Emerson Copeland EV2 Series, Copeland EV2080M-L1, Copeland EV2080M-L2 Application Engineering Bulletin

Page 1
© 2018 Emerson Climate Technologies, Inc.
1
TABLE OF CONTENTS
Safety
Safety Icon Explanation ........................................... 2
Instructions Pertaining to Risk of
Electrical Shock, Fire, or Injury to Persons ............. 3
Safety Statements ................................................... 4
Introduction
Product Description ................................................. 5
Theory of Drive Operation ....................................... 5
Agency Recognition ................................................. 5
Nomenclature .......................................................... 5
Installation
Drive Handling ......................................................... 5
Mounting .................................................................. 5
Drive Dimensions..................................................... 5
Wiring Diagram ........................................................ 5
Operation & Function
............................................... 5
Hi-pot Procedure / Set-up ...................................... 5
Temperature & Humidity ......................................... 6
Pre-operation Checks ............................................. 6
Power On/Off ......................................................... 6
Communication Setting ......................................... 6
Input Voltage and Input Current ............................. 6
Dynamic DC Bus Voltage Control by Buck ............ 6
Speed Control ......................................................... 6
Start-up ................................................................... 6
Shutdown ................................................................ 6
Fault Clearing ......................................................... 6
Lockout Faults ........................................................ 6
Stator Heat Control ................................................ 6
Status Indication ..................................................... 7
4 States of RGB LED (DS1-LED) ....................... 7
Rolling LED ......................................................... 7
Power Interrupt ....................................................... 7
Drive Configuration ................................................ 7
High Pressure Cut Out ........................................... 7
Drive Cooling .......................................................... 7
Drive Over Temperature Protection ....................... 7
Air Cooled Heat Exchanger ................................... 8
Cold Plate Heat Exchanger .................................... 8
Foldback ................................................................. 8
Troubleshooting ..................................................... 8
EMC Guidelines ..................................................... 8
Figures
Drive Assembly 3D Wiring Diagram ....................... 9
Drive Assembly 2D Wiring Diagram ..................... 10
Tables
Communication Connector Pin Definition ............ 11
Sensor Connector Pin Definition .......................... 11
Addendum
AE8-1429 R1
January 2018
EV2 Three Phase Series Variable Speed Drives
517-625V, 8.0 kW
These commodities, technology or software, are subject to the U.S. Export Administration Regulations (EAR). Diversion contrary to U.S. law is prohibited. ECCN: EAR99
Page 2
© 2017 Emerson Climate Technologies, Inc.
2
AE8-1429
Safety Instructions
Copeland Scroll™ variable speed drives are manufactured according to the latest U.S. and
European Safety Standards. Particular emphasis has been placed on the user's safety. Safety icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These instructions should be retained throughout the lifetime of the compressor. You are
strongly advised to follow these safety instructions.
Safety Icon Explanation
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury. CAUTION, without the safety alert symbol, is used to address practices not related
to personal injury.
FLAMMABLE
DANGER
WARNING
CAUTION
NOTICE
CAUTION
Page 3
© 2017 Emerson Climate Technologies, Inc.
3
AE8-1429
Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect and lock out power before servicing.
Discharge all capacitors for a minimum of two minutes before servicing.
Use compressor with grounded system only.
Molded electrical plug must be used when required.
Refer to original equipment wiring diagrams.
Electrical connections must be made by qualified electrical personnel.
Failure to follow these warnings could result in serious personal injury.
WARNING
PRESSURIZED SYSTEM HAZARD
System contains refrigerant and oil under pressure.
Remove refrigerant from both the high and low compressor side before
removing compressor.
Never install a system and leave it unattended when it has no charge,
a holding charge, or with the service valves closed without electrically locking out the system.
Use only approved refrigerants and refrigeration oils.
Personal safety equipment must be used.
Failure to follow these warnings could result in serious personal injury.
WARNING
FIRE HARD
Open flames and smoking are strictly forbidden.
Continuously check if the ambient atmosphere is nonexplosive.
During service make sure that:
o The area is well ventilated. o The materials and equipment used are suitable for use under
explosive conditions.
o Only non-sparking tools are used. o Anti-static gloves and clothes are used. o A build-up of electrostatic charges is avoided.
In the case of explosive atmosphere:
o Immediately stop the compressor and de-energize the power
supply of the compressor and any other electrical component/ equipment such as crankcase heater.
o No unshielded flame is allowed.
Before opening the refrigeration, system or working on it with an unshielded
flame:
o Continuously check if the ambient atmosphere is non-explosive
and ensure proper ventilation of the room before creating any naked flame. No naked flame is allowed in an explosive atmosphere.
When atmosphere reaches a dangerous concentration of flammable gas:
o Avoid any ignition source and ventilate the room further.
Closed all valves tightly if any parts of the refrigeration systems are charged
with flammable refrigerants.
Page 4
© 2017 Emerson Climate Technologies, Inc.
4
AE8-1429
WARNING
BURN HAZARD
Do not touch the compressor until it has cooled down.
Ensure that materials and wiring do not touch high temperature areas of
the compressor.
Use caution when brazing system components.
Personal safety equipment must be used.
Failure to follow these warnings could result in serious personal injury or
property damage.
R290 MIXTURE IN POTENTIALLY EXPLOSIVE ATMOSPHERE
R290 mixed with air can create an explosive atmosphere.
Immediately stop the compressor and ventilate the room if an explosive
atmosphere is detected.
No open flame is allowed.
CAUTION
COMPRESSOR HANDLING
Use the appropriate lifting devices to move compressors.
Personal safety equipment must be used.
Failure to follow these warnings could result in personal injury or
property damage.
Safety Statements
Refrigerant compressors must be employed only for their intended use.
Only qualified and authorized HVAC or refrigeration personnel are permitted to install commission and
maintain this equipment.
Electrical connections must be made by qualified electrical personnel.
All valid standards and codes for installing, servicing, and maintaining electrical and
refrigeration equipment must be observed.
Page 5
© 2018 Emerson Climate Technologies, Inc.
