Emerson CP-60Z Brochures and Data Sheets

Industrial Power for
Business-Critical Continuity
Chloride CP-60Z AC UPS System
5 to 60kVA - 1ph and 3ph output
The Chloride CP-60Z industrial Uninterruptible Power Supply (UPS) system is the result of latest industrial requirements combined with R&D innovations to offer an improved
efciency and reduced operating costs
industrial UPS.
The Chloride CP range is designed to meet the stringent electrical and mechanical
requirements in industrial environments.
Each Chloride CP product is based on inter-
changeable sub-assemblies to allow full customization, in compliance with client’s technical specication and with project documentation requirements.
Benets
Energy savings - Improved efciency means
reduced power consumption and smaller air conditioning system
Project savings - Higher input power factor and
lower inrush current allow smaller upstream transformer, switchgear and cables and reduce line current and losses in the cables.
 Safe and easy maintenance - Segregated
manual bypass and front access to major com­ponents improve safety and reduce MTTR
 Asset Management System - The UPS is com-
patible with the Emerson AMS Suite Intelligent Device Manager which helps to ensure an efcient preventive maintenance
Custom-designed AC UPS systems to secure industrial processes
The Chloride CP-60Z is available from 5 to 60kVA in single-phase or three-phase
output conguration. It offers a wide choice of DC battery voltages (110V, 220V or 400V) and of output voltages (from 1x110 V to 3x415V) to best t the applica­tion.
The UPS uses patented digital Vector Control technology which increases the UPS performances, enables active conditioning of the load and allows personalised system settings.
The Chloride CP-60Z can be adapted for project-specic requirements. A wide choice of industrialized extras allow system customization according to the most demanding technical specications.
To further improve load availability and process reliability, the system is able to operate in dual parallel conguration, centralized or distributed, with single or dual batteries, and can include AC bus-tie.
Key Features
 Low Ripple Voltage to reduce battery stress
and optimize its lifetime
Low inrush current < 4In (12-pulse) not to
oversize mains power supply
SCR-based rectier, 6 or 12 pulses, with
improved operation to signicantly reduce the mains’ pollution (THDi) and the input RMS
current
Proven reliability: The unique design allows
the UPS to continuously operate at full load at a
permanent 40°C ambient temperature
Galvanic isolation: input and output transfor-
mers are standard on the complete range.
Ingress protection IP42 is provided as
standard to operate in the most demanding environments
Compatibility with Nickel-Cadmium and Lead-
Acid batteries, open or gas-recombination types
Multilingual digital graphic display with
embedded event log
Wide choice of congurations, options, and
remote monitoring solutions
Applications
The Chloride CP-60Z is the best solution, both cost effective and environmental friendly, to meet industrial requirements of a wide range of sectors,
such as:
Oil & Gas, offshore and onshore Rening and Petrochemical industries  Water infrastructures Mining
Transportation (rail, metro, tramway)
Industrial Power for
Business-Critical Continuity
Chloride CP-60Z AC UPS System
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
Emerson, Business-Critical Continuity and
Emerson Network Power are trademarks of
Emerson Electric Co. or one of its afliated companies.
©2013 Emerson Electric Co.
