Emerson Copeland PerformanceAlert Installation And Operation Manual

Page 1
026-1724 Rev 0 12-MAY-2008
Copeland®
PerformanceAlert™
Gateway System
Installation and
Operation Manual
Page 2
Page 3
1640 Airport Road, Suite 104
Kennesaw, GA 30144
Fax: (770) 425-9319
ALL RIGHTS RESERVED.
The information contained in this manual has been carefully checked and is believed to be accurate. However, Com­puter Process Controls, Inc. assumes no responsibility for any inaccuracies that may be contained herein. In no event will Computer Process Controls, Inc. be liable for any direct, indirect, special, incidental, or consequential damages resulting from any defect or omission in this manual, even if advised of the possibility of such damages. In the interest of continued product development, Computer Process Controls, Inc. reserves the right to make improvements to this manual, and the products described herein, at any time without notice or obligation.
Page 4
Page 5

Table of Contents

1 OVERVIEW ................................................................................................................................................................... 1
1.1. T
HE PERFORMANCEALERT™ GATEWAY SYSTEM ....................................................................................................... 1
1.2. T
HE PERFORMANCEALERT™ GATEWAY BOARD......................................................................................................... 1
1.3. T
HE PERFORMANCEALERT
D
IAGNOSTIC MODULE ........................................................................................................................................................... 1
1.4. H
AND-HELD TERMINAL ............................................................................................................................................... 2
2 GATEWAY BOARD MOUNTING ............................................................................................................................. 3
3 GATEWAY POWER
WIRING............................................................................................................................................................................... 4
4 NETWORKING............................................................................................................................................................. 5
4.1. C
ONNECTING THE PERFORMANCEALERT™ MODULES TO THE GATEWAY BOARD..................................................... 5
4.1.1. PerformanceAlert™ Module MODBUS Wiring ................................................................................................... 5
4.1.2. PerformanceAlert™ Module MODBUS Addressing ............................................................................................ 6
4.1.3. Gateway MODBUS Wiring................................................................................................................................... 6
4.1.4. MODBUS Termination ......................................................................................................................................... 6
4.2. C
ONNECTING THE GATEWAY TO THE RS485 I/O NETWORK ....................................................................................... 6
4.2.1. Gateway Board Numbering .................................................................................................................................. 7
4.2.1.1. Setting the Gateway Address Switch .................................................................................................................................. 7
4.2.2. Setting the Baud Rate Dip Switches ...................................................................................................................... 7
4.2.3. Gateway Board RS485 I/O Termination............................................................................................................... 8
5 GATEWAY SOFTWARE SETUP............................................................................................................................... 9
6 PERFORMANCEALERT™
I/O SUMMARY................................................................................................................................................................. 10
6.1. E2 I/O B
6.2. I/O S
OARD SETUP ................................................................................................................................................. 10
ETUP FOR CONDENSED MODE ............................................................................................................................ 10
6.2.1. Condensed Mode Point Setup ............................................................................................................................. 10
6.3. I/O S
ETUP FOR EXPANDED MODE .............................................................................................................................. 11
6.3.1. Expanded Mode Point Setup ............................................................................................................................... 11
7 OPERATION ............................................................................................................................................................... 14
7.1. P
ERFORMANCEALERT™ STAT SUMMARY ................................................................................................................. 14
7.1.1. Screen 1: Comm Status ....................................................................................................................................... 14
7.1.2. Screen 2: PF Alert Alarm Status......................................................................................................................... 14
7.1.3. Screens 3 through 6: Firmware Versions ........................................................................................................... 15
7.2. I
NDIVIDUAL PERFORMANCEALERT™ MODULE STATUS............................................................................................ 15
7.2.1. Individual Module Status .................................................................................................................................... 15
7.2.1.1. Screen 1............................................................................................................................................................................. 15
7.2.1.2. Screen 2............................................................................................................................................................................. 16
7.2.1.3. Screen 3............................................................................................................................................................................. 16
7.2.1.4. Screen 4............................................................................................................................................................................. 16
7.2.1.5. Screen 5............................................................................................................................................................................. 16
7.2.2. Individual Module History .................................................................................................................................. 16
7.2.2.1. Screens 1 and 2 ................................................................................................................................................................. 16
7.2.2.2. Screens 3 through 11......................................................................................................................................................... 16
7.2.2.3. Screens 12 and 13 ............................................................................................................................................................. 17
7.2.2.4. Screen 14........................................................................................................................................................................... 17
026-1724 Rev 0 12-MAY-2008 Table of Contents • v
Page 6
7.2.2.5. Screens 15 through 17....................................................................................................................................................... 17
7.2.2.6. Screen 18 and 19............................................................................................................................................................... 17
7.2.3. Individual Module Configuration........................................................................................................................ 17
7.2.3.1. Screen 1: Rack # and Install Date ..................................................................................................................................... 17
7.2.3.2. Screen 2: Date of Installation............................................................................................................................................ 18
7.2.3.3. Screen 3: Customer Code ................................................................................................................................................. 18
7.2.3.4. Screen 4: Compressor Model............................................................................................................................................ 18
7.2.3.5. Screen 5: Serial Number ................................................................................................................................................... 18
7.2.3.6. Screen 5: Setpoints............................................................................................................................................................ 18
7.2.3.7. Screens 6 through 8: Lockout Setpoints ........................................................................................................................... 18
7.2.4. Communication Statistics.................................................................................................................................... 19
7.2.5. Resets................................................................................................................................................................... 19
7.2.5.1. Clear History Log ............................................................................................................................................................. 19
7.2.5.2. Reset PerformanceAlert™ Module................................................................................................................................... 19
8 E2 APPLICATIONS .................................................................................................................................................... 20
8.1. P
ASSING PERFORMANCEALERT™ ALARM DATA TO THE E2 ADVISORY LOG........................................................... 20
8.1.1. Generic Alarming Setup...................................................................................................................................... 20
8.1.2. Alarm Parameter Settings ................................................................................................................................... 20
8.1.2.1. Digital Alarms................................................................................................................................................................... 20
8.1.2.2. Analog Alarms .................................................................................................................................................................. 21
8.1.3. Advisory Values and Priorities ........................................................................................................................... 22
8.1.4. How the Alarm Appears in the E2 Advisory Log ................................................................................................ 22
8.2. U
SING PERFORMANCEALERT™ CURRENT TRANSDUCER VALUES AS COMPRESSOR PROOFS................................... 22
8.2.1. Creating Analog Sensor Control Applications.................................................................................................... 22
8.2.2. Programming Analog Sensor Control Applications ........................................................................................... 22
8.2.2.1. General.............................................................................................................................................................................. 23
8.2.2.2. Inputs ................................................................................................................................................................................ 23
8.2.2.3. Setpoints............................................................................................................................................................................ 23
8.2.3. Setting Up Proofing in Suction Group Applications........................................................................................... 23
vi • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 7

1 Overview

1.2. The PerformanceAlert™
The PerformanceAlert™ Gateway is designed to allow the Emerson Climate Technologies Retails Solutions fam­ily of site controllers (E2, Einstein, and REFLECS) to in-
terface directly with up to 14 Copeland
®
PerformanceAlert™ Diagnostic Modules.
The Gateway uses two network ports: one, a MODBUS port used to connect the Gateway with the Perfor­manceAlert™ modules, and the second an I/O network port that connects the Gateway to the I/O network of an E2 or Einstein control system (or COM A/D of a REFLECS net­work).
The Gateway mimics the behavior of a MultiFlex 16 in­put board, passing along data from the PerformanceAlert™ modules about compressor behavior to the site controller in the form of virtual board/point addresses. The Gateway’s board/point addresses may be used by the site controller for I/O control, logging, and alarming.
1.1. The PerformanceAlert™
Gateway System
Gateway Board
5
9
7
1
Hand-Held Terminal Jack
2
RS485 I/O Network
3
RS485 Receiver Bus Net I/O Net Term Jumpers
4 5
Receiver Bus Term Jumpers
6
General Status LED
LEGEND
7
Alarm Status LED Dip Switch
8
Power Connector
9
I/O Net Status LED
10
Receiver Bus Status LED
11

