Emerson 4195KAE, 4195KS, 4195KA, 4195KAM, 4195KAME Instruction Manual

...
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
4195KA, K B, KC, and KS Series Gauge Pressure Controllers
1. Introduction
Scope of Manual 1-3. . . . . . . . . . . . . . . . . . . . . . . .
Description 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 1-4. . . . . . . . . . . . . . . . . . . . . . . . . .
Educational Services 1-4. . . . . . . . . . . . . . . . . . . .
2. Installation
Controller Mounting Orientation 2-1. . . . . . . . . . .
Pipestand Mounting 2-1. . . . . . . . . . . . . . . . . . . . .
Panel Mounting 2-1. . . . . . . . . . . . . . . . . . . . . . . . .
Wall Mounting 2-1. . . . . . . . . . . . . . . . . . . . . . . . . .
Actuator Mounting 2-1. . . . . . . . . . . . . . . . . . . . . .
Pressure Connections 2-2. . . . . . . . . . . . . . . . . . .
Process Pressure Connection 2-3. . . . . . . . . . .
Supply Pressure Connection 2-4. . . . . . . . . . . .
Remote Set Point (suffix letter M)
Pressure Connection 2-4. . . . . . . . . . . . . . . .
External Feedback Pressure Connection
(4195KB Series Controllers Only) 2-4. . . . . .
Vent 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. 4195KA Series Proportional-Only Controllers Adjustments for 4195KA Series Controllers 3-1.
Manual Set Point Adjustment 3-1. . . . . . . . . . . .
Remote Set Point (suffix letter M)
Adjustment 3-1. . . . . . . . . . . . . . . . . . . . . . . . .
Proportional Band Adjustment (PB ADJ) 3-1. .
Changing Controller Action 3-2. . . . . . . . . . . . . .
Switching The Auto/Manual Station
(suffix letter E) 3-2. . . . . . . . . . . . . . . . . . . . . .
Prestartup Checks for 4195KA Series
Controllers 3-2. . . . . . . . . . . . . . . . . . . . . . . . . .
Startup for 4195KA Series Controllers 3-3. . . . .
Calibration of 4195KA Series Controllers 3-4. . .
General Calibration Instructions 3-4. . . . . . . . .
Process Indicator Zero and Span
Calibration 3-4. . . . . . . . . . . . . . . . . . . . . . . . .
Remote Set Point (suffix letter M)
Zero and Span Calibration 3-6. . . . . . . . . . . .
Flapper Alignment 3-6. . . . . . . . . . . . . . . . . . . . .
Principle of Operation for 4195KA Series
Controllers 3-7. . . . . . . . . . . . . . . . . . . . . . . . . .
Overall Operation 3-7. . . . . . . . . . . . . . . . . . . . . .
Remote Set Point (suffix letter M)
Operation 3-8. . . . . . . . . . . . . . . . . . . . . . . . . .
Auto/Manual Station (suffix letter E)
Operation 3-8. . . . . . . . . . . . . . . . . . . . . . . . . .
4. 4195KB Series Proportional-Plus-Reset Controllers and 4195KC Series Proportional-Plus-Reset-Plus-Rate Controllers
Adjustments for 4195KB and KC Series
Controllers 4-1. . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Set Point Adjustment 4-1. . . . . . . . . . . .
Remote Set Point (suffix letter M)
Adjustment 4-1. . . . . . . . . . . . . . . . . . . . . . . . .
Proportional Band Adjustment (PB ADJ) 4-2. .
Changing Controller Action 4-2. . . . . . . . . . . . . .
Reset Adjustment 4-2. . . . . . . . . . . . . . . . . . . . . .
Rate Adjustment 4-2. . . . . . . . . . . . . . . . . . . . . . .
Anti-Reset Windup (suffix letter F)
Adjustment 4-2. . . . . . . . . . . . . . . . . . . . . . . . .
Switching the Auto/Manual Station
(suffix letter E) 4-3. . . . . . . . . . . . . . . . . . . . . .
Prestartup Checks for 4195KB and
KC Series Controllers 4-3. . . . . . . . . . . . . . . . .
Startup for 4195KB and KC Series
Controllers 4-4. . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration of 4195KB and KC Series
Controllers 4-4. . . . . . . . . . . . . . . . . . . . . . . . . .
General Calibration Instructions 4-5. . . . . . . . .
Process Indicator Zero and Span
Calibration 4-5. . . . . . . . . . . . . . . . . . . . . . . . .
Remote Set Point (suffix letter M)
Zero and Span Calibration 4-5. . . . . . . . . . . .
Flapper Alignment 4-7. . . . . . . . . . . . . . . . . . . . .
Anti-Reset Windup (suffix letter F)
Differential Relief Valve Calibration 4-9. . . .
Principle of Operation for 4195KB and
KC Series Controllers 4-10. . . . . . . . . . . . . . . .
Overall Operation 4-10. . . . . . . . . . . . . . . . . . . . .
Anti-Reset Windup (suffix letter F)
Operation 4-13. . . . . . . . . . . . . . . . . . . . . . . . .
Remote Set Point (suffix letter M)
Operation 4-13. . . . . . . . . . . . . . . . . . . . . . . . .
