Emerson Copeland Screw SCH2, Copeland Screw SCA2 Applications Manual

Page 1
AE4-1322
Copeland ScrewCopeland Screw
Copeland Screw
Copeland ScrewCopeland Screw
CompressorsCompressors
Compressors
CompressorsCompressors
April 2002
Semi-Hermetic Compact Semi-Hermetic Compact
Semi-Hermetic Compact Semi-Hermetic Compact
SCH2 & SCA2SCH2 & SCA2
SCH2 & SCA2
SCH2 & SCA2SCH2 & SCA2
High Temp Compressors
35 – 140 Horsepower
1 General1 General
1 General
1 General1 General
2 Design and functions2 Design and functions
2 Design and functions
2 Design and functions2 Design and functions
2.1 Design features
2.2 Compression process Vi control
2.3 Capacity control and start unloading
2.4 Hydraulic control
2.5 Starting the compressor
2.6 Infinite capacity control Oil circulation
Contents
5 Economizer operation5 Economizer operation
5 Economizer operation
5 Economizer operation5 Economizer operation
Application ManualApplication Manual
Application Manual
Application ManualApplication Manual
5.1 General
5.2 Operation principal
5.3 ECO operation with subcooling circuit
5.4 ECO operation with intermediate pressure receiver
5.5 Layout and selection recommendations
5.6 Additional components
5.7 Control
3 Lubricants3 Lubricants
3 Lubricants
3 Lubricants3 Lubricants
4 Integration into the refrigeration circuit4 Integration into the refrigeration circuit
4 Integration into the refrigeration circuit
4 Integration into the refrigeration circuit4 Integration into the refrigeration circuit
1.1 Mounting the compressor
1.2 System layout
1.3 Guide lines for special system variations
1.4 Additional cooling by liquid injection
1.5 Additional cooling by external oil cooler
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
6 Electrical connections6 Electrical connections
6 Electrical connections
6 Electrical connections6 Electrical connections
6.1 Motor design
6.2 Selection of electrical components
6.3 Compressor protection system
6.4 Schematic wiring diagrams
Page 2
Semi-hermetic compact screwsSemi-hermetic compact screws
Semi-hermetic compact screws
Semi-hermetic compact screwsSemi-hermetic compact screws SCH2/SCA2 seriesSCH2/SCA2 series
SCH2/SCA2 series
SCH2/SCA2 seriesSCH2/SCA2 series 35 to 140 HP Nominal motor power35 to 140 HP Nominal motor power
35 to 140 HP Nominal motor power
35 to 140 HP Nominal motor power35 to 140 HP Nominal motor power
11
GeneralGeneral
1.
General
11
GeneralGeneral
This new series represents the result of further develop­ment to provide a simplified and favorably priced screw compressor for use in factory made systems.
Contrary to the semi-hermetic and open type, SHM/ SHL and SDM/SDL compressor models for commercial and industrial installation, the compact screws are designed with an integral oil separator. The effort involved in installation is therefore comparable with that for semi-hermetic reciprocating compressors.
In addition to this, the electrical control and the monitor­ing of the oil circuit has been simplified. The proven basic construction and the ease of service have been retained.
The most modern screw compressor technology is now available in the middle capacity range for compact liquid chillers and air conditioning equipment.
2. Design and function2. Design and function
2. Design and function
2. Design and function2. Design and function
2.1 Design features
Copeland Compact screws are of the twin rotor design with a newly-developed profile geometry (lobe ratio 5:6). The main parts of these compressors are the two rotors (male and female rotor), which are fitted into a closed housing. The rotors are precisely located at both ends in rolling contact bearings (radial and axial), which, in conjunction with the generously sized oil supply chambers, provides optimum emergency running characteristics.
Owing to the specific design, this type of compressor does not require any working valves. To protect against reverse running when the compressor is switched off (expansion operation) a check valve is incorporated in the discharge chamber (this valve does not, however, replace any check valves required by the system design). An internal pressure relief valve is utilized for over-pressure protection.
The compressor is driven by a three-phase asynchro­nous motor, which is built into the compressor housing. The motor rotor is located on the shaft of the male screw rotor. Cooling is achieved by cold refrigerant
AE4-1322
vapor, which mainly flows through bores in the motor rotor.
The main technical features:
Balanced product rangeBalanced product range
Balanced product range
Balanced product rangeBalanced product range
• •
8 basic models
• •
• •
Tight performance graduation
• •
Minimal space requirements and convenientMinimal space requirements and convenient
Minimal space requirements and convenient
Minimal space requirements and convenientMinimal space requirements and convenient piping designpiping design
piping design
piping designpiping design
• Shortest installed length in its performance category
- shut-off valves / connections within compressor dimensions
• Suction and discharge gas connections can be rotated in 90° increments
• Terminal box accessible from top, wire access from underneath
Universal applicationsUniversal applications
Universal applications
Universal applicationsUniversal applications
••
R134a, R407C and R22
••
••
R404A, R507A upon request
••
••
With or without economizer
••
••
Optimized R-134a version (SCA2)
••
New high-efficiency profileNew high-efficiency profile
New high-efficiency profile
New high-efficiency profileNew high-efficiency profile
• Further developed geometry
• High rigidity
• Patented manufacturing process for highest precision
• High tip speed to minimize blow-by
Double-walled, pressure-compensated rotorDouble-walled, pressure-compensated rotor
Double-walled, pressure-compensated rotor
Double-walled, pressure-compensated rotorDouble-walled, pressure-compensated rotor housinghousing
housing
housinghousing
••
Extremely stable, therefore no expansion even at
••
high pressure levels
••
Additional sound attenuation
••
Proven, long-life bearings with pressure unloadingProven, long-life bearings with pressure unloading
Proven, long-life bearings with pressure unloading
Proven, long-life bearings with pressure unloadingProven, long-life bearings with pressure unloading
• Robust axial bearings in tandem configuration
• Bearing chamber pressure isolated by seal rings
• Pressure unloading of axial bearings
Optimized oil managementOptimized oil management
Optimized oil management
Optimized oil managementOptimized oil management
• Three-stage oil separator
• Long-life oil filter 10 µ mesh size
• Pressure relieved bearing chamber ensuring mini­mum refrigerant dilution in the oil and thus higher viscosity
Large volume motor for part winding or direct startLarge volume motor for part winding or direct start
Large volume motor for part winding or direct start
Large volume motor for part winding or direct startLarge volume motor for part winding or direct start
- optional star delta design- optional star delta design
- optional star delta design
- optional star delta design- optional star delta design
• Especially high efficiency
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
2
Page 3
• Integrated PTC sensors in each winding coil
• Slot keys for maximum operating safety
• Stator is slide fit (field replaceable)
Intelligent electronicsIntelligent electronics
Intelligent electronics
Intelligent electronicsIntelligent electronics
• Thermal motor temperature control by winding PTCs
• Phase sequence control for direction of rotation
• Manual reset lock-out
• Oil temperature protection by PTC sensor
Flexible with additional coolingFlexible with additional cooling
Flexible with additional cooling
Flexible with additional coolingFlexible with additional cooling
• Direct liquid injection
• External oil cooler for extended application and highest efficiency
Dual capacity controlDual capacity control
Dual capacity control
Dual capacity controlDual capacity control
• Infinite or 4-step slide control with V
compensation.
