Chloride CP-70Z 31 AC UPS System
5 to 250kVA - 1ph output
Industrial Power for
Business-Critical Continuity™
The Chloride CP-70Z industrial
Uninterruptible Power Supply system
(UPS) is the agship product of
Chloride Industrial Power. It combines
conservative design topology with
proven digital control technology to
offer the best performances in any
electrical and environmental condition.
The Chloride CP range is designed to meet
the stringent electrical and mechanical requirements in industrial environments.
Each Chloride CP product is based on
interchangeable sub-assemblies to allow full
customization, in compliance with client’s
technical specication and with project documentation requirements.
Benets
n Tailor made systems to comply with all
customer’s specications.
n Ruggedized solutions for demanding
environments: extended temperatures,
vibrations, dust, elevation, dripping water
and moisture.
n Efcient maintenance thanks to easy front-
access to all vital modules of the system.
Key Features
n Reliability - Unique design which allows
the UPS to continuously operate for at least
20 years at full load at a permanent 40°C
ambient temperature.
n On-line double conversion - UPS classied
VFI SS 111 as per IEC62040-3
n Robust mechanical design - the system
withstands vertical and horizontal
acceleration stress tests up to 0.5g as
standard
n Galvanic isolation –input and output
transformers as standard
n Multilingual digital graphic display with
embedded event log
n Remote monitoring capabilities: Modbus,
Probus, DF1, ethernet, volt-free contact,
monitoring software
n Fully customized electrical and mechanical
solutions – On demand design to comply
with every standards (e.g. UL, ANSI, NEMA,
IEC, CSA, ABS, DNV)
n Full compatibility with lead-acid and nickel-
cadmium batteries sealed or vented
Applications
The Chloride CP-70Z AC UPS System range suits all
applications such as:
n Oil and Gas offshore and onshore
n Rening and petrochemical plants
n Power generation plants
n Transportation (rail, metro, tramway)
The Chloride CP range is designed to meet the harshest electrical and
mechanical requirements in industrial environments.
Each Chloride CP product is based on interchangeable sub-assemblies to allow
full customization, in compliance with client’s technical specication and with
project documentation requirements.
Associated with an industrial stand-by battery, the Chloride CP-70Z 31 range
is dedicated to protect critical industrial single phase AC equipments and
processes from the damaging effects of power interruption and losses
.
Chloride CP-70Z 31 UPS System
5 to 250 kVA - 1ph output
Industrial Power for
Business-Critical Continuity™
Ratings - Output power (kVA) vs DC intermediate voltage (Vdc)
110–120Vdc 220-240Vdc 400Vdc
2.5
5
7.5
10 10
15 15
20 20
25 25
30 30
40 40 40
50 50 50
60 60 60
Up to 250 kVA on request
80 80
100 100
120 120
Options
Rectier 12-pulse rectier
Battery Battery circuit protection box
System Dual congurations
Mechanical Up to IP42 external
Communication Front-panel analog meters (72x72 class 1.5)
Non-exhaustive list of options. Consult us for any other requirements.
Harmonic lter
Ripple lters
Blocking diode
Other input voltage (3x190 to 3x690VAC)
Inrush current limitation to 8In
Surge and Lightning protections
Battery cabinet
Low-voltage disconnect contactor
Battery Management System
Battery room temperature sensor
Hot stand-by conguration
Input / intermediate /output isolators
DC/DC serial regulator
isolated DC/DC converter
AC distribution
Earth fault monitoring
Backfeed protection
Internal lighting
Anti-condensation heater
Temperature monitor
Special cabinet identication
Reserve transformer
Reserve st abilizer
Top cable entry
Other frame colour
Anti-seismic design
Transducers
Additional Volt-free contacts
Remote monitoring via Modbus
Remote monitoring via other bus
PPVis monitoring software
Passive or active mimic panel
Standards
Compliance IEC 62040 (-1, -2, -3) / 60146 (-1-1, -1-3, -2) / IEC 60950
Conformity Low voltage directive: 2006/95/EC
IEC 61000-6-2 - IEC 61000-6-4
IEC 60529 / IEC 60439 / IEC 60076
EMC directive: 2004/108/EC
CE Mark
Technical Data
Input
AC voltage 3 x 400V (380, 415)*
Voltage tolerance +/- 10%
Frequency 50Hz (60Hz)
Frequency tolerance +/- 5%
Intermediate DC Circuit
Nominal DC voltage 110 / 120 / 220 / 240 / 400 V
Voltage stability +/- 1% in oat mode, input within tolerance
Voltage ripple 1% RMS, in oat, battery connected
Current limitation I nominal
Charging characteristic UI according to DIN 41773
Ouput
Available ratings see table above (at PF 0.8 lagging)
AC Voltage 1 x 230V (220, 240) ; 1 x 110V (115, 120)*
Frequency 50Hz (60Hz)
Frequency stability
• with internal oscillator +/- 0.5%
• with reserve synchronism +/-3% (from 0.2 to 6% adjustable)
Frequency response <1Hz/s (0.1Hz/s for parallel systems)
Voltage stability (for 0-100% load variation)
• static +/-1% (+/-2% for parallel systems)
• dynamic +/-2% (+/-3% for parallel systems)
Overload inverter
• 1 minute 150% of nominal power
• 10 minutes 125% of nominal power
Short circuit clearance
• 100 ms 250% of nominal current
• 5 s 175% of nominal current
Distortion
• With 100% linear load 3%
• With 100% non-linear load Complies with IEC 62040-1-2
Allowable power factor 0.5 lagging to 0.5 leading
Allowable crest factor 3
Battery
Typ e Lead Acid or Nickel Cadmium vented or
Autonomy From few minutes to several hours, as per
Battery current limitation
(typical, oat & charge modes)
Battery current limitation
(typical, boost mode)
General Data
Operating temperature 0 to 40°C*
Storage temperature (°C) -20 to +70°C
Relative humidity (%) <90% non condensing
Operating altitude (m) 1000 m max without derating
Cooling Forced ventilation
Efciency Up to 90% according to rating
External protection IP 20* according to IEC 60529
Noise (dB) 60 – 75 dB according to rating
Frame colour Grey RAL 7032
Dimensions Varying according to ratings & options
* other available on request
+/-1.5% for parallel rectiers
recombination
customer’s requirement
0.1C (Lead Acid battery)
0.2C (Nickel Cadmium battery)
0.05C (Lead acid battery)
0.1C (Nickel Cadmium battery)
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or
omissions.
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
n AC Power
n Connectivity
n DC Power
n Embedded Computing
Emerson Network Power I S S.A.S
30 Avenue Montgol er - BP90 - 69684 Chassie u Cedex France
T: +33 (0)4 78 40 13 56 F: +33 (0)4 78 90 58 90
Industrial.Sales.Chloride@Emerson.com
EmersonNetworkPower.com
n Embedded Power
n Industrial Power
n Infrastructure Management & Monitoring
n Outside Plant
Emers on Electric Co. or one of i ts afliate d companies.
CP70Z 31 AC UPS Syst em-DSUK-Rev2-02/2013
n Power Switching & Controls
n Precision Cooling
n Racks & Integrated Cabinets
n Services
Emerson, Business-Critical Continuit y and
Emers on Network Po wer are trademarks of
©2013 Emerson Elec tric Co.