Emerson Controlinc 320B Quick Startup Guide Manuals & Guides

Controlinc Quick Startup Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
September 2020
Notes
September 2020
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Table of Contents
Section 1: Quick Start Guide
1.1 Setup Instructions ................................................................................................ 9
1.2 Entering Setup Mode ...........................................................................................9
1.3 Changing Setup Parameters ................................................................................. 9
1.4 Exiting Setup Mode ..............................................................................................9
1.5 Direct Command Mode ......................................................................................10
1.6 Valve Control Mode ...........................................................................................10
1.7 Valve Travel Limits ..............................................................................................11
1.8 ESD Function ......................................................................................................11
1.9 ESD/Monitor Relay Function ............................................................................... 12
1.10 ESD Trigger Sources ...........................................................................................12
1.11 ESD Delay Time ..................................................................................................13
1.12 Position Control Bandwidth ................................................................................14
1.13 Speed Control Bandwidth ..................................................................................14
1.14 Motor Starter Type .............................................................................................15
1.15 Analog Output Control .......................................................................................15
1.16 Modulation Delay Time ......................................................................................15
1.17 Network Response Delay Time ...........................................................................16
1.18 Torque Retry (Log-Jam) Control ..........................................................................16
1.19 Network Baud Rate ............................................................................................17
1.20 Network Parity ................................................................................................... 18
1.21 Calibrate Analog I/O ...........................................................................................18
1.22 Calibrate Analog Inputs ......................................................................................19
1.23 Calibrate Analog Output ....................................................................................19
1.24 Load Factory Default Calibrate Values ................................................................20
1.25 User Relay #1 Application ...................................................................................20
1.26 User Relay #2 Application ...................................................................................21
1.27 LSA Position Setpoint .........................................................................................22
1.28 LSB Position Setpoint .........................................................................................22
1.29 Anti-water Hammer ...........................................................................................23
1.30 Opening Duty Cycle ON Timer ............................................................................23
1.31 Opening Duty Cycle OFF Timer ...........................................................................24
1.32 Closing Duty Cycle ON Timer .............................................................................. 24
1.33 Closing Duty Cycle OFF Timer ............................................................................. 25
1.34 Write Protect .....................................................................................................26
1.35 Setpoint Tracking ...............................................................................................26
Table of Contents
September 2020
Table of Contents
i
Table of Contents
September 2020
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 2: Modbus Memory Map Reference
2.1 Modbus Function Codes .....................................................................................27
2.2 Input Register Map .............................................................................................27
2.3 Input Register 03 (DCM320B only) .....................................................................28
2.4 Discrete Input Map .............................................................................................28
2.5 Coil Map .............................................................................................................29
2.6 Holding Register Map .........................................................................................30
Section 3: Network Installation Guide
Network Installation Guide ..........................................................................................31
Section 4: System Startup Guide
System Startup Guide ..................................................................................................33
Section 5: Optional Phase Monitor
Optional Phase Monitor ...............................................................................................35
Section 6: Alarm Denitions and Troubleshooting Guide
Alarm Denitions and Troubleshooting Guide ..............................................................37
Section 7: Diagnostic Features of 320B Controlinc M2CP
7.1 High Water Mark Torque Data (Max Torque Prole) ............................................38
7.2 Full Stroke Test (FST) ..........................................................................................39
7.3 Partial Stroke Test (PST) .....................................................................................43
ii
Table of Contents
Preface
DCM320B is an upgrade of DCM320A. It is a t, form, and function replacement for the DCM320A. The DCM320B may be used as a direct replacement of the DCM320A in existing installations. The primary difference is the DIP switch conguration method. The DCM320B provides more range and resolution of most conguration parameters. This handy reference is a guide to help you
get your system up and running quickly. Refer to the wiring diagram supplied with the actuator for detailed wiring information.
The rst section of this guide will help you get your Controlinc actuators hooked-up and set-up correctly. If you need to change conguration of the unit, we recommend using our Windows based DCMLink rather than setting conguration DIP switches
shown in this guide. Setting network station address DIP switches is required. The second section of this manual is the Modbus
memory map reference to help congure your host database. If you are using the Controlinc Network Master, then refer to the
manual supplied with that unit for memory maps. Section three of this manual is a brief system startup guide to help you do things in the proper order to achieve a successful system startup. This last section also covers optional phase monitor module. This document covers Revision F and later revision boards.
!WARNING
Failure to follow instructions for proper electrical wiring, storage, setup, and maintenance may cause serious injury, damage equipment, or void the warranty. Refer to Manual E796 for instructions on storage, electrical hook-up, and maintenance.
Notes
September 2020
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 1: Quick Start Guide
Step 1: Identify network topology
Identify network topology from Figures 2 and 3, and note the ports being used (Ports A,B,C,D).
Refer to page 23 for guidance on network planning and installation.
Step 2: Set network jumpers and switches
If network topology is parallel bus, then remove network termination and bias by turning OFF S1 and S2 of SW4 on the DCM 320B card. Remove jumpers JP1 and JP2 on the CAM05,
if installed. Terminations must be left in the most distant unit on the network. If E>Net is
selected, all ports must be terminated. Baudrate range selection is not required on DCM 320B but is required on CAM05. Refer to Figure 5 for jumper and DIP switch locations.
Step 3: Connect network wiring (Refer to page 23 for guidance)
Wire network ports selected in Step 1. Refer to Figure 4 when wiring Ports A and B on TBM 320A module. Refer to Figure 5 when wiring Ports C and D on the CAM05 module.
Step 4: Connect auxiliary I/O wiring
Section 1: Quick Start Guide
September 2020
Refer to Figure 4 when connecting discrete auxiliary I/O wiring. Note that some functions must
be jumpered between screw terminals if not wired to external contacts. Analog I/O wiring is
connected to the DCM 320B module as shown in Figure 5.
Step 5: Set network station address
Each node (valve actuator) on the network must have a unique station address. Locate DIP switch SW1 on the DCM 320B card shown in Figure 5. Locate the desired station address on pages 7 and 8. Set the DIP switches of SW1 to the corresponding pattern shown beside the selected address. Press execute button to store address.
NOTE:
We highly recommend using the windows based DCMLink to congure the actuators. DCMLink
is available at www.emerson.com or your local Actuation Technologies distributor. If using
DCMLink, you may skip step 6 below.
Quick Start Guide
1
Section 1: Quick Start Guide
September 2020
Figure 1 DCMLink Homescreen
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Step 6: Select conguration parameters
The actuator may be congured using the 5 DIP switches of SW2 and 8 DIP switches of SW1. This is a back-up means of conguring the unit if DCMLink is not available. The actuator
is normally shipped with factory default settings. These settings may be changed by the
following procedure. Locate DIP switches SW1, SW2, and Setup Execute Button on the
DCM 320B module shown in Figure 5. Place the Selector Switch in the "OFF" position. Select
the feature or conguration parameter from the conguration tables in this manual. Set
the DIP switches per the corresponding switch pattern and then press the execute button.
If the conguration parameter is valid, the green (setup data good) LED will ash. If error data is entered, the red (setup data error) LED will light until the error is corrected. Repeat
this procedure for each parameter to be revised. Return all 5 DIP switches of SW2 to the OFF position and return the 8 DIP switches of SW1 to the network station address when
conguration is complete. With all SW2 switches OFF and the address switches set, press the execute button to store the network address to nonvolatile conguration memory.
2
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Figure 2 Controlinc Model 320B RS485 Network Topology Options
Single
Multidrop
Bus
Redundant Multidrop
Bus
Single
E>Net
Redundant E>Net
E>Net
Ring
Section 1: Quick Start Guide
September 2020
Redundant
E>Net Ring
Limits: 32 units
4,000 ft
total
Turn OFF
S1 abd S2 of SW4 on
320B card
(except last actuator)
Limits based on EIA standard for RS485 bus networks
Limits: 32 units
4,000 ft
total
Requires
CAM05
module
Turn OFF S1 and S2 of SW4 on DCM320B and
remove JP1 and JP2 on
CAM05 card
Limits: 254 units
5,000 ft
between units or
200 miles
total
Limits: 254 units
5,000 ft
between units or
200 miles
total
Requires
CAM05
module
Limits: 254 units
5,000 ft
between units or
200 miles
total
EIM Network Master required
for ring network topology
E>Net requires network terminations and bias to be asserted at all ports of all series connected E>Net actuators. Networks may be a combination of parallel bus and series E>Net connections. Limit number of parallel connected units to 15 between series connected E>Net units.
