Parts Ordering ........................................................12
Parts List .................................................................12
TYPICAL CS403
AND CSB403
Introduction
Scope of the Manual
This manual provides instructions for the Installation,
Startup, Adjustment, Maintenance, and Parts
Ordering information for the Type TM600 Integral
True-Monitor regulator.
The Type TM600 must be installed on service
regulators with body connections suitable for the
Type TM600.
www.fisherregulators.com
D103126X012
Type TM600
Specications
The Specications section lists the specications for Type TM600 congurations. The following information is
stamped on the nameplate of the Type TM600: Spring Range and Orice Size. Additional operating information is
located on the Primary Regulator nameplate.
Available Congurations
Type TM600I—Integral True-Monitor™ regulator
with internal registration
Type TM600E—Integral True-Monitor regulator
with external registration
Body Size and End Connection Styles
See the Instruction Manual of the primary regulator
for available Body Sizes and End Connections.
PRIMARY REGULATOR SERIESINSTRUCTION MANUAL
CS400D103120X012
CP400D103122X012
CSB400D103123X012
CS800D103124X012
Allowable Inlet Pressures
(1)
See Table 8
Port Size
1 inch / 25 mm
Monitor Set Pressure Range
(1)
14 inches w.c. to 7.5 psig / 35 to 517 mbar
Maximum Downstream Pressures
Casing: 25 psig / 1.7 bar
To Avoid Internal Parts Damage:
5 psig / 345 mbar over set pressure
Operating: 7.5 psig / 517 mbar
Setpoints of Primary Regulator and Integral Monitor
CS400, CP400, and CS800 Series: same as
primary regulator
CSB400 Series: external only
Approximate Weight
14 pounds / 6.3 kg
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Product has passed Regulator Technologies testing for lockup down to -40 degrees.
(1)
(1)(2)
WARNING
!
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or re causing property damage and
personal injury or death.
Fisher® regulators and integral TrueMonitor regulators must be installed,
operated, and maintained in accordance
with federal, state and local codes, rules
and regulations, and Emerson Process
Management Regulator Technologies, Inc.
(Regulator Technologies) instructions.
If the regulator vents gas or a leak
develops in the system, service to the unit
2
may be required. Failure to correct trouble
could result in a hazardous condition.
Call a gas service person to service the
unit. Only a qualied person must install
or service the regulator.
Description
The Type TM600 Integral Monitor provides
True-Monitor Protection by taking the place of a
separate service regulator on monitor applications.
Intended for commercial and light industrial
applications, it can be used for pressure reducing
service on natural, manufactured, or LP gas. To be
functional, Type TM600 must be mounted on primary
regulators with orices up to 1 inch / 25 mm. The
Type TM600 is not currently orderable separate from
a service regulator.
Type TM600
MONITOR
ADJUSTING
SCREW
PRESSURE
RETAINING
PLUG (DO NOT
REMOVE IF
PRESSURIZED)
M1061
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTEGRAL MONITOR
MONITOR
CONTROL
SPRING
MONITOR LEVER
MONITOR ORIFICE
VALVE STEM
MONITOR DISK
CONTROL SPRING
VALVE DISK
ORIFICE
RELIEF
VALVE
SPRING
LEVER
PRIMARY REGULATOR
ADJUSTING
SCREW
PRESSURE
RETAINING
PLUG (DO NOT
REMOVE IF
PRESSURIZED)
As downstream pressure registers under the main
diaphragm of the Primary Regulator, it also registers
under the diaphragm of the Integral Monitor. If for
any reason the Primary Regulator ceases to regulate
downstream pressure below the setpoint of the
Integral Monitor, the monitor will begin to throttle the
ow and maintain a downstream pressure below the
maximum pressure indicated in Tables 1 through 7.
If the Primary Regulator is equipped with a token
internal relief valve, it will begin to relieve to provide
an indication via smell that the Integral Monitor is
controlling the downstream pressure. As downstream
demand decreases, the Integral Monitor closes to
maintain a downstream pressure below the maximum
value given in Tables 1 through 7. As downstream
demand increases, the Integral Monitor opens to
supply additional gas ow as needed to maintain
downstream pressure.
Installation
WARNING
!
All vents should be kept open to permit
free ow of gas to the atmosphere.
Protect openings against entrance of
rain, snow, insects or any other foreign
material that may plug the vent or vent
line. When installing outdoors, point the
spring case vent of the Primary regulator
and Integral Monitor downward to allow
condensate to drain. This minimizes the
possibility of freezing and accumulation
of water or other foreign materials
entering the vent and interfering with
proper operation.
Under enclosed conditions or indoors,
escaping gas may accumulate and be
an explosion hazard. In these cases,
the vents should be piped away from the
regulator to the outdoors.
3
Type TM600
INTERNAL REGISTRATION PLUG BLOCKS
THE OUTLET PRESSURE COMMUNICATION
FROM THE OUTLET OF THE VALVE BODY TO
THE INTEGRAL MONITOR. THIS ALLOWS THE
DOWNSTREAM CONTROL LINE TO CONTROL
THE INTEGRAL MONITOR.
