Emerson CS800 Instruction Manual

Instruction Manual Form 5837
November 2014
CS800 Series
CS800 Series Commercial / Industrial Pressure Reducing Regulators
P1235
TYPE CS800 REGULATOR
P1521
TYPE CS803 REGULATOR WITH TRUE-MONITOR™ PROTECTION
Figure 1. Typical CS800 Series Pressure Reducing Regulators
Introduction ............................................................................1
Speci cations ........................................................................2
Principle of Operation ............................................................3
Installation and Overpressure Protection ............................10
Startup .................................................................................14
Adjustment...........................................................................14
Shutdown.............................................................................16
Maintenance and Inspection................................................16
Parts Ordering .....................................................................20
Parts List..............................................................................22
P1234
TYPE CS800IQ WITH HIGH CAPACITY RELIEF
P1692
TYPE CS804IT REGULATOR WITH INTEGRAL
TYPE VSX8 SLAM-SHUT MODULE
Introduction
Scope of the Manual
This Instruction Manual provides instructions for the installation, maintenance and parts ordering information of CS800 Series service regulators. Instructions and parts list for the Type TM600 Integral True-Monitor are found in Instruction Manual D103126X012. Instructions and parts list for the Type VSX8 slam-shut are found in Instruction Manual D103127X012.
D103124X012
www.fisherregulators.com
CS800 Series
Specications
The Specications section lists the specications for the CS800 Series regulators. The following information is stamped on the regulator at the factory: Type number, date of manufacture, spring range, orice size, maximum inlet pressure, maximum operating outlet pressure and outlet pressure. Exceeding any of these limits may damage regulator parts.
Available Congurations
See Table 1
Body Sizes, Material, End Connections and Pressure Ratings
(1)
See Table 3
Maximum Inlet Pressures
(1)
Emergency: 175 psig / 12.1 bar Operating: See Table 4
Maximum Outlet Pressure
(1)
Emergency Regulator Casing: 15 psig / 1.0 bar Integral Monitor Casing: 25 psig / 1.7 bar Integral Slam-shut Casing: 87 psig / 6.0 bar To avoid internal parts damage: 3 psig / 0.21 bar
differential above outlet pressure setting
Operating Pressure Ranges
(1)
Regulator: See Table 5 Integral True-Monitor™: See Tables 8 and 9 Slam-shut Module: See Tables 10 to 11
Secondary Seat™ Protection Outlet Pressures
See Table 7
Spring Case Vent Connection
Internal Relief: 1 NPT High Capacity Relief: 2-1/2 NPT
Internal Relief Performance
See Table 6
Token Relief Performance
Approximate Token Relief Start-to-Discharge:
See Table 6
Orice Sizes, Flow Coefcients and IEC Sizing Coefcients
See Table 4
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Product has passed Emerson Process Management Regulator Technologies, Inc. (Emerson™) testing for lockup, relief start-to-discharge and reseal down to -40 degrees.
Pressure Registration
Internal or External
Temperature Capabilities
(1)(2)
-20 to 150°F / -30 to 66°C
According to European PED Directive that rates products to a minimum temperature of -4°F / -20°C and a maximum temperature of 140°F / 60°C:
-4 to 140°F / -20 to 60°C
Approximate Weight
With Threaded Body
Type CS800/CS820: 25 lbs / 11 kg Type CS803/CS823: 34 lbs / 16 kg Type CS804/CS824: 31 lbs / 16 kg Type CS805/CS825: 26 lbs / 12 kg Type CS806/CS826: 26 lbs / 12 kg
High-Pressure Types
For CS85x add 2 lbs / 1 kg to types listed above
With Flanged Body
Add 11 lbs / 5 kg to weights listed above
PED Conformity Statement and Information
Types CS800, CS804, CS820, CS824, CS850 and CS854 are in conformity with the Pressure Equipment
Directive PED 97/23/EC and are classied under
Category I for units without a slam-shut and Category IV for units with a slam-shut. See Table 2.
For Types CS800, CS820 and CS850, equipment and pipeline situated on outlet side of the regulator are either
- not subject to the PED (PS ≤ 0.5 bar) or
- subject to (PS > 0.5 bar) in which case they should
come under Category I maximum
PED Related Information
See Table 2
WARNING
!
Failure to follow these instructions or to properly install and maintain this equipment
could result in an explosion and/or re
causing property damage and personal injury or death.
®
Fisher
regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson™ instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
2
Call a gas service person to service the
unit. Only a qualied person must install or
service the regulator.