Figure 1-2 - Gateway Board

The PerformanceAlert™ Gateway (Figure 1-2) allows you to connect up to fourteen (14) PerformanceAlert™ Di­agnostic Modules. On the I/O network, the Gateway board mimics the behavior of one or more 16AI boards, which use virtual 16AI board/point addresses to pass along infor­mation from the modules to the E2.
The PerformanceAlert™ Gateway is capable of operat­ing in one of two different modes: a Condensed Mode, which maps a single 16AI point to the alarm status of each PerformanceAlert™ module, and an Expanded Mode, which maps sixteen 16AI points for each module, includ­ing alarm status for all alarm types, current transducer val­ues, and discharge line temperature.
4
11
3
10
2
1
68
26502044
In Condensed Mode, the PerformanceAlert™ Gateway mimics the equivalent of one 16AI board. In Expanded Mode, the PerformanceAlert™ Gateway mimics the equiv-

Figure 1-1 - Typical Layout of PerformanceAlert™ Modules and Gateway Board

A typical layout of a CPC-controlled Perfor-
manceAlert™ network configuration is shown in Figure 1-
alent of up to fourteen 16AI boards.
1.3. The PerformanceAlert™
Diagnostic Module
1. Each compressor in each rack is equipped with one Per­formanceAlert™ Diagnostic Module. All modules are wired together in a single MODBUS daisy-chain and con­nected to the PerformanceAlert™ Gateway board. The Gateway Board is also connected to the E2 via the I/O net­work, where it mimics the behavior of a MultiFlex input board (16AI) and sends values from the modules to the E2 as virtual board/point addresses.
The Copeland® PerformanceAlert™ Diagnostic Mod­ule is a breakthrough innovation for troubleshooting refrig­eration system faults. The module can be installed in the electrical box of the condensing unit near the compressor contactor or in the electrical panel of a refrigeration rack system. By monitoring and analyzing data from the Cope-
®
land
brand compressors, the module can accurately detect
the cause of electrical and system related issues.

The PerformanceAlert™ Gateway System Overview • 1

Page 8
The PerformanceAlert™ Gateway is compatible with
the following PerformanceAlert™ module part numbers:
P/N
®
Application
®
Perfor-
Copeland
943-0059-00 1-phase Scroll
943-0057-00 3-phase Scroll
943-0053-00 1-phase Reciprocating
943-0055-00 3-phase Reciprocating

Table 1-1 - Copeland® PerformanceAlert™ Module Part Numbers

Installation and operation of the Copeland
manceAlert™ Diagnostic Module is documented and sup­ported by Copeland
®
, and is beyond the scope of this document. For more information, visit www.EmersonCli­mate.com or contact Emerson Climate Technologies, Inc. at 1-888-EMR-9950.

1.4. Hand-Held Terminal

Figure 1-3 - Hand-Held Terminal (HHT)

The Hand-Held Terminal (HHT) (P/N 811-3110), shown in Figure 1-3, connects directly to the RJ11 jack on the Gateway and is used to configure and view status for the Gateway and its associated modules.
2 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 9
2 Gateway Board
Mounting
The Gateway is typically mounted in the same area as the site controller, near the controller’s 16AI, 8RO, and other RS485 Network peripherals. The Gateway is de­signed to fit into a standard 3" snap track (supplied with the board) or may be mounted in a panel or on stand-offs. Fol­low the dimensions in Figure 2-1 for panel mounting.

Figure 2-2 - Snap-Track Installation

Figure 2-1 - Gateway Board Mounting Dimensions

The Gateway should be mounted in an environment with ambient temperature between -40°F and 150°F, with a non-condensing relative humidity between 5% and 95%.
Gateway boards are not supplied with an enclosure but come with a snap-track for easy installation. The insulation sheet and I/O board must be removed from the track before the track is mounted. The snap-track is mounted using the
0.1875” mounting slots. Figure 2-2 shows this installation procedure.
Hand-Held Terminal Gateway Board Mounting • 3
Page 10
3 Gateway Power
Wiring
Input Voltage
Power

Table 3-1 - Gateway Power Requirements

The Gateway requires 24VAC power from a Class 2
center-tapped transformer.
Emerson Climate Technologies Retail Solutions sup­plies several sizes of center-tapped transformers for power­ing multiple 16AIs, 8ROs, and other RS485 peripheral boards of the E2, Einstein, and REFLECS systems.
Refer to your controller’s user manual for information on how to use the center-tapped transformers listed in Ta- ble 3-1 to power multiple RS485 I/O devices for the US and Canada.
Figure 3-1 shows how to connect the 56VA and 80VA transformers to the Gateway power connector.
P/N
Power Rating

Table 3-1-US and Canada Power Ratings for CPC Transformers

24VAC, Class 2, 50/60Hz
5VA
Three-Board Six-Board
640-0056 640-0080
5 6 VA 8 0 VA
Figure 3-1 - Pinout for the 56VA (640-0056) and 80VA (640-
0080) Transformers
4 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 11

4 Networking

Networking the PerformanceAlert™ Gateway System requires interconnecting the Gateway with all Perfor­manceAlert™ modules on the MODBUS network, as well as connecting the Gateway to the E2 via the RS485 I/O net­work port.
Cable Type
Emerson Climate Technologies Retail Solutions speci­fies all RS485 I/O and MODBUS wiring used by the E2 must be Belden 8641 (24AWG, 300V, CPC P/N 135-
8641); Belden 8761 (22 AWG, 300V not stocked by CPC); or a 600V-shielded 22AWG equivalent stocked by CPC (P/ N 135-0600). These are two-connector shielded twisted pair cable that support a maximum daisy chain cable dis­tance of 4000 feet (1219 m) between the E2 and the end de­vice on the network.
4.1. Connecting the Perfor-
manceAlert™ Modules To the Gateway Board
MODBUS network devices must be installed using a daisy-chain network structure. A daisy-chain connects the Gateway and all associated PerformanceAlert™ modules in a single unbranched network segment, with termination resistance applied to the network at the two end devices. Figure 4-1 shows two diagrams of valid daisy-chain net­work structures, one with the Gateway at the beginning of the network segment, and one with the Gateway in the mid­dle of a network segment.

4.1.1. PerformanceAlert™ Module MODBUS Wiring

Figure 4-2 - PerformanceAlert™ MODBUS Wire Connection
The MODBUS connector for the PerformanceAlert™ module is located as shown in Figure 4-2. Connect the MODBUS network cable segment(s) so that the BLACK wire connects to all positive (+) terminals and the WHITE wire connects to all negative (-) terminals. Connect the SHIELD wire to the GND terminal of the connector.
The GND terminal of each module must also be con­nected to a separate solid earth ground, using a 14AWG wire no more than six (6) inches in length.
The best earth ground sources to use are listed below, in priority order:
• A large metal panel or plate that is connected to a good electrical ground. A panel or plate that is at least 3 feet by 3 feet (0.9 m by 0.9 m) is desirable.
• Earth grounded steel rack.
• Water pipes (metal, assuming there are no plastic sections).
• Electrical system earth ground.
Note: If grounding against a metal plate or panel that is coated or painted, scrape away the coating to expose the bare metal before making the ground attachment.

Figure 4-1 - MODBUS Daisy Chain Structures

Connecting the PerformanceAlert™ Modules To the Gateway Board Networking • 5

Page 12

4.1.2. PerformanceAlert™ Module MODBUS Addressing

Figure 4-3 - PerformanceAlert™ MODBUS Addressing
Jumpers AD1 through AD4 on the PerformanceAlert™ module set the MODBUS device address. Modules should be uniquely numbered in sequence starting with 1 and con­tinuing in numerical order up to 14. Refer to Figure 4-3 for jumper settings for each address number.