INSTALL DOWNSTREAM CONTROL LINE. INTEGRAL
MONITOR CONTROL LINE SHOULD BE SEPARATED
FROM THE PRIMARY REGULATOR CONTROL LINE TO
PROVIDE MONITOR FUNCTION IF DAMAGE SHOULD
OCCUR TO THE PRIMARY REGULATOR DOWNSTREAM
CONTROL LINE.
The Type TM600 Integral Monitor has an
outlet pressure rating lower than their
inlet pressure rating. Overpressuring
any portion of the regulators beyond
the limits in Specications section and
Tables 1 through 8 may cause leakage,
damage to regulator parts, or personal
injury due to bursting of pressurecontaining parts.
INSTALL
DOWNSTREAM
CONTROL LINE
HERE
PRIMARY REGULATOR
General Installation Instructions
Before installing the Type TM600:
• Check for damage, which might have occurred
during the shipment.
• Check for and remove any dirt or foreign
material, which may have accumulated in the
regulator body.
• Blow out any debris, dirt, or copper sulfate in the
copper tubing and the pipeline.
If the Type TM600 is exposed to an
overpressure condition, it should be
inspected for any damage that may have
occurred. Integral Monitor operation
below these limits does not preclude
the possibility of damage from external
sources or from debris in the pipeline.
4
• Apply pipe compound to the external threads
of the pipe before installing the pipe into the
Type TM600 vent or external control line port.
• Make sure gas ow through the primary
regulator is in the same direction as the arrow
on the body. “Inlet” and “Outlet” connections are
clearly marked.
Type TM600
Table 1. Type CS403 Setpoints and Associated True-MonitorTM Setpoints, with Token Relief
PRIMARY REGULATORINTEGRAL MONITOR
Typical Regulator
Setpoint
Inch w.c. mbarInch w.c.mbarInch w.c.mbarInch w.c.mbar
4103.5 to 59 to 13GE30198X012Red
5124.5 to 6.511 to 16GE30195X01Purple
7176 to 815 to 20GE30188X012Gold
11277.5 to 1119 to 28GE30189X012Blue
143510 to 1425 to 35GE30224X012 Unpainted
184512 to 1930 to 48GE30196X012Green
1 psig69
2 psig1381 to 2 psig69 to 138GE30190X012Black
3 psig2072 to 5.5 psig 138 to 380 GE30197X012Yellow
5 psig3452 to 5.5 psig 138 to 380 GE30197X012Yellow7.5 psig517
1. Integral Monitor setpoints shown represent the minimum Monitor setpoint for the Primary regulator Type CS400 with a Token Relief. Higher monitor setpoints can be chosen,
e.g., for a Primary regulator setpoint of 7 inches w.c. / 17 mbar, the Integral Monitor can also be set at 21 inches w.c. / 52 mbar, 1 psig / 69 mbar, or higher.
Spring Range
18 inches w.c.
to 1 psig
Spring Part
Number
45 to 69GE30225X012Orange
Spring
Color
Monitor Setpoint
215218 to 3045 to 75GE30196X012Green
1 psig6926 to 4065 to 99GE30225X012Orange
215218 to 3045 to 75GE30196X012Green
1 psig6926 to 4065 to 99GE30225X012Orange
215218 to 3045 to 75GE30196X012Green
1 psig6926 to 4065 to 99GE30225X012Orange
1 psig6926 to 4065 to 99GE30225X012Orange
1.5 psig1031.4 to 2.9 psig97 to 200GE30190X012Black
1 psig6926 to 4065 to 99GE30225X012Orange
1.5 psig1031.4 to 2.9 psig97 to 200GE30190X012Black
1.5 psig1031.4 to 2.9 psig97 to 200GE30190X012Black
2.5 psig1721.4 to 2.9 psig97 to 200GE30190X012Black
2.5 psig1721.4 to 2.9 psig97 to 200GE30190X012Black
3.5 psig2412.6 to 3.7 psig179 to 255GE35081X012Purple
3.5 psig 2412.6 to 3.7 psig179 to 255GE35081X012Purple
5 psig3453.6 to 6 psig248 to 414GE30192X012Dark Blue
5 psig3453.6 to 6 psig248 to 414GE30192X012Dark Blue
6 psig414
6 psig414
7 psig483
(1)
5.1 to 7.5 psig352 to 517GE33121X012Red4 psig2762 to 5.5 psig 138 to 380 GE30197X012Yellow
Spring Range
Spring Part
Number
Spring
Color
Installation Location
• The installed Type TM600 should be adequately
protected from vehicular trafc and damage from
other external sources.
• Install both Primary and Type TM600 Integral
Monitor with both vents pointing vertically
down, see Figure 4. If the vents cannot be
oriented in a vertically down position, then
Type TM600 must be installed under a separate
protective cover. Installation with the vents down
allows condensation to drain, minimizes the entry
of water or other debris from entering the vent, and
minimizes vent blockage from freezing precipitation.
• Do not install Type TM600 in a location where
there can be excessive water accumulation or
ice formation, such as directly beneath a down
spout, gutter, or roof line of building. Even
a protective hood may not provide adequate
protection in these instances.
• Install the Type TM600 so that any gas discharge
through the vents or vent assemblies is over
3 feet / 0.91 meters away from any building opening.
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.