i
Alternative operation modes by varying the control sequence only - no need for compressor modification
• Simple control by solenoid coils
• Automatic start unloading
Economizer with sliding suction positionEconomizer with sliding suction position
Economizer with sliding suction position
Economizer with sliding suction positionEconomizer with sliding suction position
• Unique for compact screws
• Efficient economizer operation with part load as well
• Highest cooling capacity and energy efficiency at full and part load conditions
Fully equippedFully equipped
Fully equipped
Fully equippedFully equipped
• Capacity control / start unloading
• Suction and Discharge shut-off valve
• Check valve in discharge gas outlet
• Oil sight glass
• Insertion type oil heater with sleeve
• Oil fill / drain service valve
• Suction gas filter with large surface are and fine mesh
• Electronic protection system
Proven optional accessoriesProven optional accessories
Proven optional accessories
Proven optional accessoriesProven optional accessories
• Oil level switch
• Shut-off valve / adapter for economizer operation and liquid injection
• Adapter for external oil cooler
2.2 Compression process V2.2 Compression process V
2.2 Compression process V
2.2 Compression process V2.2 Compression process V
-control-control
-control
-control-control
ii
i
ii
With screw compressors, suction, compression and discharge occur in one flow direction. With this process the suction gas is pressed into the profile hollows by the profile peaks. The volume is steadily reduced and it is thereby compressed. The compressed gas is then discharged through a discharge port whose size and geometry determine the so called “internal volume ratio
AE4-1322
(Vi)”. This value must have a defined relationship to the mass flow and the working pressure ratio, to avoid losses in efficiency due to over- and under-compres­sion.
The internal discharge ports of the SCH2/SCA2 screw compressors are designed for a very wide application range.
In view of high efficiency and operational safety a part of the discharge channel is integrated into the control slide, which enables a Vi control at part load conditions. Due to this the internal volume ratio (Vi) virtually re­mains constant down to approximately 70% part load.
The economizer channel built into the control slide is another outstanding feature (figure 3). It enables a fully functional operation of the subcooler circuit indepen­dently from the compressor’s load conditions. This is a design solution which is unique for screw compressors of this size. This ensures highest possible capacity and efficiency at both full and part load conditions. For details regarding economizer operation see Section 5.
2.3 Capacity control and start unloading2.3 Capacity control and start unloading
2.3 Capacity control and start unloading
2.3 Capacity control and start unloading2.3 Capacity control and start unloading
SCH2/SCA2 models are provided as a standard with a “Dual Capacity Control” (slide system). This allows for
infinite infinite
infinite or
infinite infinite
4-step capacity control4-step capacity control
4-step capacity control without compressor
4-step capacity control4-step capacity control
modifications. The different operating modes can be achieved by changing the control sequences of the solenoid valves.
The special geometry of the slide means that the volume ratio Vi is adjusted to the operating conditions in part-load operation. This provides particularly high efficiency.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
3
Page 4
AE4-1322
Oil Hydraulic Scheme
Another feature of this system is the automatic start­unloading. It reduces starting torque and acceleration times considerably. This not only puts lower stresses on motor and mechanical parts but also reduces the load on the power supply network.
Significant design features are the robust dimensioning as well as the precise guidance of the slide elements and the control piston. Capacity control is achieved by means of solenoid valves that are flanged on to the compressor. A “dual set point controller” or any similar component is suitable as a control module.
2.4 Hydraulic control2.4 Hydraulic control
2.4 Hydraulic control
2.4 Hydraulic control2.4 Hydraulic control
Figure 3 shows the design principle of the hydraulic scheme. By moving the slide the suction gas flow is controlled.
If the slide is moved totally to the suction slide (in the figure 3 to the left), the working space between the profiles is filled with suction gas. The more the slide is moved to the discharge slide, the smaller the resulting profile volume becomes. Less refrigerant is taken in. The mass flow is lower, and the cooling capacity decreases.
Figure 3
chamber increases. The slide is moved to the suction side. The cooling capacity increases.
If the valve CR1, CR2 or CR3 is opened, the pressure on the hydraulic piston decreases. By means of the discharge gas the slide is pressed to the discharge side. The cooling capacity is reduced.
2.5 Starting the compressor2.5 Starting the compressor
2.5 Starting the compressor
2.5 Starting the compressor2.5 Starting the compressor
During the shut - down of the compressor the solenoid valve CR3 is open. The pressure in the hydraulic cylinder is then released. The spring (fig. 3) pushes the slide to the discharge side end position.
When starting the compressor, it is unloaded. Valve CR4 is energized on demand thus moving the slide towards the suction side. The refrigerating capacity increases to the set load condition by energizing the valves CR1, CR2 or CR3.
2.6 Infinite capacity control2.6 Infinite capacity control
2.6 Infinite capacity control
2.6 Infinite capacity control2.6 Infinite capacity control
Infinite capacity control is recommended for systems where high control accuracy is required. For control principle see charts A, B, and C.
The slide is controlled by a hydraulic piston. If the valve CR4 is opened, the oil pressure in the pressure
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
If the actual value is within the set control range H, the cooling demand of the plant remains unchanged. Then
4
Page 5
AE4-1322
there is no need to move the slide. No solenoid valve is energized.
The control input can be the air or water temperature at the evaporator or the suction pressure.
Chart A
Control Sequence – Infinite Capacity ControlControl Sequence – Infinite Capacity Control
Control Sequence – Infinite Capacity Control
Control Sequence – Infinite Capacity ControlControl Sequence – Infinite Capacity Control
Minimum CapacityMinimum Capacity
Minimum Capacity
Minimum CapacityMinimum Capacity
mm
m
mm
CR 1 2 3 4 Start/Stop mmlm
⇑⇑
Cap
mmml
⇑⇑ ⇓⇓
Cap
mmlm
⇓⇓ ⇔
Cap
mmmm
Cap. 100% mmml Cap. Min.W mmlm
Chart B
Control Sequence – Infinite Capacity ControlControl Sequence – Infinite Capacity Control
Control Sequence – Infinite Capacity Control
Control Sequence – Infinite Capacity ControlControl Sequence – Infinite Capacity Control
Minimum Capacity 50%Minimum Capacity 50%
Minimum Capacity 50%
Minimum Capacity 50%Minimum Capacity 50%
Cap 4 Cap.
⇑⇑
⇑⇑
mm
m
mm mm
m
mm
mm
m
mm ll
l
ll
ll
l
ll mm
m
mm
mm
m
mm
Min.50%
Increased cooling demandIncreased cooling demand
Increased cooling demand
Increased cooling demandIncreased cooling demand
If the actual value exceeds the upper set point, the cooling demand has increased (operating point A in fig.
4). The solenoid valve CR4 is opened for short intervals
till the actual value is within the set control range again (operating point B). Now the compressor operates with increased cooling capacity.
Chart C
Control Sequence – 4-Step Capacity ControlControl Sequence – 4-Step Capacity Control
Control Sequence – 4-Step Capacity Control
Control Sequence – 4-Step Capacity ControlControl Sequence – 4-Step Capacity Control
Decreased cooling demandDecreased cooling demand
Decreased cooling demand
Decreased cooling demandDecreased cooling demand
A decreased cooling demand falls below the lower set point (operating point C). The solenoid valve CR3 now opens for short intervals till the actual value is within the set control range again (operating point D). The compressor operates with decreased cooling capacity.
With the solenoid valves CR3 / CR4, capacity can be controlled between 100% and nominally 25%. Alterna­tively valves CR2 / CR4 can be energized; in this case control will be limited between 100% and nominally 50%.
The limitation to a minimum of approximately 50% cooling capacity is recommended for the following application conditions (control with valves CR2 / CR4):
• In case of operation at high-compression ratios / condensing temperatures, the main concern is high discharge temperature.
