Emerson CSB400 Instruction Manual

Page 1
Instruction Manual Form 5836
June 2014
CSB400 Series
CSB400 Series Commercial / Industrial Pressure Reducing Regulators
P1426 P1425
P1424
TYPICAL TYPE CSB403 REGULATOR WITH INTEGRAL TRUE-MONITOR™ REGULATOR
Figure 1. Typical CSB400 Series Pressure Reducing Regulators
TYPICAL TYPE CSB400 REGULATOR
Introduction
TYPICAL TYPE CSB404 REGULATOR WITH INTEGRAL TYPE VSX4 SLAM-SHUT MODULE
Introduction ..................................................................... 1
Speci cations .................................................................2
Principle of Operation ..................................................... 8
Installation and Overpressure Protection ..................... 11
Commissioning ............................................................. 15
Adjustment....................................................................15
Shutdown......................................................................17
Maintenance and Inspection.........................................19
Parts Ordering ..............................................................20
Parts List.......................................................................21
www.fisherregulators.com
Scope of the Manual
This Instruction Manual provides installation, maintenance and parts ordering information for the CSB400 Series regulators. Instructions and parts lists for other equipment mentioned in this instruction manual are found in separate manuals.
D103123X012
Page 2
CSB400 Series
Specications
The Specications section lists the specications for the CSB400 Series Regulators. The following information is stamped on the nameplate of CSB400 Series: Type and Class, Maximum Outlet Pressure and Spring Range.
Available Congurations
See Table 1
Regulator Type: Differential Strength (DS)
Accuracy Class: Up to AC5
(depending on Outlet Pressure)
Lock-up Class: Up to SG10
(depending on Outlet Pressure)
Failure Mode: Fail Open (FO)
Body Sizes and End Connection Styles
See Table 5
Integral Strength (IS) Pressure Ratings
(1)
See Table 3
Differential Strength (DS) Pressure Ratings and
Flow and Sizing Coefcients
(1)
See Table 4
Operating Pressure Ranges
(1)
Regulator: See Table 6 Integral True-Monitor™ Module: See Table 7 Slam-Shut Module: See Table 8
Maximum Outlet Pressures
(1)
Emergency: 4.0 bar / 58 psig To Avoid Internal Parts Damage:
Type CSB450: 1 bar / 14.5 psig above outlet pressure setting All other Types: 0.34 bar / 5 psig above outlet pressure setting
Operating: 3.0 bar / 43.5 psig
Spring Case Vent Connection
1 NPT
Orice Size
17.5 mm / 11/16 inch
Pressure Registration
Internal, External or Dual (Internal and External)
Operating Temperature (TS)
(1)(2)
According to PED Standards: All Types: -20 to 66°C / -4 to 150°F Non-PED with standard construction:
Types CSB400/CSB404, CSB420/CSB424:
-20 to 66°C / -4 to 150°F
Types CSB450/CSB454
(3)
:
-30 to 66°C / -20 to 150°F
Non-PED with low temperature construction:
Types CSB400F/CSB404F
(3)
, CSB420F/CB424F
-30 to 66°C / -20 to 150°F
Approximate Weights
With Threaded body Type CSB400: 4.1 kg / 9 pounds
Type CSB403: 9.1 kg / 20 pounds Type CSB404: 5.0 kg / 11 pounds
With Flanged Body:
Add 4.1 kg / 9 pounds to threaded weights listed above
PED Conformity Statement and Information
The CSB400 Product Series is in conformity with the Pressure Equipment Directive PED 97/23/EC. The exceptions to this previous statement are the Types CSB403 and CSB423. Both of these types are
not yet certied to conform with the PED Directive.
Pressure regulator does not require any supplementary upstream safety accessory for protection against overpressure compared with its design pressure PS, when upstream reducing station is sized for a max downstream incidental MIPd <= 1.1 PS.
PED Related Information
See Table 2
(3)
:
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
2. Standard token relief set values listed in Table 8 are based on -20 to 60°C / -4 to 140°F.
3. Product has passed Emerson Process Management Regulator Technologies, Inc. (Regulator Technologies) testing for lockup, relief start-to-discharge and reseal down to -40°.
2
Page 3
Table 1. Available Congurations
CSB400 Series
TYPE NUMBER
C S B 4
OPTIONS
PRESSURE CONSTRUCTION AND UPSTREAM MONITOR APPLICATIONS
0 Low Pressure Applications (Outlet Pressure: 17 to 100 mbar / 7 to 40 inches w.c.)
1 Low Pressure, Upstream Monitoring Applications
2 Medium Pressure Applications (Outlet Pressure: 100 to 517 mbar / 40 to 208 inches w.c.)
3 Medium Pressure, Upstream Monitoring Applications
5 High Pressure Applications
OVERPRESSURE PROTECTION
0 Without Overpressure Protection Module
0F Low Temperature Capability, Without Overpressure Protection Module
3 With Integral True-Monitor™ Module
3F Low Temperature Capability, With Integral True-Monitor Module
4 With Type VSX4 Slam-shut Module
4F Low Temperature Capability, With Type VSX4 Slam-shut Module
PRESSURE REGISTRATION
D Dual Registration (Best solution for quick changing loads)
E External Registration
I Internal Registration
RELIEF
N No Relief
T Internal Token Relief
Example: Type number CSB424DT: Type CSB400 regulator constructed for medium pressure applications, with Type VSX4 slam-shut module, Dual pressure registration and Internal Token relief.
1. Not available with Integral True-Monitor option.
2. Not available with Integral True-Monitor or Token Relief option.
3. Available with External Pressure Registration only.
4. Reference Instruction Manual D103126X012 for information regarding the Type TM600 Integral True-Monitor module.
5. Reference Instruction Manual D103127X012 for information regarding the Type VSX4 Slam-Shut module.
(2)
(Outlet Pressure: 0.50 to 3.0 bar / 7 to 43.5 psig)
(4)
(5)
(1)(3)
(Outlet Pressure: 17 to 100 mbar / 7 to 40 inches w.c.)
(1)(3)
(Outlet Pressure: 100 to 517 mbar / 40 to 208 inches w.c.)
(4)
(5)
WARNING
!
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion
and/or re causing property damage and
personal injury or death.
Fisher® regulators must be installed, operated, and maintained in accordance with federal, state, and local codes, rules and regulations and Regulator Technologies instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
Call a gas service person to service the
unit. Only a qualied person must install
or service the regulator.
Description
CSB400 Series regulators are typically installed on industrial and commercial applications. See Table 1 for
Available Congurations. Low, Medium and High outlet
pressure constructions are available via Types CSB400, CSB420 and CSB450, respectively, that provide outlet setpoints ranging from 17 mbar to 3.0 bar / 7 inches w.c. to 43.5 psig. Also available are upstream monitoring
congurations such as Types CSB410 and CSB430,
which are installed upstream of the primary regulator to provide overpressure protection.
Types that include an “F” refer to the cold temperature construction of the base Type number. For example, the Type CSB404F provides a cold temperature construction
of the Type CSB404. Refer to the Operating Temperature
section found on the following page for additional information regarding temperature capabilities and refer to Table 7 for inlet pressure limitations. For types that include an “F”, refer to the base type number for general information such as Principles of Operation, Maintenance instructions, Warnings and Cautionary notes.
3
Page 4
CSB400 Series
TS
REGULATOR SLAM SHUT SERIAL NO.
TEMP CLASS DOM
PS FLUID GROUP CAT LOC
Std: EN334
TYPE PSD
Pumax Pmax
Matl
Wds
Case
Failure Mode
REGULATOR
DN SEAT BODY PN MATL
0062
PED mfg: Chartres,
France
REGULATOR SLAM SHUT SERIAL NO.
PATENT PENDING
0062
SLAM SHUT
Std: EN14382
TS
PS FLUID GROUP CAT LOC
DN SEAT BODY PN MATL
RELAIS Pu Max
RELAY Max IN
MATL P max CASE Max OUT
TYPE PSD CLASS
Wdso Wdsu
OP range UP range
PED mfg: Chartres,
France
SLAM-SHUT NAMEPLATE
Figure 2. CSB400 Series Regulator, Slam-shut and Integral True-Monitor™ Nameplates and Labels
TYPE DESCRIPTION PED CATEGORY FLUID GROUP
CSB400, CSB400F, CSB410, CSB420,
CSB420F, CSB430 and CSB450
CSB404, CSB404F, CSB414, CSB424,
CSB424F, CSB434 and CSB454
European EN Reference Standards EN 334, EN 14382
TEMP CLASS DOM
REGULATOR NAMEPLATES
Table 2. PED Information
Base regulator I
Regulator with Slam-Shut Module IV
TYPE PSD
Pumax Pmax
Std: EN334
PATENT PENDING DOM
LOC
MAX EMER
Wds
REGULATOR
PED mfg: Chartres,
France
MAX IN ORIFICE SPG RANGE
OUT OUT
Failure Mode
TYPE NO.