5
INTRODUCTION Product Description
The inverter drive has been developed specifically for the variable speed compressor. The drive will power the compressor, control the compressor running speed, provide compressor and drive protection and communicate with the master controller. The drive requires cooling and is typically installed in a system near the compressor.
Theory of Drive Operation
The primary purpose of the drive is to convert the 50/60 Hz AC input voltage into a variable frequency, variable voltage output to power the variable speed scroll compressor. The drive conditions the AC input Voltage through a series of conditioning processes to arrive at the desired output. The drive first converts the AC input voltage into a DC bus. The DC voltage is then pulse-width modulated to replicate a sinusoidal current at the desired frequency and voltage.
Agency Recognition
UL 60730-1
Nomenclature
The model number of the drive includes the power rating and nominal voltage input to the drive. Contact
Application Engineering
for all the alpha and numeric
characters in the drive model number.
INSTALLATION Drive Handling
Caution must be used when lifting and installing the drive. Failure to use caution may result in bodily injury.
The drive is designed to meet creepage and clearance requirements for a maximum altitude of 2000 meters.
Correct handling and storage of the drive is
essential in preventing mechanical damage.
Box and the protection bag inside the box need to
be carefully opened. Do not use any sharp material to open the protection bag, which may damage the drive.
Never cut across the drive with any sharp
materials.
Do not hold by the components on the drive or
drive accessories, this can damage them.
Once opened do not stack the drives on each other.
When handling the drive, the only correct way is to
hold it by the edges of the heatsink.
Do not drop any mechanical tools on the drive or
drive accessories.
It is always recommended to use ESD control
wristbands while touching any part of the drive.
Personnel handling the drives in a manufacturing plant environment should guard against static electricity by using the appropriate equipment – antistatic wrist straps and mats.
Mounting
The drive should be located within 5 feet of the compressor since the wiring between the drive, and the compressor is unshielded.
Air-cooled drives are supported inside the HVAC system by an extended heatsink plate. The plate mounts through an opening in the cabinet sheet metal to expose the heat exchanger to the condenser fan air stream. The flange contains a gasket surface to prevent water from entering the electronics side of the control box.
The flat plate option accommodates installation to systems using the mating gas or liquid cooled cold plate heat exchanger. The mating cold coupling plate is designed by OEM to accommodate the system design.
There are holes in the drive mounting flange for mounting purposes. These holes will accommodate a M5 sized screw for mounting.
Drive Accessories and Dimensions
Contact
Application Engineering
for all the drawings
and detailed dimensions with tolerances.
Wiring Diagram
Refer to
Figures 1-2
for a detailed description of the
drive wiring diagrams. Refer to
Tables 1-2
for a
detailed description of the connector pins definition.
OPERATION & FUNCTION Hi-pot Procedure / Set-up
Refer to
Addendum
for hi-pot procedure and setup. Please call your Application Engineer for additional details.
Page 6
© 2017 Emerson Climate Technologies, Inc.
6
AE8-1429
Temperature & Humidity
Drive operating temperature range: -20°C to 55°C Drive storage temperature range: -40°C to 85°C Humidity: Maximum Relative Humidity 95%
Pre-operation Checks
Check the drive carefully before use it. Make sure that all the wires are correctly and tightly connected. Improper operation may cause fire or injury to persons.
Power On/Off
The drive should use rated AC power supply: 50/60Hz, 517-625V on EV20XXM-LX-XXX models.
Use of incorrect power supply may damage the drive. The user should make sure that the correct combination of a power supply, drive, and accessories are used.
When powering off the drive, make sure to wait for at least 60 seconds to ensure that the drive is completely turned off.
Communication Setting
The drive is designed to be used in a master-slave configuration where the master is a system controller. Standard Modbus protocol RTU is available.
Users can also change the slave ID, baud rate, parity and stop bit method. Detailed parameters and default values are in the Modbus Map (refer to
Addendum
).
Modbus uses a three-layer protocol – physical, data link, and application. Refer to
Addendum
for additional
details.
Input Voltage and Input Current
The drives are designed for rated AC power supply: 50/60Hz, 517-625V on EV20XXM-LX-XXX drive models. Published performance of the drive and compressor combination will have a performance tolerance specified on the compressor performance data sheet when the Drive input voltage is in the specified range as above.
Drive
Max AC Input Current
EV2080L 11A RMS
Dynamic DC Bus Voltage Control by Buck
The drive has dynamic DC bus voltage control function, which is capable of improving efficiency.
Speed Control
The frequency range of EV2 is from 15Hz to 120Hz. If the frequency set by system controller is less than 15Hz but not zero, then the compressor will work at 15Hz. Similarly, if the frequency set by system controller is greater than 120Hz, then the compressor will work at 120Hz.
Start-up
Refer to
Addendum
for start-up procedures and requirements.
Shutdown
Refer to
Addendum
for shutdown procedures and requirements.
Fault Clearing
In the Modbus relationship, the drive is considered a slave, and the system controller is the master. Faults will not clear unless they are commanded to.
To clear faults, use the following method:
1. The compressor has been shut down for at least 35 seconds.
2. The fault condition no longer exists (registers 78-
85).
3. The drive has received a zero speed command (register 101 = 0).
4. The drive has been disabled (register 100 = 0).
5. Write '1' to register 103.
Faults will not clear unless all items above are true.
Lockout Faults
There are specific faults that will cause the drive to 'lockout' after 10 consecutive occurrences. These faults are noted in the
Addendum
. These faults will not
clear unless the power to the drive is fully cycled.
Stator Heat Control
In actual use, the system controller may decide whether to preheat or not according to the environment. When preheating is needed, the system controller sends register 100 a compressor enable command and register 102 a stator heating power value. The drive transmits up to 50W DC power to warm-up the compressor.
The stator heating is ON if the followings are true:
1. There are no active errors.
Page 7
© 2017 Emerson Climate Technologies, Inc.
7
AE8-1429
2. Compressor enabled.
3. Compressor speed is set zero.
4. Stator heater power setting is from 10~50.
If the system sends a speed demand to the drive while the stator is heating, the drive should stop stator heating and start the compressor. While running, if the system sends a zero-speed command, the drive should shut down the compressor automatically, and then resume the stator heating to the value saved in Stator Heater Power Memory Register (a value or zero = off).