• For systems with multiple compressors either used in split or singlecircuits. Under these conditions capacity control between 100 and 50%, in combina­tion with individual compressor on/off cycling, guarantees highest possible efficiency – without significant restrictions in the application range. Due to the usually lowered condensing temperature at part load conditions, the lead compressor can even be operated very effectively down to nominal 25% of cooling capacity (with valves CR3 / CR4)
2.7 4-step capacity control2.7 4-step capacity control
2.7 4-step capacity control
2.7 4-step capacity control2.7 4-step capacity control
This type of capacity control is particularly suited to systems with high inertia – in connection with indirect cooling, for example. Liquid chillers are typical applica­tions. Chart C shows the control of the solenoid valves or the individual capacity steps.
CR 1 2 3 4 Start/Stop mmlm Cap 25% mmly Cap 50% mlmy Cap 75% lmmy Cap. 100% mmmm
Solenoid Coil De-Energized Solenoid Coil De-Energized
m
Solenoid Coil De-Energized
Solenoid Coil De-Energized Solenoid Coil De-Energized
Solenoid Coil EnergizedSolenoid Coil Energized
l
Solenoid Coil Energized
Solenoid Coil EnergizedSolenoid Coil Energized
Solenoid Coil Pulsing (10 secs. on / 10 secs. off) Solenoid Coil Pulsing (10 secs. on / 10 secs. off)
y
Solenoid Coil Pulsing (10 secs. on / 10 secs. off)
Solenoid Coil Pulsing (10 secs. on / 10 secs. off) Solenoid Coil Pulsing (10 secs. on / 10 secs. off)
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
The cycle time of the intermitting valve, CR4, should be adjusted to about 10 seconds before commissioning. Even shorter intervals may be necessary, particularly with systems with high pressure differences. Therefore, in this case adjustable time relays should be used. For this type of operation a restriction of minimum refrigeration capacity to approximately 50% is also recommended, as with the systems described in Section 2.6. Control is then effected with the CR4 valve (intermittent) and with CR1 (75%) and CR2 (50%).
5
Page 6
AE4-1322
2.8 Oil circulation2.8 Oil circulation
2.8 Oil circulation
2.8 Oil circulation2.8 Oil circulation
The lubrication circuit is designed as is typical for screw compressors. This type of design, however, has a vessel directly flanged-on to the compressor housing at the high-pressure side. It contains the oil reservoir. The vessel simultaneously serves as an oil separator.
The oil circulation results from the pressure difference to the oil injection point, where the pressure level is slightly above suction pressure. The oil flows through a generously sized filter element to the throttle point and subsequently to the bearing chambers and the profile spaces of the rotors. The oil is then transported together with the refrigerant vapor in the direction of compression. In addition to lubrication it also provides a dynamic seal between the rotors and between the housing and the rotors. The oil then flows together with the compressed vapor into the reservoir vessel. Here oil and vapor are separated in a highly efficient process. The oil collects in the lower part of the separator vessel
Figure 4
Infinite capcity control scheme
and flows back into the compressor either direct or via an external oil cooler. Depending on the operating conditions the circulating oil must be cooled with liquid injection or an external oil cooler (see Section 4.4 and
4.5)
Monitor the oil circuitMonitor the oil circuit
Monitor the oil circuit
Monitor the oil circuitMonitor the oil circuit
• For short circuits additional cooling and for small system volumes and refrigerant charges: indirect monitoring by means of oil temperature protection (standard)
without without
without refrigerant injection for
without without
CAUTION!CAUTION!
CAUTION!
CAUTION!CAUTION!
Lack of oil leads to a dramaticLack of oil leads to a dramatic
Lack of oil leads to a dramatic
Lack of oil leads to a dramaticLack of oil leads to a dramatic
temperature increase.temperature increase.
temperature increase.
temperature increase.temperature increase.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
6
Page 7
AE4-1322
• For circuits cooling and / or for greater system volumes: Direct monitoring by means of an oil level monitor in the oil separator(optional accessory) is recom­mended.
3 Lubricants3 Lubricants
3 Lubricants
3 Lubricants3 Lubricants
Apart from the lubrication it is also the task of the oil to provide dynamic sealing of the rotors. Special demands result from this with regard to viscosity, solubility and foaming characteristics. Copeland approved oils may therefore be used only.
Important instructionsImportant instructions
Important instructions
Important instructionsImportant instructions
• Observe the application limits of the compressors.
• The lower limit value of the discharge gas tempera­ture (140°F) is a reference value only. It must be ensured by sufficient suction super-heat that the discharge gas temperature is at least 54°F (R134a, R404A / R507A mi. 36°F) above the condensing temperature.
• Ester oils Solest170 (for HFC refrigerants) and CP4214-320 (for R22) are very hygroscopic. Special care is therefore required when dehydrating the system and when handling open oil containers.
withwith
with refrigerant injection for additional
withwith
Figure 5
Mounting and installation
4.1 Mounting the compresso4.1 Mounting the compresso
4.1 Mounting the compressor
4.1 Mounting the compresso4.1 Mounting the compresso
With stationary systems the compressor has to be installed horizontally.
In case of marine application, mounting in direction of the longitudinal axis of the boat may be required. Detailed layout recommendation can be provided upon request.
Anti-vibration mountingsAnti-vibration mountings
Anti-vibration mountings
Anti-vibration mountingsAnti-vibration mountings
• A corrected design may be necessary for direct­expansion evaporators with finned tubes on the refrigerant side (consultation with manufacturer).
The above information corresponds to the present status of our knowledge and is intended as a guide for general applications. This information does not have the purpose of confirming certain oil characteristics or their suitability for a particular case.
4 Integration into the refrigeration circuit4 Integration into the refrigeration circuit
4 Integration into the refrigeration circuit
4 Integration into the refrigeration circuit4 Integration into the refrigeration circuit
Compact screw compressors are well suited for integration in factory-assembled plants (liquid chillers and air conditioning units). Their use in extended systems is also possible, for example, with remotely installed condenser.
Systems with multiple compressors should preferably be designed with individual circuits. Parallel compound is possible, but requires a special oil equalizing system by means of oil level control.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
Rigid mounting of the compressor is possible. The use of anti-vibration mountings especially matched to the compressors is recommended, however, to reduce the transmission of body radiated noise.
With direct mounting on water cooled condensers:
CAUTION!CAUTION!
CAUTION!
CAUTION!CAUTION!
Do not mount the compressor directlyDo not mount the compressor directly
Do not mount the compressor directly
Do not mount the compressor directlyDo not mount the compressor directly
on the condenseron the condenser
on the condenser
on the condenseron the condenser
condenser structural mmember! condenser structural mmember!
condenser structural mmember!
condenser structural mmember! condenser structural mmember!
Damage of the condenser is possibleDamage of the condenser is possible
Damage of the condenser is possible
Damage of the condenser is possibleDamage of the condenser is possible
(fatigue fractures). Use anti-vibration (fatigue fractures). Use anti-vibration
(fatigue fractures). Use anti-vibration
(fatigue fractures). Use anti-vibration (fatigue fractures). Use anti-vibration
mountings!mountings!
mountings!
mountings!mountings!
The installation of the anti-vibration mountings is shown in figure 5. The bolts should only be tightened until slight deformation of the upper rubber disc is just visible.
7
. Do not use the. Do not use the
. Do not use the
. Do not use the. Do not use the
Page 8
4.2 System layout4.2 System layout
4.2 System layout
4.2 System layout4.2 System layout
Oil heaterOil heater
Oil heater
Oil heaterOil heater
AE4-1322
The compressor is installed in the refrigerating circuit similar to semi-hermetic reciprocating compressors.
Plant design and pipe layoutPlant design and pipe layout
Plant design and pipe layout
Plant design and pipe layoutPlant design and pipe layout
The pipelines and the system layout must be arranged so that the compressor cannot be flooded with oil or liquid refrigerant during shutdown.
Suitable measures are (also as a simple protection against liquid slugging during start)
• either to raise the suction line after the evaporator (goose neck)
• or to install the compressor above the evaporator.