INTEGRAL TRUE-MONITOR NAMEPLATE
Groups 1 and 2 according to PED 97/23/EC, 1st and 2nd family gas according to EN 437 or other
gases (compressed air, nitrogen).
The gas must be non-corrosive, clean
(ltration on inlet side necessary) and dry.
Matl Case
SERIAL NO.
RELIEF
MAX OP
Table 3. Integral Strength (IS) Pressure Ratings
MAXIMUM ALLOWABLE PRESSURE
TYPE
MAXIMUM EMERGENCY INLET PRESSURE
CSB400, CSB400F, CSB404 and CSB404F
CSB420, CSB420F, CSB424 and CSB424F
CSB450 and CSB454
CSB410 and CSB414
CSB403, CSB403F, CSB423 and CSB423F
CSB403 and CSB423
1. For the Integral Strength (IS) version, the maximum value of PS and P
P
S
bar psig bar psig
4.0 58 4.0 58
should be similar to the PSD used for the Differential Strength (DS) version.
umax
(1)
/
MAXIMUM OPERATING INLET PRESSURE
P
umax
Table 4. Differential Strength (DS) Pressure Ratings and Flow and Sizing Coefcients
TYPE
CSB400F and CSB404F
CSB403F and CSB423F 6.0 87 10.0 145
CSB403 and CSB423
CSB430 and CSB434
CSB400 and CSB404
CSB420F and CSB424F
CSB420 and CSB424
CSB450 and CSB454
1. If ordered with a PN 16 anged connection, PS rating is a maximum of 16.0 bar / 232 psig. PS rating may be lower than 16.0 bar / 232 psig as indicated by this table.
SPECIFIC MAXIMUM
ALLOWABLE
PRESSURE / MAXIMUM
EMERGENCY OUTLET
PRESSURE
PSD P
bar psig bar psig bar psig mm Inch CgCvC1X
MAXIMUM
OPERATING INLET
PRESSURE
umax
MAXIMUM
EMERGENCY
INLET PRESSURE
6.0 87 12.0 174
P
S
ORIFICE
(1)
SIZE
FLOW
COEFFICIENTS
WIDE OPEN
10.0 145 10.0 145CSB410 and CSB414
4.0 58
17.5 11/16 428 11 43 1.16 0.84 0.90
10.0 145 12.0 174
16.0 232 20.0 290
IEC SIZING
COEFFICIENTS
F
T
D
(1)
F
L
4
Page 5
Table 5. Body Sizes, Material, End Connections and Pressure Ratings
BODY MATERIAL INLET SIZE, NPS OUTLET SIZE, NPS END CONNECTION
1 1 1-1/4 1-1/4 114 4.5 1-1/2 1-1/2 114 4.5
NPT
2 2 127 5
1 1
1 1-1/4 114 4.5
Ductile Iron
1-1/4 1-1/4 114 4.5
Rp
1-1/2 1-1/2 114 4.5
2 2 127 5
DN 50 / 2 DN 50 / 2
DN 40 / 1-1/2
(1)
DN 40 / 1-1/2
(1)
CL150 FF 254 10
PN 10/16 254 10
PN 16 Slip-On 184 7.24 1 2-1/4 Rp x GAZ 105 4.1 1 1
WCC Steel
1-1/4 1-1/4 114 4.5 1-1/2 1-1/2 114 4.5
1 1
1-1/4 1-1/4 114 4.5
NPT
Rp
1-1/2 1-1/2 114 4.5
1. Uses Rp 1-1/2 x 1-1/2 threaded body with PN 16 slip-on anges.
Table 6. CSB400 Series Primary Regulator Outlet Pressure Ranges
TYPE
CSB400, CSB400F, CSB403, CSB403F, CSB404, CSB404F,
CSB410 and CSB414
CSB420, CSB420F, CSB423, CSB423F, CSB424, CSB424F,
CSB430 and CSB434
CSB450 and CSB454
OPERATING PRESSURE
RANGES, W
d
mbar Inch w.c. mm Inch mm Inch
17 to 24 6.8 to 9.6 GE30191X012 Pink 2.03 0.080 152 6.00
24 to 35 9.6 to 14 GE43955X012 Orange Stripe 2.19 0.086 110 4.35
35 to 60 14 to 24.1 GE30201X012 Dark Green 3.23 0.127 11 0 4.35
54 to 100 21.7 to 40 GE30202X012 Tan 2.85 0.112 127 5.00
100 to 160 1.45 to 2.3 psig GE35081X012 Purple Stripe 3.86 0.152 124 4.90
138 to 300 2.0 to 4.4 psig GE30192X012 Dark Blue 4.27 0.168 118 4.65
276 to 517 4 to 7.5 psig GE33121X012 Red 4.93 0.194 11 8 4.65
500 mbar to 1 bar 7.3 to 14.5 psig GE30203X012 Light Blue 5.59 0.220 102 4.00
1 to 3 bar 14.5 to 43.5 psig GE30204X012 Light Green 6.73 0.265 100 3.95
PART
NUMBER
CSB400 Series
FACE-TO-FACE DIMENSION BODY PRESSURE RATING
mm Inch bar psig
100 4
100 4
100 4
100 4
SPRING
COLOR
SPRING WIRE
DIAMETER
20.0 290
16.0 232
20.0 290
SPRING FREE LENGTH
Table 7. Primary Regulator and Integral True-Monitor™ Outlet Pressure Ranges
PRIMARY REGULATOR INTEGRAL TRUE-MONITOR
TYPE
CSB403
CB403F
CSB423
CB423F
1. Recommended minimum Integral True-Monitor setpoints shown.
Factory Setpoint Set Pressure Range
mbar psig mbar psig
20 8 in w.c. 17 to 24
and
and
30 12 in w.c. 24 to 35
50 20 in w.c. 35 to 60
138 2 100 to 160 1.45 to 2.3
207 3 138 to 300 2.0 to 4.4
345 5 276 to 517 4 to 7.5 Red GE33121X012
6.8 to
9.6 in w.c.
9.6 to
14 in w.c.
14 to
24 in w.c.
0.78 to
1.45
Color P/N
Pink GE30191X012
Orange
Stripe
Dark
Green
Tan GE30202X012
Purple
Stripe
Dark Blue
GE43955X012
GE30201X012
GE35081X012
GE30192X012
Factory Token Relief Set
% of
REG. Set
170% 35 14 in w.c.
150% 45 18 in w.c.
140% 70 1
130% 90 1.3 138 2 97 to 200
130% 180 2.6 241 3.5 197 to 255 2.6 to 3.7 Purple GE35081X012
125% 260 3.8 345 5
125% 430 6.25 448 6.5
mbar psig mbar psig mbar psig
No Token Relief 37 15 in w.c. 30 to 52
No Token Relief
No Token Relief
No Token Relief
No Token Relief 172 2.5 97 to 200
No Token Relief 276 4
No Token Relief 414 6
(1)
Factory Setpoint
52 21 in w.c. 45 to 75
70 1 65 to 99
103 1.5 97 to 200
(1)
Spring Range
21 in w.c.
30 in w.c.
40 in w.c.