Description
CS800 Series regulators are typically installed on industrial and commercial applications. See Table 1 for available
congurations. Constructions with External Registration, e.g., Type CS800EN, require an external control line.
The CS800 Series offers multiple forms of overpressure protection including:
Internal Relief - Minimizes downstream pressure buildup
by relieving gas through the diaphragm assembly and out the 1 NPT vent to atmosphere in the event of an overpressure situation.
C S 8
Table 1. Available Congurations
TYPE NUMBER
OUTLET PRESSURE CONSTRUCTION
0 Low Pressure Applications (Outlet Pressure: 3.5 to 30 in. w.c. / 9 to 75 mbar)
2 Medium Pressure Applications (Outlet Pressure: 1 to 5.5 psig / 0.07 to 0.38 bar)
5 High Pressure Applications (Outlet Pressure: 5 to 10 psig / 0.34 to 0.69 bar)
OVERPRESSURE PROTECTION MODULE
0 Without Overpressure Protection Module
3 With Integral True-Monitor Module
4 With Slam-shut Module
5 With Secondary Seat Protection
6 With Secondary Seat Protection with controlled bleed to indicate Secondary Seat is functioning
PRESSURE REGISTRATION
I Internal Registration
E External Registration
RELIEF
N Non-Relieving
R Internal Relief
Q High-Capacity Relief
T Token Relief
L Low Flow Token Relief
Example: Type Number CS800IR: Type CS800 regulator without Overpressure Protection Module with Internal Pressure
Registration and with Internal Relief.
1. High-pressure Construction is not available with True Monitor Protection, Secondary Seat Protection or Relief.
2. Available only with Internal Relief or High-Capacity Relief Constructions.
3. Available only with Non-Relieving or Token Relief Constructions.
4. Reference Instruction Manual D103126X012 for information regarding the Type TM600 Integral True-Monitor or Instruction Manual D103127X012 for Type VSX8 safety slam-shut module.
(4)
(3)
(4)
OPTIONS
CS800 Series
(1)
(2)
High Capacity Relief - Provides an increase in relief performance over basic internal relief via a 2-1/2 NPT vent
thereby offering a signicant improvement in the level of
overpressure protection to the downstream system in the event of an overpressure occurrence.
Integral True-Monitor™ Protection - Provides a monitoring regulator integrally mounted on the inlet side of the valve
body that assumes control of ow to the downstream system should the primary regulator cease to regulate ow.
Secondary Seat™ Protection - Provides a solution to the most common cause of regulators failing to shutoff by employing a secondary seating surface to provide shutoff
in the event the primary orice seating surface becomes
damaged or blocked.
Slam-Shut Protection - Discontinues gas service by shutting the gas off if there is an overpressure or underpressure condition.
Principle of Operation
Types CS800, CS820 and CS850 Base Regulators Operation
Refer to Figures 2 and 3. When downstream demand decreases, the pressure under the diaphragm increases. This pressure overcomes the regulator setting (which is set by the regulator control spring). Through the action of the pusher post assembly, lever and valve stem, the valve disk moves closer
to the orice and reduces gas ow. If demand downstream
increases, pressure under the diaphragm decreases. Spring force pushes the pusher post assembly downward, the valve
disk moves away from the orice and the gas ow increases
downstream as the regulator opens in response to the decreased pressure underneath the diaphragm.
The Type CS800IR regulator includes an internal relief valve for overpressure protection. If the downstream pressure
exceeds the regulator setting by 7 in. w.c. to 2.5 psig / 17 to
172 mbar (depending on the type number and main spring
used), the relief valve opens and excess gas is vented through the stabilizer vent in the upper spring case. Units with standard internal relief valve have 1 NPT vent size,
Figure 2, while units with high-capacity relief valve have
2-1/2 NPT vent size, Figure 3.
The Types CS800IT, CS800IL, CS800ET and CS800EL provide a low-capacity/token relief. Token relief provides relief from minor overpressure caused by nicks or dents on
the orice or by thermal expansion of gas in the downstream
line. Token relief also provides a token or signal, in the form of odor, that an overpressure situation is occurring.
Types CS803 and CS823 Integral True-Monitor Operation
Types CS803 and CS823 combine the operation of a conventional two-regulator wide-open monitor set into one body, see Figure 4. The Integral True-Monitor is installed on the inlet side of the body and serves to control downstream pressure in the situation where the Primary regulator can no longer regulate downstream pressure.