Additional safety is provided by a solenoid valve installed directly before the expansion valve. In addition the discharge line should first be angled downwards after the shut-off valve.
Due to the low level of vibration and discharge gas pulsation the suction and discharge lines can be made without the use of flexible elements or mufflers. However, pipelines must be sufficiently flexible and supported to not exert any strain on the compressor. The most favorable pipe runs are designed parallel to the compressor axis and the discharge line first leading downwards. The distance to the axis should be as short as possible and the parallel pipe section should be at least half the compressor’s length. Finally, long radius elbows should be used.
Due to gas pulsations there can be vibrations espe­cially in discharge and economizer lines. Therefore critical pipe lengths (+/- 15%) with their natural fre­quencies being in resonance with the compressor pulsations must be avoided.
An oil heater is provided to prevent too high a concen­tration of refrigerant in the oil during shutdown. It is mounted in a heater sleeve and can be replaced if necessary without accessing the refrigerating circuit. For electrical connection see section 6.4.
Figure 6
Typical system design
Additional insulation of the oil separatorAdditional insulation of the oil separator
Additional insulation of the oil separator
Additional insulation of the oil separatorAdditional insulation of the oil separator
Operation at low ambient temperatures or at high temperatures on the discharge side during standstill (such as heat pumps) requires additional insulation of the oil separator.
Among other things the operating conditions and the refrigerant (sonic speed) as well as the compressor’s pulsation frequency must be considered in the calcula­tion.
The base frequency of the compressor is approx. 250Hz (50Hz network) or 300 Hz (60 Hz network). Frequencies of higher orders (500 / 1000 Hz or 600 / 1200 Hz) should also reviewed at in the final layout.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
Filter drierFilter drier
Filter drier
Filter drierFilter drier
Generously sized filter driers of suitable quality should be used to ensure a high degree of dehydration and to maintain the chemical stability of the system.
Suction side cleaning filterSuction side cleaning filter
Suction side cleaning filter
Suction side cleaning filterSuction side cleaning filter
The use of a suction side filter (filter mesh 25 m) will protect the compressor from damage due to dirt from the system and is strongly recommended for site built systems.
8
Page 9
AE4-1322
Expansion valve and evaporatorExpansion valve and evaporator
Expansion valve and evaporator
Expansion valve and evaporatorExpansion valve and evaporator
Expansion valve and evaporator have to be adjusted using utmost care. This is especially important for those systems that cover a large control range, e.g. 100% to 25%. In each case, sufficient suction gas superheat and stable operating conditions must be assured in full load as well as part load modes. Depending on the evaporator’s design and performance range several circuits may be necessary each with separate expansion and solenoid valves.
3.3 Guidelines for special system variations3.3 Guidelines for special system variations
3.3 Guidelines for special system variations
3.3 Guidelines for special system variations3.3 Guidelines for special system variations
Pump down circuitPump down circuit
Pump down circuit
Pump down circuitPump down circuit
If the evaporator and / or the suction line can become warmer than the compressor during shutdown, a “pump down” cycle must be incorporated in addition to the oil heater.
Additional check valve in the discharge line andAdditional check valve in the discharge line and
Additional check valve in the discharge line and
Additional check valve in the discharge line andAdditional check valve in the discharge line and automatic sequence controlautomatic sequence control
automatic sequence control
automatic sequence controlautomatic sequence control
For systems with multi-circuit condensers and / or evaporators, an increased danger exists when indi­vidual circuits are shut off. During this period liquid refrigerant can migrate into the evaporator (no tempera­ture and pressure equalization possible). In these cases an additional check valve must be installed in the discharge line. In addition the compressors should be operated with an automatic sequence control.
The same is also valid for individual systems without temperature and pressure equalization during longer shutdown. In extreme cases a suction accumulator or “pump down” cycle can also become necessary.
Additional oil level controlAdditional oil level control
Additional oil level control
Additional oil level controlAdditional oil level control
accumulator is recommended to protect against liquid slugging. To effectively avoid increased oil carry-over (such as due to a rapid decrease of pressure in the oil separator), the oil temperature must remain at least 54° F above the condensing temperature during charge over. In addition, it may be necessary to install a pressure regulator immediately after the oil separator to limit pressure drop. Under certain conditions it is also possible to turn off the compressor shortly before the change over procedure and to restart after pressure equalization. It must however be assured that the compressor is operating with the required minimum pressure differential no longer than 30 seconds (see application ranges Section 9).
3.4 Additional cooling by means of direct liquid3.4 Additional cooling by means of direct liquid
3.4 Additional cooling by means of direct liquid
3.4 Additional cooling by means of direct liquid3.4 Additional cooling by means of direct liquid injectioninjection
injection
injectioninjection
Additional cooling is required in areas of high condens­ing and / or low evaporating temperatures. A relatively simple method is direct liquid inject at the economizer connection.
The following criteria must be followed to ensure reliable operation and to avoid excessive dilution of the oil.
Liquid inject valveLiquid inject valve
Liquid inject valve
Liquid inject valveLiquid inject valve
Specially designed expansion valves are only suitable for liquid injection. They must control the discharge temperature to setting of 190°F (e.g. Danfoss TEAT20, also series 935-101-B, Sporian Y1037).
The valve bulb must be mounted on the discharge line:
• Clean the tubes surface carefully to bright metal. Distance from discharge shut-off valve approx. 8 to 10 inches.
The above guidelines also apply to systems with long pipelines (suchas a remote evaporator and / or con­denser). In addition the compressor must be equipped with an oil level switch (accessory). For electrical connection see Section 6.4.
Systems with reverse cycling and hot gas defrostSystems with reverse cycling and hot gas defrost
Systems with reverse cycling and hot gas defrost
Systems with reverse cycling and hot gas defrostSystems with reverse cycling and hot gas defrost
These system layouts require individually system design review to protect the compressor against liquid slugging and increased oil carry-over. A suction
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
• Apply heat transfer paste to the contact surface.
• Fix the bulb firmly with adequate pipe clips. Mind heat expansion!
• Insulate the bulb and the section of discharge line
9
Page 10
AE4-1322
Pipe runsPipe runs
Pipe runs
Pipe runsPipe runs
To ensure a bubble free liquid supply to the liquid injection valve, the connection must be made on the bottom of a horizontal section of the liquid line.
Installation of the liquid inject valve at the com-Installation of the liquid inject valve at the com-
Installation of the liquid inject valve at the com-
Installation of the liquid inject valve at the com-Installation of the liquid inject valve at the com­pressorpressor
pressor
pressorpressor
• Min. 6 to 8 in. above liquid injection connection
CAUTION!CAUTION!
CAUTION!
CAUTION!CAUTION!
VV
ibration fractures possible! install liquidibration fractures possible! install liquid
V
ibration fractures possible! install liquid
VV
ibration fractures possible! install liquidibration fractures possible! install liquid
injection and solenoid valves withinjection and solenoid valves with
injection and solenoid valves with
injection and solenoid valves withinjection and solenoid valves with
adequate supports!adequate supports!
adequate supports!
adequate supports!adequate supports!
Check for vibration during operation!Check for vibration during operation!
Check for vibration during operation!
Check for vibration during operation!Check for vibration during operation!
Calculating the cooling capacity of the liquidCalculating the cooling capacity of the liquid
Calculating the cooling capacity of the liquid
Calculating the cooling capacity of the liquidCalculating the cooling capacity of the liquid injection valveinjection valve
injection valve
injection valveinjection valve
Figure 7
Liquid injection valve (system design)
• With the selection software
• Consider the most extreme conditions to be expected during actual operation:
- min. evaporating temperature
- max. suction gas superheat and condensing temperature
Further conditions for valve selectionFurther conditions for valve selection
Further conditions for valve selection
Further conditions for valve selectionFurther conditions for valve selection
• Pressure at the injection point:
- R134a approximately 30 to 45 psig above suction pressure R407C, R22 approx. 40 to 50 psig above suction pressure
- Never size the valve too large danger of refrigerant flooding!