1.4 to 2.9 Black GE30190X01269 1 54 to 100
248 to 414 3.6 to 6
352 to 517 5.1 to 7.5 Red GE33121X012
Color P/N
12 to
18 to
26 to
Blue GE30189X012
Green GE30196X012
Orange GE30225X012
Dark Blue
GE30192X012
5
Page 6
CSB400 Series
Table 8. Regulator and Slam-shut OPSO and UPSO Pressure Ranges
REGULATOR SLAM-SHUT MODULE
TYPE
Set Pressure
Range
Standard
Setpoints
Token Relief
(1)(2)
Set
Available
Token Relief
Range Shown
as a % of Regulator
Setpoint
Overpressure Shutoff (OPSO) Underpressure Shutoff (UPSO)
Minimum Required
Difference
between Token
Relief and OPSO Set
Standard
OPSO Set
(1)
Values
P
Range as a %
of Regulator
dso
OPSO Set
Setpoint
Standard
UPSO Set
(1)
Values
P
Range as a %
of Regulator
dsu
UPSO Set
Setpoint
CSB404,
CSB404F
and
CSB414
CSB424,
CSB424F
and
CSB434
mbar psig mbar psig mbar psig Min
17 to 240.25 to
24 to 350.35 to
35 to 600.51 to
54 to
0.8 to
100
100 to
1.5 to
160
138 to
2.0 to
300
276 to
4.0 to
517
500 to
7.3 to
1000
20 0.29 34 0.49
0.35 21 0.30 36 0.52 45 0.65 11 0.16
27 0.39 41 0.59
30 0.44 45 0.65 57 0.83 15 0.22
0.51
35 0.50 53 0.76 67 0.96 18 0.26
50 0.70 70 1.0
0.87 60 0.87 84 1.2 108 1.57 30 0.44
75 1.10 98 1.4
1.5 100 1.5 130 1.9 170 2.47 50 0.73
150 2.2 195 2.8
2.3 160 2.3 208 3.0 264 3.83 80 1.2
300 4.4 375 5.4 125% 140% 50 0.73 450 6.53 150% 165% 150 2.2 50% 70%
4.4
500 7.3 625 9.1 125% 140% 60 0.87 700 10.2 140% 180% 250 3.6 50% 70%
7.5
1000 14.5 - - - - - - - - - - - - - - - - - - - - - - - - 1320 19.2 112% 140% 500 7.3 50% 70%
14.5
170% 215% 8 0.12
150% 160% 10 0.14
140% 158% 16 0.23
130% 140% 20 0.29
130% 140% 40 0.58
(2)
Max mbar psig mbar psig Min Max mbar psig Min Max
43 0.62
215% 270%
51 0.74
190% 200%
90 1.3
180% 200%
128 1.85
170% 190%
248 3.59
165% 175%
10 0.15
50% 56%
14 0.20
50% 60%
25 0.36
50% 70%
38 0.54
50% 70%
75 1.1
50% 70%
1200 17.4 - - - - - - - - - - - - - - - - - - - - - - - - 1600 23.2 112% 133% 600 8.7
(3)
CSB454
1. Standard factory set shown. Factory set is at the Minimum value of the range indicated. Range indicated is a percentage of Setpoint. Percentage indicated is based on the Set Pressure Range in which that setpoint resides. If non-standard sets are required, adherence must be made to constraints shown in Table 7, including Token Relief Set Range, OPSO and UPSO set range and Minimum Required difference between Token Relief and OPSO Set.
2. Minimum Token Relief values apply to -20 to 60°C / -4 to 140°F service temperatures. For service below -20°C / -4°F, add 8 mbar / 0.12 psig to the minimum Token Relief value listed.
3. Token Relief is not available for the Type CSB454.
1000 to
3000
1500 21.6 - - - - - - - - - - - - - - - - - - - - - - - - 1900 27.6 112% 127% 750 10.9
14.5 to
43.5 2000 29.0 - - - - - - - - - - - - - - - - - - - - - - - - 2400 34.8 112% 120% 1000 14.5
3000 43.5 - - - - - - - - - - - - - - - - - - - - - - - - 3400 49.3 112% 113% 1500 21.8
50% 70%
Example: If a non-standard setpoint is needed, see the following example for the proper use of Table 8. Non-standard setpoint = 140 mbar / 2 psig, using the value presented above, the factory set of the token relief will be
1.3 x 140 = 182 mbar / 2.6 psig. The factory OPSO and UPSO set pressures are 165% and 50% of the non-standard setpoint, respectively. The resulting settings are: OPSO = 231 mbar / 3.4 psig and UPSO = 70 mbar / 1 psig.
6
Page 7
205 /
8.09
CSB400 Series
249 /
9.81
SPRING
(1)
REMOVAL
152 /
5.97
A
B
A
A/2
A/2
54 /
2.13
171 /
6.72
275 /
10.81
A
A/2
291 /
11.46
45 /
1.79
A
A/2
151 /
5.95
1 NPT
SCREENED
VENT
208 /
8.18
307 /
12.08
SPRING REMOVAL
146 /
5.77
SLAM-SHUT
MODULE
TRUE-MONITOR™
MODULE
(2)
A
A/2
GE34270
1. MAXIMUM SPRING REMOVAL CLEARANCE FOR BOTH THE PRIMARY REGULATOR AND INTEGRAL TRUE-MONITOR IS 158 mm / 6.2 inches.
2. MAXIMUM SPRING REMOVAL CLEARANCE FOR THE SLAM SHUT IS 80 mm / 3.1 inches.
Figure 3. CSB400 Series Dimensions
Table 9. CSB400 Series Dimensions
BODY SIZE, NPS
BODY END
CONNECTION STYLE
1
1-1/4 114 4.5
1-1/2 114 4.5
NPT or Rp
2 127 5
DN 50 / 2 CL150 FF or PN 10/16 254 10
1 x 1-1/4 Rp 114 4.5
1 x 2-1/4 Rp x GAZ 105 4.1 20 0.8
DN 40 / 1-1/2 PN 16 Slip-On 184 7.2 97 3.8
FACE-TO-FACE DIAMETER (A) PITOT TUBE (B)
mm Inch mm Inch
100 4
97 3.8
mm / INCH
7
Page 8
CSB400 Series
REGULATOR ORIFICE
REGULATOR DISK
M1143
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
REGULATOR ADJUSTING SCREW
REGULATOR CONTROL SPRING
BALANCED PORT ASSEMBLY
VALVE STEM
LEVER
TOKEN RELIEF SPRING
PUSHER POST
EXTERNAL CONTROL LINE (SENSE LINE)
Figure 4. Type CSB400DT Dual Registered Regulator Operational Schematic
Additional overpressure protection options include Types CSB403 and CSB423, which offer True-Monitor™ protection provided by an integral monitor module installed on the inlet side of the valve body. This Integral True-Monitor assumes control of the pressure to the downstream system should the primary regulator fail to regulate. The Types CSB404, CSB424 and CSB454 are examples of
CSB400 Series congurations that offer a slam-shut module that shuts off the ow of gas to the downstream system in
the event of outlet pressure rising above or falling below the
predened levels due to a failure.
Optional token relief is available, which acts as a low­capacity internal relief valve to relieve minor overpressure situations due to nicks or other minor damage to the
orice or disk, or due to thermal expansion of the
downstream system.
Internal, external or dual outlet pressure registration is available. Constructions with dual or external registration require an external control line / sense line. For quick changing loads, dual sense is recommended as it provides the quickest response time.
Principle of Operation
Type CSB400 Base Regulator Operation
Refer to Figure 4. When downstream demand
decreases, the pressure under the regulator diaphragm increases. This pressure overcomes the regulator setting (which is set by the regulator control spring). Through the action of the pusher post assembly, lever and valve stem, the valve disk moves closer to the
orice and reduces gas ow. If demand downstream
increases, pressure under the regulator diaphragm decreases. Spring force pushes the pusher post assembly downward, the valve disk moves away from
the orice, and the gas ow increases downstream
as the regulator opens in response to the decreased pressure underneath the regulator diaphragm.
Type numbers with a “T”, for example, Type CSB400IT, provide a token or low-capacity relief. The Token relief provides relief from minor overpressure caused by nicks
or dents on the orice or by thermal expansion of gas in
the downstream line. Token relief also provides a token or signal, in the form of odor, that an overpressure situation is occurring.
8
Page 9
CSB400 Series
EXTERNAL CONTROL LINE (SENSE LINE)
WIDE-OPEN INTEGRAL TRUE-MONITOR REGULATOR PRIMARY REGULATOR
M1145
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
MONITOR LEVER
MONITOR ADJUSTING SCREW
REGULATOR ORIFICE
MONITOR CONTROL SPRING
MONITOR DISK
MONITOR VALVE STEM
MONITOR ORIFICE
MONITOR OPENING SPRING
REGULATOR ADJUSTING SCREW
BALANCED PORT ASSEMBLY
REGULATOR VALVE STEM
REGULATOR LEVER
REGULATOR CONTROL SPRING
TOKEN RELIEF SPRING
PRESSURE RETAINING PLUG (DO NOT REMOVE WHILE UNIT IS PRESSURIZED)
REGULATOR PUSHER POST
Figure 5. Type CSB403IT Internally Registered Primary Regulator with Externally Registered Integral True-Monitor™ Operational Schematic
OPSO SET SPRING
PROXIMITY SWITCH PLUG
M1146
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
OPSO ADJUSTING SCREW
VENT
RESET KNOB
SLAM-SHUT DISK
TYPE VSX4 SLAM-SHUT MODULE PRIMARY REGULATOR
UPSO ADJUSTING SCREW
UPSO SPRING
SENSE BLOCKING SCREW
SLAM-SHUT ORIFICE
REGULATOR ORIFICE
VALVE STEM
LEVER
REGULATOR ADJUSTING SCREW
REGULATOR CONTROL SPRING
TOKEN RELIEF SPRING
EXTERNAL CONTROL LINE (SENSE LINE)
Figure 6. Type CSB404ET Externally Registered Regulator and Slam-shut Operational Schematic
9
Page 10
CSB400 Series
CSB400 SERIES REGULATOR
REGULATOR VENT POINTED DOWNWARD
GE27692
PROTECT VENT PIPE WITH RAIN CAP
NPS 2 TYPE 289H RELIEF VALVE
Figure 7. CSB400 Series Regulator Installed with the Vent Pointed Downward and with a
Type 289H Relief Valve for High Capacity Relief
Type CSB403 Integral True-Monitor™ Operation
Type CSB403 combines the operation of a conventional two-regulator wide-open monitor set into one body, see Figure 5. The Integral True-Monitor is installed on the
inlet side of the body and serves to throttle ow and
maintain an acceptable downstream pressure in the case where the primary regulator ceases to regulate downstream pressure. During normal operation the Integral True-Monitor is in a wide-open state as its setpoint is set higher than the primary regulator. See Table 7 for guidance regarding the setpoints of the regulator and associated Integral True-Monitor sets. If the downstream pressure should rise to the setpoint of the Internal Monitor due to a loss of pressure control by the primary regulator, the Integral True-Monitor
will assume control and regulate the ow to the
downstream system. If token relief is present, it will relieve a small amount of gas to the atmosphere as an indication that the Integral True-Monitor is controlling the downstream pressure.