Status Indication
There is one control chip on the drive board. And drive board has both RGB LED (DS1), and Rolling 7­segment LED for drive status display.
4 states of RGB LED (DS1-LED)
1. PURPLE: When the drive is in programming mode via bootloader.
2. GREEN Solid: When the drive is in normal state (no faults) in standby mode and the compressor is not running. The LED will be solid GREEN.
3. GREEN Blinking: When the compressor is running, LED will blink at 1Hz in GREEN.
4. RED: When the drive has any active faults or protections.
Rolling LED
There is also a Rolling LED for drive status display. For further information, refer to Tables 7 & 8 for detailed functionality and display status modes.
Power Interrupt
Power interrupts can result in a drive trip that won't harm the drive. The drive can withstand interrupts of a short duration (<=10 ms) but will trip on anything longer.
Drive Configuration
Another feature available on the drive is the option to change communication parameters, configure the drive to use different types of compressors and sensors. Modbus registers 200 - 207 and 210 -213 serve this function (refer to
Modbus Map
within the
Addendum
for details). These options are password protected. Register 200
must have the correct password written before any parameters can be changed. All register functions and default values are located in the
Modbus Map
.
Registers 201-204 are for communication
parameters.
Registers 203 and 204 are automatically
configured by the drive, based on baud rate and parity information from the system controller.
Register 205 is for compressor model type.
Registers 206 & 207 are for sensor type
configurations.
Register 210 is controlled shutdown rate
configuration.
Register 211 and 212 are configured for speed
ramp-up and ramp-down rate configuration.
Register 213 is configured for ramp-up speed
during compressor start-up.
Once configured only changes to registers 201-204 will require power cycle for the changes to be implemented.
Refer to
Addendum
for configuration process flow and
communication settings process flow.
High Pressure Cut Out
CN5 on EV2080X-LX-XXX is a 2-port connector on drive model. The output is a 3.3VDC signal. The high­pressure cutout switch must be normally closed. If the switch is open, the drive will not operate. The output current for the high-pressure contact will range from 300uA to 400uA. To ensure correct functionality of the high-pressure switch for the system’s lifetime, typically gold-plated contacts are recommended. Refer Table-2 for detailed pinout.
This port is hardware Protected Electronic Circuit (PEC), and software is Class-B according to UL60730-1.
Drive Cooling
Because of the power electronics used in the drive and the associated heat generation, drive cooling is required to keep the drive components in their design temperature range. The allowable temperature range of the drive (The ambient air surrounding the drive) is ­4°F to 131°F. Drive temperature should be monitored during system development at system extreme conditions to ensure that the maximum allowable drive
temperature isn’t exceeded. The highest drive
temperature will typically occur during high load conditions or during high drive ambient.
Drive Over Temperature Protection
The drive is self-protected against high internal temperatures. There are different modes of protection; temperature high and foldback. For temperature high refer to
Troubleshooting Table
within
Addendum
.
For foldback protection refer to Section 2 in the
Addendum
for more information.
Page 8
© 2017 Emerson Climate Technologies, Inc.
8
AE8-1429
Air Cooled Heat Exchanger
Drives cooled by the aluminum air-cooled heat exchanger are designed to be in the air flow stream of the condenser. The air-cooled heat exchanger must be installed so that the heat exchanger fins are parallel to the cooling air flow. The airflow must be a minimum of 3 meters/sec measured at the outlet of the heatsink in the direction of airflow.
Cold Plate Heat Exchanger
The cold plate design can be used when another cooling source is available – suction gas from the evaporator coil, subcooled liquid refrigerant, glycol solution from a geothermal loop, water from a cooling tower, etc. When the refrigerant is used for drive cooling, the heat given up by the drive is transferred into the refrigeration system. This can be a net gain for heating applications and a net loss for cooling applications.
There must be thermal grease between flat plate cold plate. There is no standard for the thickness requirement of thermal grease; normally, it's between
0.2mm-0.4mm. The entire surface of the flat plate must be covered. Dow Corning TC-5022 silicone heat sink compound or a similar product is recommended. Contact
Application Engineering
for cold plate
details. The soldering/brazing that is required to connect the
cooling source to the cold plate should be performed before the cold plate is attached to the drive, to prevent overheating drive components with the torch.
Foldback
To protect the drive components or the compressor, the compressor speed will 'foldback' or slow down to help reduce risk to components. The foldback event(s) will be flagged in the drive's Modbus registers. This will
allow the operating system to respond and mitigate the conditions causing foldback.
For further information refer to Section 2 in the
Addendum. TROUBLESHOOTING
The drive may indicate fault or protection for various reasons. If fault or protection occurs, users should power down the drive, check the drive, and check the drive running condition carefully. For the description, check and handling of these faults or protections, please refer to the
Troubleshooting – Fault and
Protection
within
Addendum
EMC Guidelines:
Install the star earth (ground) connection as close
as possible to the drive. A non-coating screw is recommended for installation on the service panel to maintain a good ground connection. The star connection includes: – System Input ground – Drive ground
The usage of additional ferrites and numbers of
turns in the input power supply cables, compressor cables, sensor cables are optional but preferred based on system application and noise level.
Any of the input power supply cables, sensor
cables, compressor cables and communication cables should not cross or touch each other to avoid noise coupling.
Usage of shielded cable is optional depending on
system application, but if used it’s mandatory to
have correct connections on both sides of the cable.
Page 9
© 2018 Emerson Climate Technologies, Inc.
9
Figure 1 – Drive Assembly 3D Wiring Diagram
Page 10
© 2017 Emerson Climate Technologies, Inc.
10
AE8-1429
Figure 2 – Drive Assembly 2D Wiring diagram
Page 11
© 2017 Emerson Climate Technologies, Inc.