3
CS800 Series
Table 2. PED Information
TYPE DESCRIPTION BODY MATERIAL PED CATEGORY FLUID GROUP
CS800, CS820 and CS850 Base regulator Ductile Iron and WCC Steel I
CS804, CS824 and CS854
European EN Reference Standards EN 334, EN 14382
Table 3. Body Sizes, Materials, End Connections and Maximum Cold Working Pressure Ratings
Regulator with
Slam-shut Module
Ductile Iron and WCC Steel IV
Groups 1 and 2 according to PED 97/23/EC,
st
and 2nd family gas according to EN 437 or
1
other gases (compressed air, nitrogen).
The gas must be non-corrosive, clean
(ltration on inlet side necessary) and dry.
(5)
TYPE
BODY
MATERIAL
END
CONNECTION
BODY SIZE
PART NUMBER
FACE-TO-FACE
DIMENSION
In. DN In. mm psig bar
BODY INLET
PRESSURE RATING
1-1/4 - - - - GE25859X012 6.12 155
CS800, CS805, CS806, CS820,
CS825, CS826
and CS850
NPT
Gray Cast Iron
CL125 FF
Gray Cast Iron NPT 2
NPT
1-1/2 - - - - GE26296X012 6.12 155
(1)
2
- - - - GE26300X012 6.12 155
2 - - - - ERAA02462A0 7.5 191
2 50 GE26301X012 7.5 191
2 50 GE26303X012 10 254
(2)
- - - - ERAA02437A0 6.12 155 175 12.1
(4)
1-1/4
- - - - GE26306X012 6.12 155
1-1/2 - - - - ERAA02453A1 6.12 155
175 12.1
2 - - - - ERAA02437A1 6.12 155
250 17.2
232 16
290 20
(3)
, CS820
CS800
(3)
CS850
, CS803,
CS823, CS804,
CS824 and CS854
(3)
,
Ductile Iron
WCC Steel
Rp 2 - - - - ERAA02715A1 6.12 155
(4)
CL125 FF /
CL150 FF
2 50 GE48292X012 7.5
2 50 ERAA02711A1 10 254
2 50 ERAA02718A1 10.5 267
PN 10/16
NPT
2 50 GE48296X012 7.5
2 50 ERAA02719A1 10 254
(4)
1-1/4
- - - - GE26306X022 6.12 155
1-1/2 - - - - ERAA02453A2 6.12 155
(4)
2 - - - - ERAA02437A2 6.12 155
Rp 2 - - - - ERAA02715A2 6.12 155
191
191
(4)
(4)
CL150 RF 2 50 ERAA02720A2 10 254
PN 10/16 2 50 ERAA02719A2 10 254 232 16
1. Standard on Types CS800, CS820 and CS850.
2. Standard on Types CS803, CS804, CS823, CS824 and CS854.
3. If a ductile iron or steel body material is selected without an Integral True-Monitor™ or slam-shut Overpressure Protection (OPP) device, the port located at the bottom of the body will receive an aluminum plug.
4. Not available on Types CS804, CS824 and CS854.
5. The pressure/temperature limits in this Instruction Manual or any applicable standard or code limitation should not be exceeded.
Table 4. Inlet Pressure Ratings and Flow and Sizing Coefcients
MAXIMUM OPERATING INLET PRESSURE
ORIFICE SIZE
TO OBTAIN OPTIMUM PERFORMANCE
psig Setpoints In. w.c. Setpoints
In. mm psig bar psig bar psig bar C
1/4
(1)
6.4
(1)
125 8.6 125 8.6
3/8 9.5 125 8.6 125 8.6 110 3.8 29.5 0.55 0.90
1/2 13 100 6.9 100 6.9 210 7.2 29.5 0.55 0.93
5/8 16 80 6.5 60 4.1 320 10.1 31.8 0.64 0.88
3/4 19 80 6.5 60 4.1 450 13.3 34 0.73 0.84
7/8 22 60 4.1 50 3.4 600 16.7 36 0.82 0.81
(1)
1
(1)(2)