The Type CSB403 provides the option of internal or external downstream pressure registration. External registration requires a downstream sensing line. See Figure 9 for guidance regarding installation of the
downstream control line. Refer to the Type TM600
Instruction Manual for additional details of Integral True-Monitor operation.
Type CSB404 Slam-shut Operation
The Type VSX4 slam-shut module on the Type CSB404 regulator is a fast acting shut-off device that provides overpressure (OPSO) or over and underpressure (OPSO / UPSO) protection by completely shutting off the
ow of gas to the downstream system. See Table 8 for
guidance regarding the typical setpoints of the regulator and associated slam-shut OPSO and also the combined OPSO and UPSO setpoints. The Type VSX4’s actions are independent of the Type CSB404 regulator and of variations to the inlet pressure. The Type VSX4 comes standard with external downstream pressure registration,
with the option for internal registration only on the Rp 1 x 2-1/4 GAZ body. External registration requires a
downstream sensing line. See Figure 10 for guidance regarding installation of the downstream control line.
The Type VSX4 shut-off disk is normally in the open (reset) position, see Figure 6. If the downstream pressure below the slam-shut diaphragm increases (or decreases) until it reaches the slam-shut setpoint, this diaphragm moves upward (or downward) to release the trip mechanism which allows the spring force on the stem to push the disk against the seat, shutting off
all gas ow. To reset the slam shut after gas has been
shut off, refer to the Type VSX4 Instruction Manual for additional details.
10
Page 11
CSB400 Series
In order for the Underpressure Shutoff (UPSO) of any slam shut to be triggered, the downstream pipe pressure must drop below the UPSO setpoint. In the case of a downstream line break, numerous factors can prevent the downstream pipe pressure from decreasing below the slam-shut UPSO setpoint. These factors include the distance of pipe to the break, the diameter of the pipe, size of the break and the number of restrictions, such as valves, elbows and bends, downstream of the regulator and/or slam-shut device. Due to these factors additional
protections should be installed to stop ow in the event
of a line break.
Installation and Overpressure Protection
Install in accordance with provisions of EN 12186 / EN 12279.
WARNING
!
Personal injury or system damage may result if this regulator is installed, without appropriate overpressure protection, where service conditions could exceed the limits
given in the Specications section and/
or regulator nameplate. Regulator and equipment installation should be adequately protected from physical damage.
All vents should be kept open to permit
free ow of gas to the atmosphere. Protect
openings against entrance of rain, snow, insects or any other foreign material that may plug the vent or vent line. On outdoor installations, point the spring case vent downward to allow condensate to drain, see Figures 7 through 10. This minimizes the possibility of freezing and of water or other foreign materials entering the vent and interfering with proper operation.
For the Type CSB403 with Integral True-Monitor™ or the Type CSB404 with Slam shut, point the vents of both the primary regulator and Integral True-Monitor or slam shut downward to allow condensate to drain. From the factory, the Integral True-Monitor or slam shut will always point in the same direction as that of the primary regulator.
Under enclosed conditions or indoors, escaping gas may accumulate and be an explosion hazard. In these cases, the vent should be piped away from the regulator to the outdoors.
In case of complete disassembly of the equipment (body included) from the pipeline, care must be taken not to bend, hit or otherwise damage the pitot tube (key 83 Figure 15) that protrudes beyond the body outlet. Damage to the pitot tube could result in inaccurate internal pressure registration and loss of regulation quality.
CAUTION
CSB400 Series regulators have an outlet pressure rating lower than their inlet pressure rating. If actual inlet pressure can exceed the outlet pressure rating, outlet overpressure protection is necessary. However, overpressuring any portion of the regulators beyond the
limits in the Specications section may
cause leakage, damage to regulator parts or personal injury due to bursting of pressure-containing parts.
Some type of external overpressure protection should be provided to the CSB400 Series if inlet pressure will be high enough to damage downstream equipment. Common methods of external overpressure protection include relief valves, monitoring regulators, shut-off devices, and series regulation.
If the regulator is exposed to an overpressure condition, it should be inspected for any damage that may have occurred. Regulator operation below the
limits specied in the Specications section
and regulator nameplate does not preclude the possibility of damage from external sources or from debris in the pipeline.
11
Page 12
CSB400 Series
INLET PRESSURE OUTLET PRESSURE
WIDE-OPEN MONITORING REGULATOR PRIMARY WORKING REGULATOR
MINIMUM OF 4 X OUTLET PIPING DIAMETER
UPSTREAM BLOCK VALVE
INLET PRESSURE
OUTLET PRESSURE
Figure 8. Type CSB400 “Series Monitor” Regulator Downstream Control Line Installation
Before installing the regulator, check for damage which might have occurred in shipment. Also check for dirt or foreign matter which may have accumulated in the regulator body or in the pipeline. Apply pipe compound to the external threads of the pipeline and install the regulator so that
ow is in the direction of the arrow cast on
the body. The diaphragm casing assembly can be rotated to any position relative to the body. Loosen the two cap screws (key 71, Figure 11) in order to rotate the diaphragm casing assembly.
General Installation Instructions
Before installing the regulator,
Check for damage, which might have occurred during shipment.
Check for and remove any dirt or foreign material, which may have accumulated in the regulator body.
DOWNSTREAM BLOCK VALVE
Blow out any debris, dirt or copper sulfate in the copper tubing and the pipeline.
Apply pipe compound to the external threads of the pipe before installing the regulator.
• Make sure gas ow through the regulator is in the same
direction as the arrow on the body. “Inlet” and “Outlet” connections are clearly marked.
Verify that:
- Equipment limits of utilization (PS, TS) corresponds
to the desired operating conditions.
- The inlet is protected by an appropriate device(s) to
avoid exceeding the allowable limits (PS, TS).
When designing a pressure reducing station using a CSB regulator, make an analysis if it is necessary to take into account the effects of wind, snow and temperature to avoid unnecessary load and
movement to the anges of the equipment.
If needed, a support may be used under the piping
and regulator/slam-shut body to avoid excessive pressure force on the regulator/slam shut.
12
Page 13
PRIMARY REGULATOR
CSB400 Series
M1062
UPSTREAM BLOCK VALVE
MINIMUM OF 4 X OUTLET PIPING DIAMETER
INTEGRAL TRUE-MONITOR™
Figure 9. Type CSB403 Downstream Control Line Installation
PRIMARY REGULATOR
DOWNSTREAM BLOCK VALVE
UPSTREAM BLOCK VALVE
M1063
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
MINIMUM OF 4 X OUTLET PIPING DIAMETER
SLAM SHUT
Figure 10. Type CSB404 Downstream Control Line Installation
DOWNSTREAM BLOCK VALVE
13
Page 14
CSB400 Series
Installation Location
The installed regulator should be adequately protected from vehicular trafc and damage from
other external sources.
Install the regulator with the vent pointed vertically down, see Figures 7 through 10. If the vent cannot be installed in a vertically down position, the regulator must be installed under a separate protective cover. Installing the regulator with the vent down allows condensation to drain, minimizes the entry of water or other debris from entering the vent, and minimizes vent blockage from freezing precipitation.
Do not install the regulator in a location where there can be excessive water accumulation or ice formation, such as directly beneath a downspout, gutter or roof line of building. Even a protective hood may not provide adequate protection in these instances.