11
AE8-1429
Table 1 – Communication Connector Pin Definition
Pin
Number
Description
Figure
1
RS485 (+)
2
Not Used
3
Not Used
4
RS485 (-)
5
Common
6
EMI Drain Wire
Description
Part Number
6-Pin Connector Housing
Molex 0039012065
or Equivalent
Connector Pins
Molex 0039000038
or Equivalent
Table 2 – Sensor Connector Pin Definition
Pin
Number
Description Figure
1
Sensor Pin-1
2
Sensor Pin-2
3
Not Used
4
Not Used
A1
High Pressure Signal
A2
3.3VDC
(DLT Sensor) Connector (Pin -1 to 4) P/N Information
Description
Part Number
4-Pin Connector Housing
Molex 39-01-2045 or Equivalent
Connector Pins
Molex 39-00-0428 or Equivalent
(HPS) Connector (A1/A2) P/N Information
Description
Part Number
2-Pin Connector Housing
JST Sales America XLP-02V or
Equivalent
Connector Pins
JST Sales America SXF-41T-P0.7
or Equivalent
The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable, reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.
Page 12
TABLE OF CONTENTS
1 Start-up and Shutdown Sequence of The Compressor ............................................................... 2
2 Drive Foldback Information ............................................................................................................... 3
3 Modbus Map ....................................................................................................................................... 5
4 Drive Configuration Flow Charts .................................................................................................... 11
5 Drive Status Display – Rolling Led ................................................................................................ 12
6 Troubleshooting Guide .................................................................................................................... 13
7 Hi-pot Testing .................................................................................................................................... 15
8 Accessories ....................................................................................................................................... 16
ADDENDUM to AE8-1429 10/31/2017
Page 13
1 START-UP AND SHUTDOWN SEQUENCE OF THE COMPRESSOR
Table 1 - Start-up Sequence
Stage
Description
Target Speed (rpm)
Ramp Up Rate (rpm/s)
Duration (s)
I
Compressor continues to ramp up
1500 (configurable)
375
4
II
Compressor remains at the platform speed
1500
-
10
III
Compressor reaches commanded speed
Commanded
Default = 60
-
Table 2 - Shutdown Sequence
Stage
Description
Target Frequency
(rpm)
Ramp Down Rate
(rpm/s)
I
Compressor Shutdown requested
- -
II
Compressor gets to minimum speed
900
Default = 150
III
Compressor Stop
- -
Figure 1 – Start-up Sequence
Speed
Time
1500-3500 RPM (Reg.213)
Customer configured
4S
14
S
10S
375RPM/S
60-360RPM/S (Reg.211)
60-360RPM/S (Reg.212)
Ramp Up/Down rate is Customer configured
Page 14
Figure 2 – Shutdown Sequence
2 DRIVE FOLDBACK INFORMATION
Table 3 – Input Current Foldback
Condition
Action taken by the Drive
1
Input Current >= Foldback Current
Will reduce the speed at the rate of 120 rpm/s
2
Recovering Current <= Input Current < Foldback Current
Will remain in the current speed
3
Input Current < Recovering Current
Speed will be recovered to commanded speed
4
If the compressor load is not recovered and continue to exceed the foldback limit in one of the conditions below:
After compressor running speed has reached to Envelope min foldback speed and then stay Envelope min foldback speed for >= 30sec. OR
If the original running speed was already < Envelope min foldback speed for >= 30sec
Compressor will be tripped
Stop
Shutdown Initiated
60-360RPM/S (Reg.210)
900RPM (Minimum Speed)
Shutdown Down rate is Customer configured
Page 15
Table 4 – Output Torque Foldback
Condition
Action taken by the Drive
1
Output Torque >= Foldback Limit of operating speed range
Will reduce the speed at the rate of 60 rpm/s
2
Recovering Torque <= Output Torque < Foldback Limit of operating speed range
Will remain in the current speed
3
Output Current < Recovering Current
Speed will be recovered to commanded speed
4
If the compressor load is not recovered and continue to exceed the foldback limit in one of the conditions below:
After compressor running speed has reached to Envelope min foldback speed and then stay at Envelope min foldback speed for >= 30sec. OR
If the original running speed was already < Envelope min foldback speed for >= 30sec
Compressor will be tripped
Table 5 – IGBT Temperature Foldback
Condition
Action taken by the Drive
1
IGBTTemperature >= Foldback Temperature
Will reduce the speed at the rate of 180 rpm/s
2
Recovering Temperature <= IGBT Temperature < Foldback Temperature
Will remain in the current speed
3
IGBT Temperature < Recovering Temperature
Speed will be recovered to commanded speed
4
If the compressor load is not recovered and continue to exceed the foldback limit in one of the conditions below:
After compressor running speed has reached to Envelope min foldback speed and then stay at Envelope min foldback speed for >= 30sec. OR
If the original running speed was already < Envelope min foldback speed for >= 30sec
Compressor will be tripped
Table 6 – Inverter Temperature Foldback
Condition
Action taken by the Drive
1
Inverter Temperature >= Foldback Temperature
Will reduce the speed at the rate of 180 rpm/s
2
Recovering Temperature <= Inverter Temperature < Foldback Temperature
Will remain in the current speed
3
Inverter Temperature < Recovering Temperature
Speed will be recovered to commanded speed
4
If the compressor load is not recovered and continue to exceed the foldback limit in one of the conditions below:
After compressor running speed has reached to Envelope min foldback speed and then stay at Envelope min foldback speed for >= 30sec. OR
If the original running speed was already < Envelope min foldback speed for >= 30sec
Compressor will be tripped
Page 16
3 MODBUS MAP
Modbus
Register
Register Type
Description
Fault
Shutdown
Units
Bytes
Data Format
0
Serial and
Model Numbers
(Read)
Drive Model Number
N/A
N/A
32
bytes
ASCII
charact
er
string
EV20XXM-C1-19X/89X 0XX:power Ex. 055 = 5.5kW max capacity
1
Drive Serial Number
N/A
N/A
32
bytes
ASCII
charact
er
string
ADXXXXXXX Ex. AD13K0001 AD: Production Code 13:2013,production year. K: Month Code, A=Jan, B=Feb,…,L=Dec. 0001: Product Serial Number.
