z-port
(P2). The valve is floating the stream and is not required to control.
Model 710P760 Combination Solenoid On-Off and Back Pressure Control in Parallel
Both pilots have been illustrated as separate functions on a basic valve (Models 710 and 760). Now the pilots are combined on a
single valve.
When two (2) pilots are in parallel, only one pilot must be open for the main valve to open, but both pilots must close to
assure the main valve closes.
The advantage of multiple controls is to incorporate various functions on a single valve.
CLOSED POSITION - Both pilots are closed. The solenoid de-energized. Inlet pressure (P1) is less
than the back pressure pilot setting. Y-port (P3) to Z-port (P2) is closed. X-port (P1) and Y-port (P3)
pressures are balanced. The main valve spring being the differential force, closes the piston and
keeps it seated.
OPEN CONTROLLED POSITION - The solenoid pilot is closed (de-energized). The back pressure
pilot is partially open, bypassing the solenoid pilot. Inlet pressure has slightly exceeded the back
pressure pilot spring setting. Z-port (P2) is being opened by the throttling of the pilot, reducing the
pressure on Y-port (P3). The decreasing pressure at Y-port (P3) plus the main valve spring force
establishes a position of the valve piston such that it balances inlet pressure (P1) equal to the pilot
setting (Plus or minus 2 psi).
FULL OPEN - NO CONTROL - The solenoid pilot is open (energized), bypassing the back pressure
pilot which is closed. As long as the solenoid pilot is open, the back pressure control function is
bypassed and cannot perform, even though inlet pressure (P1) is less than the pilot spring setting.
Y-port (P3) is open to Z-port (P2). The valve is floating the stream and is not required to control.
Model 788 DVC Digital Control Electric Shut-off Valves
These valves are normally closed (N.C.) and they will open only when both solenoids are energized. The valves are fail-safe
as they close upon loss of power. They use the line product as the source of hydraulic power to open and close the main valve
piston. An electrical supply controlled by an electronic preset is the source of power for energizing the two solenoids.
These valves are used mainly for batching and they provide a means of reducing the rate of flow on startup and before final shutoff of a predetermined delivery. This minimizes surges of pressure and line shock and assures + 1/4 gallon shut-off (sizes 2 inch
- 6 inch) of the preset volume.
The total system generally consists of three pieces of equipment: (1) a flowmeter, (2) electronic preset with digital control, and
(3) a digital electric control valve. The electronic preset is the device used to set the predetermined volume of liquid that is to be
delivered by the valve.
Operational Sequence
With both solenoids de-energized, the main valve is closed as shown in Figure 6-1. The main valve can be infinitely positioned
anywhere between 0 - 100% open by digital control of the solenoids. With both solenoids energized, as shown in Figure 6-3, the
valve begins to open. It will only open to the programmed flow rate set in the electronic preset. Normally, the electronic preset
is programmed to digitally control low flow start-up, maximum flow rate, low flow rate before shut-off and no flow. The electronic
preset will automatically energize and de-energize the solenoids to position the main valve to limit the required flow rate. When
the required flow rate is reached, the solenoids will be as shown in Figure 6-2. This hydraulically locks the main valve piston
in position. Should flow increase, the valve will close slightly to adjust to the required flow rate. All of the positioning is done by
digitally controlling the two solenoids as shown in Figure 6-1, 6-2 and 6-3.
CLOSED POSITION - The normally closed solenoid is closed. The normally open solenoid is open. Y-port (P3)
to Z-port (P2) is closed. X-port (P1 and Y-port (P3) pressures are balanced. The main valve spring being the
differential force, closes the piston and keeps it seated.
Solenoid Pilot (N.O.)Solenoid Pilot (N.C.)
Needle
Valve
P2
Flow
= Inlet Pressure
= Outlet Pressure
Strainer
P3
P1
Figure 6-1
34
Technical Guide
Position
Indicator
Z
X
Z
Y
DAN-LIQ-TG-44-rev0813
November 2013
OPEN - CONTROL POSITION - The normally closed solenoid is closed. The normally open solenoid is closed.
Y-Port (P3) to Z-port (P2) is closed. X-port (P1) to Y-port (P3) is closed. The product cannot flow to or from
the top of the piston. The piston is hydraulically locked in position until the electronic preset commands the
Solenoid Pilot (N.O.)Solenoid Pilot (N.C.)