1-3/8
1. Not available on the Types CS805, CS806, CS825 and CS826.
2. Not available on the Types CS803 and CS823.
(1)
25
(1)(2)
35
30 2.1 25 1.7 765 20.1 38.1 0.92 0.77
15 1.0 15 1.0 1125 29.8 37.7 0.90 0.76
4
MAXIMUM
EMERGENCY INLET
PRESSURE
175 12.1
WIDE-OPEN FLOW
COEFFICIENTS
g
C
v
C
IEC SIZING COEFFICIENTS
1
X
50 2.1 24.6 0.38
T
F
L
0.89
F
0.99
D
CS800 Series
Table 5. Outlet Pressure Ranges
TYPE
OUTLET PRESSURE RANGE
In. w.c. mbar In. mm In. mm
3.5 to 6
(1)
9 to 15
(1)
COLOR CODE PART NUMBER
Red GE30337X012 0.15 3.8 6.8 173
5.5 to 8.5 13 to 21 Black GE30338X012 0.17 4.3 6.8 173
CS800, CS803, CS804, CS805
and CS806
5.5 to 8.5 13 to 21
8 to 12 20 to 30 Purple GE30339X012 0.17 4.3 7.4 188
Brown [Use with Low
Inlet (LIN) Option]
GE49043X012 0.16 4.1 8.3 211
10 to 16 25 to 40 White GE30340X012 0.18 4.6 7.4 188
14 to 30 35 to 75 Dark Green GE30341X012 0.20 5.2 7.5 191
CS820, CS823, CS824, CS825
and CS826
CS850 and
CS854
1. In order to achieve the complete spring range listed, in some applications it may be required to re-orient the actuator/spring case to point downward to utilize the weight of the
internal components.
1 to 2.5 psig 69 to 170 Dark Blue GE30342X012 0.25 6.4 7.5 191
1.5 to 3.5 psig 100 to 241 Orange GE46922X012 0.26 6.6 7.1 180
2.5 to 5.5 psig 170 to 380 Yellow GE30343X012 0.29 7.5 6.7 170
5 to 10 psig 345 to 690
Green with
White Stripe
GE30344X012 0.39 9.9 7.6 192
Table 6. Approximate Internal Relief Valve Start-to-Discharge Pressure above Setpoint
INTERNAL RELIEF AND
HIGH CAPACITY RELIEF
CONTROL
SPRING
SETPOINT SET RANGE
Start-to-Discharge Pressure
Range above Setpoint
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
GE30337X012 4 10 3.5 to 6 9 to 15 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30338X012 7 17 5.5 to 8.5 13 to 21 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE49043X012
(LIN)
7 17 5.5 to 8.5 13 to 21 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30339X012 11 27 8 to 12 20 to 30 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30340X012 14 35 10 to 16 25 to 40 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30341X012 1 psig 69 14 to 30 35 to 75
GE30342X012 2 psig 138
GE46922X012 3 psig 207
GE30343X012 5 psig 345
1. Low start-to-discharge option is only available on the main control spring ranges up to 10 to 16 in. w.c. / 25 to 40 mbar.
1 to
2.5 psig
1.5 to
3.5 psig
2.5 to
5.5 psig
70 to 170
100 to 240
170 to 380
7 in. w.c. to
1 psig
7 in. w.c. to
2 psig
7 in. w.c. to
2 psig
7 in. w.c. to
2.5 psig
17 to 69 - - - - - - - - 8 to 16 20 to 40
17 to 138 - - - - - - - -
17 to 138 - - - - - - - -
17 to 170 - - - - - - - - 1 to 2 psig 69 to 138
Table 7. Secondary Seat™ Protection Outlet Pressures
TYPES CS805 AND CS825 TYPES CS806 AND CS826
Secondary Seat
CONTROL SPRING SPRING RANGE SETPOINT
Color Part Number In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
Black GE30338X012 5.5 to 8.5 13 to 21 7 17 11 27 12 30 25 62 23 57
Brown
GE49043X012 5.5 to 8.5 13 to 21 7 17 11 27 12 30 25 62 23 57
(LIN)
White GE30340X012 10 to 16 25 to 40 14 35 19 47 20 50 36 89 33 81
Dark
GE30341X012 14 to 30 35 to 75 1 psig 69 1.2 psig 83 1.3 psig 90 2.1 psig 0.14 bar 2 psig 0.14 bar
Green
Dark
GE30342X012
Blue
Yellow GE30343X012
1. Downstream pressure buildup with Secondary Seat xed bleed in operation and regulator relief valve relieving to atmosphere.