Additional components in the liquid lineAdditional components in the liquid line
Additional components in the liquid line
Additional components in the liquid lineAdditional components in the liquid line
• Solenoid valve (energized parallel to compressor contactor)
• Filter dryer (if required)
• Liquid sight glass
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
10
Page 11
3.5 Additional cooling by means of external oil3.5 Additional cooling by means of external oil
3.5 Additional cooling by means of external oil
3.5 Additional cooling by means of external oil3.5 Additional cooling by means of external oil coolercooler
cooler
coolercooler
AE4-1322
• Oil coolers must be controlled by thermostats (see table for temperature settings).
The application of an external oil cooler (air, water or refrigerant cooled) instead of refrigerant inject provides additional extension of the application envelopes and even better efficiency.
When calculating an oil cooler, worst case operating conditions must be used:
• Min. evaporating temperature
• Max. suction gas superheat
• Max. condensing temperature
• Operation mode (capacity control, ECO)
Oil cooler capacity can be calculated by using the selection software.
Recommendations for external oil coolersRecommendations for external oil coolers
Recommendations for external oil coolers
Recommendations for external oil coolersRecommendations for external oil coolers
• Connections for external oil coolers are located on the back side of the compressor below the dis­charge shut-off valve (oval or rectangular flange). The flange is replaced by a tube adaptor (option):
• Install oil cooler as close as possible to the com­pressor.
• Piping design must avoid gas pockets and any drainage of oil into the compressor during shut­downs (installation of the oil cooler preferably at compressor level or below).
• For rapid heating of the oil circuit and minimizing the pressure drop with cold oil an oil by-pass (or even heating the cooler during shut down) is required under the following conditions:
- the oil temperature in the cooler drops below
60°F during shut down,
- the oil volume of cooler plus oil piping exceeds
the compressor’s oil charge,
- The oil cooler is an integral part of the con-
denser coil
• The by-pass valve should have a temperature responsive modulating control function. The use of a solenoid valve for intermittent control would require highly sensitive control thermostat and a minimal switching differential (effective temperature variation < 18°F).
• The oil side pressure drop during normal operation should not exceed 7 psig.
• Due to the additional oil volume (cooler, piping) a solenoid valve may be necessary in the oil line. This is to avoid oil migration into the compressor during shutdowns. The solenoid valve must be installed close to the compressor’s oil inlet connec­tion and its electric control should be parallel to the contactor’s normally open contact. Recommended additional components:
- Sight glass to check oil flow,
- Manual shut-off ball valves in both feed and return lines for ease of service,
- Oil filter (max. 25 µ mesh size)
With an additional oil volume (cooler and piping) of 10% of the compressor’s standard oil charge and assured cleanliness of components and pipes the above mentioned measures can be omitted.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
Figure 8
External oil cooler connection
Water cooled oil coolerWater cooled oil cooler
Water cooled oil cooler
Water cooled oil coolerWater cooled oil cooler
Temperature control by thermostatic water regulator (for set point see table, required sensor temperature should be equal to or greater than 250°F).
11
Page 12
Figure 9
Water-cooled oil cooler
Air cooled oil coolerAir cooled oil cooler
Air cooled oil cooler
Air cooled oil coolerAir cooled oil cooler
Temperature control by thermostatic switching on and off or stepless speed control of the cooler fan (see table for set point, required sensor temperature should be equal to or greater than 250°F).
AE4-1322
Thermosyphon oil cooling (cooling by refrigerant)Thermosyphon oil cooling (cooling by refrigerant)
Thermosyphon oil cooling (cooling by refrigerant)
Thermosyphon oil cooling (cooling by refrigerant)Thermosyphon oil cooling (cooling by refrigerant)
Temperature control either by thermostatic regulation valve for refrigerant feed or by-pass valve (see table for set point; admissible operating and sensor temperature should be equal to or greater than 250°F).
As an example figure 11 shows a layout with a primary receiver after the condenser. An alternative layout of the thermosyphon circuit as well as refrigerant circulation by means of a pump or an ejection is also possible (information upon request).
If the oil coolers is integrated into the condenser the by-pass valve controls the temperature (see table for set point; admissible operating and / or sensor tem­perature should be equal to or greater than 250°F).
DL SL
Figure 10
Air cooled oil coolers
Figure 11
Thermosyphon oil cooling
4 Economizer operation
1.1 General1.1 General
1.1 General
1.1 General1.1 General
SCH2/SCA2 screw compressors are designed for economizer operation “ECO”. With this operation mode both cooling capacity and efficiency are improved by means of a sub-cooling circuit or 2-stage refrigerant expansion. There are capacity and efficiency advan­tages in ECO operation over the conventional applica­tion, particularly at high condensing temperatures.
A unique feature of the compact screws is the econo­mizer channel integrated into the control slide (fig.12). This enables to operate the sub-cooling circuit regard­less of the compressor load condition. Screw com­pressors with a fixed ECO suction position have this frequently located in the suction area of the rotors during part load and then has no effect.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
12
Page 13
5.2 Operation principle5.2 Operation principle
5.2 Operation principle
5.2 Operation principle5.2 Operation principle
AE4-1322
5.3 Economizer operation with sub-cooling circuit5.3 Economizer operation with sub-cooling circuit
5.3 Economizer operation with sub-cooling circuit
5.3 Economizer operation with sub-cooling circuit5.3 Economizer operation with sub-cooling circuit
With screw compressors the compression process occurs only in one flow direction (see Section 2.2). This fact enables to locate an additional suction port at the rotor housing. The position is selected so that the suction process has already been completed and a slight pressure increase has taken place. Via this connection an additional mass flow can be taken in, which has only a minimal effect on the flow from the suction side.
The pressure level at the ECO suction point is similar to the intermediate pressure with 2-stage compres­sors. This means that an additional sub-cooling circuit or intermediate pressure receiver for 2-stage expansion can be integrated into the system. This design achieves a significantly higher cooling capacity through additional liquid sub-cooling. At the same time, there is a relatively low increase in the compressor’s power input, as the total working process becomes more efficient – due to the higher suction pressure, among other things.
System with sub-cooling circuit
Figure 12
With this operation mode a heat exchanger is utilized as a liquid sub-cooler. A part of the refrigerant mass flow from the condenser enters the sub-cooler via an expansion device, and evaporates upon absorbing heat from the counter-flowing liquid refrigerant (sub-cooling). The superheated vapor is taken in at the compressor’s ECO connection, mixed with the mass flow from the evaporator and compressed to a high pressure.
With this type of operation the sub-cooled liquid is under condensing pressure. Therefore the piping to the evaporator does not require any special features – apart from insulation.The system can be applied universally.
5.4 ECO operation with intermediate pressure5.4 ECO operation with intermediate pressure
5.4 ECO operation with intermediate pressure
5.4 ECO operation with intermediate pressure5.4 ECO operation with intermediate pressure receiverreceiver
receiver
receiverreceiver
This layout version for 2-stage refrigerant pressure relief is particularly advantageous in connection with flooded evaporators and is therefore primarily used in plants with large cooling capacity.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
13
Page 14
5.5 Layout and selection recommendations5.5 Layout and selection recommendations
5.5 Layout and selection recommendations
5.5 Layout and selection recommendations5.5 Layout and selection recommendations
Pipe layoutPipe layout
Pipe layout
Pipe layoutPipe layout
• Design the sub-cooler so that during shutdown, neither liquid refrigerant nor oil can enter the com­pressor.