Needle
Strainer
P1
X
P3
Y
Valve
Z
P2
= Inlet Pressure
= Outlet Pressure
= Controlled Pressure
OPEN POSITION - (no control) - The normally closed solenoid is open. The normally open solenoid is closed.
Y-port (P3) is open to Z-port (P2). X-port (P1) is closed off by the normally open solenoid. The pressure on the
bottom of the piston (P1) is greater than the pressure at (P3) plus the spring force; (P1 minus P2) is equal to
or greater than the spring force. Therefore, (P1) pressure pushes the piston open. No flow control is required.
Solenoid Pilot (N.O.)Solenoid Pilot (N.C.)
Strainer
Figure 6-2
Needle
Valve
P3
Y
P1
X
Z
P2
= Inlet Pressure
= Outlet Pressure
Figure 6-3
35
Technical Guide
Technical Guide
DAN-LIQ-TG-44-rev0813
DAN-LIQ-TG-44-rev0208
November 2013
February 2008
Section 7
POWER CYLINDER OPERATED VALVES
Model 531, 535, 578 and 588 (N.C.) Pressure to Open and Model 532 and 536 (N.O.) Pressure to Close
Power cylinder operated valves can perform various functions. The power cylinder can be full open or closed or the pressure can
be regulated for two-stage batch control or digital batch control.
All valves employ a bias spring in the power cylinder. There is no spring behind the main valve piston. The power cylinder spring
requires 30 psi to make a full stroke. An optional spring to make a full stroke at 15 psi is available for selected applications.
These valves use the line product or an auxiliary supply pressure (pneumatic or hydraulic) to operate the power cylinder. The
main valve piston and the power cylinder piston are of balanced design.
The valves are used in a variety of applications such as:
1. Automatic tank safety shut-off
2. Line block valve
3. Emergency shut-off or opening
4. Batching, single or two-stage operation, or digital batch control
The pressure drop across the valve is very low as it follows a Cv curve. Anytime the valve is closed, it is inherently a check valve
without adding any additional controls. The main valve piston is balanced at all positions.
CLOSED POSITION - The differential pressure between (P1) and (P2) is less than the spring force of the power
cylinder spring. This indicates the pump is not running or insufficient differential pressure (P1 minus P2) to
overcome the spring force of the power cylinder spring. The power cylinder spring provides the differential
force to close the main valve piston and/or keep it seated.
TANK SAFETY CONTROL
Power
Cylinder
Sense
Line (LO)
P2
Sense
Line (HI)
P1
Pump
= Pump and Valve
Outlet Pressure
= Valve Inlet Pressure
Figure 7-1
36
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
OPEN POSITION - The differential pressure between (P1) and (P2) has exceeded the total spring
force of the power cylinder spring (P1 minus P2). This keeps the valve in a full-open position.
Sense
Line (HI)
Power
Cylinder
= Pump and Valve
Outlet Pressure
= Valve Inlet Pressure
Figure 7-2
7-3 CLOSED POSITION - The solenoid pilot is de-energized. This blocks the supply of pressure
and vents the power cylinder pressure (P3) to atmosphere. The power cylinder spring provides the
differential force to close the main valve piston and keep it seated. The valve will not allow flow
from the forward or reverse direction. 7-4 OPEN POSITION - The solenoid pilot is energized, thus
opening the supply pressure to the power cylinder (P3). The supply pressure is equal to or greater
than the total spring force. This keeps the valve in a full-open position. Product can flow through
the main valve in either direction.
Sense
Line (LO)
P2
P1
Closing
Speed
Exhaust
Supply
Pressure
Opening
Speed
Flow
P3
= Inlet Pressure
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
3-Way Solenoid
Pilot (N.C.)
Vent
(Closed)
P3
P2P1
Power
Cylinder
P2P1
(Open)
Figure 7-4
Figure 7-3
37
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
DIGITAL CONTROL VALVES
Model 588 DVC (N.C.) Digital Control Electric Shut-off Valve
Digital Control electric shut-off valves are normally closed (N.C.) and they will open only when both solenoids are energized. The
valves are fail-safe as they close upon loss of auxiliary power medium. They use an auxiliary power source (typically regulated
instrument air) to open and position the valve. An electrical supply controlled by an electronic preset is the source of power for
energizing the two solenoids.