2. Outlet pressure values listed are at maximum operating inlet pressure rating per orice. See Table 4.
3. If the outlet pressure rises above setpoint exceeds 3 psig / 207 mbar, inspect internal parts and replace if damaged.
1 to
2.5 psig
2.5 to
5.5 psig
69 mbar to
0.17 bar
0.17 to
0.38 bar
2 psig 0.14 bar 2.6 psig 0.17 bar 2.6 psig 0.18 bar 3.8 psig 0.26 bar 3.7 psig 0.26 bar
5 psig 0.34 bar 6.3 psig 0.43 bar 6.3 psig 0.43 bar 7.4 psig 0.51 bar 8.2 psig 0.56 bar
Shut-off Pressure
Orice Size, In. / mm Orice Size, In. / mm
3/8 / 9.5 5/8 / 16 3/8 / 9.5 5/8 / 16
SPRING WIRE DIAMETER SPRING FREE LENGTH
TOKEN RELIEF
Low Start-to-Discharge
Start-to-Discharge Pressure
Option
(1)
Start-to-Discharge Pressure
Range above Setpoint
Range above Setpoint
7 in. w.c. to
1 psig
0.5 to
1.5 psig
(2)
Downstream Build-up
Pressure
17 to 69
35 to 100
(1)(2)(3)
5
CS800 Series
Table 8. Primary Regulator and Integral True-Monitor™ Outlet Pressure Ranges without Token Relief
PRIMARY REGULATOR INTEGRAL TRUE-MONITOR
Type
CS803IN
and
CS803EN
CS823IN
and
CS823EN
Typical Setpoint
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
4 10 GE30337X012 3.5 to 6 9 to 15 Red
7 17 GE30338X012 5.5 to 8.5 13 to 21 Black
7 17 GE49043X012 5.5 to 8.5 13 to 21
11 27 GE30339X012 8 to 12 20 to 30 Purple
14 35 GE30340X012 10 to 16 25 to 40 White
1 psig 69 GE30341X012
2 psig 138 GE30342X012 1 to 2.5 psig
3 psig 207 GE46922X012
5 psig 345 GE30343X012
Spring Part
Number
Spring Range
14 to
30
1.5 to
3.5 psig
2.5 to
5.5 psig
35 to 75
69 to
170
100 to
241
170 to
380
Spring
Color
Brown
(LIN)
Dark
Green
Dark
Blue
Orange
Yellow
Setpoint
14 35 GE30189X012 12 to 21 30 to 52 Blue
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
14 35 GE30189X012 12 to 21 30 to 52 Blue
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
14 35 GE30189X012 12 to 21 30 to 52 Blue
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
1.5 psig 103 GE30190X012
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
1.5 psig 103 GE30190X012
1.5 psig 103 GE30190X012
2 psig 138 GE30190X012
3.5 psig 241 GE35081X012
2.5 psig 172 GE30190X012
3 psig 207 GE35081X012
5 psig 345 GE30192X012
3.5 241 GE35081X012
4 276 GE30192X012
6 414 GE33121X012 4 to 7.5
6 414 GE33121X012 4 to 7.5
7 483 GE33121X012 4 to 7.5
7.5 517 GE33121X012 4 to 7.5
Spring Part
Number
Spring Range
1.4 to
2.9 psig
1.4 to
2.9 psig
1.4 to
2.9 psig
1.4 to
2.9 psig
2.6 to
3.7 psig
1.4 to
2.9 psig
2.6 to
3.7 psig
3.6 to 6 psig
2.6 to
3.7 psig
3.6 to 6 psig
Spring
Color
97 to 200 Black
97 to 200 Black
97 to 200 Black
97 to 200 Black
179 to
255
97 to 200 Black
179 to
255
248 to
414
179 to
255
248 to
414
276 to
517
276 to
517
276 to
517
276 to
517
Purple
Purple
Dark Blue
Purple
Dark Blue
Red
Red
Red
Red
6
Type
CS803IT, CS803IL,
CS803ET and
CS803EL
CS823IT, CS823IL,
CS823ET and
CS823EL
CS800 Series
Table 9. Primary Regulator and Integral True-Monitor™ Outlet Pressure Ranges with Token Relief
PRIMARY REGULATOR INTEGRAL TRUE-MONITOR
Setpoint
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
4 10 GE30337X012 3.5 to 6 9 to 15 Red
7 17 GE30338X012 5.5 to 8.5 13 to 21 Black
7 17 GE49043X012 5.5 to 8.5 13 to 21
11 27 GE30339X012 8 to 12 20 to 30 Purple
14 35 GE30340X012 10 to 16 25 to 40 White
1 psig 69 GE30341X012 14 to 30 35 to 75