• Until operating conditions are established during temporary operation without economizer and when switching off the compressor, the compressor can discharge a certain amount of oil through the ECO connection. Oil transfer into the sub-cooler must therefore be prevented by a pipe bending vertically upwards with a check valve (see fig.13).
In order to avoid instability of the check valve when the ECO circuit is switched off, a by-pass-line with a solenoid valve towards the suction side must also be included (1/4”). The solenoid valve is only open when the ECO is not operating. This way it creates sufficient closing pressure for the check valve.
AE4-1322
• Pipe vibrations: Due to the pulsations emitting from the profile area of the compressor, critical pipe lengths must be avoided. See also Section 4.2.
5.6 Additional components5.6 Additional components
5.6 Additional components
5.6 Additional components5.6 Additional components
Refrigerant sub-coolerRefrigerant sub-cooler
Refrigerant sub-cooler
Refrigerant sub-coolerRefrigerant sub-cooler
Frost proof shell and tube, coaxial or plate heat exchangers are suitable as sub-coolers. In the design phase the relatively high temperature gradient on the liquid side must be taken into consideration.
For capacity determination see output date in the compressor software:
• Sub-cooler capacity
• ECO mass flow
• Saturated ECO temperature and
• Liquid temperature.
Layout parametersLayout parameters
Layout parameters
Layout parametersLayout parameters
• See Section 6 for electric control. Other layout versions are also possible, but must be checked for their suitability and operating safety in individual tests.
• The ECO connection leads directly into the profile area. For this reason a high degree of cleanliness must be maintained for sub-cooler and pipes.
• Dimension of the ECO suction line: In view of the usually short pipe lengths, the following pipe diameters can be used: SCH2 5000 to 9000 1 ¼” – 12 Rotolock SCA2 3500 to 7000 SCH2 11H0 to 14H0 1 ½” – 12 Rotolock SCA2 9000 to 11H0
Min 6 – 8” rise
• Intermediate temperature
- corresponds to the evaporating temperature in the sub-cooler
- for layout design, take 18°F suction gas superheat into consideration
• Liquid temperature (inlet) As a nominal selection basis, liquid sub-cooling of 4°F is assumed
example: tc = 90°F liquid temperature (inlet) = 86ºF.
• Liquid temperature (outlet) The software pre-set date are based on 18°F above saturated ECO temperature
Example: tm = +68ºF liquid temperature (outlet) = 86ºF
Input of individual data is possible. Keep in mind, however, that in practice a stable operating mode is very difficult to achieve with differences between liquid temperature (outlet) and saturated ECO temperature of less than 18°F.
Figure 13
Liquid injection connections
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
14
Page 15
Thermostatic expansion valvesThermostatic expansion valves
Thermostatic expansion valves
Thermostatic expansion valvesThermostatic expansion valves
• Valve layout for liquid sub-cooler:
- Basis is the sub-cooling capacity
- Evaporating temperature corresponds to the ECO intermediate temperature.
- Valves with a superheat adjustment of about 10 K should be used in order to avoid unstable operation when switching on the sub-cooling circuit and in connection with load fluctuations.
- If the sub-cooling circuit is also operated under part-load conditions, this must be given due consideration when designing the valves.
• Valve layout for evaporator: Due to the high degree of liquid sub-cooling suction mass flow is much lower than with systems with similar capacity and no sub-cooler (see software data). This requires a modified layout. In this context the lower vapor content after expansion must also be taken into consideration. For further hints on the layout of expansion valves and evapora­tors see Section 4.2.
5.7 Control5.7 Control
5.7 Control
5.7 Control5.7 Control
Between that start and the stabilization of operating conditions, the solenoid valve of the sub-cooling circuit is switched on time delayed or depending on suction pressure. For further hints and a schematic layout diagram see Section 6.4.
AE4-1322
The compressors are supplied as standard with part winding motors of connection (Part Winding “PW”). Start delta motors are available as special design.
Part winding motorsPart winding motors
Part winding motors
Part winding motorsPart winding motors
Starting methods (connections according to figures 14 and 15):
• Part winding start to reduce the starting current
• Direct on line start (DOL)
Start delta motorsStart delta motors
Start delta motors
Start delta motorsStart delta motors
Starting methods (connections according to figures 16 and 17).
The start current value in star mode (1/3 ofThe start current value in star mode (1/3 of
The start current value in star mode (1/3 of
The start current value in star mode (1/3 ofThe start current value in star mode (1/3 of the direct on line value) is generally statedthe direct on line value) is generally stated
the direct on line value) is generally stated
the direct on line value) is generally statedthe direct on line value) is generally stated according to standard locked rotor condi-according to standard locked rotor condi-
according to standard locked rotor condi-
according to standard locked rotor condi-according to standard locked rotor condi­tions. In realitytions. In reality
tions. In reality
tions. In realitytions. In reality obtained during the start. Moreoverobtained during the start. Moreover
obtained during the start. Moreover
obtained during the start. Moreoverobtained during the start. Moreover switching from start to delta mode there is aswitching from start to delta mode there is a
switching from start to delta mode there is a
switching from start to delta mode there is aswitching from start to delta mode there is a current peak as high as the direct start value.current peak as high as the direct start value.
current peak as high as the direct start value.
current peak as high as the direct start value.current peak as high as the direct start value. This is caused by the voltage interruptionThis is caused by the voltage interruption
This is caused by the voltage interruption
This is caused by the voltage interruptionThis is caused by the voltage interruption during switch-over of the contactors, whichduring switch-over of the contactors, which
during switch-over of the contactors, which
during switch-over of the contactors, whichduring switch-over of the contactors, which results in a speed drop due to theresults in a speed drop due to the
results in a speed drop due to the
results in a speed drop due to theresults in a speed drop due to the compressorcompressor
compressor
compressorcompressor
, however, however
, however
, however, however
’’
s small rotating masses.s small rotating masses.
s small rotating masses.
’’
s small rotating masses.s small rotating masses.
, approx. 50% are, approx. 50% are
, approx. 50% are
, approx. 50% are, approx. 50% are
, when, when
, when
, when, when
6 Electrical connection6 Electrical connection
6 Electrical connection
6 Electrical connection6 Electrical connection
6.1 Motor design6.1 Motor design
6.1 Motor design
6.1 Motor design6.1 Motor design
Figure 14
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
Figure 15
15
Figure 16
Figure 17
Page 16
Figure 18
Power factor correction on individual compressors
AE4-1322
6.2 Selection of electrical components6.2 Selection of electrical components
6.2 Selection of electrical components
6.2 Selection of electrical components6.2 Selection of electrical components
Cables, contractors and fusesCables, contractors and fuses
Cables, contractors and fuses
Cables, contractors and fusesCables, contractors and fuses
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Nominal power is not the same asNominal power is not the same as
Nominal power is not the same as
Nominal power is not the same asNominal power is not the same as
maximum motor power! When selectingmaximum motor power! When selecting
maximum motor power! When selecting
maximum motor power! When selectingmaximum motor power! When selecting
cables, contactors and fuses: cables, contactors and fuses:
cables, contactors and fuses:
cables, contactors and fuses: cables, contactors and fuses:
operating current / maximum motoroperating current / maximum motor
operating current / maximum motor
operating current / maximum motoroperating current / maximum motor
power must be considered. See chapter 8. power must be considered. See chapter 8.
power must be considered. See chapter 8.
power must be considered. See chapter 8. power must be considered. See chapter 8.
Contactor selection: according toContactor selection: according to
Contactor selection: according to
Contactor selection: according toContactor selection: according to
operational category operational category
operational category
operational category operational category
Part winding motorsPart winding motors
Part winding motors
Part winding motorsPart winding motors
The following current values appear in the part wind­ings:
PW1 PW2 50% 50%
Both of the contactors should be selected for at least 60% of the maximum operating current.