3
Software
Version (Read)
Allowed maximum
Speed (for speed limit
protection)
N/A
Hz
2 Bytes
Value: 0~120 = 0~120Hz Ex. : If value = 100, then maximum allowed running speed = 100Hz
4 Allowed minimum
Speed (for speed limit
protection)
N/A
Hz
2 Bytes
Value: 0~120 = 0~120Hz Ex. : If value = 100, then minimum allowed running speed = 100Hz
12
DSP Boot Version (High
Word)
N/A
N/A
2 Bytes
16.8.8 Ex. 4.20.0: 4=Internal ver; 20=Major ver;
0=Minor ver
16.8.8 Ex. 4.20.0: 4=Internal ver; 20=Major ver;
0=Minor ver
13
DSP Boot Version (Low
Word)
N/A
N/A
2 Bytes
14
DSP Main Version (High
Word)
N/A
N/A
2 Bytes
15
DSP Main Version (Low
Word)
N/A
N/A
2 Bytes 16
Trip Limits
(Read)
Compressor Phase Over
Current
N/A
Amps (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
17
AC Input Over Current
N/A
Amps (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
18
DC Bus Over Voltage
N/A
Volts (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
19
DC Bus Under Voltage
N/A
Volts (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
20
AC Input Over Voltage
N/A
Volts (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
21
AC Input Under Voltage
N/A
Volts (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
22
Power Module Over Temp
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
23
IGBT Over Temp
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
32
DC Bus Voltage Low
N/A
Volts (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
34
Board Temp High
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
35
Power Module Temp High
N/A
Celsius
2 Bytes
11.5
Page 17
Ex. If Value = 512, then Conversion = 512/(2^5)
36
IGBT Temp High
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
38
Sensor 2 (Thermistor, DLT)
High Temp Limit
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
48
Drive
Status/Readings
(Read)
Torque Fold Back Status
N/A
N/A
2 Bytes
0 = No ; 1 = Yes
49
Power Module & IGBT Temp
Fold Back Status
N/A
N/A
2 Bytes
0 = No ; 1 = Yes
50
AC Input Current Fold Back
Status
N/A
N/A
2 Bytes
0 = No ; 1 = Yes
53
Compressor Phase_U
Current
N/A
Amps (RMS)
2 Bytes
8.8 Ex. If Value = 512, then Conversion = 512/(2^8)
54
Compressor Phase_V
Current
N/A
Amps (RMS)
2 Bytes
8.8 Ex. If Value = 512, then Conversion = 512/(2^8)
55
Compressor Phase_W
Current
N/A
Amps (RMS)
2 Bytes
8.8 Ex. If Value = 512, then Conversion = 512/(2^8)
56
Buck IGBT Current
N/A
Amps (Avg)
2 Bytes
8.8 Ex. If Value = 512, then Conversion = 512/(2^8)
57
DC Bridge Voltage for 575V
drive
N/A
Volts (DC)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
58
Sensor 1 (HP transducer
only) Reading
N/A
N/A
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
59
Power-Up Status
N/A
N/A
2 Bytes
0 = Not Ready 1 = Power-Up Complete
60
Compressor running speed
N/A
RPM
2 Bytes
15.1 Ex. If Value = 512, then Conversion = 512/(2^1)
61
Torque
N/A
Nm
2 Bytes
7.9 Ex. If Value = 512, then Conversion = 512/(2^9)
62
Torque Limit
N/A
Nm
2 Bytes
7.9 Ex. If Value = 512, then Conversion = 512/(2^9)
64
DC Bus Voltage
N/A
Volts (DC)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
65
AC Input Voltage
N/A
Volts (RMS)
2 Bytes
12.4 Ex. If Value = 512, then Conversion = 512/(2^4)
66
AC Input Current
N/A
Amps (RMS)
2 Bytes
8.8 Ex. If Value = 512, then Conversion = 512/(2^8)
67
AC Input Power
N/A
Watts
2 Bytes
16.0 Ex. If Value = 512, then Conversion = 512/(2^0)
68
Compressor Phase Current
N/A
Amps (RMS)
2 Bytes
8.8 Ex. If Value = 512, then Conversion = 512/(2^8)
70
Power Module Temp
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
77
Sensor 2 (Thermistor, DLT)
Reading
N/A
Celsius
2 Bytes
11.5 Ex. If Value = 512, then Conversion = 512/(2^5)
Compressor Phase Over
Current
Immediate
Shutdown
N/A
Bit 0
0 = No ; 1 = Yes Lockout (After 10 fault occurrences*)
Page 18
78
1st Fault
Occurred
(Read)
AC Input Over Current
Immediate
Shutdown
N/A
Bit 1
0 = No ; 1 = Yes
DC Bus Over Voltage
Immediate
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
DC Bus Under Voltage
Immediate
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
AC Input Over Voltage
Immediate
Shutdown
N/A
Bit 4
0 = No ; 1 = Yes
AC Input Under Voltage
Immediate
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Sensor 1 (High Pressure
Switch Open)
Immediate
Shutdown
N/A
Bit 8
0 = No ; 1 = Yes
Power Module Over Temp
Immediate
Shutdown
N/A
Bit 11
0 = No ; 1 = Yes
IGBT Over Temp
Immediate
Shutdown
N/A
Bit 12
0 = No ; 1 = Yes
Lost Rotor Position
Immediate
Shutdown
N/A
Bit 13
0 = No ; 1 = Yes Lockout (After 10 fault occurrences*)
Pre-charge Relay Open
N/A
N/A
Bit 15
0 = No ; 1 = Yes
79
1st Fault
Occurred
(Read)
DC Bus Voltage Low
N/A
N/A
Bit 0
0 = No ; 1 = Yes
Torque Limit Fold Back
Timeout
Controlled
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Power Module Temp. Fold
Back Timeout
Controlled
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
AC Input Current Fold Back
Timeout
Controlled
Shutdown
N/A
