Chloride CP-70i 01 - DC/AC inverter
2.5 to 250kVA - 1ph output
Industrial Power for
Business-Critical Continuity™
The Chloride CP-70i industrial
inverter is the agship inverter of
Chloride Industrial Power. It combines
conservative design topology with proven digital control technology to offer the best performances in any electrical and environmental
condition.
The Chloride CP range is designed to meet the stringent electrical and mechanical requirements in industrial environments. Each Chloride CP product is based on inter­changeable sub-assemblies to allow full customization, in compliance with client’s
technical specication and with project
documentation requirements.
Benets
n Made to order DC/AC inverter solutions
to exactly t the industrial application
requirements
n Ruggedized solutions for demanding
environments: high temperatures, vibrations, dust, elevation, dripping water and moisture
n Efcient maintenance thanks to easy
front-access to all vital modules of the system
Custom-designed DC/AC inverters to supply critical industrial processes.
The Chloride CP-70i 01 converts a DC input voltage into a perfect sinusoidal single­phase output voltage to provide power to critical AC loads. It uses the patented digital Vector Control technology which increases the performances of power components and enables an active conditioning of the load. The result is improved reliability for the process and enhanced safety for the personnel.
The CP-70i 01 range is available from 2.5kVA to 250kVA. It offers a wide choice of DC input voltages (from 110Vdc to 240Vdc) and of output voltages.
The CP-70i 01 range is also available with 400Vdc input. This conguration can be combined with a CP-70R 30 rectier-charger in order to design specic high ratings
double conversion AC UPS systems.
To further improve load availability and process reliability, the CP-70i 01 is able to
operate in dual parallel conguration, with centralized or distributed reserve line, and
can include an AC bus-tie.
Key Features
n Reliability - Unique design which allows
the inverter to continuously operate for at least 20 years at full load at 40°C
n Robust mechanical design - The inverter
withstands vertical and horizontal acceleration stress tests up to 0.5g as standard
n Galvanic isolation - Output transformer is
included as standard
n Multilingual digital graphic display with
embedded event log
n Remote monitoring capabilities: Modbus,
Probus, DF1, ethernet, volt-free contacts,
monitoring software
n Fully customized electrical and mechanical
solutions – On demand design to comply with every standard (e.g. UL, ANSI, NEMA, IEC, CSA, ABS, DNV)
Applications
The Chloride CP-70i DC/AC inverter range suits applications such as:
n Oil and Gas offshore and onshore n Rening and petrochemical plants n Conventional power generation plants n Transmission and Distribution substations n Transportation (rail, metro, tramway)
Chloride CP-70i 01 DC/AC inverter
2.5 to 250 kVA - 1ph output
Industrial Power for
Business-Critical Continuity™
Ratings - Output power (kVA) vs DC intermediate voltage (Vdc)
110–120Vdc 220-240Vdc
2.5
5
7.5
10 10
15 15
20 20
25 25
30 30
40 40
50 50
60 60
80 80
100 100
120 120
160
200
250
Options
Inverter Dual congurations
Input / output isolators AC distribution Earth fault monitoring Internal lighting Anti-condensation heater Temperature monitor
Special cabinet identication
Reserve transformer Reserve stabilizer
Mechanical Up to IP42 external
Top cable entry Other frame colour Anti-seismic design
Communication Front-panel analog meters (72x72 class 1.5)
Transducers Additional Volt-free contacts Remote monitoring via Modbus Remote monitoring via other bus PPVis monitoring software Passive or active mimic panel
Non-exhaustive list of options. Consult us for any other requirements.
Technical Data
Input
DC voltage 110 / 120 / 220 / 240 (400V on request)
Voltage tolerance +18% /- 20%
Output
Available ratings see table (at PF 0.8 lagging)
AC Voltage 1 x 230V (220, 240) ; 1 x 110V (115, 120)*
Frequency 50Hz (60Hz)
Frequency stability
with internal oscillator +/- 0.05%
with reserve synchronism +/-4% (from 1.2 to 6% adjustable)
Frequency response <1Hz/s (0.1Hz/s for parallel systems)
Voltage stability (for 0-100% load variation)
static +/-1% (+/-2% for parallel systems)
dynamic VFI SS 111 - Complies with IEC/EN 62040-3,
Overload inverter
1 minute 150% of nominal power
10 minutes 125% of nominal power
Short circuit clearance
100 ms 250% of nominal current
5 s 175% of nominal current
Harmonic voltage distortion
With 100% linear load < 3%
With 100% non-linear load ≤ 5% (non linear load dened by IEC 62040)
Allowable power factor 0.5 lagging to 0.5 leading
Allowable crest factor 3/1
General Data
Operating temperature 0 to 40°C*
Storage temperature (°C) -20 to +70°C
Relative humidity (%) <90% non condensing
Operating altitude (m) 1000 m max without derating
Cooling Forced ventilation
Efciency Up to 91% according to rating
External protection IP 20* according to IEC 60529
Noise (dB) 60 – 75 dB according to rating
Frame colour Grey RAL 7032
Dimensions Varying according to ratings & options
* other available on request
Standards
Compliance IEC 62040 (-1, -2, -3) / 60146 (-1-1, -1-3, -2) / IEC 609650
Conformity Low voltage directive: 2006/95/EC
IEC 61000-6-2 - IEC 61000-6-4
IEC 60529 / IEC 60439 / IEC 60076
EMC directive: 2004/108/EC
CE Mark
class 1
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
Emerson Network Power I S S.A.S
30 Avenue Montgol er - BP90 - 69684 Chassieu Cedex France T: +33 (0)4 78 40 13 56 F: +33 (0)4 78 90 58 90
Industrial.Sales.Chloride@Emerson.com EmersonNetworkPower.com
n AC Power n Connectivity n DC Power n Embedded Computing
n Embedded Power
n Industrial Power
n Infrastructure Management & Monitoring n Outside Plant
Emers on Electric Co. or one of i ts afliate d companies.
CP70i 01 DC/AC inverter- DSUK-Rev3-06/2013
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network Power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
n Power Switching & Controls n Precision Cooling n Racks & Integrated Cabinets n Services
Emerson, Business-Critical Continuit y and
Emers on Network Po wer are trademarks of
©2013 Emerson Elec tric Co.
Loading...