Install the regulator so that any gas discharge through the vent or vent assembly is over 0.91 m / 3 feet away from any building opening.
Regulators Subjected to Heavy Snow Conditions
Some installations, such as in areas with heavy snowfall, may require a hood or enclosure to protect the regulator from snow load and vent freeze over.
CSB400 Series regulators with an “ET” or “EN” in the type number use external pressure registration. To communicate the downstream pressure to the regulator, connect a downstream control line tubing to the 3/4 NPT control line tapping in the lower diaphragm casing and connect the other end of the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter.
For Types CSB400 and CSB404 with external control lines, use tubing with an outer diameter of 9.5 mm /
0.375 inch or larger. For Types CSB420, CSB424, CSB450 and CSB454 with external control lines, use tubing with an outer diameter of 13 mm / 0.5 inch or larger.
The Types CSB410, CSB414, CSB430 and CSB434 are dedicated wide-open monitoring regulators and are
installed upstream of a primary working regulator. Refer
to Figure 8 for installation of the downstream control line. To communicate the downstream pressure to the wide-open monitor regulator, connect a downstream control line tubing to the 3/4 NPT control line tapping in the lower diaphragm casing of the monitor regulator and connect the other end of the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter.
For Types CSB410 and CSB414, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger.
For Types CSB430 and CSB434, use tubing with an outer diameter of 13 mm / 0.5 inch or larger.
Downstream Control Line Installation
WARNING
!
Failure to install a downstream control line could result in a hazardous condition. Install downstream control line(s) to the slam-shut device when construction uses external pressure registration.
The regulator and slam-shut device will not control pressure or shutoff if a downstream control line is not installed on those constructions where external pressure registration is required.
Downstream Control Line Installation with Integral True-Monitor™
Refer to Figure 9. When installing the Types CSB403
and CSB423 regulators, connect downstream control line tubing to the lower casing of the primary regulator, and run the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter. Connect a second, separate downstream control line tubing to the lower casing of the Integral True-Monitor, and run the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter.
For Type CSB403 with external control lines, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger for both the primary regulator and Integral True-Monitor.
14
Page 15
CSB400 Series
For Type CSB423 with external control lines, use tubing with an outer diameter of 13 mm / 0.5 inch or larger for both the primary regulator and Integral True-Monitor™.
Downstream Control Line Installation with Slam shut
Refer to Figure 10. When installing the Types CS404ET,
CS404EN, CSB424ET, CSB424EN and CSB454EN regulators, connect downstream control line tubing to the lower casing of the regulator and run the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter. Connect a second, separate downstream control line tubing to the lower casing of the slam shut and run the tubing downstream of the regulator outlet a minimum distance of 4 times the outlet pipe diameter.
For Type CSB404 with external control lines, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger for the primary regulator and 6.4 mm / 0.25 inch or larger for the slam shut.
For Types CSB424 and CSB454 with external control lines, use tubing with an outer diameter of 13 mm / 0.5 inch or larger for the primary regulator and 6.4 mm / 0.25 inch or larger for the slam shut.
Installation with External Overpressure Protection
If the regulator is used in conjunction with a Type 289H relief valve, it should be installed as shown in Figure 7. The outside end of the vent line should be protected with a rainproof assembly. The Type 289H is typically set 25 mbar / 10 inches w.c. higher than the outlet pressure setting of the regulator, up to 75 mbar / 30 inches w.c. outlet pressure. For pressure greater than this, set the Type 289H 0.05 bar / 0.75 psi higher than the outlet pressure setting of the regulator.
Vent Line Installation
The CSB400 Series regulators have a 1 NPT screened vent opening in the spring case. If necessary to vent escaping gas away from the regulator, install a remote vent line in the spring case tapping. Vent piping should be as short and direct as possible with a minimum number of bends and elbows. The remote vent line should have the largest practical diameter. Vent piping on regulators with token relief must be large enough
to vent all relief valve discharge to atmosphere without excessive backpressure and resulting excessive pressure in the regulator.
For types with optional Token relief, this low capacity relief is located in the spring case of the primary regulator. If necessary to vent escaping gas away, install a remote vent line in the spring case tapping of the primary regulator as described above. Periodically check all vent openings to be sure that they are not plugged or obstructed.
CSB400 Series outlet pressure ranges are shown in Table 6. Outlet pressure higher than 0.34 bar / 5 psig above the setpoint may damage internal parts such as the diaphragm head and valve disk. The maximum
emergency (casing) outlet pressure is 4.0 bar / 58 psig.
Commissioning
CAUTION
Pressure gauges must always be used to monitor downstream pressure during Startup.
With the downstream system depressurized, use the following procedure to start up the regulator.
1. Check to see that all appliances are turned off.
2. Slowly open the upstream shut-off valve.
3. Check inlet and outlet pressure for correct values.
4. Check all connections for leaks.
5. Turn on utilization equipment and recheck the pressures.
Adjustment
Note
For types that include the Integral True-Monitor module, refer to the Instruction Manual for Type TM600 Integral True-Monitor for adjustment and maintenance of the Integral True-Monitor. For the types that include the slam-shut module, refer to the Instruction Manual for Type VSX4 slam shut for adjustment and maintenance of the slam shut.
15
Page 16
CSB400 Series
The range of allowable pressure settings for the primary regulator is stamped on the nameplate. If the required setting is not within this range, substitute the correct spring (as shown in Table 6). If the spring is changed, re-stamp the nameplate to indicate the new pressure range.
A pressure gauge must always be used to monitor downstream pressure while adjustments are being made.
For Types CSB400 and CSB420
1. Remove the closing cap (key 60, Figure 16).
2. To increase the outlet setting, turn the adjusting screw (key 65) clockwise. To decrease the outlet setting, turn the adjusting screw counterclockwise.
3. Replace the closing cap.
For Type CSB450
1. Loosen the hex nut (key 58, Figure 16).
2. To increase the outlet setting, turn the adjusting screw (key 65, Figure 16) clockwise. To decrease the outlet setting, turn the adjusting screw counterclockwise.
3. Tighten the hex nut.
CSB400 Series with Integral True-Monitor™
When adjusting the primary regulator and Integral True-Monitor for operation, ensure that the pressure differences between the primary regulator and the integral monitor shown in Table 7 are observed. For example, if the primary regulator setpoint is set at 20 mbar / 8 inches w.c., then the Integral True-Monitor should be set at a minimum of 35 mbar / 14 inches w.c. or higher.
To test the Integral True-Monitor operation, the primary regulator setpoint must be adjusted above the Integral True-Monitor’s setpoint to simulate a failure of the primary regulator. If the spring range of the primary
regulator is sufciently high, it can simply be adjusted
above the Integral True-Monitor’s setpoint by following step 2 above. Otherwise, a different spring with a setpoint higher than the Integral True-Monitor’s setpoint must be installed to check the operation of the Integral True-Monitor.
CSB400 Series with Slam shut
When adjusting the primary regulator and slam shut for operation, refer to Table 8 for the OPSO setpoints and also the combined OPSO and UPSO setpoints of the slam shut for a given regulator spring ranges.
CAUTION
Equipment installed downstream the Type VSX slam shut device can be damaged if the following procedure for resetting the Type VSX slam shut device is not followed. This equipment includes the integral Type VSX or regulator configurations.
Step 1:
To properly reset the Type VSX slam shut after it has been tripped to the closed position, a at-head
screwdriver must be inserted into the position shown in Figure 8 on the backside of the reset button (refer to Type VSX4 Instruction Manual, key 30, Figure 8).
Step 2:
The screwdriver should be slowly rotated to gradually pull the reset button (refer to Type VSX4 Instruction Manual, key 30) away from the Type VSX device. This slow movement allows for a slow bleed of the pressure across the Type VSX slam shut’s disk and seat area. The operator should be able to hear the pressure bleeding through the system.
Step 3:
When the pressure has equalized and the air bleeding sound has dissipated, the reset button (refer to Type VSX4 Instruction Manual, key 30) should be pulled completely away from the Type VSX slam shut device by hand until the internal shut-off mechanism has been re-latched.
Step 4:
Once the operator feels the click of the re-latch occurring, the reset button (refer to Type VSX4 Instruction Manual, key 30) should be pushed completely back into its original position.
16
Page 17
19
55
L2
38
L2
L1
62
L2
60
L2
65
100
CSB400 Series
TORQUE:
1.7 TO 3.4 N•m /
L2
15 TO 30 INCH-POUNDS
96
4
6
20
19
L1
35
77
L1
75
L1
74
25
L2
TORQUE: 47 TO 61 N•m / 35 TO 45 FOOT-POUNDS
27
L1
21
18
11
L1
L1
ERAA04154
APPLY LUBRICANTS (L) / SEALANT (S)
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT L2 = ANTI-SEIZE LUBRICANT S1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Lubricants and sealant must be selected such that they meet the temperature requirements.