Limits: 254 units
5,000 ft
between units or
200 miles
total
Requires
CAM05
module
Quick Start Guide
3
Section 1: Quick Start Guide
September 2020
Figure 3
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Shield
Shield
Bus Network
Jumpers common shield through the network
E>Net
Shield
Shield
4
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Figure 4 TBM 320A Hook-up Diagram
Section 1: Quick Start Guide
September 2020
NOTE:
TBM320A is used with both DCM320A and DCM320B.
Quick Start Guide
5
Section 1: Quick Start Guide
September 2020
Figure 5
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
6
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Figure 6 Conguration Data and Network Station Address (SW1)
Section 1: Quick Start Guide
September 2020
Quick Start Guide
Figure 6 Conguration Data and Network Station Address (SW1) continued.....
7
Section 1: Quick Start Guide
September 2020
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
To store network station address to nonvolatile
conguration memory,
set all SW2 switches to
OFF, set SW1 switches
to the desired address, place selector switch in
OFF position and then
press execute button.
Addresses 0 and 255 are reserved for broadcast. Addresses 254 is reserved on secondary port.
8
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.1 Setup Instructions
The DCM 320B is factory congured as specied by the customer purchase order. If eld setup changes are required, follow setup instructions below. If unsure about setup of a module,
known factory default settings may be reloaded as shown under "Direct Command Mode".
When executed, the module loads known parameters from program memory to EEPROM conguration memory. Default parameters are highlighted in this manual by a box around the
default or the value is listed.
1.2 Entering Setup Mode
Locate DIP switches SW1, SW2, Setup Execute Button and LED indicators on the DCM 320B
(See Figure 5). SW2 switches select mode and SW1 switches select setup parameters and network station address.
1) Record network station address of SW1. These switches must be returned to the same setting before exiting setup.
2) Place selector switch in the OFF position.
3) Select desired setup mode by setting SW2 as indicated on this and following pages.
4) Verify the DCM320B has entered setup mode by a rapid ashing CPU GOOD light.
Section 1: Quick Start Guide
September 2020
1.3 Changing Setup Parameters
The ve switches (S1 - S5) of SW2 select the parameter/mode to be congured. The eight
switches of SW1 (S1 - SB) are used to select desired setup data.
1) Locate the desired setup parameter to be revised on pages 10 through 26.
2) Set the ve switches of SW2 per the switch pattern shown for desired mode.
3) Set SW1 switches as shown or refer to the switches on Figure 6 for desired value. Selected values are multiples of the stated resolution for each parameter.
4) When both SW2 and SW1 switches are set, press the execute button to store the setup parameter to nonvolatile memory.
5) Verify the green LED (setup data good) light ashes. If an invalid enter is made, the red LED (setup data error) light will turn on until the error is corrected.
1.4 Exiting Setup Mode
1) Tum off all ve SW2 switches.
2) Place selector switch in the OFF position.
3) Return SW1 switches to the Network Station Address recorded in Step 1 under "Entering Setup Mode" above.
4) Press the Execute Button.
5) Verify the DCM320B has returned to the normal run mode by a slow ashing CPU GOOD light.
Quick Start Guide
9
Section 1: Quick Start Guide
September 2020
1.5 Direct Command Mode
SW2
All SW2 switches OFF. Normal run mode. Return all SW2 switches to this position after setup.
SW2
S1 ON = Direct Command Mode. Select the desired command by setting SW1 switches as follows.
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
SW1
SW1
SW1
S1 ON = Reload Factory Defaults. Loads default settings as listed or designated by rectangle around description under each setup mode parameter in this manual.
S2 ON = Reset passcode protection.
S1, S2 ON = Archive Torque Prole. Stores torque prole to
EEPROM for later retrieval by host computer.
1.6 Valve Control Mode
(Setpoint Source)
SW2
S2 ON = Valve Control Modes. Select the desired control mode by setting SW1 switches as follows.
SW1
All SW1 switches OFF = Remote Host Control.
Host may write Setpoint or Open, Stop, Close.
Required by F.Fieldbus for modulating control.
SW1
SW1
S1 ON = Control from AIN1 (Torque Analog Input). Position control with Potentionmeter or 0 - 5 V signal connected to P3.
S2 ON = Control from AIN2 (User Analog Input #1). Position control with 4 - 20 mA signal connected to P4-2.
SW1
S1, S2 ON = Control from AIN3 (User Analog Input #2). Position control with 4 - 20 mA signal connected to P4-4.
SW1
S3 ON = Block Valve Control Mode. Required by Foundation Fieldbus for discrete control mode.
SW1
S1, S3 ON = Pulse Input Control Mode. 24 V DC discrete control
wired to User Input #1 (OPEN) and User Input #2 (CLOSE).
10
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.7 Valve Travel Limits
SW2
S1, S2 ON = Valve Travel Limits Mode.
SW1
All switches OFF = Open and Close Position Limits. Open to LSO and Close to LSC.
SW1
S1 ON = Enable close valve torque seat. Open to LSO and Close to TSC.
SW1
S2 ON = Enable torque backseat. Open to TSO and Close to LSC.
SW1
S1, S2 ON = Enable close torque seat and torque backseat.
Open to TSO and Close to TSC.
Section 1: Quick Start Guide
September 2020
1.8 ESD Function
SW2
S4 ON, Select ESD Function setup mode.
SW1
SW1
SW1
SW1
SW1
SW1
All SW1 switches OFF. Stay-Put (Stop) and do not operate ESD relay. Factory default.
S1 ON, Go closed on ESD and do not
operate ESD relay.
S2 ON, Go open on ESD and do not
operate ESD relay.
S1, S2 ON, Go closed on ESD and operate ESD relay.
S3 ON, Go open on ESD and operate ESD relay.
S1, S3 ON, Stay-Put and operate ESD relay.
Do not operate close or open outputs.
Quick Start Guide
11
Section 1: Quick Start Guide
September 2020
1.9 ESD/Monitor Relay Function
SW2
S2, S3 ON, Select ESD/Monitor Relay Function.
SW1
All SW1 switches OFF. Deactivate relay when an alarm is detected.
SW1
S1 ON, Activate relay when software
based ESD is detected.
SW1
S2 ON, Activate relay on command from
remote network host. Factory default.
1.10 ESD Trigger Sources
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
NOTE:
At least one source must be selected, or ESD is disabled.
S1, S4 ON, Select ESD Trigger setup mode.
SW1
All SW1 switches OFF. Disable ESD.
SW1
S1 ON, Enable ESD on command
from network host. Factory default.
SW1
S2 ON, Enable ESD Relay control on local
ESD discrete input.
SW1
S1, S2 ON, Enable ESD on command from host and En­able ESD Relay control on local ESD discrete input.
SW1
S3 ON, Enable ESD on loss of communications
from host.
SW1
SW1
SW1
S1, S3 ON, Enable ESD on loss of command
from network host and Enable ESD on loss of communications from host.
S2, S3 ON, Enable ESD Relay control on local
ESD discrete input and Enable ESD on loss of communications from network host.
S1, S2, S3 ON, Enable ESD on command from network
host. Enable ESD Relay control on local ESD input and Enable ESD on loss of communications from the host.
12
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.11 ESD Delay Time
SW2
S1, S2, S4 ON, Select ESD delay setup mode.
Select delay time by setting SW1 switches as shown on Figure 6.
Range = 0 to 60 seconds Resolution = 1 second Default = 0
Example: Set ESD delay time to 30 seconds.
SW1
Locate the DIP switch pattern for 30 on Figure 6.
NOTE:
ESD Delay Time applies only to software generated ESD and not to the hardwired local ESD input.
Section 1: Quick Start Guide
September 2020
Notes on hardwired Local Inhibit/ESD:
1) Local ESD is a hardwired closed loop circuit wired to TBM tenninals 27 (+) and 28 (-) using either an external 24 V DC power supply or the internal 24 V DC power available at tenninals 26 (+) and 29 (-). See Figure 4.