Star delta motorsStar delta motors
Star delta motors
Star delta motorsStar delta motors
Calculate mains and delta contactor each to at least 60%, start contactor to 33% of the maximum operating current.
MaximumMaximum
Maximum
MaximumMaximum
AC 3.AC 3.
AC 3.
AC 3.AC 3.
Power factor correctionPower factor correction
Power factor correction
Power factor correctionPower factor correction
For the reduction of the reactive current when using inductive loads (motors, transformers), power factor correction systems (capacitors) are increasingly being used. However, apart from the undisputed power supply advantages, experience shows that the layout and execution of such systems is not a simple matter, as insulation damage on motors and increased contact arcing on contactors can occur.
With a view to a safe operating mode, the correction system should be designed to effectively prevent “over­correction” in all operating conditions and the uncon­trolled discharge of the capacitors when starting and shutting down the motors.
General design criteriaGeneral design criteria
General design criteria
General design criteriaGeneral design criteria
• Maximum power factor (P.F. 0.95 - taking into consideration all load conditions.)
Individual correction (Fig. 21)Individual correction (Fig. 21)
Individual correction (Fig. 21)
Individual correction (Fig. 21)Individual correction (Fig. 21)
• With capacitors that are directly fitted to the motor (without the possibility of switching off with contactors), the capacitor capacity must never be greater than 90% of the zero-load reactive capacity of the motor (less than 25% of max. motor power). With higher capacities there is the danger of self­exiting when shutting off, resulting in damage to the motor.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
16
Page 17
AE4-1322
• For part winding start a separate capacitor should be used for each half of the winding (50% each). Only one capacitor is used for start delta motors (parallel to contactor K1).
• In the case of extreme load fluctuations (large capacity range) combined with high demands on a low reactive capacity, capacitors that can be switched on and off with contactors (in combination with a discharge throttle) may be necessary. Design is similar to central correction.
Central correction (Fig. 22)Central correction (Fig. 22)
Central correction (Fig. 22)
Central correction (Fig. 22)Central correction (Fig. 22)
• When the designing, connected loads and the operating times of all inductive loads (including fluorescent lamps if they do not have their own correction) must be taken into consideration.
• The number of capacitor stages must be selected so that the smallest unit does not have a larger capacity than the lowest inductive load (with P.F.
0.95). Extreme part load conditions are particularly critical, such as can occur during the night, at weekends or while being put into operation. If loads are too low the entire correction device should be disconnected from the power supply.
• With central correction (as well as with individual correction with contactor control) discharge throttle must always be provided. Reconnection to the power supply may only occur after complete discharge and a subsequent time delay.
The layout of correction systems for motors with direct starting is similar.
CAUTION!CAUTION!
CAUTION!
CAUTION!CAUTION!
It is essential to observe the generalIt is essential to observe the general
It is essential to observe the general
It is essential to observe the generalIt is essential to observe the general design and layout instruction of thedesign and layout instruction of the
design and layout instruction of the
design and layout instruction of thedesign and layout instruction of the
correction system manufacturer correction system manufacturer
correction system manufacturer
correction system manufacturer correction system manufacturer
Frequency inverterFrequency inverter
Frequency inverter
Frequency inverterFrequency inverter
Operation with a frequency inverter is possible. How­ever, layout and operating conditions must be individu­ally approved by Copeland
3.3 Compressor protection system3.3 Compressor protection system
3.3 Compressor protection system
3.3 Compressor protection system3.3 Compressor protection system
The SCH2/SCA2 compressors are fitted with the protection device INT69VSY-II.
Monitoring functionsMonitoring functions
Monitoring functions
Monitoring functionsMonitoring functions
• Winding temperature (PTC sensors in motor winding)
- Interruption of the control current with excess temperature
- Manual reset (after winding has cooled) by interruption of supply voltage L/N for at least 2 seconds
• Oil temperature (sensor with PTC resistance in oil sump)
- Function as above (winding temperature)
..
.
..
..
.
..
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
Figure 20
Power factor correction on central power system
17
Page 18
• Direction of rotation/phase sequence (direct mea­surement at compressor terminals)
- Immediate interruption of control current and
lock-out with wrong direction of rotation / phase sequence (indication via signal contact 12)
- Reset (after correction of fault) by interruption of
the supply voltage L/N for at least 2 seconds.
The protection device is built into the terminal box. The wiring to the motor and oil temperature PTC sensors and also to be motor terminals is factory mounted. The electrical connections to the device should be made according to figure 21 or 22 and the schematic wiring diagrams.
In principle the device could be also built into the control panel. In the case it is essential to adhere to the following recommendations:
Special attention must be given when fitting the INT69VSY-II in the control panel:
AE4-1322
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Make sure that the rotation monitoring isMake sure that the rotation monitoring is
Make sure that the rotation monitoring is
Make sure that the rotation monitoring isMake sure that the rotation monitoring is
functioning! Tfunctioning! T
functioning! T
functioning! Tfunctioning! T
INT69VSYINT69VSY
INT69VSY
INT69VSYINT69VSY
according to the wiring diagram. according to the wiring diagram.
according to the wiring diagram.
according to the wiring diagram. according to the wiring diagram.
the jumper L/D1 at this time.the jumper L/D1 at this time.
the jumper L/D1 at this time.
the jumper L/D1 at this time.the jumper L/D1 at this time.
The following requirements must be ensured byThe following requirements must be ensured by
The following requirements must be ensured by
The following requirements must be ensured byThe following requirements must be ensured by the control logic:the control logic:
the control logic:
the control logic:the control logic:
• Minimum time of standstill: 1 minute. Valid during maintenance also! Returning time of the control slide - CR3 (Y3) energized
• Maximum cycling rate 6 to 8 starts per hour!
• Minimum running time desired 5 minutes!
• Switch-over time part winding 0.5 seconds start delta 1 second
erminal D1 of theerminal D1 of the
erminal D1 of the
erminal D1 of theerminal D1 of the
-II must be connected-II must be connected
-II must be connected
-II must be connected-II must be connected RemoveRemove
Remove
RemoveRemove
• The connecting cables to the motor terminals must be wired in the sequence described (L1 to terminal “1” etc.) Check with a direction of rotation indicator!
• Danger of induction! Only use shielded cables or a twisted pair to connect to the PTC motor sensors and oil tempera­ture PTC sensors.
• Additional fuses (4 A) must be incorporated in the connecting cables between “L1/L2/L3” of the protection device and the motor terminals “1/2/3”.
• The terminals T1-T2 on the compressor and 1-2 on protection device must not come into contact with supply or control voltage.
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
If the rotation direction is wrong: DangerIf the rotation direction is wrong: Danger
If the rotation direction is wrong: Danger
If the rotation direction is wrong: DangerIf the rotation direction is wrong: Danger
of severe compressor damage! of severe compressor damage!
of severe compressor damage!
of severe compressor damage! of severe compressor damage!
6.4 Schematic wiring diagrams6.4 Schematic wiring diagrams
6.4 Schematic wiring diagrams
6.4 Schematic wiring diagrams6.4 Schematic wiring diagrams
The following schematic wiring diagrams show ex­amples of application for
start each with infinite and 4-step capacity con-start each with infinite and 4-step capacity con-
start each with infinite and 4-step capacity con-
start each with infinite and 4-step capacity con-start each with infinite and 4-step capacity con­trol.trol.
trol. In addition optional control schemes for liquid
trol.trol.
injection, economizer operation and oil level controls are included.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
part winding and star deltapart winding and star delta
part winding and star delta
part winding and star deltapart winding and star delta
Instruction for start delay timer with economizerInstruction for start delay timer with economizer
Instruction for start delay timer with economizer
Instruction for start delay timer with economizerInstruction for start delay timer with economizer operationoperation
operation
operationoperation
The switching-on device F7 must ensure that the refrigerant flow to the liquid sub-cooler is not switched on until operating conditions have sufficiently stabi­lized. This is achieved by using the solenoid valve Y6.