Bit 4
0 = No ; 1 = Yes
Auto Config Communication
Timeout
N/A
N/A
Bit 6
0 = No ; 1 = Yes
Modbus Communication Lost
Controlled
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
Sensor 2 (Thermistor, DLT)
High Temp
Controlled
Shutdown
N/A
Bit 8
0 = No ; 1 = Yes
Board Temp High
Controlled
Shutdown
N/A
Bit 10
0 = No ; 1 = Yes
Power Module Temp High
Controlled
Shutdown
N/A
Bit 11
0 = No ; 1 = Yes
IGBT Temp High
Controlled
Shutdown
N/A
Bit 12
0 = No ; 1 = Yes
80
Multiple Faults
Occurred
(Read)
Compressor Phase Over
Current
Immediate
Shutdown
N/A
Bit 0
0 = No ; 1 = Yes Lockout (After 10 fault occurrences*)
AC Input Over Current
Immediate
Shutdown
N/A
Bit 1
0 = No ; 1 = Yes
DC Bus Over Voltage
Immediate
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
DC Bus Under Voltage
Immediate
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
AC Input Over Voltage
Immediate
Shutdown
N/A
Bit 4
0 = No ; 1 = Yes
AC Input Under Voltage
Immediate
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Sensor 1 (High Pressure
Switch Open)
Immediate
Shutdown
N/A
Bit 8
0 = No ; 1 = Yes
Power Module Over Temp
Immediate
Shutdown
N/A
Bit 11
0 = No ; 1 = Yes
IGBT Over Temp
Immediate
Shutdown
N/A
Bit 12
0 = No ; 1 = Yes
Lost Rotor Position
Immediate
Shutdown
N/A
Bit 13
0 = No ; 1 = Yes Lockout (After 10 fault occurrences*)
Pre-charge Relay Open
N/A
N/A
Bit 15
0 = No ; 1 = Yes
DC Bus Voltage Low
N/A N/A
Bit 0
0 = No ; 1 = Yes
Torque Limit Fold Back
Timeout
Controlled
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Page 19
81
Multiple Faults
Occurred
(Read)
Power Module Temp. Fold
Back Timeout
Controlled
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
AC Input Current Fold Back
Timeout
Controlled
Shutdown
N/A
Bit 4
0 = No ; 1 = Yes
Auto Config Communication
Timeout
N/A
N/A
Bit 6
0 = No ; 1 = Yes
Modbus Communication Lost
Controlled
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
Sensor 2 (Thermistor, DLT)
High Temp
Controlled
Shutdown
N/A
Bit 8
0 = No ; 1 = Yes
Board Temp High
Controlled
Shutdown
N/A
Bit 10
0 = No ; 1 = Yes
Power Module Temp High
Controlled
Shutdown
N/A
Bit 11
0 = No ; 1 = Yes
IGBT Temp High
Controlled
Shutdown
N/A
Bit 12
0 = No ; 1 = Yes
82
1st Fault
Occurred
(Read)
Compressor Phase Current
Imbalance
Immediate
Shutdown
N/A
Bit 0
0 = No ; 1 = Yes
Micro Electronic Fault or
Drive EEPROM Fault
Immediate
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes Lockout (After 10 fault occurrences*)
Motor Over Speed
Immediate
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
Sensor 1 (HP Transducer)
fault – High Pressure
Sensing Low
Immediate
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Compressor Model Configuration Error
Immediate
Shutdown
N/A
Bit 6
0 = No ; 1 = Yes
High Pressure Sensor Type
Configuration Error
Immediate
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
83
1st Fault
Occurred
(Read)
Sensor 2 (Thermistor, DLT)
Low Temp or Open
Controlled
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Power Module Temp Low or
Sensor Open fault
Controlled
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Fault Limit Lockout
N/A
N/A
Bit 15
Lockout Status 0 = No ; 1 = Yes
84
Multiple Faults
Occurred
(Read)
Compressor Phase Current
Imbalance
Immediate
Shutdown
N/A
Bit 0
0 = No ; 1 = Yes
Micro Electronic Fault or
Drive EEPROM Fault
Immediate
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes Lockout (After 10 fault occurrences*)
Motor Over Speed
Immediate
Shutdown
N/A
Bit 3
0 = No ; 1 = Yes
Sensor 1 (HP Transducer)
fault – High Pressure
Sensing Low
Immediate
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Compressor Model Configuration Error
Immediate
Shutdown
N/A
Bit 6
0 = No ; 1 = Yes
High Pressure Sensor Type
Configuration Error
Immediate
Shutdown
N/A
Bit 7
0 = No ; 1 = Yes
85
Multiple Faults
Occurred
(Read)
Sensor 2 (Thermistor, DLT)
Low Temp or Open
Controlled
Shutdown
N/A
Bit 2
0 = No ; 1 = Yes
Power Module Temp Low or
Sensor Open fault
Controlled
Shutdown
N/A
Bit 5
0 = No ; 1 = Yes
Fault Limit Lockout
N/A
N/A
Bit 15
Lockout Status 0 = No ; 1 = Yes
Page 20
Modbus
Register
Register Type
Description
Bytes
Data Format
Default
Values
Additional Notes
100
Standard
Commands
(Read/Write)
Compressor
Enable
2 Bytes
0 = Disable 1 = Enable
0
101
Compressor
Speed Demand
2 Bytes
16.0 Ex. If Value = 512, then Conversion = 512/(2^0) 1RPM/bit
0
102
Stator Heater
Demand
2 Bytes
16.0 0 = Disable Ex. If Value = 512, then Conversion = 512/(2^0) 1Watt/bit
0
103
Faults Clear
Command
2 Bytes
1=Fault Clear , non-1= No Action
0
200
Customer
Configuration
Parameter
(Read/Write)
Map access
Password
2 Bytes
Password = 0x2345 Customer access to 201~213
N/A
201
Modbus Format
2 Bytes
2 = RTU
2
The drive has a feature to detect the
baud rate and parity of the system
controller and automatically configure to
those values.
Example: If controller is running at
19200bps and Even parity, 1 stop bit.