2) Local ESD will inhibit control from the DCM320B module, local push buttons and
selector switch. To force valve closed on local ESD, insert jumper between terminals 9 and 10. To force valve open on local ESD, insert jumper between terminals 8 and 9. Actuator will Stop (Stay-Put) if no jumpers are inserted between terminals 8-9 or 9-10.
3) To override motor thermal contacts during local ESD, insert jumper between terminals XO and 53.
WARNING:
!
Do not override thermals in a hazardous area.
4) Software activated ESD can activate Local ESD by wiring N.C. contacts of ESD/Monitor relay (terminals 32 and 33) in series with Local lnhibit/ESD inputs at terminals 27 and 28.
Quick Start Guide
13
Section 1: Quick Start Guide
September 2020
1.12 Position Control Bandwidth
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
SW2
Example: Set control bandwidth to 2.5%.
S3, S4 ON, Select position control bandwidth
(Deadband) setup mode.
Select bandwidth by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0.1% to 5.0% (0 - 50) Resolution = 0.1% Default = 1.0%
SW1
Locate the DIP switch pattern for 25 on Figure 6,
i.e. 2.5 x 0.1% resolution = 2.5%.
1.13 Speed Control Bandwidth
SW2
S1, S3, S4 ON, Select speed control bandwidth
setup mode.
Select bandwidth by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0.3% to 10.0% (3 - 100) Resolution = 0.1% Default = 3.0%
Example: Set speed control bandwidth to 5%.
SW1
Locate the DIP switch pattern for 50 on Figure 6,
i.e. 50 x 0.1% resolution = 5.0%.
NOTE:
Speed control bandwidth is meaningful only when a VFD motor starter is used. Speed control bandwidth must be greater than position control bandwidth.
14
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.14 Motor Starter Type
SW2
S1, S2, S3 ON, Select type of motor starter installed.
Select motor started type by setting SW1 switches.
SW1
All SW1 switches OFF. Enable Electro-mechanical motor starter. Factory Default.
SW1
S1 ON, Enable Solid-State Relay (SSR)
motor starter type.
SW1
S2 ON, Enable Variable Frequency Drive (VDF)
motor starter type.
1.15 Analog Output Control
Section 1: Quick Start Guide
September 2020
SW2
S3 ON, Select source for analog output. Select AO#1 source by setting SW1 switches.
SW1
SW1
All SW1 switches OFF. Enable Network Host control of analog output AO#1. Factory default.
S1 ON, Enable Position Feedback
control of analog output AO#1.
1.16 Modulation Delay Time
SW2
S2, S3, S4 ON = Modulation Delay Timer Mode.
Select delay time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 25.5 seconds (0 - 255) Resolution = 0.1 second Default = 0.1 second
Example: Set modulation delay time to 6 seconds.
Quick Start Guide
SW1
Locate the DIP switch pattern for 60 on Figure 6,
i.e. 60 x 0.1 second resolution = 6.0 seconds
15
Section 1: Quick Start Guide
September 2020
1.17 Network Response Delay Time
1.17.1 Primary Network Ports A and B
SW2
S1, S2, S3, S4 ON, Select Ports A and B response
delay mode.
Select delay time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 8 to 60 mS (8 - 60) Resolution = 1 mS Default = 8 mS
Example: Set response delay to 15 mS.
SW1
Locate the DIP switch pattern for 15 on Figure 6.
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.17.2 Secondary Network Ports C and D
SW2
S5 ON, Select Ports C and D response delay mode.
Select delay time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 8 to 60 mS (8 - 60) Resolution = 1 mS Default = 8 mS
1.18 Torque Retry (Log-Jam) Control
SW2
S1, S3 ON, Select Close Torque (Log-Jam) function.
SW1
All SW1 switches OFF. Disable close torque retry (Log-Jam) funstion. Factory default.
SW1
S1 ON. Enable close torque retry (Log-Jam) function.
16
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.19 Network Baud Rate
1.19.1 Primary Network Ports A and B
Section 1: Quick Start Guide
September 2020
SW2
S1, S5 ON. Select baud rate for primary network ports A and B.
Select baud rate by setting SW1 switches as shown below. Default = 9600.
1.19.2 Secondary Network Ports C and D
SW2
SW1 SW1
SW1 SW1
SW1 SW1
S2, S5 ON. Select baud rate for secondary network ports C and D.
Select baud rate by setting SW1 switches as shown below. Default = 19200.
All OFF = 1200
S1 = 2400
S2 = 4800 S1, 3 = 38400
S1, 2 = 9600
S3 = 1900
Quick Start Guide
17
Section 1: Quick Start Guide
September 2020
1.20 Network Parity
1.20.1 Primary Network Ports A and B
SW2
S1, 2, 5 ON. Select parity for primary network. Select parity by setting SW1 switches as shown below.
1.20.2 Secondary Network Ports C and D
SW2
S1, 2, 5 ON. Select parity for secondary network. Select parity by setting SW1 switches as shown below.
SW1
SW1
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
All SW1 switches OFF = No parity
S1 = Even parity
SW1
S2 = Odd parity
1.21 Calibrate Analog I/O
SW2
S1, 3, 5 ON. Select analog input and ouput calibration mode.
Set SW1 to select the desired analog input or output calibration,
apply calibration current to input or connect 4 - 20 mA meter to output and then press execute button.
18
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.22 Calibrate Analog Inputs
SW1
S2 ON, Set Torque analog input Zero.
Input zero offset resistance/voltage.
SW1
S1, 2 ON, Set Torque analog input Span.
Input full scale resistance/voltage.
SW1
S2, 3 ON, Set User #1 analog input Zero.
Input 4 mA offset current.
SW1
S1, 2, 3 ON, Set User #1 analog input Span.
Input 20 mA full scale current.
SW1
S2, 4 ON, Set User #2 analog input Zero.
Input 4 mA offset current.
SW1
S1, 2, 4 ON, Set User #2 analog input Span.
Input 20 mA full scale current.
Section 1: Quick Start Guide
September 2020
1.23 Calibrate Analog Output
SW1
S2, 3, 4 ON, Increase zero analog output at AO#1
while the Execute button is pressed.
SW1
S1, 2, 3, 4 ON, Decrease zero analog output at AO#1
while the Execute button is pressed.
SW1
S5 ON, Increase full scale analog output at AO#1
while the Execute button is pressed.
SW1
S1, 5 ON, Decrease full scale analog output at AO#1
while the Execute button is pressed.
Quick Start Guide
19
Section 1: Quick Start Guide
September 2020
1.24 Load Factory Default Calibrate Values
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
SW1
All OFF. Torque
input Zero.
SW1
S3 ON, User AIN#1 Zero.
SW1
S4 ON, User AIN#2 Zero.
SW1
S3, 4 ON, Analog Out Zero.
SW1
S2, 5 ON, Load factory default calibration values for all analog inputs and outputs for both Zero and Span.
SW1
SW1
SW1
SW1
S1 ON, Tprque
input Span.
S1, 3 ON, User
AIN#1 Span.
S1, 4 ON, User
AIN#1 Span.
S1, 3, 4 ON,
Analog Out Span.
1.25 User Relay #1 Application
SW2
SW1
SW1
SW1
SW1
SW1
SW1
SW1
SW1
SW1
SW1
S2, S3, S5 ON, Select User Relay#1 setup mode.
Select user relay#1 function by setting SW1 switches as shown below.
All SW1 switches OFF, Direct control of N.O
relay from network master. Factory default.
S1 ON, Activate normally open (N.O) relay
when Selector Switch in Remote position.
S2 ON, Activate normally open (N.O) relay
when Selector Switch in Local position.
S1, S2 ON, Activate normally open (N.O) relay at LSA limit setpoint, if LSA position congured.
S3 ON, Activate normally open (N.O)
relay when any ESD is active.
S1, S3 ON, Direct control of normally closed (N.C)
contact from network master.
S2, S3 ON, Activate normally closed (N.C) relay
when Selector switch in Remote position.
S1, S2, S3 ON, Activate normally closed (N.C) relay
when Selector switch in Local position.
S4 ON, Activate normally closed (N.C) relay at LSA limit setpoint, if LSA position congured.