With frequent starting from high suction pressure, a pressure switch should be sued. The set point should be sufficiently above the nominal evaporating tempera­ture in order to prevent the economizer solenoid valve Y6 from short cycling.
For systems with relatively constant pull down cycles (such as liquid chillers), an alternative is to use a time relay. The delay time must then be checked individu­ally for each individual systems.
LegendLegend
Legend
LegendLegend
B2 Control Unit F1 Main fuse F2 Compressor fuse F3 Control circuit fuse F4 Control circuit fuse F5 High pressure cut out F6 Low pressure cut out F7 Start delay timer “Economizer” F8 Oil level switch (option) F13 Thermal overload “motor” PW1
18
Page 19
AE4-1322
F14 Thermal overload “motor” PW2 H1 Signal lamp “motor fault” (over temp / phase
failure) H4 Signal lamp “oil level fault” K1 Contactor “first PW” (for PW) “Mains contactor”
(Y/) K2 Contactor “second PW” (PW) “Start contactor”
(Y) K3 “Delta contactor” (Y)) K4 Auxiliary contactor (option) K2T Time relay “pause time” K3T Time relay “part winding: or “star delta” K4T Time relay “oil level switch” K5T Fixed pulse relay “CR4” flashing function on / off
10 seconds M1 Compressor Q1 Main switch R1 Oil heater * R2 Oil temperature sensor (PTC) * R3-8 Motor PTC sensor * S1 On-off switch S2 Fault reset “motor & discharge temperature”
and/or “direction of rotation”
S4 Fault reset “oil level” U Screening unit (if required, such as from Murr
Elektronik) Y1 SV “capacity control” * Y2 SV “capacity control” * Y3 SV “capacity control” * Y4 SV “capacity control” * Y5 SV “liquid line” Y6 SV “refrigerant injection” alternatively
“econimizer” Y7 SV “economizer by-pass” INT69VSY-II
Control device for motor protection and dis
charge gas superheat protection * SV Solenoid valve
* Parts are included with compressor
Capacity control Y1 CR1, Y2 CR2 Y3 CR3, Y4 CR4
Figure 21
Part winding start wiring diagram
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
19
Page 20
AE4-1322
Figure 23
Part winding start options
Figure 22
Part winding start with 4-step capacity control
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
20
Page 21
Data for accessories and oil chargeData for accessories and oil charge
Data for accessories and oil charge
Data for accessories and oil chargeData for accessories and oil charge
Liquid sub-coolingLiquid sub-cooling
Liquid sub-cooling
Liquid sub-coolingLiquid sub-cooling
AE4-1322
• Oil heater: 115/230 VAC SCH2 5000 to 9000 200W SCA2 3500 to 7000 SCH2 11H0 to 14H0 300W SCA2 9000 to 11H0
• Capacity control: 24/115/230 VAC 50/60 Hz
• Oil charge: Solest170 for R134a, R407C, R404A and R507A CP4214-320 for R 22
Oil heaterOil heater
Oil heater
Oil heaterOil heater
Ensures the lubricity of the oil even during long stand­still periods. It prevents increased refrigerant dilution into the oil and therefore reduction of viscosity.
The oil heater must be used during the shutdown for
• outdoor installation of the compressor (insulate the oil separator additionally if necessary)
• long off cycles
• high refrigerant charge
• danger of refrigerant condensation into the compressor
10 Performance data10 Performance data
10 Performance data
10 Performance data10 Performance data
For detailed compressor selection with the option of individual data input our selection software is available as CD-ROM or can be downloaded from our internet web site. The resulting output data include all impor­tant performance parameters for compressors and additional components, application ranges, technical data and dimensional drawings. Moreover, specific data sheets can be generated which may either be printed out or transferred into other software programs, such as Excel, for further use.
Basic parametersBasic parameters
Basic parameters
Basic parametersBasic parameters
Evaporating and condensing temperatures correspond to “dew point” conditions (saturated vapor). With zeotropic blends like R407C this leads to a change in the basic parameters (pressure levels, liquid tempera­tures) compared with data according to “intermediate temperatures” used so far. As a consequence this results in a lower numerical value for cooling capacity and efficiency (COP).
With standard conditions
nono
no liquid sub-cooling is
nono
considered. Therefore the rated cooling capacity and efficiency (COP) show lower values in comparison to data based on 9 or 15°F of sub-cooling.
Economizer operationEconomizer operation
Economizer operation
Economizer operationEconomizer operation
Data for economizer operation system inherently include liquid sub-cooling. The liquid temperature is defined as 18°F above saturated temperature (dew point with R407C) at economizer inlet (t
= tms +
cu
18°F).
10.1 Compressor selection by software10.1 Compressor selection by software
10.1 Compressor selection by software
10.1 Compressor selection by software10.1 Compressor selection by software
• Select the menu
CSH Compact Screws.
• Type the desired Cooling Capacity.
• Select desired operating conditions:
-Refrigerant and for R407C
-Reference temperature
-Evaporating temperature
-Condensing temperature
-Without or with economizer
-Liquid Sub-cooling
-Suction Gas superheat or suction gas temp.
-Useful superheat
-Power supply
• Hit Calculate. In the window Output Data the selected compres­sors with performance data are shown (fig. 24).
• Data output: At this stage an input of individual text (Head line) is possible.
- Print: Print-out at standard printer, with application limits (application ranges)
- Export: Output as ASCII file
10.2 Finding compressor performance data using10.2 Finding compressor performance data using
10.2 Finding compressor performance data using
10.2 Finding compressor performance data using10.2 Finding compressor performance data using the softwarethe software
the software
the softwarethe software
• Select the menu CSH Compact Screws.
• Select Compressor Type.
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
21
Page 22
• Select the desired operating conditions:
- Refrigerant and for R407C reference temperature
- Evaporating temperature
- Without or with economizer
- UCT. gas superheat or suction gas temperature
- Useful superheat
- Capacity regulator
- Power supply
• Hit
Calculate. In the window Output Data the selected compressor with performance data is shown.
• Data output: at this stage an input of individual text (Head line) is possible.
- Print: Print out at standard printer, with applica-
tion limits (application ranges)
- Export: Output as ASCII file
Operating point in application limits diagram
•Hit Limits. Standard application limits diagram with operating point (blue cross) is shown in the window. Further window: application limits diagram for ECO.
AE4-1322
TT
echnical data of a compressorechnical data of a compressor
T
echnical data of a compressor
TT
echnical data of a compressorechnical data of a compressor
• Hit T. Data. Window Data appears, in which the technical data are listed. Further windows: Dimensions (dimensional drawing and Notes (notes and legend)
• Export all data with Print (Print-out at standard printer, or Export (as ASCII file).
Export performance tables
• Hit Tables. The blank Performance Table is shown in the window.
• Check the default values (white fields) and change where necessary. The Input Values can only be changed in the window Single Point Calculation.
•Hit Calculate. The Performance Table is shown in the window.
• Export the data with Print (print-out at standard printer, Export (as ASCII file) or Copy into the clipboard).
© 2002 Copeland Corporation Issued 4-2002 Printed in U.S.A.
22
Copeland is a registered trademark and Copeland
Screw is a trademark of Copeland Corporation. The
Emerson Climate Technologies logo is a trademark and
service mark of Emerson Elelctric Co.
Loading...