4.1.3. Gateway MODBUS Wiring

4.1.4. MODBUS Termination

Figure 4-4 - Gateway Board MODBUS Wiring
Connect the Gateway to the MODBUS network as shown in Figure 4-4. Connect the BLACK wire to RS485+, the WHITE wire to RS485-. Connect the SHIELD wire to the middle (0v) terminal.
For convenience, when the Gateway is not the end of the daisy-chain, the MODBUS connector has a second set of terminals.
Figure 4-5 - MODBUS Termination
To minimize network interference on the MODBUS network, the daisy chain must be terminated at both end­points, with all devices in between left unterminated. Refer to the diagram in Figure 4-1 for diagrams showing the dai­sy chain endpoints.
The PerformanceAlert™ module is terminated by plac­ing a jumper across the TRMNTR pins. The Gateway board is terminated by setting the three jumpers next to the MODBUS connector to the TERMINATION setting as shown in Figure 4-5.
4.2. Connecting the Gateway to
the RS485 I/O Network
Connect the RS485 I/O Network wire to the three-ter­minal connector on the Gateway board as shown in Figure 4-6. For further information about how RS485 networks are configured, refer to your site controller’s user manual.
6 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 13

Figure 4-6 - Connecting the Gateway to the RS485 Network

4.2.1. Gateway Board Numbering

The E2, Einstein, or REFLECS controller interprets the PerformanceAlert™ Gateway board as one or more 16AI Analog Input boards. The number of virtual "boards" is de­pendent on two things: the setting of the board’s address DIP switch, and whether the PerformaceAlert Gateway will operate in "Condensed" or "Expanded" data mode.
In Condensed mode, the Gateway behaves in the same manner as one 16AI board whose address is equal to the address set by the DIP switches (see Figure 4-7 on page 7).
In Expanded mode, the Gateway assigns each Perfor­manceAlert™ module a 16AI address equal to its MOD­BUS address. For example, when modules 1 through 8 are enabled through the Gateway in Expanded mode, the Gate­way behaves as eight 16AI boards numbered 1 through 8. The address DIP switches have no function when the Gate­way is set to Expanded mode.
4.2.1.1. Setting the Gateway Address Switch
MODBUS
BAUD
RATE
Figure 4-7 - Gateway Dip Switch Numbering
If using the PerformanceAlert™ Gateway in Con­densed Mode, set the address DIP switches to the virtual 16AI board address you wish the Gateway to use (Figure 4-7). The Gateway in Condensed mode behaves in the same manner as one 16AI board whose address is equal to the address set by the DIP switches.
4.2.2. Setting the Baud Rate Dip Switch-
es
Dip switches 6 and 7 (Figure 4-8) control the baud rate at which the Gateway communicates with the site control­ler on the RS485 Network. These switches must be set to the same baud rate setting as the E2, Einstein, or REFLECS (usually 9600 baud).
Dip switch 8 controls the baud rate on the MODBUS network. Since the PerformanceAlert™ module communi­cates at 9600 baud only, set this switch to the DOWN posi­tion to select 9600 baud (see Figure 4-8).
Connecting the Gateway to the RS485 I/O Network Networking • 7
Page 14
G
ATEWAY
S
DIP SWITCH
I/O NETWORK OR COM A AND D BAUD RATE
2345678
1
I/O NET BAUD RATE SETTINGS
9600 19200
MODBUS BAUD RATE SETTINGS
Figure 4-8 - Dip Switch Setting for Numbering Gateway
MODBU BAUD RATE
9600
4.2.3. Gateway Board RS485 I/O Termi­nation
Figure 4-9 - Gateway RS485 I/O Network Termination
If the Gateway board will be an end device on the RS485 I/O network daisy chain, set the three jumpers next to the I/O Network connector to the TERMINATION posi­tion as shown in Figure 4-9.
8 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 15
5 Gateway Software
Setup
When the Gateway and all PerformanceAlert™ mod­ules are correctly powered up and networked, the Gateway firmware must be configured with a Hand-Held Terminal (HHT) to set the Gateway’s data mode, enable used Perfor­manceAlert™ MODBUS addresses, and disable unused MODBUS addresses.
1. Plug the HHT into the HHT jack. The Open­ing Screen will be shown.
PF ALERT GATEWAY 810-3730 VER: 1.10B07 02 (PRESS )
2. From the opening screen, press the DOWN ARROW key to display the Main Menu
screen.
SELECT: 1 1=INDIVIDUAL 2=STAT SUMMARY 3=GW SETUP
repeat until all are set correctly.
PF ALERT-1 : ENB PF ALERT-2 : ENB PF ALERT-3 : ENB PF ALERT-4 : ENB
IMPORTANT: Always set unused ad­dresses to "DIS." In Expanded Mode, this will allow the 16AI board number to be used by other I/O network devices (see Section 6.3., I/O Setup for Expanded Mode).
5. To move to the next screen, press DOWN ARROW until the cursor moves off the bot­tom of the HHT screen, then press DOWN ARROW one more time. The next screen, showing PF ALERT-5 through 8, will be shown.
6. Repeat steps 4 and 5 until all PF ALERT fields are set. From the fourth and last PF ALERT field screen, press the DOWN AR­ROW key to scroll to the next config screen,
the Data Mode screen.
PF ALERT DATA:
CONDENSED
3. Press RIGHT ARROW to move the cursor to the SELECT field, then press 3 to choose GW SETUP. Press the DOWN ARROW key twice to enter your selection and view the PF
Alert Enable screens.
PF ALERT-1 : UNK PF ALERT-2 : UNK PF ALERT-3 : UNK PF ALERT-4 : UNK
The four PF Alert Enable screens have a total of four­teen fields numbered PF ALERT-1 through PF ALERT-14. These fields correspond to the addresses of the connected PerformanceAlert™ modules. The field values represent whether the module at that address is enabled (ENB), dis­abled (DIS), or unknown (UNK) meaning no module with that address is currently communicating with the gateway. For each address, if a module is connected and is using that address, the PF ALERT field corresponding to that number must be set to ENB (enable). All others must be set to DIS or left in the UNK state.
4. Press the RIGHT ARROW key to move the cursor to the PF ALERT 1 field at the top of the screen. Use the MINUS (-) key to change the field’s value from DIS (if no module is connected that uses this address) or ENB (if a module will use this address). Use the UP ARROW and DOWN ARROW keys to move the cursor to other fields on the screen, and
7. Press RIGHT ARROW to move the cursor to the Data Mode field. Use the MINUS (-) key to toggle between CONDENSED and EX­PANDED mode. Refer to Section 6.2., I/O
Setup for Condensed Mode, and Section 6.3., I/O Setup for Expanded Mode, for a complete
description of both modes. When finished, press DOWN ARROW twice to save changes and move to the next screen.
8. The final screen under the GW SETUP menu option is a read-only status screen showing the configuration of the I/O and MODBUS networks. The first two lines, IONET AD­DRESS and IONET BAUD, show the board number and baud rate as set by the Gateway board’s DIP switches. The last two lines, MOD BAUD and MOD PARITY, will al­ways read 9600 and NONE respectively, since the Gateway’s MODBUS port needs to be set to 9600 baud with no parity. If MOD BAUD reads 19200, the Gateway dip switch is set wrong and must be switched to the DOWN position (see Figure 4-8 on page 8)
IONET ADDR:1 IONET BAUD:9600 MOD BAUD :9600 MOD PARITY:NONE
Connecting the Gateway to the RS485 I/O Network Gateway Software Setup • 9
Page 16
6 PerformanceAlert™
I/O Summary

6.2. I/O Setup for Condensed Mode

During operation, the PerformanceAlert™ Gateway
serves two main functions:
• Communicating with, and collecting information from, the PerformanceAlert™ modules, and
• Passing along information from the modules to the site controller in the form of virtual 16AI point val­ues.
This section will show how to map data points from the Gateway to I/O points in the site controller for both data modes (Condensed and Expanded).