S3 ON, Activate normally closed (N.C) relay
when any ESD is active.
20
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.26 User Relay #2 Application
Section 1: Quick Start Guide
September 2020
SW2
SW1
SW1
SW1
SW1
SW1
SW1
SW1
SW1
SW1
SW1
S1, S2, S3, S5 ON, Select User Relay#2 setup mode.
Select user relay#1 function by setting SW1 switches as shown below.
All SW1 switches OFF, Direct control of N.O
relay from network master. Factory default.
S1 ON, Activate normally open (N.O) relay
when Selector Switch in Remote position.
S2 ON, Activate normally open (N.O) relay
when Selector Switch in Local position.
S1, S2 ON, Activate normally open (N.O) relay at LSB limit setpoint, if LSB position congured.
S3 ON, Activate normally open (N.O)
relay when any ESD is active.
S1, S3 ON, Direct control of normally closed (N.C)
contact from network master.
S2, S3 ON, Activate normally closed (N.C) relay
when Selector switch in Remote position.
S1, S2, S3 ON, Activate normally closed (N.C) relay
when Selector switch in Local position.
S4 ON, Activate normally closed (N.C) relay at LSB limit setpoint, if LSB position congured.
S3 ON, Activate normally closed (N.C) relay
when any ESD is active.
Quick Start Guide
NOTE:
User Relay #1 and User Relay #2 are non-latching SPST type. When power to the actuator is lost,
both relays are de-energized and the contacts will open. Do not apply these relays to critical control applications where closed contacts are required during loss of power.
21
Section 1: Quick Start Guide
September 2020
1.27 LSA Position Setpoint
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
SW2
Example: Set LSA position to 30%.
SW1
S4, 5 ON, Select LSA position setup mode.
Select LSA by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 100% Resolution = 1% Default = 0 (LSA disabled)
Locate the DIP switch pattern for 30 on Figure 6.
1.28 LSB Position Setpoint
SW2
Example: Set LSB position to 60%.
S2, 4, 5 ON, Select LSB position setup mode.
Select LSB by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 100% Resolution = 1% Default = 0 (LSB disabled)
SW1
Locate the DIP switch pattern for 60 on Figure 6.
22
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.29 Anti-water Hammer
SW2
S2, 4, 5 ON, Select anti-water hammer setup mode.
Select anti-water hammer position by setting SW1 switches as shown on Figure 6. (see example below). This is the position that anti-water hammer is activated while the valve is closing.
Range = 0 to 100% Resolution = 1% Default = 0 (anti-water hammer disabled)
Example: Set Anti-water hammer position to 10%.
SW1
Locate the DIP switch pattern for 10 on Figure 6.
1.30 Opening Duty Cycle ON Timer
Section 1: Quick Start Guide
September 2020
SW2
Example: Set Anti-water hammer position to 10%.
SW1
S1, 3, 4, 5 ON, Select opening duty cycle ON timer.
Select opening ON time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 65 seconds Resolution = 1 second Default = 0 (Timer disabled)
Locate the DIP switch pattern for 6 on Figure 6.
Quick Start Guide
23
Section 1: Quick Start Guide
September 2020
1.31 Opening Duty Cycle OFF Timer
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
SW2
Example: Set opening OFF timer to 9 seconds.
SW1
S2, 3, 4, 5 ON, Select opening duty cycle OFF timer.
Select opening OFF time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 65 seconds Resolution = 1 second Default = 0 (Timer disabled)
Locate the DIP switch pattern for 9 on Figure 6.
1.32 Closing Duty Cycle ON Timer
SW2
Example: Set closing ON timer to 6 seconds.
SW1
S1, 2, 4, 5 ON, Select closing duty cycle ON timer.
Select closing ON time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 65 seconds Resolution = 1 second Default = 0 (Timer disabled)
Locate the DIP switch pattern for 9 on Figure 6.
24
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
1.33 Closing Duty Cycle OFF Timer
Section 1: Quick Start Guide
September 2020
SW2
Example: Set closing OFF timer to 9 seconds.
S3, 4, 5 ON, Select closing duty cycle OFF timer.
Select closing OFF time by setting SW1 switches as shown on Figure 6. (see example below).
Range = 0 to 65 seconds Resolution = 1 second Default = 0 (Timer disabled)
SW1
Locate the DIP switch pattern for 9 on Figure 6.
NOTE:
Duty cycle timers are active only when selector switch is in REMOTE position. Opening and
closing speed of the valve may be adjusted (slowed) by enabling the opening or closing duty
cycle timers. Duty cycle timers are available only with a solid-state or VFD starter. Anti-water hammer duty cycle is is xed at 50% duty with one second ON time and one second OFF time for SSR and VFD starters and two seconds ON time and two seconds OFF time for
electro-mechanical starter. When activated, the Anti-water hammer function overrides the
closing duty cycle timer. If duty cycle or Anti-water hammer functions are used in any Anti
water hammer scheme, ElM must be advised of system parameters and conditions.
Quick Start Guide
25
Section 1: Quick Start Guide
September 2020
1.34 Write Protect
Prevent conguration changes through network CAM connection when write protect is
enabled. Requirement for Foundation Fieldbus and Hart. Modbus communication will not be
affected. Register 12 Bit 5 is to be dened as Write Protect.
To Enable Select Write Protect:
SW2
S2, 4 ON
SW1
Locate the DIP switch pattern for 10 in Figure 6
To Disable Write Protect:
SW2
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
S2, 4 ON
SW1
Locate the DIP switch pattern for 37 in Figure 6
1.35 Setpoint Tracking
To Enable Setpoint Tracking:
SW2
S2, 4 ON
SW1
Locate the DIP switch pattern for 26 in Figure 6
To Disable Setpoint Tracking:
SW2
S2, 4 ON
SW1
Locate the DIP switch pattern for 53 in Figure 6
26
Quick Start Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 2: Modbus Memory Map Reference
September 2020
Section 2: Modbus Memory Map Reference
2.1 Modbus Function Codes
Host beginning
register 01 Read Coil Status 00001 02 Read Input Status 10001 03 Read Holding Register 40001 04 Read Input Register 30001 05 Force Single Coil 00001 06 Preset Single Register 40001 07 Read Exception Status 08 Loopback Diagnostic Test 15 Force Multiple Coils 00001 16 Preset Multiple Registers 40001 17 Report Slave I.D.
NOTE:
All registers are zero based. Add one to inputs, coils or holding registers when conguring host
database. See host beginning registers above.