These valves are used mainly for batching and they provide a means of reducing the rate of flow on startup and before final shutoff of a predetermined delivery. This minimizes surges of pressure and line shock and assures ±1/4 gallon shut-off (sizes 2" - 6")
of the preset volume.
The total system generally consists of three pieces of equipment: (1) a flowmeter, (2) electronic preset with digital control, and
(3) a digital electric control valve. The electronic preset is the device used to set the predetermined volume off liquid that is to be
delivered by the valve.
Operational Sequence
With both Solenoids de-energized, the main valve is closed as shown in Figure 7-5. The main valve can be infinitely positioned
anywhere between 0-100% open by digital control of the solenoids. With both solenoids energized, as shown in Figure 7-7, the
valve begins to open. It will only open to the programmed flow rate set in the electronic preset. Normally, the electronic preset
is programmed to digitally control low flow start-up, maximum flow rate, low flow rate before shut-off and no flow. The electronic
preset will automatically energize and de-energize the solenoids to position the main valve to limit the required flow rate. When
the required flow rate is reached, the solenoids will be as shown in Figure 7-6. This pneumatically locks the power cylinder piston
in position. Should flow increase, the valve will close slightly to adjust to the required flow rate. All of the positioning is done by
digitally controlling the two solenoids as show in Figure 7-5, 7-6 and 7-7.
CLOSED POSITION - The normally closed solenoid is closed. The normally open solenoid is open, venting the
power cylinder pressure (P3) to atmosphere. The power cylinder spring provides the differential force to close
the main valve piston and keep it seated. The closing speed needle valve controls how fast the valve closes
or responds to a flow rate change.
Solenoid (N.O.)Solenoid (N.C.)
Closing
Speed
Exhaust
Power
Cylinder
P2
Supply
Pressure
(30 PSI Max)
Opening
Speed
Flow
P1
P3
Vent
Figure 7-5
= Inlet Pressure
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
Figure 7-5
38
45
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
OPEN - CONTROL POSITION - The normally closed solenoid is closed. The normally open solenoid is closed.
The power cylinder medium (P3) cannot flow to or from the power cylinder. The piston is pneumatically
locked in position until the electronic presets command the valve to open or close as required to maintain the
desired flow rate.
Solenoid (N.C.)Solenoid (N.O.)
Supply
Pressure
(30 PSI Max)
= Inlet Pressure
Opening
Speed
P3
P1
Flow
Closing
Speed
Exhaust
Power
Cylinder
P2
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
Figure 7-6
OPEN POSITION - NO CONTROL - The normally closed solenoid is open. The normally open
solenoid is closed, blocking the exhaust port, and pressure (P3) is applied to the power cylinder.
The pressure on the bottom of the power cylinder piston (P3) is greater than the pressure applied
by the spring force. Therefore, causing the valve to go full open (No Control). The opening speed
needle valve controls how fast the valve opens or responds to a flow rate change.
Opening
Speed
Supply
Pressure
(30 PSI Max)
= Inlet Pressure
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
Solenoid (N.C.)Solenoid (N.O.)
P3
P1
Flow
Figure 7-7
46
39
Closing
Speed
Exhaust
Power
Cylinder
P2
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
TWO STAGE VALVES
Model 578 (N.C.) Two-stage Electric Shut-off Valve
Two-Stage Control electric shut-off valves are normally closed (N.C.) and they will open only when both solenoids are energized.
The valves are fail-safe as they close upon loss of auxiliary power medium. They use an auxiliary power source (typically
regulated instrument air) to open and position the valve for high and low flow. Flow limiting control is not available. An electrical
supply controlled by a preset is the source of power for energizing the two solenoids.
These valves are used mainly for batching and they provide a means of reducing the rate of flow on startup and before final
shut-off of a predetermined delivery. This minimizes surges of pressure and line shock and assures ±1/4 gallon shut-off (sizes
2" - 6") of the preset volume.
The total system consists of four pieces of equipment: (1) a flow meter, (2) a preset counter, (3) dual sequencing switches, and
(4) a two-stage electric shut-off valve. The preset counter is the device used to set the predetermined volume of liquid that is
to be controlled by the valve. The valve closes in two stages. The first stage closure reduces the flow rate through the valve to
approximately 10% to 20% of the rated capacity of the meter. The second stage closes the valve when the predetermined volume
of liquid has passed through the meter. See Figures 7-8, 7-9 and 7-10.