(1)
:
13
TORQUE:
1.7 TO 3.4 N•m / 15 TO 30 INCH-POUNDS
14
10
L1
22
S1
5
7
95
8
TORQUE:
1.7 TO 3.4 N•m / 15 TO 30 INCH-POUNDS
51
Figure 11. CSB400 Series Regulator Assembly
WARNING
!
In the case of a downstream line break, numerous factors affect the capability to evacuate gas from the pipeline. These factors include the distance of pipe to the break, the diameter of the pipe, size of the break and the number of restrictions, such as valves, elbows and bends, downstream of the regulator and/or slam-shut device. Due to these factors additional protections
should be installed to stop ow in the
event of a line break.
Dow Corning® is a mark owned by Dow Corning Corporation.
Shutdown
Installation arrangements may vary, but in any installation it is important that the valves be opened or closed slowly and that the outlet pressure be vented before venting inlet pressure to prevent damage caused by reverse pressurization of the regulator. The following steps apply to the typical installation as indicated.
1. Open valves downstream of the regulator.
2. Slowly close the upstream shut-off valve.
3. Inlet pressure should automatically be released
downstream as the regulator opens in response to the lowered pressure underside of the diaphragm.
4. Close outlet shut-off valve.
17
Page 18
CSB400 Series
3
2
1
15
16
9
TORQUE:
7.1 TO 10.1 N•m / 63 TO 90 INCH-POUNDS
S1
72
TORQUE: 14 TO 18 N•m /
80
10 TO 13 FOOT-POUNDS
76
70
TORQUE: 14 TO 18 N•m /
71
10 TO 13 FOOT-POUNDS
17
ERAA04154
APPLY SEALANT (S)
S1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Sealant must be selected such that it meets the temperature requirements.
2. The torque range as specied is initial assembly torque. Due to elastomeric compression, the torque values indicated may decrease. Minimum inspection torque is 4 N•m / 35 inch-pounds.
(1)
:
Figure 11. CSB400 Series Regulator Assembly (continued)
18
Page 19
CSB400 Series
Maintenance and Inspection
WARNING
!
To avoid personal injury or equipment damage, do not attempt any maintenance
or disassembly without rst isolating
the regulator from system pressure and relieving all internal pressure as described in “Shutdown”.
Regulators that have been disassembled for repair must be tested for proper operation before being returned to service. Only parts manufactured by Regulator Technologies should be used for repairing Fisher® regulators. Restart gas utilization equipment according to normal startup procedures.
Due to normal wear or damage that may occur from external sources, this regulator should be inspected and maintained periodically. The frequency of inspection and replacement depends on the severity of service conditions, test results found during the annual test, and on applicable codes and regulations. In accordance with applicable National or Industry codes, standards and regulations/recommendations, all
hazards covered by specic tests after nal assembly, before applying the CE
marking, shall also be covered after every subsequent reassembly at installation site in order to ensure that the equipment will be safe throughout its intended life.
Periodic inspection must be performed on the CSB400 Series that include the Integral True-Monitor™ or slam-shut overpressure protection modules to ensure that they protect the downstream system in the event the primary regulator losses pressure control. This inspection must test that the Integral True-Monitor or slam-shut functions as intended.
Note
For adjusting setpoints above 100 mbar /
1.5 psig, use a 13 mm / 1/2-inch hex driver, a 13 mm / 1/2-inch socket or a 27 mm / 1-1/16-inch socket to turn the adjusting screw (key 65).
Disassembly to Replace the Regulator Main Diaphragm
1. Remove the closing cap (key 60, Figure 11) or loosen
hex locknut (key 58, Figure 16). Turn the adjusting screw (key 65) or nut (key 58) counterclockwise to ease spring (key 38) compression.
2. Remove the adjusting screw (key 65) and spring
(key 38).
3. Remove hex nuts (key 16, Figure 11) and cap screws
(key 15, Figure 11). Separate the upper spring case (key 1) from the lower casing assembly (key 9).
Note
When disassembling a CSB400 Series regulator, lift the upper spring case (key 1) straight up in order to avoid hitting the stem (key 44).
4. Slide the diaphragm assembly (key 55) away
from the body (key 70) to unhook the pusher post (key 51) from the lever (key 10). Lift off the diaphragm assembly (key 55).
5. a. For none relieving units such as the
Types CSB400IN and CSB400EN, unscrew the cap (key 45), see Figure 12, high-pressure Non-
Relief and low-pressure Non-Relief assemblies. The cap fastens the R.V. spring seat (key 43)
to the pusher post (key 51). Unscrew the cap to
separate the R.V. spring seat (key 43), diaphragm
assembly (key 55) and pusher post (key 51).
b. For units with internal token relief such as
Type CSB400IT, refer to Figure 12, unscrew the adjusting upper seat (key 47). This will allow for
removal of the relief spring (key 41), R.V. spring
seat (key 43), diaphragm assembly (key 55) and pusher post (key 51).
19
Page 20
CSB400 Series
6. Reassemble the spring case (key 1) unit in the reverse order of the above steps. Before tightening the cap screws (key 15) or stem (key 44) into the pusher post (key 51), place the loosely-assembled diaphragm assembly (key 55) into position in the lower casing (key 9), being sure that the pusher post (key 51) is hooked on the lever (key 10). Rotate the diaphragm (key 55A) so that the diaphragm and lower casing (key 9) holes are aligned. Tighten the stem (key 44) or diaphragm retainer (key 45) for HP and LP non-relief assemblies.
Disassembly to Replace Valve Disk, Balanced Port Assembly Diaphragm and
Regulator Orice
1. Remove the bolts (key 71, Figure 11) which hold the lower spring casing (key 9) to the body (key 70). Separate the lower spring casing (key 9) from the body (key 70).
2. Check the body O-ring (key 21) for wear.
3. Remove the balanced port assembly (key 35, Figures 11 and 13) from the body, make sure to rotate the assembly toward the outlet of the body as it is being removed to clear the sense tube from the body.
4. Examine the valve disk (key 35K) for nicks, cuts and other damage. If damage is present, it is recommended to replace both the disk and also the balanced port diaphragm (key 35F) and associated diaphragm O-ring (key 35M), that comes into direct
contact with the inner ange of the balanced port
diaphragm. Start the process of replacing the disk by disassembling the balanced port assembly.
Remove the four cap screws (key 35R) and then the
cap (key 35G).
5. Grasp the spring retainer (key 35C) and slide the brazed housing (key 35A) away to expose the diaphragm (key 35F) and disk (key 35K). Still grasping the spring retainer (key 35C) insert a 5 mm Allen wrench into the disk screw (key 35E) and unscrew.
6. Remove the disk (key 35K) and discard if damaged Slide the diaphragm O-ring (key 35M) off the stem (key 35B) along with the diaphragm (key 35F). Slide the new diaphragm over the stem in the same manner that it was removed, make sure that it completely contacts the surface of the inner retainer (key 35J).
7. Reassemble the Balanced Port assembly in reverse order of the above. Ensure Dow Corning® 33 or comparable extreme low temperature lubricant completely coats the O-ring (key 35M), stem (key 35B) and the center bore of the outer retainer (key 35H).
8. Examine the seating edge of the orice (key 25). If
it is nicked or rough, replace the orice and O-ring
(key 27). If a slam shut or monitor is installed on the backside of the body, refer to the applicable Instruction Manual for inspection and removal of the
overpressure protection orice (key 26) and O-ring
(key 27).
9. Reassemble the regulator in reverse order of the above steps.
Regulator Reassembly
As indicated by the square callouts in Figures 11 to 17, it is recommended that a good quality pipe thread sealant
be applied to pressure connections and ttings and a
good quality extreme low temperature lubricant, such as Dow Corning® 33, be applied to O-rings. Also apply an anti-seize compound to the adjusting screw threads,
orice threads and other noted areas as needed.
Parts Ordering
The type number, orice size, spring range and date of
manufacture are stamped on the nameplate. Always provide this information in any correspondence with
your local Sales Ofce regarding replacement parts or
technical assistance.
When ordering replacement parts, reference the key number of each needed part as found in the following parts list. Separate kit containing all recommended spare parts is available.
Dow Corning® is a mark owned by Dow Corning Corporation.