2.2 Input Register Map
(Use function code 04) 00 Inputs 0-15 (Live discrete inputs) 01 Inputs 16-31 (Standard valve status) 02 Inputs 32-47 (DCM320 valve status) 03 Inputs 48-63 (Specic to DCM320B)
Modbus Memory Map Reference
27
Section 2: Modbus Memory Map Reference
September 2020
2.2 Input Register 03 (DCM320B only)
48 DCM is in Setup Mode 49 AIN1 Signal fault 50 AIN2 Signal fault 51 AIN3 Signal fault 52 Software triggered ESD active 53-63 Reserved inputs (always zero)
2.4 Discrete Input Map
(Inputs 0 through 15 are hardware inputs)
(use function code 02) 00 Open limit switch (LSO) 27 Phase monitor alarm 01 Close limit switch (LSC) 28 Local ESD alarm 02 Contactor Aux. open contact 29 Actuator fail alarm 03 Contactor Aux. close contact 30 No input (always zero) 04 Selector switch Local/Manual 31 Unit alarm (above alarms OR'ed) 05 Selector switch Remote/Auto 32 Open limit switch (LSO) 06 Open torque switch (TSO) 33 Close limit switch (LSC) 07 Close torque switch (TSC) 34 Stopped (valve stopped in mid travel) 08 Power monitor alarm 35 Opening (valve moving open) 09 Motor thermal overload 36 Closing (valve moving close) 10 Phase monitor 37 Valve stall alarm (valve not moving) 11 Local ESD alarm 38 Selector switch in Local/Manual 12 Aux. alarm input (VFD fault) 39 Unit alarm (alarms OR'ed) 13 User discrete input #1 40 Motor thermal overload alarm 14 User discrete input #2 41 Power monitor alarm 15 Reserved 42 Primary network alarm 16 Open limit switch (LSO) 43 Secondary network alarm 17 Close limit switch (LSC) 44 Open torque alarm (TSO) 18
Opening (valve moving open)
19
Closing (valve moving close)
20
Selector switch Local/Manual
21
Selector switch Remote/Auto
22
Open torque switch (TSO)
23
Close torque switch (TSC)
24
Valve stall alarm (valve not moving)
25 Power monitor alarm 52 ESD active alarm 26 Motor thermal overload alarm 53 EEPROM active cong
45 Close torque alarm (TSC) 46 Local ESD input alarm 47 Phase monitor alarm 48 RESERVED 49 Torque out of range 50 AIN1 out of range 51 AIN2 out of range
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
28
Modbus Memory Map Reference
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
2.5 Coil Map
(Coils 0 through 7 are hardware outputs)
(use function code 01, 05 and 15)
00 Close motor starter output 43 Enable Stop on ESD with ESD relay 01 Open motor starter output 44 Enable ESD trigger from host 02 Solid-state relay NFC speed control 45 Enable ESD trigger on local ESD input 03 ESD/Monitor relay output 46 Enable ESD trigger from loss of com. 04 User relay #I/Override relay 47 Conguration conict error detected 05 User relay #2 48 Select AIN1 as setpoint source 06 Primary network channel 1 enable 49 Select AIN2 as setpoint source 07 Secondary network channel 2 enable 50 Select AIN3 as setpoint source 08 Host OPEN valve command 51 Move to Default on AIN1 fault 09 Host STOP command 52 Move to Default on AIN2 fault 10 Host CLOSE valve command 53 Move to Default on AIN3 fault 11 Host ESD command 54 reserved 12 Enable normal modulating mode 55 Enable setpoint tracking 13 reserved 56 reserved 14 Enable VFD starter control mode 57 Select N.C. contacts for Relay #1 15 Enable pulse control mode 58 Enable Relay #1 as Override on ESD 16 Open limit switch status (LSO) 59 Activate Relay #1 in Remote/Auto 17 Close limit switch status (LSC) 60 Activate Relay #1 in Local/Manual 18 Opening status (valve moving open) 61 Activate Relay #1 at LSA setpoint 19 Closing status (valve moving close) 62 Select N.C. contacts for Relay #2 20 Selector switch Local/Manual 63 Enable Relay #2 as Override on ESD 21 Selector switch Remote/Auto 64 Activate Relay #2 in Remote/Auto 22 Open torque alarm (TSO) 65 Activate Relay #2 in Local/Manual 23 Close torque alarm (TSC) 66 Activate Relay #2 at LSB setpoint 24 Valve stall alarm (valve not moving) 67 Set primary network to odd parity 25 Power monitor alarm 68 Set primary network to even parity 26 Motor overload alarm (Motor thermal) 69 Set secondary net to odd parity 27 Phase monitor alarm 70 Set secondary net to even parity 28 Local ESD alarm 71 Enable primary network alarm 29 Actuator fail alarm 72 Enable secondary network alarm 30 reserved for host (always zero) 73 reserved 31 Unit alarm (all alarms OR'ed) 74 reserved 32 Enable torque seat mode 75 Enable MRTU operating mode 33 Enable logjam retry mode 76 Enable torque backseat 34 Enable 4-20mA feedback at A0#1 77 Save torque prole to EEPROM 35 Enable monitor relay, else ESD relay 78 CPU has reset 36 Enable passcode protection 79 Load factory default conguration 37 Enable solid-state starter contol mode 80 Write protect 38 reserved 81 Setup mode
39 Enable Close on ESD w/o ESD relay 100 Host OPEN valve command 40 Enable Open on ESD w/o ESD relay 101 Host CLOSE valve command 41 Enable Close on ESD with ESD relay 102 Host STOP command
42 Enable Open on ESD with ESD relay 103 Host ESD command
Section 2: Modbus Memory Map Reference
September 2020
Modbus Memory Map Reference
29
Section 2: Modbus Memory Map Reference
September 2020
2.6 Holding Register Map
(RO = Read Only RW = Read/Write)
(Use function 03, 06 and 16)
00 RW Coils 0-15 42 RW Passcode char 1(LSB) and 2(MSB)
01 RO Coils 16-31 43 RW Passcode char 3(LSB) and 4(MSB)
02 RW Coils 32-47 44 RO Firmware version
03 RW Coils 48-63 45 RO Compatibility number
04 RW Coils 64-79 46 reserved
05 RO Inputs 0-15 47 reserved
06 RO Inputs 16-31 48 RO Torque@ 10% valve position
07 RO Valve Position 1.0% increments 49 RO Torque@ 20% valve position
08 RO Valve Status inputs 32-47 50 RO Torque@ 30% valve position
09 RO Valve Status inputs 16-31 51 RO Torque@ 40% valve position
10 RW Analog Output (0-4095) 52 RO Torque@ 50% valve position
11 RW Valve Position Setpoint (0-4095) 53 RO Torque@ 60% valve position
12 RO Inputs 48-63 54 RO Torque@ 70% valve position
13 RO Valve Position (0.1% increments) 55 RO Torque@ 80% valve position
14 RO Position Analog Input (0-4095) 56 RO Torque@ 90% valve position
15 RO Torque Analog Input (0-4095) 57 RO Torque prole @ 10%
16 RO User Analog Input #1 (0-4095) 58 RO Torque prole @ 20%
17 RO User Analog Input #2 (0-4095 59 RO Torque prole @ 30%
18 RW Water Hammer setpoint (1-20%) 60 RO Torque prole @ 40%
19 RW Modulation delay (0.1-25.5 sec) 61 RO Torque prole @ 50%
20 RW ESD Delay timer (0-65.5 sec) 62 RO Torque prole @ 60%
21 RW Position Bandwidth (0.1-5.0%) 63 RO Torque prole @ 70%
22 RW Speed Bandwidth (0.5-10%) 64 RO Torque prole @ 80%
23 RW Default Position Setpoint (0-4095) 65 RO Torque prole @ 90%
24 RW Torque AIN Zero offset, raw cnts 66 RW Accumulator #1 (User Input #1)
25 RW Torque AIN Span, raw AID counts 67 RW Accumulator #1 (User Input #2)
26 RW User AIN1 Zero offset, raw counts 68 RW Lost COM ESD delay (mS)
27 RW User AIN1 Span, raw AID counts 69 RW Stall time delay (mS)
28 RW User AIN2 Zero offset, raw counts 70 RW RW Valve Travel Time/1% (mS)
29 RW User AIN2 Span, raw AID counts 100 RO RO Unit I.D.
30 RW A0#1 Zero offset, raw counts
31 RW A0#1 Span, raw D/A counts
32 RW LSA Setpoint (0-4095)
33 RW LSB Setpoint (0-4095)
34 RW Close ON duty cycle (0-65.5 sec)
35 RW Close OFF duty cycle (0-65.5 sec)
36 RW Open ON duty cycle (0-65.5 sec)
37 RW Open OFF duty cycle (0-65.5 sec)
38 RW Primary network baudrate
39 RW Primary network response delay
40 RW Secondary network baudrate
41 RW Secondary network response dela
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
NOTE:
1) Unless otherwise specied, analog I/O is
unsigned integer in range of 0-4095.
2) All time parameters are in mS.
3) Torque readings are raw AID counts.
4 ) T o r q u e p r o  l e v a l u e s a r e r e a d f r o m E E P R O M .
5) Do not write to reserved registers.
30
Modbus Memory Map Reference
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 3: Network Installation Guide
Section 3: Network Installation Guide
Step 1: Plan the network topology
Before connecting actuators, the entire network layout should be planned. Select desired
network topology from Figures 2 and 3. Topologies may be bus or E>Net or a combination of bus and E>Net. All networks may be redundant or ring or redundant rings. Limit the number of parallel connected bus units to 15 between E>Net units. Network planning should include
node addressing, wire routing, terminations, and grounding.
Step 2: Select network cable
Ensure correct cable is being used. Networks require twisted pair and shielded cable with a characteristic impedance between 50 and 120 Ohms. Capacitance between conductors must be less than 30 pF/ft (98 pF/m); 10-15 pF/ft is ideal. Shielding may be aluminum foil with drain
wire. Only cables with stranded conductors are recommended. Insulating and outer jacket
materials must be selected for the application environment. Following are acceptable Belden or equivalent cables for most network applications.