CP60Z-DSUK-Rev0-01/2013
AC Power
Connectivity
DC Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Embedded Computing
Embedded Power
Industrial Power
Precision Cooling
Racks & Integrated Cabinets
Services
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network Power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power IS S.A.S
30 avenue Montgoler - BP90 - 69684 Chassieu Cedex - France T: +33 (0)4 78 40 13 56 F: +33(0)4 78 90 58 90
Industrial.sales.Chloride@Emerson.com EmersonNetworkPower.com
5 to 60 kVA - 1 ph and 3ph output
Ratings - Output Power at cos phi 0.8 (kVA) vs battery voltage (Vdc)
110-120 Vdc 220-240 Vdc 400 Vdc
5 5 -
10 10 ­20 20 ­30 30 -
- 40 40
- 50 50
- 60 60
Technical Data
Input
Input voltage (other voltage on request) 400 VAC (380; 415) ±10% Inrush current < 8 x In (6-pulse version)
Power factor up to 0.94 Frequency range 50 Hz (60 Hz factory setting) ±5%
Intermediate DC circuit
Nominal DC voltage 110 / 120 / 220 / 240 / 400 VDC Voltage stability ±1% in float mode, input within tolerance
Voltage ripple (battery connected) 0.25% RMS, in oat mode
Current limitation I nominal Charging characteristic IU according to DIN 41773
Output
Available ratings (see table above) from 5 to 60 kVA (at PF 0.8 lagging)
AC voltage:
Single phase
Three phase
Frequency 50 Hz (60 Hz factory setting) Frequency stability:
with internal oscillator
with reserve synchronism
Voltage stability (0-100% load variation):
static
dynamic
Overload inverter (in % of nominal power) 150%/1 min - 125%/10 min
Short-circuit clearance:
1-ph output (in % of nominal current)
3-ph output (in % of nominal current)
Voltage distorsion:
with 100% linear load with 100% non linear load
Allowable power factor 0.5 lagging to 0.5 leading Allowable crest factor 3/1
Battery
Typ e Lead Acid or Nickel Cadmium,
Autonomy From few minutes to several hours,
Battery current limitation 0.1C (lead acid) / 0.2C (Nickel Cadmium)
General Data
Rectier efciency up to 90 % (according to rating and cong.)
Operating temperature From 0 to 40 °C Storage temperature From -20 °C to +70 °C (battery excluded)
Relative humidity <90 % non condensing at 20 °C
Operating altitude 1000 m (without system derating) Cooling Fan-assisted with redundant monitored fans
External ingress protection IP 42 Noise less than 66 dB (according to rating) Input / output isolation 2500 VAC / 1 minute Frame colour RAL 7032 Dimensions Varying according to ratings and options
< 4 x In (12-pulse version)
±1.5% for parallel chargers
230 VAC (220, 240) ; 110 VAC (115, 120) 400 VAC (380, 415) ; 220 VAC (190, 208)
±3% (from 0.2 to 6% factory setting)
±1% (±2% for parallel systems)
VFI SS 111 - complies to IEC62040-3, class 1
315%/100 ms - 220%/5 s (Ph-N)
≤5 % (complies with IEC 62040-1-2)
±0.05%
250%/100 ms - 175%/5 s
<3 %
vented or recombination
as required and specied
Standards
Compliance IEC 62040 (-1, -2, -3) / 60146 (-1-1, -1-3, -2) / IEC 60950
IEC 61000-6-2 - IEC 61000-6-4 IEC 60529 / IEC 60439 / IEC 60076
Conformity EMC Directive 2004/108/CE
Low Voltage Directive (LVD) 2006/95/CE CE Mark
Options
Rectier 12-pulse SCR rectier
Special 3-ph input voltage (up to 3x690Vac)
Surge and/or lighning protections
Input circuit breaker
Battery Battery circuit protection box (Fuse or circuit breaker)
Battery reversed polarity detection Battery Low Voltage Disconnection (LVD) Battery black start Battery room temperature sensor for battery charge compensation DC earth fault detection
Output AC earth fault detection
Output fuse switch or circuit breaker
Reser ve Reserve input circuit breaker
Reserve transformer (H class) Reserve stabilizer (servo-controlled)
Stabilizer output isolator
System Dual congurations
AC distribution (circuit breakers)
Backfeed protection
Internal cabinet lighting Auxiliary power socket
Anti-condensation heater UPS cabinet temperature monitor
Special cabinet identication (Tag, nameplate)
Mechanical Top cable entry
Special frame color Special feet height
Special keylock
Special gland plate
Lifting eyes 2mm panels thickness
Communication Front panel analogue meters (72x72, class 1 or class 1.5)
Transducers 4-20mA
Additional volt-free contacts
Modbus RTU (RS232 or RS485) Modbus / TCP Probus IEC61850 protocol PPVis monitoring software AMS compatibility kit
Passive mimic panel
Active mimic panel with integrated LEDs Special lamp indicator on front panel (22mm diameter)
Loading...