2 psig 138 GE30342X012 1 to 2.5 69 to 170
3 psig 207 GE46922X012 1.5 to 3.5 100 to 241 Orange
5 psig 345 GE30343X012 2.5 to 5.5 170 to 380 Yellow
Spring Part
Number
Spring Pressure
Range
Spring
Color
Brown
(LIN)
Dark
Green
Dark Blue
Setpoint
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
21 52 GE30196X012 18 to 30 45 to 75 Green
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
1.5 psig 103 GE30190X012 1.4 to 2.9 psig 97 to 200 Black
1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
1.5 psig 103 GE30190X012 1.4 to 2.9 psig 97 to 200 Black
2 psig 138 GE30190X012 1.4 to 2.9 psig 97 to 200 Black
3 psig 207 GE35081X012 2.6 to 3.7 psig 179 to 255 Purple
3 psig 207 GE35081X012 2.6 to 3.7 psig 179 to 255 Purple
4 psig 276 GE30192X012 3.6 to 6 psig 248 to 414 Dark Blue
5 psig 345 GE30192X012 3.6 to 6 psig 248 to 414 Dark Blue
6 psig 414 GE33121X012 5.1 to 7.5 psig 352 to 517 Red
7 psig 483 GE33121X012 5.1 to 7.5 psig 352 to 517 Red
7.5 psig 517 GE33121X012 5.1 to 7.5 psig 352 to 517 Red
Spring Part
Number
Spring Pressure Range
Spring
Color
Table 10. Regulator and Slam-Shut Overpressure Shutoff (OPSO) Pressure Ranges
REGULATOR
Type
CS804
CS824
CS854 7 psig 483 5 to 10 psig 345 to 690 9 psig 621
1. For units equipped with Token Relief, if Non-Factory Slam-shut OPSO setpoints are specied, they must be higher than the Token Relief Start-to-Discharge values provided in Table 6.
2. If Non-Factory OPSO setpoints are specied, the allowable OPSO setpoint cannot exceed the maximum of 3 psig / 207 mbar above the regulator setpoint in order to ensure no internal
parts damage from overpressure.
Factory Setpoint Spring Range Factory Setpoint
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
4 10 3.5 to 6 9 to 15 19 47
7 17 5.5 to 8.5 14 to 21 22 55
7 (optional) 17 (optional) 5.5 to 8.5 14 to 21
11 27 8 to 12 20 to 30
14 35 10 to 16 25 to 40 30 75 24 to 78 60 to 190 GF02170X012 / Orange
14 (optional) 35 (optional) 10 to 16 25 to 40 2 psig 138
1 psig 69 14 to 30 35 to 75 2 psig 138
2 psig 138 1 to 2.5 psig 69 to 170 3.5 psig 241
3 psig 207
5 psig 345
1.5 to
3.5 psig
2.5 to
5.5 psig
100 to 241 5 psig 345
170 to 380 7 psig 483
25 62 16 to 44 40 to 110 GF02169X012 / Red
SLAM-SHUT DEVICE
Over Pressure Shut-off (OPSO)
(1)
Spring Range
12 to 25 30 to 60 GF02168X012 / Brown
1.4 to
4.1 psig
2 to 7.3 psig 138 to 503 GF02172X012 / Green
3.2 to
8.5 psig
5.8 to
13 psig
(2)
97 to 283 GF02171X012 / Pink
221 to 586 GF02173X012 / Silver
400 to 896 GF04353X012 / Yellow
Spring
Part Number
and Color
7
CS800 Series
Table 11. Regulator and Slam-Shut Underpressure Shutoff (UPSO) Pressure and Overpressure Shutoff (OPSO) Ranges
REGULATOR
FACTORY
TYPE
CS804
CS824
CS854 7 psig 483
1. If Non-Factory UPSO setpoints are specied, a minimum differential of 4 in. w.c. / 10 mbar between UPSO setpoint and regulator setpoint must be maintained in order to ensure a
secure latch of the Slam-Shut.
2. For units equipped with Token Relief, if Non-Factory Slam-shut OPSO setpoints are specied, they must be higher than the Token Relief Start-to-Discharge values provided in Table 6.
3. If Non-Factory OPSO setpoints are specied, the allowable OPSO setpoint cannot exceed the maximum of 3 psig / 207 mbar above the regulator setpoint in order to ensure no internal
parts damage from overpressure.