6.1. E2 I/O Board Setup

The E2 must be configured to communicate with the Gateway by adding the board(s) to the system configura­tion.
Log in to the E2 with an access level high enough to change configuration, and press Connected I/O Boards and Controllers screen.
I to open the
Note: If you will be using the Perfor­manceAlert™ Gateway in Expanded Mode, skip this section and follow the instructions in Section 6.3., I/O Setup for Expanded Mode.
In Condensed Mode, the Gateway behaves as a single 16AI board address whose address is set by the board’s ad­dress DIP switches (see Section 4.2.1.1., Setting the Gate- way Address Switch).

Points 1 through 14 of this virtual board correspond to the overall alarm status of PerformanceAlert™ modules #1 through #14. The point will be ON as long as one or more of the following failure conditions are active:

1. The PerformanceAlert™ module is not com­municating with the Gateway, OR
2. Alert code 4, 5, 6, 7, 8, and/or 10 are active, OR
3. The compressor is in lockout

6.2.1. Condensed Mode Point Setup

To set up the Gateway’s virtual 16AI points for use in logging, alarming, and I/O control, press PUT DEFINITIONS) to access the Input Status screen.
Sixteen rows in the Input Status table will have the same number in the Brd field as the virtual 16AI address of the Gateway board. These rows correspond to "points" 1 through 16 on the Gateway. Since 15 and 16 are invalid PerformanceAlert™ module addresses, these points will be unused and will always be OFF.
I (IN-
To make a point ready for use by the E2, you must set the input name and type from this screen:
4. Use the arrow keys until the cursor highlights the Application field in the row correspond­ing to the point you wish to set up.

Figure 6-1 - Connected I/O Boards Screen

Add as many 16AIs as are necessary to cover the board number(s) used by the PerformanceAlert™ Gateway. The E2 will add the specified number of 16AI boards, num­bered 1 through the number you entered, to the network
configuration. Press
After adding the board(s), press LINE STATUS) to view the current status of the network. Verify that the address(es) used by the PerformanceAlert™ Gateway are shown in this list and read "Online."
10 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Jto save and exit.
I (ON-
5. Press
6. When prompted to select the data type, select
A - SETUP
- Digital. The Digital Input setup screen
will be displayed.
7. In the Point Name field, enter a unique name that will help you & others easily know the function of this point. For example, if setting up point 1, which will be the alarm status of PerformanceAlert™ module #1, an appropri­ate name would be PF ALERT CMP1.
8. Press
J to save the name and return to
Page 17
the Input Status screen. The point will now display a "D" (for digital) in the Type col­umn, and will also display the current value of the point in the Value field (ON or OFF).
9. Repeat steps 1 through 5 until all points are defined.
When finished, the points are ready for use in E2 appli­cations. If you wish to set up the Condensed Mode points so that alarms from PerformanceAlert™ are written to the E2 Advisory Log, refer to Section 8.1.1., Generic Alarm- ing Setup.
You may wish to use the Gateway points as inputs for Digital Sensor control applications, where you may set up output control. Refer to the E2 User’s Guide (P/N 026-
1610) for Digital Sensor Control setup instructions.
6.3. I/O Setup for Expanded
Mode
If you will be using the PerformanceAlert™ Gateway in Condensed Mode, skip this section and follow the instructions in Section 6.2., I/O Setup for Condensed Mode.
NOTE: Expanded Mode may not be used if networking the Gateway to an RMCC. The RMCC will only support Condensed Mode.
and functions are fixed and are the same for each module. Table 6-1 lists the point numbers and their data types and functions.
Point # Type Function
1 Digital High DLT Warning
2 Digital System Component Trip
3 Digital Compressor Short Cycle
4 Digital Compressor Locked Rotor
5 Digital Open Circuit
6 Digital Missing Phase
7 Digital 3 Phase Circuit Failure
8 Digital Welded Contactor
9 Digital Low Voltage Notice
10 Digital Communication Failure
11 Digital DLT Open/Short Failure
12 Digital Relay State
13 Analog T1 Current (0-655 Amps)
14 Analog T3 Current (0-655 Amps)
15 Analog Discharge Line Temperature
(-58°F—266°F)
16 Digital Digital Summary (same as alarm
summary output in Condensed mode (Section 6.2.) )

Table 6-1 - PerformanceAlert™ Gateway Expanded Mode Input Map

In Expanded mode, for every PerformanceAlert™ module address set to "enable" (ENB) in the Gateway (see step 4 of the Gateway Setup instructions in Section 5), the Gateway board will emulate a 16AI board whose board number is the same number as the PerformanceAlert™ module. When a PerformanceAlert™ module is set to "dis­able" (DIS) in the Gateway, the Gateway board does not use this board number, meaning it may be used by other MultiFlex input boards.
Each virtual 16AI board address shares sixteen data points corresponding to alarm states and sensor values from the PerformanceAlert™ module. The point numbers
Points 1 through 11 are alarm states. They will be ON whenever the corresponding alarm type is active on the PerformanceAlert™ module, and OFF when the alarm type is not active.
Point 12 represents the digital state of the Perfor­manceAlert™’s compressor relay (ON when the compres­sor relay is ON, and OFF when the compressor is OFF).
Points 13 and 14 are the measured currents through T1 and T3 respectively.
Point 15 is the measured temperature read from the dis­charge line temperature sensor.
Point 16 has the same function as the alarm state point in Condensed Mode. It is ON whenever any alarm is active on the PerformanceAlert™ module. Consequently, when­ever any of the points from 1 through 11 are ON, point 16 will be ON as well.

6.3.1. Expanded Mode Point Setup

To set up the Gateway’s virtual 16AI points for use in logging, alarming, and I/O control, press PUT DEFINITIONS) to access the Input Status screen.
I (IN-

I/O Setup for Expanded Mode PerformanceAlert™ I/O Summary • 11

Page 18
For every board number used by the Perfor­manceAlert™ Gateway, there will be sixteen rows in the Input Status table corresponding to "points" 1 through 16 on the Gateway. To make a point ready for use by the E2, you must set the input name and type from this screen.
Setup for Digital Points (1-12, 16)
1. Use the arrow keys until the cursor highlights the Application field in the row correspond­ing to the point you wish to set up.
2. Press
3. When prompted to select the data type, select
A - SETUP
- Digital. The Digital Input setup screen
will be displayed.
4. In the Point Name field, enter a unique name that will help you & others easily know the function of this point. For example, if setting up point 1 on board #3, which will be the High DLT warning for PerformanceAlert™ module #3, an appropriate name would be HIGH DLT CMP3.
5. Press
6. Repeat steps 1 through 5 until all digital
Setup for Points 13 and 14 (Current Transducers)
1. Use the arrow keys until the cursor highlights
2. Press
3. When prompted to select the data type, select
J to save the name and return to
the Input Status screen. The point will now display a "D" (for digital) in the Type col­umn, and will also display the current value of the point in the Value field (ON or OFF).
points are defined.
the Application field in the row correspond­ing to the point you wish to set up.
A - SETUP
- Analog. The Analog Input setup screen
will be displayed.
4. In the Point Name field, enter a unique name that will help you & others easily know the function of this point. For example, if setting up point 13 on board #3, which will be the T1 current for PerformanceAlert™ module #3, an appropriate name would be T1 AMPS CMP3.
5. In the Sensor Type field, press F4 to access the Look-Up table. Highlight "Linear" as the
sensor type, and press
6. In the Select Eng. Units field, press F4 to ac­cess the Look-UP table. Highlight "A" as the
unit type, and press
7. The Low Eng Units and High Eng Units
> to select.
> to select.
fields near the bottom of the screen must be set to 0 and 655.5 respectively. The Low Eng Units by default should read 0 and will not re­quire modification. Move the cursor to the High Eng Units field and enter 655.5 as the new value.
8. Press
9. Repeat steps 1 through 8 until all current
Setup for Point 15 (Discharge Line Temp)
1. Use the arrow keys until the cursor highlights
2. Press
3. When prompted to select the data type, select
J to save the name and return to
the Input Status screen. The point will now display a "A" (for digital) in the Type col­umn, and will also display the current value of the point in the Value field (ON or OFF).
transducer points have been defined.
the Application field in the row correspond­ing to the point you wish to set up.
A - SETUP
- Analog. The Analog Input setup screen
will be displayed.
4. In the Point Name field, enter a unique name that will help you & others easily know the function of this point. For example, if setting up point 15 on board #1, an appropriate name would be DLT CMP1.
5. In the Sensor Type field, press F4 to access the Look-Up table. Highlight "Linear" as the
sensor type, and press
6. In the Select Eng. Units field, press F4 to ac­cess the Look-UP table. Highlight "DF" (if using °F on this E2) or "DC" (if using °C on
this E2) as the unit type, and press lect.
7. Set the Low Eng Units and High Eng Units.
• If using °C (DC) as the unit, enter -50 as
the Low Eng Unit and 130 as the High Eng Unit.
• If using °F (DF) as the unit, enter -58 as the
Low Eng Unit and 266 as the High Eng Unit.
8. Press
When finished, the points are ready for use in E2 appli­cations. You may wish to use the Gateway points as inputs for Analog and Digital Sensor control applications, where
J to save the name and return to
the Input Status screen. The point will now display a "D" (for digital) in the Type col­umn, and will also display the current value of the point in the Value field (ON or OFF).
> to select.
> to se-
12 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 19
you may set up logging, alarming, and (if desired) output control. Refer to the E2 User’s Guide (P/N 026-1610) for Analog and Digital Sensor Control setup instructions.
I/O Setup for Expanded Mode PerformanceAlert™ I/O Summary • 13
Page 20