September 2020
24AWG
9841, 12.8 pF/ft
22AWG
8761, 24 pF/ft
20AWG
8762, 27 pF/ft
18AWG
8760, 24 pF/ft
16AWG
8719, 23 pF/ft
14AWG
8720, 24 pF/ft
8162, 9729, and 9842 are 24AWG, 2-pair cables with <13 pF/ft
Step 3: Route cable away from electrical interference
Network cables should enter the electrical enclosure at the bottom or lowest point near the
transformer end. Route cable around the transformer end, normally in a counter clockwise
direction to the top side of the TBM. Never install network cable in the same conduit with power conductors. Never route network cable through the high voltage contactor area. The cable should never lie across the TBM or hinder the protective cover of the TBM. Always use the shortest distance and keep excess cable to a minimum; 6" typical.
Network Installation Guide
31
Section 3: Network Installation Guide
September 2020
Step 4: Observe polarity and network grounding
Each network connection is polarized + and - on wiring diagrams. Always use consistency in wiring and the use of wire colors to track polarity. The cable shield or drain wire must be connected to the designated (SH) terminal at each port of each actuator. The shield must be
connected to earth ground at only one point. Some networks may require a jumper between
shield connections (Terminals 22 and 23) of each actuator to carry the shield through the network. The shield connection of each actuator is isolated from earth. Do not allow the shield to touch circuits on the TBM or the metal enclosure. Use plastic electrical tape or heat shrink tubing to isolate the shield or drain wire.
Step 5: Wire preparation and connections
Screw terminals of the TBM have wire clamps that accept wires without terminals but may be applied if desired. Strip insulation back 3/8" when connecting directly to the TBM screw terminals. Do not allow wire clippings to fall on the TBM or into the actuator enclosure. Protect conductors and the shield or drain wire to prevent contact with the TBM. Use plastic electrical tape or heat shrink tubing to prevent bare conductors from contacting other circuits or earth ground.
Step 6: Wire preparation and connections
Use DCMLink or Controlinc Pocket Technician to test the network prior to connecting to a host or network master. The DCMLink is a Windows application that will run on a laptop using an RS232 to RS485 adapter or the Network Interface Unit (NIU) for connecting to the network.
After all actuators are veried to operate in Local mode, test each actuator to verify all network
connections and each actuator operates via the network in Remote mode.
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
32
Network Installation Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 4: System Startup Guide
Step 1: Set position and torque limit switches
Set open and close position and torque switches while operating valve full open and close with local push buttons. Refer to Manual E796 for limit switch setting instructions.
Step 2: Set DIP switches
Set address DIP switches to unique address as shown in the rst section of this guide. Refer to
Figure 5 for location of DIP switches. Refer to network station address switch settings on Figure 6. Also remember to check baud rate of each actuator to ensure it matches the host system.
Step 3: Check network wiring
Check polarity of each network connection per wiring connections shown in Figure 3 of this guide. Ensure shield is connected at each actuator and is earth grounded at only one point. Refer to page 26 for additional instructions on network installation.
Step 4: Check network terminations
Bus networks require termination resistance and bias at each end of the network. Remove
termination and bias on all modules except the last, most distant unit at the end of the
network. Always leave termination and bias on every unit when using E>Net. See Figure 4 for
location of DIP switches and jumpers for termination and bias selection. Verify quiescent line
bias is 250mV minimum during no communication activity.
Section 4: System Startup Guide
September 2020
Step 5: Test network
Use DCMLink software to test each actuator. Ensure each station address is tested and verify received data. View communication signals with oscilloscope to ensure good signal strength and clean waveforms. Repeat test for each actuator on redundant network if installed.
System Startup Guide
33
Section 4: System Startup Guide
September 2020
Step 6: Verify network master conguration
If using the Controlinc Network Master, refer to the User Manual supplied with the system for setup details. If direct connecting to your DCS, SCADA, or PLC system, refer to the
manufacturer's supplied documentation. Verify network baud rate and parity match the
settings of the actuators. Verify the master is congured for the total number of actuators
and database matches network address assignments per actuator location on network. Take
system out of test or diagnostic mode when nished.
Step 7: Test host interface
If using the Controlinc Network Master, use Modbus host test software supplied with the system to test slave port(s) of the network master. If direct connect to other host equipment,
use software supplied with that equipment to test actuators. Verify database for each node and I/O point by tag name and mapping of each point to operator's screen. Operate each valve open and close or to setpoint. Test each auxilliary I/O point.
Tools:
1) Speed handle or 3/8" battery drill with 1/2" thin wall socket
2) Common screwdriver
3) Multimeter (VOM)
4) Portable oscilloscope (optional)
5) Laptop computer with Windows
6) DCMLink w/ RS485 adapter
7) Other system test software supplied with host system
8) Programming cables
9) 4-20mA calibrator for analog I/O
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
34
System Startup Guide
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 5: Optional Phase Monitor
Section 5: Optional Phase Monitor
If your actuator contains the optional phase monitor, then this section applies.
The phase monitor module shown in Figure 7 is mounted on the back side of the DCM 320B module facing the motor starter.
Figure 7
Correct phase and voltage
Phase are out of sequence
Loss of phase or low voltage on one phase
YEL
GRN
RED
September 2020
P/N 84137
Optional Phase Monitor
35
Section 5: Optional Phase Monitor
September 2020
NOTE:
We advise using phase sentry mode rather than phase correction.
Phase sentry mode will cause the actuator to shut down if phases are out of sequence for proper electric motor rotation or a loss of phase is detected. Phase correction mode will cause the actuator to correct the phase sequence and continue to operate when phases are out of sequence. Either mode will cause the actuator to shut down if a loss of phase (single-phasing) is detected.
To select modes, do the following:
1) Remove TBM 320A termination panel.
2) Locate 3-pin jumper P9 on bottom of board marked PC and PS.
PC means Phase Correction.
PS means Phase Sentry.
3) Move the shorting strap to the desired mode selection (PC or PS).
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
36
Optional Phase Monitor
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 6: Alarm Denitions and Troubleshooting Guide
Section 6: Alarm Denitions and
Troubleshooting Guide
Table 1.
Alarm Denition / explanation Actions to be taken
Open Torque Alarm
Close Torque Alarm
Valve Stall Alarm
Power Monitor Alarm
Motor Thermal Overload
Phase Monitor Alarm
Hardwired - ESD Alarm
Actuator Fail Alarm
Com No-Response
Alarm
Unit Alarm
Actuator exceeded open torque limit setting
Actuator exceeded close torque imit setting
No actuator movement or position feedback after 8 seconds upon a commanded movement
Indicates lost control voltage, or lost power, or lost phas
(if supplied with a Phase Sentry Module)
Protects motor windings from increased internal temperature rise when under increased load or duty cycle.
Indicates the condition of the three-phase primary power supply. Can detect lost phase or incorrect phase.
External hardwired circuit is activated on an open circuit. Local ESD overrides other commands based on
conguration to Open, Close or Stay
Put when there is Emergency Shut Down (ESD) trigger or loose/missing ESD Inhibit Jumpers on the Terminal Board Terminals.
Indicates Conguration Error or
control circuit connection is when a
conguration parameter out of range
Indicates there is no communication from the actuator to the host via Modbus RS485 Network.
Universal Alarm indicating actuator has experienced an event; or any of
the control or conguration alarms
noted above except Lost Communications.
Check torque switch dial setting for open torque limit and proper orientation of Torque Switch Rotor Assembly Cams
Check torque switch dial setting for close torque limit and proper orientation of Torque Switch Rotor Assembly Cams
Check wire leads for potentiometer connection to P2 of DCM 320B module.
RED Lead to Bottom (Pin 3)
Check for proper potentiometer movement
Check for complete control circuit for commanded action
Check for correct Selector Switch position
Verify DCM320B is not in conguration mode
Check motor thermals
Check primary and secondary fuses
Verify primary power is present
Check for open circuit between terminals 1 and X0 if motor thermal leads are connected
Check incoming primary power source.