SETPOINT
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
7 17 5.5 to 8.5
11 27 8 to 12
14 35 10 to 16
1 psig 69 14 to 30
2 psig 138
3 psig 207
5 psig 345
SPRING
RANGE
1 to
2.5 psig
1.5 to
3.5 psig
2.5 to
5.5 psig
5 to
10 psig
14 to
21
20 to
30
25 to
40
35 to
75
69 to
170
100 to
241
170 to
380
345 to
690
0.5 psig 35
1.75 psig 121
3.5 psig 241
Under Pressure Shut-off (UPSO) Over Pressure Shut-off (OPSO)
FACTORY
SETPOINT
3 7
6 15 25 62
9 22 30 75
1 psig 69
3 psig 207 7 psig 483
SPRING RANGE
(1)
2 to 12 5 to 30
0.36 to
2.3 psig
0.36 to
2.3 psig
1.5 to
7.3 psig
1.5 to
7.3 psig
25 to
160
25 to
160
100 to
500
100 to
500
SLAM-SHUT DEVICE
SPRING PART NUMBER AND
COLOR
T14168T0012 /
White
T14170T0012 /
Silver
T14170T0012 /
Silver
FA142869X12 /
Orange Stripe
FA142869X12 /
Orange Stripe
FACTORY
SETPOINT
22 55
2 psig 138
3.5 psig 241
5 psig 345
9 psig 621
(2)
SPRING RANGE
OVER UPSO
SETPOINT
17 to 28 42 to 69
1.3 to
3.1 psig
1.3 to
3.1 psig
2.7 to
5.5 psig
2.7 to
5.5 psig
(3)
90 to
214
90 to
214
186 to
379
186 to
379
SPRING PART
NUMBER AND
COLOR
GF02168X012 /
Brown
GF02170X012 /
Orange
GF02170X012 /
Orange
GF02171X012 /
Pink
GF02171X012 /
Pink
During normal operation the True Monitor™ is in a wide­open state as its setpoint is set higher than the primary regulator. See Tables 8 and 9 for guidance regarding the setpoints of the regulator and associated Integral Monitor sets. If the downstream pressure should rise to the setpoint of the True Monitor due to loss of pressure control by the primary regulator, the monitor will assume control and
regulate ow to the downstream system. If a Token relief is
present, the token relief will relieve a small amount of gas to the atmosphere as an indication that the Integral Monitor is controlling the downstream pressure.
Either internal or external downstream pressure registration is available. External pressure registration requires a
downstream sensing line. See the Type TM600 Integral True-Monitor Instruction Manual (D103126X012) for additional details of operation.
Types CS804, CS824 and CS854 Slam-Shut Operation
The Type VSX8 Slam-shut module on the CS804 Series regulators is a fast acting shutoff device that provides overpressure (OPSO) or overpressure and underpressure
(OPSO/UPSO) protection by completely shutting off the ow
of gas to the downstream system. See Tables 10 and 11 for guidance regarding the typical setpoint of the regulator
and associated OPSO and UPSO sets. The Type VSX8’s
actions are independent of the CS804 Series regulator and of variations to the inlet pressure. The Type VSX8 provides
the option of internal or external downstream pressure registration. External registration requires a downstream
sensing line. See Figure 11 for guidance regarding installation of the downstream control line.
The Type VSX8 shutoff disk is normally in the open (reset) position, see Figure 5. If the downstream pressure below the slam-shut diaphragm increases (or decreases) until it reaches the slam-shut setpoint, this diaphragm moves upward (or downward) to release the trip mechanism which allows the spring force on the stem to push the disk against
the seat, shutting off all gas ow. To reset the slam-shut after
gas has been shutoff; refer to Type VSX8 Instruction Manual (D103127X012) for additional details.
WARNING
!
In order for the Underpressure Shutoff (UPSO) of any slam-shut to be triggered, the downstream pipe pressure must drop below the UPSO setpoint. In the case of a downstream line break, numerous factors can prevent the downstream pipe pressure from decreasing below the slam-shut UPSO setpoint. These factors include the distance of pipe to the break, the diameter of the pipe, size of the break and the number of restrictions, such as valves, elbows and bends, downstream of the regulator and/ or slam-shut device. Due to these factors additional protections should be installed to
stop ow in the event of a line break.