7 Operation

During normal operation the operating status of the Per­formanceAlert™ modules can be viewed in either of three ways:
• Through E2 appliction status screens,
• Through PerformanceAlert™ Software loaded on a laptop computer, and
• Through the Hand-Held Terminal interface on the Gateway board.
The means for checking status on the E2 will depend on how you have configured the Gateway board points. If you created Sensor Control applications for each point, you may view the PerformanceAlert™ status using the Sensor Control status and summary screens. Refer to the E2 User’s Guide (P/N 026-1610) for more details.
The PerformanceAlert™ Software is a utility which connects the PerformanceAlert™ module to an RS232 or USB port on the computer and allows direct viewing of a module’s diagnostics information and setpoints. This tool
is documented and supported by Copeland the scope of this document. For more information, visit www.EmersonClimate.com Technologies, Inc. at 1-888-EMR-9950.
The Hand-Held Terminal can be used to look at the overall online and alarm summary of all modules (Section
7.1.) as well as the status of an individual Perfor­manceAlert™ module (Section 7.2.).
or contact Emerson Climate
7.1. PerformanceAlert™ Stat
Summary
1. Plug the HHT into the Gateway board’s HHT jack.
2. Press the DOWN ARROW key to move to the Main Menu.
SELECT: 2 1=INDIVIDUAL 2=STAT SUMMARY 3=GW SETUP
®
, and is beyond

7.1.1. Screen 1: Comm Status

COMM STATUS: 12345678901234 111111XXXXXXXX E2: ACTIVE
Comm Status. The list of characters on Line 3 of the
HHT display, which are numbered 1 through 14 by the numbers above them on Line 2, represent the online status of modules 1 through 14. For each module, this character will display one of the following states:
1 - PerformanceAlert™ module is communicating with the Gateway.
0 - PerformanceAlert™ module is not communicat­ing with the Gateway
X - This address is set to disable (DIS) and thus not communicating (see step 4 of Section 5).
E2 Status. The bottom line of the HHT display shows
the current state of communication between the Gateway and the E2. This field will read ACTIVE when the Gateway and E2 are communicating, or NO COMM when they are not communicating.

7.1.2. Screen 2: PF Alert Alarm Status

PF ALERT ALARM STATUS: 1234567901234 000000XXXXXXX
The list of characters on Line 4, numbered 1 through 14 by the numbers above them on Line 3, show the current alarm active status of the PerformanceAlert™ modules. For each module, this character will display one of the fol­lowing states:
1 - Active alarm, following the same criteria as the alarm status outputs (see Section 6.2. for ON crite­ria)
0 - No alarms are active on the PerformanceAlert™ module
X - This address is set to disable (DIS) and thus not communicating (see step 4 of Section 5).
3. Press RIGHT ARROW and then 2 to select "STAT SUMMARY." Press the DOWN AR­ROW key two times to navigate to the first stat summary screen.
The six screens under the Stat Summary heading will show you online status, alarm status, and firmware version for the PerformanceAlert™ modules.
14 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 21

7.1.3. Screens 3 through 6: Firmware Versions

1 ON [2.00B02] 2 ON [2.00B02] 3 ON [2.00B02] 4 ON [2.00B02]
5 ON [2.00B02] 6 ON [2.00B02] 7 OFF [ ] 8 OFF [ ]
9 OFF [ ] 10 OFF [ ] 11 OFF [ ] 12 OFF [ ]
13 OFF [ ] 14 OFF [ ]
field, enter the number of the Perfor­manceAlert™ module you wish to view.
Press DOWN ARROW twice.
PF ALERT 1-14
SELECT: 1
You may only select a PerformanceAlert™ address for a module that is set to ENABLE and is communicating with the Gateway. If a module is not enabled or is not com­municating, an error message will be given.
If the address selected is on-line, the Individual Module Menu will be shown.

7.2.1. Individual Module Status

SELECT: 1 1=STATUS 4=STATS 2=HISTORY5=RESET 3=CONFIG
These screens show the enable/disable status of all 14 PerformanceAlert™ module addresses, and the firmware versions of the connected PerformanceAlert™ modules.
Addresses set to enable will be shown as ON or OFF in these screens, while disabled module addresses will be shown as DIS.
Any time a module is enabled and communicated with a PerformanceAlert™ Gateway, its firmware revision number is recorded by the Gateway and displayed in this screen. In most cases, this means enabled modules will be shown with firmware revision numbers, and disabled ones will be shown without revision numbers between the brackets. If a module is later removed or disabled, howev­er, its revision number will remain in its address slot.
7.2. Individual Perfor-
manceAlert™ Module Status
1. Plug the HHT into the Gateway board’s HHT jack.
2. Press the DOWN ARROW key to move to the Main Menu.
SELECT: 1 1=INDIVIDUAL 2=STAT SUMMARY 3=GW SETUP
To view the status screens, press RIGHT ARROW to move the cursor to the Select field. Press 1 and then DOWN ARROW twice.
7.2.1.1. Screen 1
PF ALERT: 1 ONLINE
ALARM: NONE
This screen shows the on-line status and alarm status of the module.
The on-line status will read ONLINE, OFFLINE, or DISABLE.
The alarm status will read NONE when no alarm is ac­tive. It will read ACTIVE when one or more of the follow­ing conditions are true:
• The module is offline,
• The PerformanceAlert™ module has shut down the compressor (see Copeland
Application Engineering Bulletin and Section
7.2.3.7., or
• Alert codes 4 (Locked Rotor Alarm), 5 (Open Cir­cuit Detected), 6 (Missing Phase Alarm), 7 (Open Circuit/Reverse Phase), 8 (Welded Contactor Alarm), and/or 10 (Lost Communication) are active.
®
PerformanceAlert™
3. Press RIGHT ARROW and then 1 to select “INDIVIDUAL.” Press the DOWN ARROW key two times.
4. Press the RIGHT ARROW key. In the Select

Individual PerformanceAlert™ Module Status Operation • 15

Page 22
7.2.1.2. Screen 2
IN ST: 00000000 OUT ST: 00000000 SYS ST:0 0000 FLAGS : 00000000
7.2.2.1. Screens 1 and 2
LAST 10 ALARMS: A1 -MOST RECENT A10-PAST 24H A1: 10 A2: 4
This status screen shows the input, output, system, and
warning flag status displayed as bits.
7.2.1.3. Screen 3
POWER V : 0.00 CT1 (A) : 1.04 CT2 (A) : 0.96 LRA PEAK: 0.00
This status screen shows the module’s input power (in volts), the value of CT1 and CT2 (in amps), and the LRA Peak (in amps).
7.2.1.4. Screen 4
PK RMS A : 1.0 LINE TEMP: 78.00 NOW ALERT: 0
This status screen shows the peak RMS current (in amps), the current discharge line temperature (in degrees Farrenheit), and the alarm code of the current alert being displayed. If any alert is being displayed, its alert descrip­tion will be shown in Line 4 of the display; otherwise, Line 4 will be blank.
7.2.1.5. Screen 5
PAST ALERT: 10 NO COMMUNICATION
This status screen shows the code number and descrip­tion of the last alert that occurred in the module (not the one currently active, if an alert is currently active).