Check transformer
Check Contactor to see the right power source are present
Check if TBM jumpers on terminal 26 to 27 and 28 to 29 are present. If connected, check external ESD
trigger circuit for closed connection.
Check actuator conguration parameter and make they are correct to their specications.
Check network connection, polarity, parity, baud rate, and modbus address
Check for active DCM320B (LEDs D1-D5)
Check that DCM320B Conguration Dipswitches are in the Run Mode
Check for other alarm conditions and resolve as necessary.
September 2020
Alarm Denitions and Troubleshooting Guide
37
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
QSG-01-10-93-0014-EN Rev. 1
Section 7: Diagnostic Features of 320B
Controlinc M2CP
7.1 High Water Mark Torque Data (Max Torque Prole)
Design Notes for the High-Water Mark Torque Data (HWMTD) on the 320B Controlinc Electronics for M2CP actuators.
7.1.1 Test Conditions
Firmware will update HWMTD continuously and not only after PST or FST.
Firmware will update HWMTD when actuator is in Remote or Local and is travelling in
open or close direction.
7.1.2 Test Description
1) Firmware will have a unique register block in RAM for open direction HWMTD from 0%
to 100% in 1% increments.
2) Firmware will have a unique register block in RAM for close direction HWMTD from
100% to 0% in 1% decrements.
3) 51 RAM Cell locations for open and another 51 RAM Cell locations for close direction.
4) Additional cells will be assigned for Time Stamp.
5) Enable/Disable HWMTD coil 1138, Reg 1230 bit 10. This bit is Enable High logic.
6) At power-up all open and close HWMTD RAM cell locations will all be 0x0000.
7) Each cell in HWMTD will contain the largest torque value for the respective actuator
stroke and direction.
7.1.3 Command to Enable HWMTD
Host will set coil 1138 as single coil command. R1230.10
Actuator will only do HWMTD if this bit is Enable High logic.
7.1.4 Command to Clear HWMTD Open
When coil 1136 is set, rmware will clear all cells of HWMTD Open direction.
Host will set coil 1136 as single coil command. R1230.8
Time Stamp will be assigned when this command was given.
Microcontroller Firmware will clear the coil.
7.1.5 Command to Clear HWMTD Close
When coil 1137 is set, rmware will clear all cells of HWMTD Close direction.
Host will set coil 1137 as single coil command. R1230.9
Time Stamp will be assigned when this command was given.
Microcontroller Firmware will clear the coil.
Quick Startup Guide
38
Diagnostic Features of 320B Controlinc M2CP
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 7: Diagnostic Features of 320B Controlinc M2CP
7.2 Full Stroke Test (FST)
Design Notes for the Full Stroke Test implementation on the 320B Controlinc Electronics for M2CP actuators.
Table 2. Parameter values and registers
Parameter Value/Range Default Register
Start Position 100% or 0% 100% R1227.L Travel Range Always 100% Pause Time 1 - 30 seconds 5 Seconds R1228.L Initiated By 1 1, Network R1228.H Status Data See Status Section R1221.H
7.2.1 Test Conditions
Actuator must be in Remote for FST to start.
Actuator must not be in alarm for FST to start.
Actuator must not have any inhibits in effect for FST to start.
Actuator will stop and FST will fail if any alarm or inhibit occurs during the test.
Issuing a start FST command will not clear a valve stall alarm or any other alarms.
Anti-water conguration to be ignored during FST.
7.2.2 Test Description
1) Actuator runs to 50% rst if it is not between 49% and 51% at startup.
2) The actuator pauses for the user congured Pause Time, 5 seconds is default time.
3) Actuator runs to the Congured Start Position (100% or 0%).
4) The actuator pauses for the user congured Pause Time, 5 seconds is default time.
5) Actuator runs to the opposite end from the Start Position (0% or 100%).
6) The actuator pauses for the user congured Pause Time, 5 seconds is default time.
7) Actuator runs to the original Start Position (100% or 0%).
8) Test status is reported in register map.
September 2020
NOTE:
If setpoint tracking is enabled in the actuator, the actuator will now run to the congured
setpoint.
Diagnostic Features of 320B Controlinc M2CP
39
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
7.2.3 FST Status and Failure Codes
Table 3. FST Status Codes R (1221).H (lower nibble)
Status Code Value
Test Initialization 0 Test Passed 1 Test Failed 2 Test in Progress 3 User Abort 4
Table 4. FST Failure Codes R (1221).H (upper nibble)
Failure Codes Value
Test Passed or is in progress 0 Actuator Alarm 1 ESD Occurred 2 Change of Mode 3 User Abort 4 Not in Remote 5 Not at Correct Starting Position 6 Invalid Stroke Test Travel Range 7 Invalid Pause Time 8 Invalid Start Position 9
Interlock Condition 10, N/A for M2CP Test in First Stroke 11, Test Description 5) Test in Mid Stroke Delay 12, Test Description 6) Test in Second Stroke 13, Test Description 7)
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
7.2.4 Event Log
Event #99 is the Full Stroke Test Event indication.
7.2.5 Command to Enable FST
Host will set coil 1116 as single coil command. R1229.4
Actuator will only do FST if this bit is enabled.
While performing FST if this bit is disable, actuator will complete FST.
7.2.6 Command to Initiate FST
Host will set coil 1022 as single coil command. R1005.6
Microcontroller Firmware will clear the coil.
7.2.7 Command to Abort FST
Host will set coil 1023 as single coil command. R1005.7
Microcontroller Firmware will clear the coil.
40
Diagnostic Features of 320B Controlinc M2CP
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
7.2.8 Command to Clear FST Prole Values
Host will set coil 1125 as single coil command. R1229.13
Microcontroller Firmware will clear the coil.
R7336 to 7438 will now all be 0x0000.
7.2.9 Command to Delete Archive FST Values
Host will set coil 1119 as single coil command. R1229.7
Microcontroller Firmware will clear the coil.
R7226 to 7328 will now all be 0x0000.
7.2.10 Command to Archive FST Prole
Host will set coil 1117 as single coil command. R1229.5
Microcontroller Firmware will clear the coil.
Firmware will save FST Open/Close prole value to ash.
FST prole value will now be written to R7226 to 7328 as archive values.
Look at register assignment below.
7.2.11 FST Header Prole
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
Table 5. FST Header Prole
Register # High Byte Low Byte Description
7330 Range Start Position 100%, 0 or 100% 7331 Initiated By Pause Time Initiate = 1, Host. Pause Time: 1 - 30 seconds 7332 N/A N/A 7333 N/A N/A 7334 Time Byte 0 Time Byte 1 Currently Time is N/A 7335 Time Byte 2 Time Byte 3 Currently Time is N/A
7.2.12 Closing (100 - 0%) FST Prole, Registry
Torque at Actuator Position:
R7336 UB LB – Torque at 1% – Torque at 0%
R7337 UB LB – Torque at 3% – Torque at 2%
...
R7385 UB LB – Torque at 99% – Torque at 98%
R7386 UB LB – N/A – Torque at 100%
7.2.13 Opening (0 - 100%) FST Prole, Registry
Torque at Actuator Position:
R7388 UB LB – Torque at 1% – Torque at 0%
R7389 UB LB – Torque at 3% – Torque at 2%
...
R7437 UB LB – Torque at 99% – Torque at 98%
R7438 UB LB – N/A – Torque at 100%
Diagnostic Features of 320B Controlinc M2CP
41
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
7.2.14 FST Header Archive
Table 6. FST Header Archive
Register # High Byte Low Byte Description
7220 Range Start Position 100%, 0 or 100% 7221 Initiated By Pause Time Initiate = 1, Host. Pause Time: 1 - 30 seconds 7222 N/A N/A 7223 N/A N/A 7224 Time Byte 0 Time Byte 1 Currently Time is N/A 7225 Time Byte 2 Time Byte 3 Currently Time is N/A
7.2.15 Closing (100 - 0%) FST Archive, Registry
Torque at Actuator Position:
R7226 UB LB – Torque at 1% – Torque at 0%
R7227 UB LB – Torque at 3% – Torque at 2%
...