20
Page 21
Parts List
CSB400 Series
Key Description Part Number
Spare Parts (Repair Parts Kit include keys 12, 19, 21, 27, 35K, 55, 62, 75 and 77)
Type CSB400 RCSB400X012 Type CSB403 RCSB403X012 Type CSB404 RCSB404X012
1 Spring Case, Aluminum GE24555X012 2 Vent Screen, 18-8 Stainless steel T1121338982
3 Retaining Ring, Steel T1120925072
4 Stabilizer Guide, 304 Stainless steel GE27061X012 5 Stabilizer, Acrylonitrile Butadiene Styrene (ABS) GE27063X012 6 Stabilizer Spring, Stainless steel GE35010X012
7 Retainer Ring, Zinc-plated steel GE27024X012 8 Stabilizer Screw, Zinc-plated steel (3 required) GE29724X012
9 Lower Casing, Aluminum GE24289X012 10 Lever, Steel Types CSB400, CSB403, CSB404, CSB410 and CSB414 GE28773X012 Types CSB420, CSB423, CSB424, CSB430, CSB434, CSB450 and CSB454 GE28772X012 11 Valve Stem, Aluminum GE27812X012
12* O-ring, Nitrile (NBR) External Registration Only 1E472706992
13 Lever Pin, 18-8 Stainless steel Types CSB400, CSB403, CSB404, CSB410 and CSB414 T14397T0012 Types CSB420, CSB423, CSB424, CSB430, CSB434, CSB450 and CSB454 (2 required) T14397T0012 14 Lever Screw, Steel Types CSB400, CSB403, CSB404, CSB410 and CSB414 (2 required) GE34243X012 Types CSB420, CSB423, CSB424, CSB430, CSB434, CSB450 and CSB454 (4 required) GE34243X012 15 Cap Screw, Steel (8 required) GE32059X012 16 Nut, Steel (8 required) GE32060X012
17 Union Ring, Aluminum GE26590X012 18 Snap Ring, 302 Stainless steel T1120637022 19* O-ring, Nitrile (NBR) (2 required) 1K594906562
20 Stem Guide, Aluminum GE26027X012
21* O-ring, Nitrile (NBR) GE45216X012
22 Pipe plug, 3/4 NPT, Steel
Internal Registration Only GE34199X012
23 Screw (For external registration only), Steel (2 required) 1E175828982 24* O-ring (For external registration only),
Nitrile (NBR) (2 required) 17A0960X012 25 Orice
Types CSB400F and CSB404F, Aluminum GG08494X012 All other Types, Brass GE31321X012
26 OPP Orice 18 mm / 0.69 inch With Integral True-Monitor™ Orice, Aluminum GE30003X012 With Slam-shut Orice, Brass GE28684X012 27* O-ring, Nitrile (NBR)
Type CSB400 (1 required) 10A3802X022 Type CSB403 (2 required) 10A3802X022 Type CSB404 (2 required) 10A3802X022
35 Balanced Port Assembly for all bodies except GAZ
Standard GE31196X012 Low temperature “F” version GE31196X022 35A Brazed Housing GE31261X012 35B Stem, Stainless steel GE31191X012
35C Spring Retainer, Zinc-plated steel GE31189X012
35D Spring, Stainless steel GE30193X012
35E Disk Screw, Zinc-plated steel GE31190X012 35F* Diaphragm, Nitrile (NBR) / Fabric GE30439X012
35G Cap, Brass GE31195X012
Key Description Part Number
35H Outer Retainer, Brass GE31187X012 35J Inner Retainer, Brass GE31186X012 35K* Disk Assembly, Brass / Nitrile (NBR)
Standard version ERSA00457A0 Low Temperature “F” version GE31185X012
35M O-ring, Nitrile (NBR) (2 required) 1E472706992 35N* O-ring, Nitrile (NBR) 1U879006562 35R Screw, Steel (4 required) GE25968X012 35S Pin, Zinc-plated steel GE31232X012 35 Balanced port assembly for Rp 1 x 2-1/4, GAZ Body
Standard GE33822X012
Low temperature “F” version GE33822X022 35A Brazed Housing GE32505X012 35B Stem, Stainless steel GE31191X012
35C Spring Retainer, Zinc-plated steel GE31189X012
35D Spring, Stainless steel GE30193X012
35E Disk Screw, Zinc-plated steel GE31190X012 35F* Diaphragm, Nitrile (NBR) / Fabric GE30439X012
35G Cap, Brass GE31195X012
3 5 H O u t e r R e t a i n e r , B r a s s G E 3 1 1 8 7 X 0 1 2 35J Inner Retainer, Brass GE31186X012 35K* Disk Assembly, Brass / Nitrile (NBR)
Standard version ERSA00457A0
Low-temperature “F” version GE31185X012
35M O-ring, Nitrile (NBR) (2 required) 1E472706992 35N* O-ring, Nitrile (NBR) 1U879006562 35R Screw, Cap, Hex Socket, Steel (4 required) GE25968X012
38 Spring
17 to 24 mbar / 6.8 to 9.6 inches w.c., Pink GE30191X012
24 to 35 mbar / 9.6 to 14 inches w.c., Orange Stripe GE43955X012
35 to 60 mbar / 14 to 24 inches w.c., Dark Green GE30201X012
54 to 100 mbar / 0.78 to 1.5 psig, Tan GE30202X012
100 to 160 mbar / 1.45 to 2.3 psig, Purple Stripe GE35081X012
138 to 30 0 mbar / 2.0 to 4.4 psig, Dark Blue GE30 1 9 2X012
276 to 517 mbar / 4 to 7.5 psig, Red GE33121X012
500 mbar to 1 bar / 7.3 to 14.5 psig, Light Blue GE30203X012
1 to 3 bar / 14.5 to 43.5 psig, Light Green GE30204X012 40 Upper Spring Seat, Steel
High Pressure, Zinc-plated steel GE32501X012 41 Relief Valve Spring, 302 Stainless steel
Types CSB400, CSB403 and CSB404, Token GE30194X012
Types CSB420, CSB423 and CSB424, Token GE42225X012
43 Relief Valve Spring Seat, Zinc-plated steel
Types CSB400 and CSB420, Non-Relief GE27327X012
Type CSB450, Non-Relief GE31677X012
Types CSB400 and CSB420, Token GE28947X012 44 Stem, Aluminum
Types CSB400 and CSB420, Token GE30895X012
45 Diaphragm Retainer, Zinc-plated steel
Types CSB400 and CSB420, Non-Relief GE30887X012
Type CSB450, Non-Relief GE33850X012
47 Upper Spring Seat, Aluminum
Types CSB400 and CSB420, Token GE33332X012
48 Restrictor Plate, Zinc-plated steel
Token GE28948X012 51 Pusher Post, Aluminum
Token ERAA00876A0
Non-Relief ERAA00875A0 53 Solid Rivet, 18-8 Stainless steel GE29761X012 54 Roller Pin, Brass GE27060X012 55* Diaphragm Assembly, Steel / Nitrile (NBR)
Without Diaphragm Head Limiter GE31248X012
With Diaphragm Head Limiter GE32140X012 55A Diaphragm - - - - - - - - - - ­55B Diaphragm Head - - - - - - - - - - -
*Recommended spare part.
21
Page 22
CSB400 Series
TORQUE: 6 TO 8 N•m / 50 TO 70 INCH-POUNDS
44
48
55B
A
55A
56
NOTE DIRECTION OF RETAINER RING INSTALLATION
TOKEN RELIEF
47
41
43
51
53
54
TORQUE: 6 TO 8 N•m / 50 TO 70 INCH-POUNDS
45
55B
A
55A
56
NOTE DIRECTION OF RETAINER RING INSTALLATION
HIGH-PRESSURE NON-RELIEF
43
107
108
109
51
53
54
TORQUE:
A
6 TO 8 N•m / 50 TO 70 INCH-POUNDS
55A
55B
45
43
51
56
53
NOTE DIRECTION OF RETAINER RING INSTALLATION
56
NOTE DIRECTION OF RETAINER RING INSTALLATION
ERAA04154
APPLY ADHESIVE (A) A = ADHESIVE
NOTE: APPLY ADHESIVE ON THE FLAT SURFACE OF THE DIAPHRAGM PLATE THAT CONTACTS THE DIAPHRAGM, TOWARD THE OUTER PERIMETER,
AND AWAY FROM THE CENTER HOLE.