7.2.2. Individual Module History

SELECT: 2 1=STATUS 4=STATS 2=HISTORY5=RESET 3=CONFIG
To view the status screens, press RIGHT ARROW to move the cursor to the Select field. Press 2 and then DOWN ARROW twice.
A3:6 A4 :4 A5:6 A6 :4 A7:6 A8 :8 A9:10 A10:1
Screens 1 and 2 show the last 10 alert condition codes that have occured on this module in the past 24 hours (counting back from the current time). The alarm codes are shown from most recent (A1) to least recent (A10).
7.2.2.2. Screens 3 through 11
HIGH DISCHARGE DAYS: C1234567 NNNNYNNN COUNT: 3
Screens 3 through 11 show the 7-day history of each of the alarm codes from 1 through 9, showing which days they have occurred. The current "day," which represents the pe­riod of time between the current time and 24 hours ago, is displayed under the "C." The remaining seven fields repre­sent alarm occurrences from 1 to 7 days previous to the cur­rent time.
If one or more alarms have occurred during any of the days displayed on this screen, a Y will appear under the day the alarm or alarms occurred. Otherwise, an N will be shown, meaning no alarms of that type occurred on that day.
The Count field at the bottom of each screen shows the cumulative total of alarms that have occurred on this mod­ule in its entire time of operation.
Table 7-1 shows the order of the screens for each alarm code type.
Screen # Alarm Code
3 HIGH DISCHARGE (Code 1)
4 COMPONENT TRIP (Code 2)
5 SHORT CYCLING (Code 3)
6 LOCKED ROTOR (Code 4)
7 OPEN CKT COMPR (Code 5)
8 MISSING PHASE (Code 6)
9 REVERSE PHASE (Code 7)
10 WELDED CONTACTS (Code 8)
11 LOW VOLTAGE (Code 9)
Table 7-1 - Alarm Status Screen Order (By Code)
16 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 23
7.2.2.3. Screens 12 and 13
WF0 HI DLT OFF WF1 LCK ROT OFF WF2 OPEN CIR OFF WF3 LOW V OFF
7.2.2.6. Screen 18 and 19
TRIP HISTORY: DAYS: C1234567 NNNNNNNN COUNT : 0
WF4 MMC OFF WF5 DLT OPEN OFF WF6 DLT SHOR OFF WF7 OFF
Screens 6 and 7 shows the current state of the warning
flags 0 through 7.
7.2.2.4. Screen 14
NOW ALERT : 0 LAST ALERT: 10
Screen 8 shows the current alert code active in the mod­ule (NOW ALERT), and the alert code that was active pre­vious to the current one (LAST ALERT).
7.2.2.5. Screens 15 through 17
CMPR: START RUN DAY1: 0 0 DAY2: 0 0 DAY3: 0 0
CMPR: START RUN DAY4: 0 0 DAY5: 0 0 DAY6: 0 0
CMPR: START RUN DAY7: 0 0 STARTS: 0 RUN : 0
The Day1 through Day7 fields show the number of times the compressor has started and the runtime (in min­utes) for the current day (Day1) and the previous 6 days (Day2 through Day7).
BYPASS HISTORY: DAYS: C1234567 NNNNNNNN COUNT : 0
Screens 18 and 19 show the 7-day history of trip condi­tions and bypass conditions, showing which days they have occurred. Screen 18 shows the history of trip conditions, while screen 19 shows the history of bypass conditions.
The current "day," which represents the period of time between the current time and 24 hours ago, is displayed un­der the "C." The remaining seven fields represent alarm oc­currences from 1 to 7 days previous to the current time.
If one or more trips or bypasses have occurred during any of the days displayed on this screen, a Y will appear un­der the day the trip(s) or bypass(es) occurred. Otherwise, an N will be shown, meaning no trips or bypasses occurred on that day.
The Count field at the bottom of each screen shows the cumulative total of trips or bypasses that have occurred on this module in its entire time of operation.

7.2.3. Individual Module Configuration

SELECT: 3 1=STATUS 4=STATS 2=HISTORY5=RESET 3=CONFIG
To view the status screens, press RIGHT ARROW to move the cursor to the Select field. Press 3 and then DOWN ARROW twice.
7.2.3.1. Screen 1: Rack # and Install Date
PF ALERT: 1 RACK : 2
The Starts and Run fields on Screen 17 show the total number of compressor starts and the total runtime (in min­utes) since the last time statistics were cleared in the mod­ule.
Individual PerformanceAlert™ Module Status Operation • 17
On this screen, you may enter a rack number . This number is stored in the module memory for reference pur­poses.
Page 24
7.2.3.2. Screen 2: Date of Installation
DATE OF INSTALLATION: DATE: 08-15-0
7.2.3.6. Screen 5: Setpoints
DLT TTP : 230.0 SEVERE ALERT OFF TIME : 20 LO V SP: 217.0
On this screen, you may enter the date the compressor was installed. This date is stored in the module memory for reference purposes.
7.2.3.3. Screen 3: Customer Code
CUSTOMER CODE
CODE: 000
On this screen, you may enter a three-character custom­er code number. This code is stored in the module memory for reference purposes.
7.2.3.4. Screen 4: Compressor Model
COMPRESSOR MODEL
This screen enables you to enter a description of the compressor model the PerformanceAlert™ module is at­tached to. Press the RIGHT ARROW key to make the cur­sor appear in Line 3 of the display. To enter text on this line, for each character use the POINT "." and MINUS "-" keys to scroll through the alphanumeric characters until the desired character is shown. Press RIGHT ARROW to move to the next character. When finished, press DOWN ARROW to enter the name, and DOWN ARROW again to save changes and exit to Screen 4.
7.2.3.5. Screen 5: Serial Number
COMPRESSOR S/N
S/N: 1234567890
On this screen, you may enter a ten-character string of text. This code is stored in the module memory for refer­ence purposes.
The DLT TTP is the high temperature setpoint for trip­ping on high discharge line temperature. When the dis­charge line temperature is above the DLT TTP setpoint (in degrees Farrenheit), a HIGH DISCHARGE alert will oc­cur.
The Severe Alert OFF Time is the minimum number of minutes the compressor will remain OFF when a trip oc­curs as a result of an alarm code 1, 4, 6, or 7. When one of these alarm codes occurs, the compressor will not reset un­til the Severe Alert OFF Time delay has elapsed.
The LO V STP is the setpoint for low voltage trip. An voltage below this value will cause a LOW VOLTAGE alert to occur. This setpoint is a fixed value and may not be altered.
7.2.3.7. Screens 6 through 8: Lockout Setpoints
DISABLED = 255 C1 LOUT CNT: 2 C2 LOUT CNT: 2 C3 LOUT CNT: 2
DISABLED = 255 C4 LOUT CNT: 2 C6 LOUT CNT: 1 C7 LOUT CNT: 1
OPEN CDT : 90
MIN ON TM : 0.10 MIN OFF TM: 0.10
CAUTION! Setting an Cx LOUT CNT field to any number other than 255 will allow the PerformanceAlert™ to shut down the com­pressor under severe conditions.
NOTE - For lockout to be enabled, the Perfor­manceAlert™ module’s Lockout Jumper must
be properly set. See the Copeland manceAlert™ Application Engineering Bulle­tin for more information about this jumper and how to set it.
®
Perfor-
For alert codes 1,2,3,4,6, and 7, the LOUT CNT field with the number corresponding to the alert code number sets the maximum number of times per day the alert must occur before a lockout will occur. For example, C1 LOUT
18 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 25
CNT will be the number of times a HIGH DISCHARGE PROTECTION alert must occur in a single 24-hour period to cause a lockout.
If you wish to set a lockout setpoint for an alert code, enter the desired maximum number of daily occurrences in the field. If you do not wish to lockout for an alert code, set the field value to 255. Table 7-2 shows the minimum and maximum values for each field.
Property Min # of
Occurrences
C1 LOUT CNT 2 6
C2 LOUT CNT 2 10
C3 LOUT CNT 2 240
C4 LOUT CNT 2 10
C6 LOUT CNT 1 10
C7 LOUT CNT 1 10
Table 7-2 - Min/Max Field Values for LOUT CNT Parameters
The Open CDT field sets the delay time (in minutes) of the lockout that will occur when an open circuit condition is present. Enter a desired lockout time between 60 and 180 minutes.
The Minimum ON Time and Minimum OFF Time fields set the minimum ON and OFF times of the compres­sor (in minutes or tenths of a minute). Specify the desired minimum times from 0.1 to 15.0 minutes.
Max # of
Occurrences