CLOSED POSITION - The normally closed solenoid is closed. The normally open solenoid is open, venting the
power cylinder pressure (P3) to atmosphere. The power cylinder spring provides the differential force to close
the main valve piston and keep it seated. The closing speed needle valve controls the closing speed.
Supply
Pressure
(30 PSI Max)
Opening
Speed
Flow
P1
Solenoid (N.O.)Solenoid (N.C.)
Closing
Speed
Exhaust
P3
Vent
Power
Cylinder
P2
= Inlet Pressure
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
Figure 7-8
43
40
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
OPEN - HIGH FLOW POSITION - The normally closed solenoid is open. The normally open solenoid is closed
blocking the exhaust vent and pressure (P3) is applied to the power cylinder. The pressure on the bottom of
the power cylinder piston (P3) is greater than the pressure applied by the spring force, therefore, causing the
valve to go full open. (Maximum flow limiting control is not available).
Solenoid (N.O.)Solenoid (N.C.)
Closing
Speed
Exhaust
Power
Cylinder
Supply
Pressure
(30 PSI Max)
= Inlet Pressure
Opening
Speed
Vent
Flow
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
Figure 7-9
OPEN LOW FLOW POSITION - The normally closed solenoid is closed. The normally open solenoid is closed.
The power cylinder supply pressure (P3) cannot flow to or from the power cylinder. During the transition
stage from high flow to low flow, the normally closed solenoid was closed and the normally open solenoid
was open, venting the power cylinder medium through the exhaust port closing speed needle valve. When the
valve reaches a predetermined low flow rate equal to 10% to 20% of the maximum flow rate, the limit switch
is activated resulting in the normally open solenoid closing. This pneumatically locks the valve in a fixed
position until the preset commands the valve to close. (Low flow start-up is available as an option).
Supply
Pressure
(30 PSI Max)
= Inlet Pressure
= Outlet Pressure
= Power Cylinder Supply Pressure
= Power Cylinder Spring Force
Opening
Speed
Flow
Solenoid (N.O.)Solenoid (N.C.)
Closing
Speed
Exhaust
Vent
Power
Cylinder
Figure 7-10
41
Technical Guide
DAN-LIQ-TG-44-rev0813
November 2013
Technical Guide
Technical Guide
DAN-LIQ-TG-44-rev0813
DAN-LIQ-TG-44-rev0208
November 2013
February 2008
Emerson Process Management
Daniel Measurement and Control, Inc.
World Area Headquarters
Houston, Texas, USA
T: 713.467.6000, F: 713.827.3880
USA Toll Free 1.888.FLOW.001
www.daniel.com
Canada: Calgary, Alberta
T: 403.279.1879, F: 403.236.1337
Asia Pacific: Singapore
T: +65.6777.8211, F: +65.6770.8001
Europe: Stirling, Scotland
T: +44 1786 433400, F: +44 1786 433401
Mid-East, Africa: Dubai
T: +971 (4) 883.5235, F: +971 (4) 883.5312
Daniel Measurement and Control, Inc. ("Daniel") is a wholly owned subsidiary
of Emerson Electric Co., and a division of Emerson Process Management. The
Daniel name and logo are registered trademarks of Daniel Industries, Inc. The
Emerson logo is a registered trademark and service mark of Emerson Electric
Co. All other trademarks are the property of their respective companies. The
contents of this publication are presented for informational purposes only, and
while every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, expressed or implied, regarding the
products or services described herein or their use or applicability. All sales are
governed by Daniels' terms and conditions which are available upon request.
We reserve the right to modify or improve the designs or specifications of such
products at any time. Daniel does not assume responsibility for the selection,
use or maintenance of any product. Responsibility for proper selection, use
and maintenance of any Daniel product remains solely with the purchaser and
end-user. All Daniel Control Valve Products presented in this publication are
protected by U.S. and international patents and patents pending.
www.daniel.com
2008 Daniel Measurement and Control, Inc. All Rights Reserved. Unauthorized duplication in whole or in part is prohibited. Printed in the USA. DAN-LIQ-TG-44-rev0208
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.