Emerson CSI 9420 Quick Installation Manual

www.mhm.assetweb.com
Quick Installation Guide
P/N MHM-97409.4 April 2010
CSI 9420
Step 1: Physical Installation Step 2: Verify Operation Step 3: Communication and Configuration
Start
End
CSI 9420 Wireless Vibration Transmitter
Quick Installation Guide
P/N MHM-97409.4
April 2010
CSI 9420
2
© 2010 CSI. All rights reserved. All marks property of owner.
IMPORTANT NOTICE
This installation guide provides basic guidelines for the CSI 9420. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations. Refer to the CSI 9420 reference manual (document number P/N 97408) for more instruction. The manual and this QIG are also available electronically on www.mhm.assetweb.com.
WARNING
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the Product Certifications section for any restrictions associated with a safe installation.
• Before connecting a 375 Field Communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
IMPORTANT NOTICE
The CSI 9420 and all other wireless devices should be installed only after the 1420 Wireless Gateway has been installed and is functioning properly . Wireless devices should also be powered up in order of proximity from the 1420 Wireless Gateway , beginning with the closest. This will result in a simpler and faster network installation.
IMPORTANT NOTICE
Shipping considerations for wireless products (Lithium Batteries):
Battery powered units are shipped without the power module installed. Please remove the power module pack prior to shipping the unit.
Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Please consult current regulations and requirements before shipping.
Emerson Process Management Machinery Health Management
835 Innovation Dr. Knoxville, TN 37932 T (US) (800) 675-4726 F (865) 218-1401
European Headquarters
Interleuvenlaan 50 Reasearch Park Inerleuven B 3001 Leuven - Belgi um T 32-16-741-403 F 32-16-400-457
Emerson Process Management Asia Pacific Private Limited
3904 Room Central Plaza 18 Harbour Road Wan-Chai Hong Kong T 852-2802-9223 F 852-2802-8227
Quick Installation Guide
P/N MHM-97409.4 April 2010
CSI 9420
3
This Quick Installation Guide applies to both the 2.4 GHz and 900 MHz Wireless HART versions of the CSI 9420. If you are unsure which version the device is, look in the upper right-hand corner of the nameplate, as illustrated in Figure 1 below.
Figure 1. Nameplates with radio frequency version highlighted by circles
Quick Installation Guide
P/N MHM-97409.4
April 2010
CSI 9420
4
STEP 1: PHYSICAL INSTALLATION
The CSI 9420 and all other wireless devices should be installed only after the 1420 Wireless Gateway has been installed and is functioning properly.
Powering the CSI 9420
Remove the rear cover of the device to access the power connections. For the battery powered version, simply plug in the power module. For the externally powered version, connect a 10...28V DC (24V nominal) power supply to the bottom two screw terminals on the right (see Figure 3). Pull the wiring through the threaded conduit entry. When selecting the power supply, note that each CSI 9420 has a peak current draw of 40 mA when awake and powering sensors.
NOTE:
Wireless devices should be powered up in order of proximity to the 1420 Wireless Gateway, beginning with the closest device to the 1420. This will result in a simpler and faster network installation.
GENERAL SENSOR HANDLING INSTRUCTIONS
The CSI 9420 utilizes special low-power sensors available from Emerson. Each sensor requires a standard 1/4” - 28 mounting location. Refer to the User’s Manual for detailed sensor mounting instructions. Sensor mounting instructions and practices are also available in a separate Sensor Installation Guide on the CD packaged with this device and at www.mhm.assetweb.com.
To maintain mechanical isolation of the sensor, a Remote Mount configuration is required, as illustrated in Figure 2. In this configuration, the sensor is mounted separately from the CSI 9420 housing, then connected to the CSI 9420. Although not required for all installations, it is common to run the cable from the sensor to the housing through conduit.
NOTE:
The word “sensor” applies to both an accelerometer and an accelerometer with embedded temperature. The word “accelerometer” refers to a sensor that measures only acceleration.
Remote Mount
1. Install sensor or accelerometers according to standard sensor installation practices. Be sure to use thread sealant on all connections.
2. Run wiring (and conduit if necessary) from the sensor to the CSI 9420.
3. Pull the wiring through the threaded conduit entry of the CSI 9420. If not using conduit, an appropriate grommet or cable-gland should be used to provide both strain relief for the cable and environmental isolation for the CSI 9420.
4. Attach the sensor wiring to the terminals as indicated in tables 1-3.
5. Connect the power pack module or external 24V DC power supply.
6. Close the housing cover and tighten to safety specification. Always ensure a proper seal by installing the electronics housing covers so that metal touches metal, but do not over
Quick Installation Guide
P/N MHM-97409.4 April 2010
CSI 9420
5
tighten.
7. Position the antenna such that it is vertical, either straight up or straight down.
Figure 2. Remote mounting of the CSI 9420 involves mount ing the device away from the eq uipment to be measured (upper left), connecting a sensor or acce leromete rs t o the equi pment and t he CSI 9 420 (upp er right), and removing the rear cover and power module of the de vi ce to co nnect the sensor wire s (bot to m).