1. Adhesive must be selected such that it meets the temperature requirements.
(1)
:
LOW-PRESSURE NON-RELIEF
54
22
Figure 12. CSB400 Series Diaphragm and Relief Assemblies
Page 23
CSB400 Series
TORQUE:
2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS
35M
L1
35E
35K
35F
35J
35S
35A
L1
35N
35H
L1
35M
35B
35C
35D
35R
35G
S2
TORQUE:
2.3 TO 2.8 N•m / 20 TO 25 INCH-POUNDS
TORQUE:
0.9 TO 1.4 N•m / 8 TO 12 INCH-POUNDS
STANDARD BALANCED PORT ASSEMBLY
35F
35J
35M
L1
TORQUE:
2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS
35E
35K
BALANCED PORT ASSEMBLY FOR Rp 1 X 2-1/4 GAZ BODY
ERAA04154
APPLY LUBRICANT (L) / SEALANT (S)
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT S2 = PERMANENT THREAD SEALANT
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
(1)
:
35N
35A
35H
L1L1
35M
35B
S2
35C
35D
35R
35G
TORQUE:
2.3 TO 2.8 N•m / 20 TO 25 INCH-POUNDS
TORQUE:
0.9 TO 1.4 N•m / 8 TO 12 INCH-POUNDS
Dow Corning® is a mark owned by Dow Corning Corporation.
Figure 13. Balance Trim Assemblies
23
Page 24
CSB400 Series
L1
L1
L1
REF HOLES “B”
L1
20
L1
12
11
20
INTERNAL OR DUAL REGISTRATION
(NO SCREWS)
11
L1
L1
B
EXTERNAL REGISTRATION
23
24
B
TORQUE:
1.7 TO 3.4 N•m / 15 TO 30 INCH-POUNDS INSTALL IN “B” HOLES (THROUGH HOLES)
L1
GE27692
APPLY LUBRICANT (L) L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
1. Lubricant must be selected such that it meets the temperature requirements.
(1)
:
Figure 14. CSB400 Series Stem Guides
Dow Corning® is a mark owned by Dow Corning Corporation.
24
Page 25
CSB400 Series
80
TORQUE: 14 TO 18 N•m / 10 TO 13 FOOT-POUNDS
74
76
ERAA04154
77
L1
DUCTILE / STEEL BODY
APPLY LUBRICANT (L) / SEALANT (S) L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT S2 = PERMANENT THREAD SEALANT
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
(1)
:
75
L1
101
70
L1
L1
75
77
80
TORQUE: 14 TO 18 N•m / 10 TO 13 FOOT-POUNDS
74
76
S2
83
GAZ BODY
82
TORQUE:
1.7 TO 3.4 N•m / 15 TO 30 INCH-POUNDS
81
Figure 15. Standard Body Assembly and Rp 1 x 2-1/4 GAZ Body Assembly
L2 L1
65
L2
ERAA04154
APPLY LUBRICANT (L) L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT L2 = ANTI-SEIZE LUBRICANT
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
62
38
96
CSB400 / CSB420 SERIES STANDARD
(1)
:
60
100
38
40 62 58
L1
L2 L2
65 61
CSB450 SERIES HIGH PRESSURE
57
Figure 16. CSB400 Series Control Spring Adjustment Assemblies
Dow Corning® is a mark owned by Dow Corning Corporation.
25
Page 26
CSB400 Series
L2
27
L1
2770 25 101
L2
L1
26
TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS
TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS
L2
L1
26
INTEGRAL TRUE-MONITOR™ ASSEMBLY
L1
27
70 27 25 101
L1
L1
L2
L2
TORQUE: 47 TO 61 N•m / 35 TO 45 FOOT-POUNDS
TORQUE: 47 TO 61 N•m / 35 TO 45 FOOT-POUNDS
L2
27
26
TORQUE:
47 TO 61 N•m /
35 TO 45 FOOT-POUNDS
TORQUE:
14 TO 18 N•m /
10 TO 13 FOOT-POUNDS
SLAM-SHUT ASSEMBLY
ERAA04154
APPLY LUBRICANTS (L) L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT L2 = ANTI-SEIZE LUBRICANT
1. Lubricants must be selected such that they meet the temperature requirements.
(1)
:
2770 25 101
Figure 17. CSB400 Series Slam-shut and Integral True-Monitor Modules
Dow Corning® is a mark owned by Dow Corning Corporation.
26
Page 27
Parts List (continued)
CSB400 Series
Key Description Part Number
56 Retaining Ring, Pusher Post Pin GE33772X012
57 Bearing ball GE33131X012 58 Hex Nut, High-Pressure, (CSB450 Series only) Steel GE33132X012 60 Closing Cap, Low-Pressure, Aluminum GE29244X012 61 Bonnet, High-Pressure,
(CSB450 Series only) Zinc-plated steel GE32499X012 62* O-ring, Nitrile (NBR) T10275X0012
65 Adjust Screw
Low-Pressure, Aluminum GE27828X012 High-Pressure, Steel GE32500X012
70 Body
Ductile Cast Iron NPT: 1 GE26463X012 1-1/4 GE26465X012 1-1/2 GE26466X012 2 GE26467X012
Rp: Rp 1 GE26468X012 Rp 1-1/4 GE26469X012 Rp 1-1/2 GE26470X012 Rp 1 x 1-1/4 GE42505X012 Rp 1 x 2-1/4, GAZ GE26482X012 Rp 2 GE26471X012
Flange: DN 50 / NPS 2, CL150 FF GE26480X012 DN 40 / NPS 1-1/2, PN 10/16 Slip-Flange GE44902X012 DN 50 / NPS 2, PN 10/16 GE26481X012 WCC Steel NPT: 1 GE26463X022 1-1/4 GE26465X022 1-1/2 GE26466X022
Rp Rp 1 GE26468X022 Rp 1-1/4 GE26469X022 Rp 1-1/2 GE26470X022
Key Description Part Number
71 Bolt, Steel (2 required) GE32061X012 72 Pipe Plug, 1/4 NPT
Steel 1C333528992
316 Stainless steel 1C3335X0012 74 Blanking Plug, Aluminum GE31255X012
75* O-ring, Metric, Nitrile (NBR) GF03442X012
76 Half Flange, Steel (2 required) GF01942X012
77* Metric O-ring, Nitrile (NBR) GF03443X012
80 Cap Screw, Steel (4 required) GE38176X012 81 Slotted Spring Pin GE32503X012
82 Tube Gasket, Nitrile (NBR) GE32502X012
83 Pitot Tube, Aluminum GE31988X012 90 Nameplate - - - - - - - - - - ­91 Warning Label - - - - - - - - - - ­93 Information Label - - - - - - - - - - ­94 Overlay Label - - - - - - - - - - -
95 Grommet, Nitrile (NBR) GE35358X012
96 Slip Disk, Stainless steel GG05787X012 100 Wire and Seal T14088T0012 101 Spring Pin, Steel GE32724X012
104 Hub, Zinc-plated steel (2 required) not shown GG02505X012 105 Flange Slip, Zinc-plated steel (2 required) not shown GG02508X012 106 O-ring, Nitrile (NBR) (2 required) not shown GE41121X012 107 Diaphragm Head Limiter, Zinc-plated steel GE28761X012 108 Diaphragm Protector, Zinc-plated steel GE42747X012
109 Pad, (CSB450 Series only) T13830T0012
27
Page 28
CSB400 Series
Industrial Regulators
Emerson Process Management Regulator Technologies, Inc.
USA - Headquarters McKinney, Texas 75070 USA Tel: +1 800 558 5853 Outside U.S. +1 972 548 3574
Asia-Paci c
Shanghai 201206, China Tel: +86 21 2892 9000
Europe Bologna 40013, Italy Tel: +39 051 419 0611
Middle East and Africa Dubai, United Arab Emirates Tel: +011 971 4811 8100
For further information visit www.emersonprocess.com/regulators
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees,
express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or speci cations of such products at any
time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
Natural Gas Technologies
Emerson Process Management Regulator Technologies, Inc.
USA - Headquarters McKinney, Texas 75070 USA Tel: +1 800 558 5853 Outside U.S. +1 972 548 3574
Asia-Paci c
Singapore 128461, Singapore Tel: +65 6770 8337
Europe Bologna 40013, Italy Tel: +39 051 419 0611 Chartres 28008, France Tel: +33 2 37 33 47 00
Middle East and Africa Dubai, United Arab Emirates Tel: +011 971 4811 8100
TESCOM
Emerson Process Management Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238 +1 800 447 1250
Europe Selmsdorf 23923, Germany Tel: +49 38823 31 287
Asia-Paci c
Shanghai 201206, China Tel: +86 21 2892 9499
The distinctive swirl pattern cast into every actuator
casing uniquely identi es the regulator as part of the
Fisher® brand Commercial Service Regulator family and assures you of the highest-quality engineering, performance, and support traditionally associated with Fisher®, Francel™ and Tartarini™ regulators. Visit www.fishercommercialservice.com to access interactive applications.
©Emerson Process Management Regulator Technologies, Inc., 2009, 2014; All Rights Reserved
Loading...