R7275 UB LB – Torque at 99% – Torque at 98%
R7276 UB LB – N/A – Torque at 100%
7.2.16 Opening (0 - 100%) FST Prole, Registry
Torque at Actuator Position:
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
R7278 UB LB – Torque at 1% – Torque at 0%
R7279 UB LB – Torque at 3% – Torque at 2%
...
R7327 UB LB – Torque at 99% – Torque at 98%
R7328 UB LB – N/A – Torque at 100%
7.2.17 Situations that cause FST to Abort
1) Change in control from Remote to OFF or Local.
2) ESD.
3) Lost Comm.
4) Abort Command from User.
7.2.18 Situations that cause FST to Fail
1) Motor Overload.
2) Over Torque.
3) Valve Stall Alarm.
4) Loss of Power.
5) Wrong Direction.
6) Loss Comm.
7) Other Alarm Condition.
42
Diagnostic Features of 320B Controlinc M2CP
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Section 7: Diagnostic Features of 320B Controlinc M2CP
7.3 Partial Stroke Test (PST)
Design Notes for the Partial Stroke Test implementation on the 320B Controlinc Electronics for M2CP actuators.
Table 7. Parameter values and registers
Parameter Value/Range Default Register
Start Position 100% or 0% 100% R1225.L Stop Position 30% 70% if at 100% 30% if at 0% 5 seconds R1228.L Travel Range 1% to 30% in increment of 1% 30% R1225.H Pause Time 1 - 30 seconds 5 seconds R1226.L Initiated By 1 1, Network R1226.H Status Data See Status Section R1221.L
7.3.1 Test Conditions
Actuator must be in Remote for PST to start.
Actuator must not be in alarm for PST to start.
Actuator must not have any inhibits in effect for PST to start.
Actuator will stop and PST will fail if any alarm or inhibit occurs during the test.
Issuing a start PST command will not clear a valve stall alarm or any other alarms.
Anti-water conguration to be ignored during PST.
7.3.2 Test Description
1) Actuator runs to the Congured Start Position (100% or 0%)
2) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
3) If congured start position is 100%, actuator will run to 70%, close PST.
4) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
5) Actuator will run to 0%.
6) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
7) Actuator will run to 30%, open PST.
8) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
9) If congured start position is 0%, actuator will run to 30%, open PST.
10) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
11) Actuator will run to 100%.
12) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
13) Actuator will run to 70%, close PST.
14) Actuator pauses for the user congured Pause Time, 5 seconds is default time.
15) Either items 3-8 or 9-14 will be executed.
16) Test status is reported in register map.
September 2020
Diagnostic Features of 320B Controlinc M2CP
43
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
NOTE:
If setpoint tracking is enabled in the actuator, the actuator will now run to the congured
setpoint.
7.3.3 PST Status and Failure Codes
Table 8. PST Status Code R1221.L (lower nibble)
Status Code Value
Test Initialization 0 Test Passed 1 Test Failed 2 Test in Progress 3 User Abort 4
Table 9. PST Failure Codes R1221.L (upper nibble)
Failure Codes Value
Test Passed or is in progress 0 Actuator Alarm 1 ESD Occurred 2 Change of Mode 3 User Abort 4 Not in Remote 5 Not at Correct Starting Position 6 Invalid Stroke Test Travel Range 7 Invalid Pause Time 8 Invalid Start Position 9 Interlock Condition 10, N/A for M2CP Test in First Stroke 11, start position to 30% or 70% Test in Mid Stroke Delay 12 Test in Second Stroke 13, opposite direction to 70% or 30%
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
7.3.4 Event Log
Event #xx is the Partial Stroke Test Event indication.
7.3.5 Command to Enable PST
Host will set coil 1112 as single coil command. R1229.0
Actuator will only do PST if this bit is enabled.
While performing PST if this bit is disabled, actuator will complete PST.
7.3.6 Command to Initiate PST
Host will set coil 1020 as single coil command. R1005.4
Microcontroller Firmware will clear the coil.
7.3.7 Command to Abort PST
Host will set coil 1021 as single coil command. R1005.5
Microcontroller Firmware will clear the coil.
44
Diagnostic Features of 320B Controlinc M2CP
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
7.3.8 Command to Clear PST Prole Values
Host will set coil 1124 as single coil command. R1229.12
Microcontroller Firmware will clear the coil.
R7116 to 7219 will now all be 0x0000.
7.3.9 Command to Delete Archive PST Values
Host will set coil 1115 as single coil command. R1229.3
Microcontroller Firmware will clear the coil.
R7006 to 7109 will now all be 0x0000.
7.3.10 Command to Archive PST Prole
Host will set coil 1113 as single coil command. R1229.1
Microcontroller Firmware will clear the coil.
Firmware will save PST Open/Close prole value to ash.
PST prole value will now be written to R7006 to 7109 as archive values.
Look at register assignment below.
7.3.11 PST Header Prole
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
Table 10. PST Header Prole
Register # High Byte Low Byte Description
7110 Range Start Position 30%, 0 or 100% 7111 Initiated By Pause Time Initiate = 1, Host. Pause Time 1 - 30 seconds 7112 N/A N/A 7113 N/A N/A 7114 Time Byte 0 Time Byte 1 Currently Time is N/A 7115 Time Byte 2 Time Byte 3 Currently Time is N/A
7.3.12 Closing (100 - 70%) PST Prole, Registry
Torque at Actuator Position:
R7116 UB LB – Torque at 1% – Torque at 0%
R7117 UB LB – Torque at 3% – Torque at 2%
...
R7166 UB LB – Torque at 99% – Torque at 98%
R7167 UB LB – N/A – Torque at 100%
7.3.13 Opening (0 - 30%) PST Prole, Registry
Torque at Actuator Position:
R7168 UB LB – Torque at 1% – Torque at 0%
R7169 UB LB – Torque at 3% – Torque at 2%
...
R7218 UB LB – Torque at 99% – Torque at 98%
R7219 UB LB – N/A – Torque at 100%
Diagnostic Features of 320B Controlinc M2CP
45
Section 7: Diagnostic Features of 320B Controlinc M2CP
September 2020
7.3.14 PST Header Archive
Table 11. PST Header Archive
Register # High Byte Low Byte Description
7000 Range Start Position 30%, 0 or 100% 7001 Initiated By Pause Time Initiate = 1, Host. Pause Time 1 - 30 seconds 7002 N/A N/A 7003 N/A N/A 7004 Time Byte 0 Time Byte 1 Currently Time is N/A 7005 Time Byte 2 Time Byte 3 Currently Time is N/A
7.3.15 Closing (100 - 70%) PST Archive, Registry
Torque at Actuator Position:
R7006 UB LB – Torque at 1% – Torque at 0%
R7007 UB LB – Torque at 3% – Torque at 2%
...
R7056 UB LB – Torque at 99% – Torque at 98%
R7057 UB LB – N/A – Torque at 100%
7.3.16 Opening (0 - 30%) PST Archive, Registry
Torque at Actuator Position:
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
R7058 UB LB – Torque at 1% – Torque at 0%
R7059 UB LB – Torque at 3% – Torque at 2%
...
R7108 UB LB – Torque at 99% – Torque at 98%
R7109 UB LB – N/A – Torque at 100%
7.3.17 Situations that cause PST to Abort
1) Change in control from Remote to OFF or Local.
2) ESD.
3) Lost Comm.
4) Abort Command from User.
7.3.18 Situations that cause PST to Fail
1) Motor Overload.
2) Over Torque.
3) Valve Stall Alarm.
4) Loss of Power.
5) Wrong Direction.
6) Loss Comm.
7) Other Alarm Condition.
46
Diagnostic Features of 320B Controlinc M2CP
Quick Startup Guide
QSG-01-10-93-0014-EN Rev. 1
Notes
September 2020
World Area Conguration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales ofce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road Wuqing Development Area
Tianjin 301700
P. R. China T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone
Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
24 Angus Crescent Longmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T +27 11 451 3700
EUROPE
Holland Fasor 6 Székesfehérvár 8000 Hungary T +36 22 53 09 50
Strada Biffi 165 29017 Fiorenzuola d’Arda (PC) Italy T +39 0523 944 411
www.emerson.com
VCIOM-15747-EN ©2020 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which
are available upon request. We reser ve the right to modify or improve the designs or specifications of such products at any time without notice.
Loading...