Then registers are automatically
configured to Reg.203 = 19200 &
Reg.204 = 1
202
ModBUS Slave ID
Address
2 Bytes
1-247
45
203
ModBUS Baud
Rate
2 Bytes
1200 = 1200BPS 2400 = 2400BPS 4800 = 4800BPS 9600 = 9600 BPS 19200 = 19200 BPS 38400 = 38400 BPS
19200
204
ModBUS Parity
2 Bytes
1=Even parity, 1 stop bit; 2=Odd parity, 1 stop bit; 3=No Parity, 2 stop bits: 4=Even parity, 2 stop bits: 5=Odd parity, 2 stop bits; 6=No parity, 1 stop bit
1
205
Compressor
Model Number
2 Bytes
0 = Not Configured 301 = ZPV0212E-2E9 (900 ­7200RPM) 311 = ZPV0212E-2E9 Rev1 (900 - 7200RPM) 410 = ZPV0282E-2E9 (900 ­7200RPM) 411 = ZPV0282E-2E9 Rev1 (900 - 7200RPM) 501 = ZPV0382E-2E9 (900 ­7200RPM) 511 = ZPV0382E-2E9 Rev1 (900 - 7200RPM) 502 = ZPV0342E-2E9 (900 ­7200RPM) 512 = ZPV0342E-2E9 Rev1 (900 - 7200RPM) 555 = ZPV0412E-2E9 (900 – 7200RPM)
0
206
Sensor 1 (HP
Switch)
2 Bytes
0 = Not Configured 100 = HP Switch N/C (normally closed)
0
207
Sensor 2 (Scroll
Thermistor, DLT)
2 Bytes
0 = N/A 100 = 10Kohm resistor (to simulate 25oC DLT temp) 200 = DLT 1 (Sensor)
0
When configured to “100”, the DLT limit
at Reg.38 is not applicable, it is only for lab usage.
210
Controlled
Shutdown Rate
Config Option
2 Bytes
16.0 0 = Not Configured Can be configured in increments of "20" (20 to 120). Decimal value of 20 = 60rpm/sec
50
Page 21
Ex. If Value = 50, then it's 150rpm/sec
These values need to be re-configured
only if different shutdown, ramp up &
ramp down rates are required.
211
Speed Ramp-up
Rate Config
Option
2 Bytes
16.0 0 = Not Configured Can be configured in increments of "20" (20 to 120). Decimal value of 20 = 60rpm/sec Ex. If Value = 20, then it's 60rpm/sec
20
212
Speed Ramp-
down Rate Config
Option
2 Bytes
16.0 0 = Not Configured Can be configured in increments of "20" (20 to 120). Decimal value of 20 = 60rpm/sec Ex. If Value = 20, then it's 60rpm/sec
20
213
Ramp-up Speed
Level Config
Option during
Start-up
2 Bytes
16.0 100RPM/bit 0 = Default Ramp-up profile at start-up Ex. 15 = 1500RPM Range: 1500RPM to 3500RPM in 100RPM increments
0
Range: 1500RPM to 3500RPM in
100RPM increments. Drive cannot be
configured outside this band.
*Note: After 10 occurrences of a particular lockout related fault within 10hours time period, the drive will go into hard lockout and need to be power cycled to clear the fault.
Page 22
4 DRIVE CONFIGURATION FLOW CHARTS
Apply Power to Drive
Write Password “0x2345”
to Register 200.
Read Registers 201 to 213
(201 & 202 are
default,203 & 204 are
autoconfigured by the
drive)
Do values match
spec?
Faults?Query fault status
Write values according to Modbus Map to Registers
205 to 213
Operate drive
Troubleshoot according to
the fault
YES
YES
NO
NO
Page 23
5 DRIVE STATUS DISPLAY ROLLING LED
Table 7 - Rolling LED Display Status Information
Item
Major Fault
Long Fault Code
1
Compressor Phase Over Current
INVERTER OVER CURRENT
2
AC Input Over Current
AC OVER CURRENT
3
DC Bus Over Voltage
DC OVER VOLTAGE
4
DC Bus Under Voltage
DC UNDER VOLTAGE
5
AC Input Over Voltage
AC OVER VOLTAGE
6
AC Input Under Voltage
AC UNDER VOLTAGE
7
AC Voltage Imbalance
AC IMBALANCE
8
Sensor 1 (High Pressure Switch Open)