8
CS800 Series
Type CS800EN Regulator
M1086
January 2008
Type CS800EN
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE
Type CS800EN Regulator
M1086
January 2008
Type CS800EN
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE
M1070
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE
DISK
CONTROL SPRING
SEAT/ORIFICE
ADJUSTING SCREW
VALVE STEM
PUSHER POST ASSEMBLY
LEVER
RELIEF VALVE STEM
RELIEF VALVE SPRING
Figure 2. Type CS800IR Internally Registered Regulator with Internal Relief Operational Schematic
DIAPHRAGM
ADJUSTING SCREW
CONTROL SPRING
DISK
VALVE STEM
SEAT/ORIFICE
M1071
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE
Figure 3. Type CS800IQ Internally Registered Regulator with High Capacity Relief Operational Schematic
LEVER
RELIEF VALVE SPRING
PUSHER POST ASSEMBLY
RELIEF VALVE STEM
DIAPHRAGM
9
CS800 Series
If the slam-shut device trips due to a lever disconnect failure of the main regulator, it is recommended that you check downstream equipment for damage prior to re-setting the slam-shut.
Types CS805 and CS825 with Secondary Seat™ Protection
CAUTION
Types CS805 and CS825 regulators do not have any means to alert when the Secondary Seat operates at lockup. Therefore, it is recommended that Internal relief or high-capacity relief are also selected or the addition of some other method of overpressure protection be added in the downstream system as discussed in the Overpressure Protection section.
Refer to Figure 6. The CS805 Series provides Secondary Seat Protection. As downstream demand decreases and downstream pressure rises to the regulator pressure lock-up value, the regulator will lock up. If, however, damage has occurred to the primary disk or
orice’s seating surface (seat) or debris has become lodged
between the primary disk and seat, the outlet pressure will continue to rise. This additional pressure causes the disk to apply additional force to the primary seat, which causes the Secondary Seat to move toward the secondary disk/sealing
surface. If downstream demand decreases to zero, then the
Secondary Seat will contact the sealing surface to provide
lockup. Refer to Table 7 for approximate lock-up values
provided by the Secondary Seat.
Types CS806 and CS826 Secondary Seat Protection with Bleed
When the Secondary Seat is providing lockup, the CS806 Series provides small bleed to the downstream system as an indication that the Secondary Seat is providing lockup. In the event that the primary seat and disk cannot provide lockup, the Secondary Seat will move into contact with a metal disk with a small drilled hole. This metal-to­metal interface and bleed hole will allow a small amount of gas to bleed downstream thereby increasing outlet pressure until the Internal relief valve begins to discharge gas to the atmosphere. The odor of this discharged gas provides an indication that the regulator is relying on the Secondary Seat for overpressure protection. See Table 7 for the Downstream Pressure Buildup of the Internal relief acting in conjunction with the Type CS806 Secondary Seat Assembly.
Secondary Seat Protection Limitations
CAUTION
Overpresssure conditions can occur in the downstream piping when the Secondary Seat Protection is installed. The Secondary Seat
Protection serves only as a backup to the primary seat for lockup. Refer to the sections on Overpressure Protection and Maintenance.
Secondary Seat Protection does not provide additional overpressure protection in the event the secondary seat or disk is damaged by debris or contamination in the pipeline or from conditions that would cause the regulator to go wide-open.
Installation and Overpressure Protection
WARNING
!
Personal injury or system damage may result if this regulator is installed, without appropriate overpressure protection, where service conditions could exceed the limits given on the regulator nameplate.
Regulator installations should be adequately protected from physical damage.
All vents should be kept open to permit
free ow of gas to the atmosphere. Protect
openings against entrance of rain, snow, insects or any other foreign material that may plug the vent or vent line. For outdoor installations, point the spring case vent downward to allow condensate to drain (see Figure 8). This minimizes the possibility of freezing and of water or other foreign materials entering the vent and interfering with proper operation.
Under enclosed conditions or indoors, escaping gas may accumulate and be an explosion hazard. In these cases, the vent should be piped away from the regulator to the outdoors. See Vent Line Installation section for the recommended venting practices.
CAUTION
The CS800 Series regulators have an outlet pressure rating lower than their inlet pressure rating. If actual inlet pressure can exceed the outlet pressure rating, outlet overpressure protection is necessary. However, overpressuring any portion of the regulators beyond the limits in the
Specications section and referenced tables
may cause leakage, damage to regulator parts or personal injury due to bursting of pressure-containing parts.
Some type of external overpressure protection should be provided if inlet pressure will be high enough to damage downstream equipment. Common methods of external overpressure protection include relief valves, monitoring regulators, shut-off devices and series regulation.
10
Loading...
+ 22 hidden pages