7.2.4. Communication Statistics

SELECT: 4 1=STATUS 4=STATS 2=HISTORY5=RESET 3=CONFIG
The Communication Statistics screen is designed to help troubleshoot potential network problems between the Gateway and a PerformanceAlert module. From the In­dividual Menu, select 4 to view the Communication Statis-
tics screen.
MSG SNT: 45520 NO RESP: 2 BAD CRC: 0 INVALID:0 MX:1
MSG SNT: The total number of messages sent.
NO RESP: The number of messages that resulted in no response.
BAD CRC: The number of messages received that had a bad CRC.
INVALID: The number of messages that resulted in an unexpected response (such as a MODBUS exception)
MX: The maximum number of consecutive times an er-
ror condition was detected in responses.
To clear all counts on this screen, press the CANCEL key. The MSG SNT, NO RESP, BAD CRC, INVALID, and MX counts will all reset to zero.

7.2.5. Resets

SELECT: 5 1=STATUS 4=STATS 2=HISTORY5=RESET 3=CONFIG
From the "Reset" menu option, you may clear a Perfor­manceAlert module’s history log or reset the module it­self. From the Individual Menu, select 5 to view the Reset Menu.
7.2.5.1. Clear History Log
SELECT: 1 1=CLEAR HISTORY 2=RESET PF ALERT
Performing a "Clear History" operation will erase all history statistics for the selected PerformanceAlert mod­ule (see Section 7.2.2.). Select 1 from the Reset menu to clear history.
THIS WILL CLEAR THE HISTORY LOG.
CLR HISTORY: NO
Press RIGHT ARROW to move the cursor to the Clr History field, and press the MINUS "-" key to toggle the field from "NO" to "YES." Press RIGHT ARROW and UP ARROW to execute the change and return to the Reset menu. The history will be erased.
7.2.5.2. Reset PerformanceAlert Module
SELECT: 2 1=CLEAR HISTORY 2=RESET PF ALERT
By selecting "Reset PF Alert" you may force a reset of the PerformanceAlert module. Select 2 from the Reset menu to reset the module.
THIS RESTARTS THE PF ALERT.
RESET UNIT : NO
Press RIGHT ARROW to move the cursor to the Reset Unit field, and press the MINUS "-" key to toggle the field from "NO" to "YES." Press RIGHT ARROW and UP AR­ROW to execute the change and return to the Reset menu. The module will reset.
Individual PerformanceAlert™ Module Status Operation • 19
Page 26

8 E2 Applications

The PerformanceAlert™ Gateway provides a means for E2 to use data from the PerformanceAlert™ modules for general logging, alarming, and control purposes. For convenience, this section will cover some of the most com­mon and useful applications of PerformanceAlert™ data in E2 applications.
8.1. Passing Perfor-
manceAlert™ Alarm Data to the E2 Advisory Log
The E2 features many advanced alarm control capabil­ities, all of which are centered around the collection of alarms kept in the E2 Advisory Log. Though the Perfor­manceAlert™ Gateway passes alarm information from PerformanceAlert™ modules to the E2, it only does so as I/O point data, not as alarms written to the E2 Advisory Log.
In order to write PerformanceAlert™ alarm data to the E2 Advisory Log, you must set up Generic Alarming pa­rameters on the Gateway’s virtual I/O points.
points set up:
Figure 8-1 - Input Status Screen (Condensed Mode Shown)
3. Highlight the point you want to set up. Press
A: SETUP. The Digital Input or Analog
Input screen will be displayed.
4. Press
A: SET ALARMS. The Digital
Alarm Setup or Analog Alarm Setup screen will appear.

8.1.1. Generic Alarming Setup

Setting up Generic Alarming for PerformanceAlert™ Gateway I/O points is done from the E2 Input Status Screen.
1. Log in to the E2 and press Definitions).
2. If you have not yet done point setup for the Gateway’s virtual I/O points, follow the steps outlined in Section 6.2.1., Condensed Mode
Point Setup or Section 6.3.1., Expanded Mode Point Setup. When point setup is com-
plete for all PerformanceAlert™ Gateway virtual I/O points, you should see the letter "D" next to each PerformanceAlert™ input point. In the example (Figure 8-1), the Gate­way is operating in Condensed Mode desig­nated as 16AI board #1, with all fourteen I/O
I (Input
Figure 8-2 - Digital Alarm Setup Screen
After completing Step 4, complete generic alarm setup by following the instructions appropriate for the input type (Digital or Analog).