HP SWITCH OPEN
9
Power Module Over Temp
INVERTER OVER TEMP
10
PFC-IGBT Over Temp
IGBT OVER TEMP
11
Lost Rotor Position
LOST ROTOR
12
Compressor Phase Current Imbalance
INVERTER CURRENT IMBALANCE
13
Micro Electronic Fault or Drive EEPROM Fault
MICRO FAULT
14
Motor Overspeed
MOTOR OVERSPEED
15
Compressor Model Configuration Error
COMPRESSOR CONFIG ERROR
16
High Pressure Sensor Type Configuration Error
HP SENSOR CONFIG ERROR
Table 8 - Rolling LED Display Status Information
Item
Minor Fault
Long Fault Code
1
DC Voltage Low
DC VOLTAGE LOW
2
Compressor Phase Current Foldback Timeout
ENVELOP FOLDBACK TIMEOUT
3
Power Module Temp. Fold Back Timeout
OVER TEMP FOLDBACK TIMEOUT
4
AC Input Current Fold Back Timeout
INPUT OC FOLDBACK TIMEOUT
5
Auto Config Communication Timeout
AUTO CONFIG TIMEOUT
6
Modbus Communication Lost
MODBUS COMMS LOST
7
Sensor 2 (Thermistor, DLT) High Temp
DLT TEMP HIGH
8
Board Temp High
MICRO TEMP HIGH
9
Power Module Temp High
INVERTER TEMP HIGH
10
PFC-IGBT Temp High
IGBT TEMP HIGH
11
Sensor 2 (Thermistor, DLT) Low Temp or Open
SENSOR 2 LOW TEMP OR OPEN
12
Fault Limit Lockout
FAULT LIMIT LOCK OUT
Page 24
6 TROUBLESHOOTING GUIDE
Item
Fault/Protection
Check and Handling
Registers
Bit
Rolling LED
Code
1
Compressor Phase
Over Current
1. Check the U/V/W connections on drive side
2. Check the compressor motor windings
3. Check the compressor is operating with in specified limits
78 80 0
INVERTER
OVER
CURRENT
2
Torque Limit Fold
Back Timeout
1. Compressor Torque ≥ foldback protection value (for 30 seconds).
2. Check if the compressor is operating outside the specified speed range.
79 81 2 ENVELOPE FOLDNACK
TIMEOUT
3
AC Input Over
Current
1. Check the line voltage is too low.
2. Check the line voltage for noise.
3. Check the compressor is operating with in specified limits.
4. If the problem still persists, then it's possibly a drive component issue. Replace the drive
78
80
1
AC OVER
CURRENT
4 DC Bus Over
Voltage
1. Check the DC bus voltage if it is > 850VDC
2. Check AC Power Supply
3. Check the compressor is operating with in specified limits.
4. Restart the drive
78 80 2 DC OVER
VOLTAGE
5 DC Bus Under
Voltage
1. Check the DC bus voltage if it is < 350VDC
2. Check the compressor is operating with in specified limits.
3. Restart the drive
78 80 3 DC UNDER
VOLTAGE
6
AC Input Over
Voltage
Check the line voltage if it is > 645VAC
78
80 4 AC OVER
VOLTAGE
7 AC Input Under
Voltage
1. Check the line voltage if it is < 500VAC
2. Check the compressor is operating with in specified limits.
78 80 5 AC UNDER
VOLTAGE
8
AC Voltage
Imbalance
Check if all input cables are connected or any line is missing. Checking if the voltage is below 500VAC. If the problem persists, replace the drive
78
80 6 AC
IMBALANCE
9
Power Module Over
Temp
Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem, still persists replace the drive.
78
80
11
INVERTER
OVER TEMP
10
IGBT Over Temp
Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem, still persists replace the drive.
78
80
12
IGBT OVER
TEMP
11 Lost Rotor Position
1. Check the U/V/W connections on drive side & compressor side.
2. Check the compressor motor windings
3. Check system charge levels, if too high this problem can occur.
78 80 13 LOST ROTOR
12
Compressor Phase
Current Imbalance
82
84 0 INVERTER
CURRENT
IMBALANCE
13
Microelectronic Fault
82 84 2
Page 25
EEPROM fault
1. DSP self-check error, restart the drive and fault should go away.
2. If problem persists, replace the drive.
MICRO FAULT
14
DC Bus Voltage Low
DC Bus Voltage is below 380V. Check the AC power supply and if the right voltage is supplied according to the drive model. The drive running condition is not stable. Check the compressor load and makes sure it is OK. Restart the drive again. If problem persist, replace the drive.
79
81
0
DC VOLTAGE
LOW
15 AC Input Current
Fold Back Timeout.
1. Check the line voltage if it is < 500VAC.
2. Check the compressor is operating with in specified limits.
3. If problem persists, replace the drive.
79 81 4 INPUT OC FOLDBACK
TIMEOUT
16
Modbus
Communication Lost
1. Check mod-bus communication cable connections.
2. Check the communication parameters are set right.
3. Power cycle the drive.
4. If problem persists, replace the drive.
79
81
7
MODBUS
COMMS
LOST
17
Sensor 2
(Thermistor, DLT)
High Temp
1. Check the DLT/Scroll Thermistor connection.
2. Check the compressor is operating with in specified limits.
79 81 8 DLT TEMP
HIGH
18
Power Module Temp
High
Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem, still persists replace the drive.
79
81
11
INVERTER
TEMP HIGH
19
IGBT Temp High
Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem, still persists replace the drive.
79
81
12
IGBT TEMP
HIGH
20
Power Module
Temp. Fold Back
Timeout
Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem, still persists replace the drive.
79
81
3
OVER TEMP
FOLDBACK
TIMEOUT
21
Sensor 1 (High
Pressure Switch
Open)
Condensing Pressure beyond limit, system issue.
78 80 8 HP SWITCH
OPEN
22
Compressor Model Configuration Error
Compressor model and configuration code do not match
82
84 6 COMPRESSO
R CONFIG
ERROR
23
High Pressure
Sensor Type
Configuration Error
Pressure sensor and configuration code do not match
82
84 7 HP SENSOR
CONFIG
ERROR
24
Sensor 2
(Thermistor, DLT)
Low Temp or Open
1. Check the DLT/Scroll Thermistor connection.
2. Check the resistance of the sensor to ensure values are with in specified limits.
83
85 2 SENSOR 2 LOW TEMP
OR OPEN
25
Fault Limit Lockout
Certain faults have a trip limit, see modbus map for details
82
84
15
FAULT LIMIT
LOCK OUT
26
Auto Config
Communication
Fault Timeout
Baud rate or Parity of the system controller not matching with drive. Check whether system controller is working, then Power Cycle the drive.
79
81 6 AUTO
CONFIG
TIMEOUT
27
Motor Over Speed
Check if the compressor is operating within specified limits. Check if the cables are not shorted. Shutdown and restart the drive.
82 84 3 MOTOR
OVERSPEED
Page 26
28
Board Temp High
Processor over-heating. Verify proper airflow over the heat-sink of the drive. Remove any obstructions. If the problem, still persists replace the drive.
79 81 10 MICRO TEMP
HIGH
7 HI-POT TESTING
There many different types of dielectric testers available. When selecting one to use ensure it has the following features:
Can test to voltages up to 4000VDC or higher.
Can read leakage currents less than 10µA.
Has Arc Detection available.
Recommended test settings:
APPLIED VOLTAGE: 3650 VDC
MAXIMUM LEAKAGE CURRENT: Contact Applications Engineer
RAMP UP TIME: 8 Seconds
DWELL TIME: 5 Seconds
RAMP DOWN: 8 Seconds
Test Procedure:
Setup test on a clean and dry non-conductive surface.
Ensure samples are handled properly and using ESD precautions.
Verify the dielectric tester is configured per “Recommended test settings”.
Contact Application Engineer for more details on connections and wiring setup.
Execute Test.
Note and record the maximum leakage current during the dwell period.
Once test is complete, safely disconnect the component and store it properly.
Page 27
8 ACCESSORIES
Accessory
Assembly P/N
Drive Models
Compressor Models
Compressor Molded Plug
Cable, Spade Terminal
529-0372-00
EV2080M-L1 EV2080M-L2
All Compressors
Cable, Line Power to AC
Choke
529-0373-00
EV2080M-L1 EV2080M-L2
All Compressors
Cable, AC Choke to Drive
529-0374-00
EV2080M-L1 EV2080M-L2
All Compressors
Cable, Modbus
Communication
529-0249-00
EV2080M-L1 EV2080M-L2
All Compressors
Loading...