Emerson CX Installation Manual

Edco CX Series
CCTV & Data Applications/Coax
The Edco CX06-M, CX06-MI and CX06-MI-SBL Surge Protective Devices (SPDs) implement three-stage hybrid technology. The SPDs address over-voltage transients with a primary Gas Discharge Tube (GDT) and secondary Silicon Avalanche Diode (SAD) components. Over-current protection, e.g. sneak and fault currents, are mitigated with solid-state resettable fuses — PTCs.
The Edco CX06-M, CX06-MI and CX06-MI-SBL SPDs are designed in accordance with NFPA 780 (2004 edition) requirements, with up to 20 kA of surge current capability. The Edco CX06-MI and CX06-MI-SBL models have an isolated ground and is recommended for use at the camera-end.
CX06-M
General Technical Specifications
Operating Voltage 5 VDC
Clamping Voltage 6 VDC
Operating Current 0.15 A
Peak Surge Current 20 kA (8 x 20 μs)
Frequency Range 0 to 20 MHz
Insertion Loss < 0.1 dB at 20 MHz
Response Time < 0.5 ns
SPD Technology GDT, SAD, w/ Series PTC
Connection Type BNC, 50/75 Ohm
Operating Temperature -40°C to +85°C
Dimensions (in / mm) M = 1.5˝ H x 1.0˝ W x 3.25˝ L
[38.1 x 25.4 x 82.55 mm]
MI = 1.5˝ H x 1.0˝ W x 4.0˝ L
[38.1 x 25.4 x 101.6 mm]
SBL = 1.7˝ H x 1.4˝ W x 2.8˝ L
[43.18 x 35.56 x 71.12 mm]
Weight (oz / kg) M = 2.3 oz [0.07 kg]
MI = 3 oz [0.09 kg]
SBL = 3 oz [0.09 kg]
Certifications UL 497B Listed
CX06-MI
CX06-MI-SBL
Features
■ Sneak/fault current protection
■ Low insertion loss
■ Shielded case
■ Models with isolated ground
■ 5 year warranty
Ordering Information
*Other configurations available, please contact factory.
Caution
Do not place this product in service on any signal line capable of supplying more than 150 mA continuously.
Attention
Ne pas placer ce produit dans le service sur une ligne de signal capable de fournir en permanence plus de 150 mA.
Head-End CX06-M
Camera-End
CX06-MI CX06-MI-SBL
Installation Instructions
Read and Understand These Instructions:
These protectors are intended for indoor use on communication loop circuits which have been isolated from the Public Switch Telephone Network.
The communication loop circuits shall not be exposed to accidental contact with the electric light or power conductors. The protectors shall be installed per the applicable requirements of the National Electric Code, ANSI/NFPA 70.
Edco CX06-M: Head-End Equipment Protection
A. Connect the Edco CX06-M in line with the coaxial cable. The
side labeled “EQUIP” should be connected to the adjacent head-end equipment.
B. Connect incoming coaxial cable to the side of the Edco
CX06-M labeled “CABLE”.
C. Connect a ground wire (10-12 AWG) between the Edco
CX06-M ground terminal and the AC power ground of head-end equipment. Keep this wire as short and straight as possible.
Only qualified personnel should install or service this system. Electrical safety pre­cautions must be followed when installing or servicing this equipment. To prevent risk of electrical shock, turn off and lock out all power sources to the unit before making electrical connections or servicing.
DANGER!
V
Edco CX06-MI and CX06-MI-SBL: Camera-End Protection
A. Connect the Edco CX06-MI or -SBL in line with the coaxial
cable. The side labeled “EQUIP” should be connected to the adjacent camera.
B. Connect incoming coaxial cable to the side of the Edco
CX06-MI or -SBL labeled “CABLE”.
C. Connect a ground wire (10-12 AWG) between the Edco
CX06-MI or -SBL ground terminal and either the AC power ground or equipment building ground at the camera location. Keep this wire as short and straight as possible.
Head-End
Equipment
(Keep ground wire
as short as possible)
CX06-M or
RM-CX06-16R
To AC Power Ground
Seulement le personnel qualifié doit installer ou maintenir ce systéme. Des précautions de sécurité en électricité doivent être suivis lors de l’installation ou de la maintenance de cet equipement. Pour eviter tout risque de choc électrique, débranchez et verouiller toutes les sources d’alimentation de cet equipement avant de.
CX06-MI or
CX06-MI-SBL
(Keep ground wire
as short as possible)
Camera-End
Equipment
To AC Power Ground
or Building Ground
Emerson Network Power Contact information
Surge Protection 100 Emerson Parkway Binghamton, NY 13905 T: (607) 721-8840 T: (800) 288-6169 F: (607) 722-8713 E: SurgeTech@Emerson.com
IO-50107 5/14 Rev. 5 Printed in USA
While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
Emerson Network Power, the Emerson Network Power logo and Edco are trademarks
www.EmersonNetworkPower.com/Surge
and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.