8.1.2. Alarm Parameter Settings

8.1.2.1. Digital Alarms
For all Condensed Mode data points, and for all Ex­panded Mode data points except 13, 14, and 15, digital alarming may be set up so that an alarm will be generated when the point transitions to the ON state.
Continuing from step 4 of Section 8.1.1., Generic Alarming Setup:
5. Set the Advisory Method field to "Select Methods."
6. In the "Alarm On an" field, set this field to "Yes" and press the right of the cursor where you may choose
which digital state will trigger the alarm. Set this field to ON.
>. A field will appear to
20 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Page 27
7. In the Report Delay and Report Priority Fields, you must decide three things: whether you want a PerformanceAlert™ advisory to be an ALARM or NOTICE in the E2 Adviso­ry log; what report priority you want the alarm to be; and how long the Perfor­manceAlert™ alarm must be active before the alarm will be generated.
Of these analog points, it is not necessary to set up ge­neric alarming on points 13 and 14. On point 15, the dis­charge line temperature, alarming already occurs with high discharge causes a trip condition to occur (in Expanded Mode, Generic Alarming should be set up for this condition on point 1). If desired, you may use Generic Alarming to generate a warning when discharge line temperature runs too close to the trip setpoint.
In the example shown in Figure 8-3, the ad­visoryis configured to be an ALARM gener­ated after a ten minute delay with a report priority of 20. You will generally want to set up critical alarms such as Locked Rotor or Phase Fail as ALARM advisories with a pri­ority of 20 or above. To keep a point from generating notices, the Report Priority under the Notice column is set to 0
To make an advisory appear as a low-priority notice, enter a 99 in the Report Priority "No­tice Levels" column and a 0 in the Report Pri­ority "Alarm Levels" column.
Figure 8-3 - Digital Alarm Settings
8. Press
J to save changes and return to the
Digital Input Setup screen. Note the OUT­PUT fields at the bottom of the screen now has the additional letter "A" at the end. This signifies that this point has active generic alarming parameters.
Continuing from step 4 of Section 8.1.1., Generic Alarming Setup:
5. Set the Advisory Method field to "Absolute Levels."
6. Set the Advisory Use field to "Instanta­neous."
7. In the "Notice Levels" column, highlight the "Occupied Hi" field, and enter the desired warning temperature threshold. This value should not be higher than the programmed DLT trip setpoint in the PerformanceAlert™.
8. In the "Notice Levels" column, set the Report Delay to the desired amount of time (in HH:MM) the discharge line temperature must remain at or above the Occupied Hi field value to cause the advisory to occur.
9. In the "Notice Levels" column, set the Report Priority to 99 (the lowest possible priority level).
10. In the "Notice Levels" column, highlight the Return to Normal Delta field, and enter the number of degrees the discharge line temper­ature must fall below the value in the Occu­pied Hi field to set the advisory status to "return-to-normal."
11. In the "Alarm Levels" column, highlight the Report Priority field and change its value to zero to disable generation of ALARM advi­sories.
9. Press
8.1.2.2. Analog Alarms
The only analog values on the PerformanceAlert™ Gateway are points 13, 14, and 15 of each virtual 16AI board that represents a PerformanceAlert™ module when the Gateway is operating in Expanded Mode. Points 13 and 14 are current values; point 15 is the discharge line temper­ature.
Passing PerformanceAlert™ Alarm Data to the E2 Advisory Log E2 Applications • 21
J to return to the Input Status
screen. Repeat steps 1 through 8 for the re­maining digital PerformanceAlert™ Gate­way points until all digital points are set up for alarming.
Page 28
When finished, the Analog Alarm Setup screen should appear similar to Figure 8-4. Press and exit to the Input Status screen.
Figure 8-4 - Analog Alarm Setup Parameters
J to save changes

8.1.3. Advisory Values and Priorities

When setting up Generic Alarming, you will want to choose advisory types and advisory priorities that are ap­propriate to the overall alarm filtering and reporting set­tings for the E2. When alarm dial-outs or annunciation devices are being used, the E2 will generally be set up to filter out low-priority alarms and notices. Refer to the E2 User’s Guide for more information about alarm reporting and dial-out settings.
8.1.4. How the Alarm Appears in the E2
Advisory Log
Because Generic Alarming is not designed specific to PerformanceAlert™ Gateway, the alarm message generat­ed when a PerformanceAlert™ alarm occurs will not spe­cifically say anything about PerformanceAlert™. Digital alarm messages will read "State Switched ’ON’", and ana­log alarm messages will read "Occupied Hi Limit Exceed­ed." The only indicator of which PerformanceAlert™ module generated the alarm will be from the point name you entered during point setup, which will be shown in the alarm’s "Property or Board/Point" column in the alarm log (Figure 8-5).
In the example in Figure 8-5, since point #1 of the Per­formanceAlert™ gateway was named "PF COMP 1" when the point was set up in Section 6.2.1., the origin of the alarm can be seen in the application name.
8.2. Using PerformanceAlert™
Current Transducer Values as Compressor Proofs
When the PerformanceAlert™ Gateway is used in Ex­panded Mode, the T1 and T3 compressor current values passed in points 13 and 14 of each virtual 16AI board can be used to verify a compressor is running when command­ed to run and OFF when commanded to be OFF.
For each compressor with a PerformanceAlert™ mod­ule installed, one Sensor Control application must be creat­ed and programmed to read the current values from the PerformanceAlert™ Gateway and turn an output ON or OFF depending on whether the current values signify the compressor is ON or OFF. This Sensor Control output will be used as the compressor proof and tied to the appropriate Suction Group compressor proof input.
8.2.1. Creating Analog Sensor Control
Applications
1. Log in to the E2 and press I (Add
Application).
2. In the "Type" field, select "Analog Sensor Control." In the "How many?" field, enter the number of compressor proofs you will be cre­ating.
3. Press
4. Press

8.2.2. Programming Analog Sensor Control Applications

>. The applications will be created.
Press
* when E2 asks if you want to edit
new applications.
H to return to the home screen.
5. Press I (Configured Applications).
6. Press
7. From the Sensor Control summary screen,
8. Press
Figure 8-5 - Example of Advisory Log with "State switched On" Advisory
22 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
to select "Sensor Controls" from the
Configured Applications menu.
highlight the name of the analog sensor con­trol you wish to edit, and press Sensor Control’s Status Screen will be
shown.
>. The
E (Setup) to begin editing.
Page 29
8.2.2.1. General
8.2.2.3. Setpoints
Figure 8-6 - Analog Sensor Control Compressor Proofing ­General Screen
In the Name field, enter "CMP x PRF" (where x is the address of the PerformanceAlert™ module whose current transducer values will be using for proofing by this appli­cation). Set all other values in this screen as shown in Fig- ure 8-6:
Num Inputs: 2
Eng Units: A
Comb Method: MIN
Show Advanced: No
8.2.2.2. Inputs
Figure 8-7 - Analog Sensor Control Compressor Proofing ­Inputs Screen
In the Inputs tab, enter the board and point address of the T1 and T3 currents from the PerformanceAlert™ Gate­way in the Input1 and Input2 fields. The board number should correspond to the address number of the Perfor­manceAlert™ module. T1 will always be point #13 and T3 will always be point #14.
Figure 8-8 - Analog Sensor Control Compressor Proofing ­Setpoints Screen
In the Setpoints tab, enter 3.0 in the CUTIN field and
2.5 in the CUTOUT field. These setpoints will result in the sensor control output being ON when the current is above 3 amps and OFF whenever it falls below 2.5 amps. Leave the Cut In Delay and Cut Out Delay fields set to 0:00:00.

8.2.3. Setting Up Proofing in Suction Group Applications

After entering the CUTIN and CUTOUT setpoints in the Setpoints tab (Section 8.2.2.3.), press ) to save changes and exit. You are now ready to configure the compressor in the suction group to use the output of the sensor control ap­plication as its proof.
The instructions below assume the compressor rack is already set up in a pre-existing Enhanced Suction group ap­plication. Refer to the E2 User’s Guide for information on setting up a suction group.
1. Press
2. Press
3. If more than one Suction Group application is
4. From the suction group’s Status Screen, press
I (Configured Applications).
to select "Suction Groups" from the
Configured Applications menu.
present, highlight the suction group the com­pressor belongs to, and press
>.
Using PerformanceAlert™ Current Transducer Values as Compressor Proofs E2 Applications • 23
Page 30
E: SETUP.
Figure 8-9 - Analog Sensor Control Compressor Proofing ­Inputs Screen
APPLICATION: Choose the name (CMPR x PROOF) you entered for the Analog Sensor Con­trol application
OUTPUT: Choose COMMAND OUT
5. Press
6. Locate the compressor stage for which you
7. Press
Figure 8-10 - Analog Sensor Control Compressor Proofing ­Setpoints Screen
8. The Proof tab should have a blank Board/
9. For each field in the Controller/Application/
4+ to navigate to the Stage Setup
tab (Figure 8-9).
wish to set up proofing. For this stage, change the value of the Proof field from "No" to "Yes."
4+ to bring up the Additional Tabs
menu. Press
Point definition named COMP PROOF with a number next to the name equal to the num­ber of the compressor stage. Move the cursor to highlight the Board field of this COMP
PROOF definition, and press change the definition type from a Board/ Point to a Controller/Application/Output type definition.
Output, use the Look-Up Table ( point the COMP PROOF input to the output of the Analog Sensor Control application.
CONTROLLER: Name of this E2
) to select the "Proof" tab.
C to
D) to
Figure 8-11 - Defined Compressor Proof Output
If defined correctly, the proof should look similar to
Figure 8-11. Press
Repeat the process outlined in this section to create all
necessary compressor proofs.
J to save changes and exit.
24 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
Loading...