Auto/Manual Station (suffix letter E)
Operation 4-13. . . . . . . . . . . . . . . . . . . . . . . . .
External Feedback Operation 4-13. . . . . . . . . .
www.Fisher.com
D200160X012
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007
Contents (continued)
5. 4195KS Series Differential Gap Controllers
Operating Information 5-1. . . . . . . . . . . . . . . . . . .
Adjustments for 4195KS Series Differential
Gap Controllers 5-1. . . . . . . . . . . . . . . . . . . . . .
Manual Set Point 5-1. . . . . . . . . . . . . . . . . . . . . .
Remote Set Point (Option M) 5-1. . . . . . . . . . . .
Proportional Band (Differential Gap) 5-1. . . . . .
Changing Controller Action 5-1. . . . . . . . . . . . . .
Auto/Manual Switching (Option E) 5-1. . . . . . .
Prestartup Checks 5-2. . . . . . . . . . . . . . . . . . . . . .
Startup 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Process Zero and Span Adjustment 5-3. . . . . .
Remote Set Point Zero and Span
(Option M) 5-4. . . . . . . . . . . . . . . . . . . . . . . . .
Setting Switching Points 5-5. . . . . . . . . . . . . . . .
Direct-Acting Controllers 5-5. . . . . . . . . . . . . . .
Reverse-Acting Controllers 5-5. . . . . . . . . . . . .
Principle of Operation 5-7. . . . . . . . . . . . . . . . . . .
Overall Operation 5-7. . . . . . . . . . . . . . . . . . . . . .
Remote Set Point (Option M) 5-8. . . . . . . . . . . .
Auto/Manual Option 5-8. . . . . . . . . . . . . . . . . . . .
6. Maintenance
Inspection and Maintenance 6-1. . . . . . . . . . . . . .
Troubleshooting 6-1. . . . . . . . . . . . . . . . . . . . . . . .
Replacing Common Controller Parts 6-1. . . . . . .
Replacing the Process Pressure Scale 6-5. . .
Replacing the Relay 6-6. . . . . . . . . . . . . . . . . . . .
Replacing the Case and Cover 6-6. . . . . . . . . .
Replacing the Gauges 6-6. . . . . . . . . . . . . . . . . .
Replacing the Supply Gauge, Proportional,
Reset, Reset Valve and Positive Tubing
Feedback Assemblies 6-7. . . . . . . . . . . . . . .
Replacing the Proportional Band Adjustment
Knob, Nozzle Assembly, and Set Point
Beam Assembly 6-7. . . . . . . . . . . . . . . . . . . . .
Replacing the Flapper Assembly and
Flapper Flexure Pivot Assembly 6-11. . . . . .
Replacing the Proportional or Reset
Bellows 6-15. . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Reset Restriction Valve
(4195KB Series) 6-17. . . . . . . . . . . . . . . . . . .
Replacing the Rate/Reset Valve Assembly
(4195KC Series) 6-18. . . . . . . . . . . . . . . . . . .
Replacing the Anti-Reset Windup
(suffix letter F) Differential Relief Valve 6-19
Replacing the Anti-Reset Windup
(suffix letter F) Relief Valve Tubing
Assembly 6-19. . . . . . . . . . . . . . . . . . . . . . . . .
Bourdon Tube Controller Maintenance
and Calibration 6-20. . . . . . . . . . . . . . . . . . . . . .
Replacing the Bourdon Tube 6-20. . . . . . . . . . .
Replacing Bourdon Tube Controller Links 6-20
Replacing Link 1 6-20. . . . . . . . . . . . . . . . . . . .
Replacing Link 2 6-21. . . . . . . . . . . . . . . . . . . .
Replacing Link 3 6-22. . . . . . . . . . . . . . . . . . . .
Replacing Link 4 6-22. . . . . . . . . . . . . . . . . . . .
Bourdon Tube Travel Stop Installation
and Adjustment 6-23. . . . . . . . . . . . . . . . . . . .
Bourdon Tube Controller Calibration:
Zero and Span Adjustment 6-24. . . . . . . . . .
Capsular Element Controller Maintenance
and Calibration 6-27. . . . . . . . . . . . . . . . . . . . . .
Replacing the Capsular Element
Assembly 6-27. . . . . . . . . . . . . . . . . . . . . . .
Replacing Capsular Element Parts 6-27. . . .
Replacing the Long Pivot Assembly 6-27. . . Replacing the Short Pivot Assembly 6-28. . . Replacing the Process Drive Flexure 6-28. .
Replacing the Process Tubing 6-29. . . . . . . .
Replacing Capsular Element
Controller Links 6-29. . . . . . . . . . . . . . . . . .
Replacing Link 1 6-30. . . . . . . . . . . . . . . . . . . .
Replacing Link 2 6-30. . . . . . . . . . . . . . . . . . . .
Replacing Link 3 6-30. . . . . . . . . . . . . . . . . . . .
Replacing Link 4 6-31. . . . . . . . . . . . . . . . . . . .
Replacing Link 5 6-31. . . . . . . . . . . . . . . . . . . .
Capsular Element Controller
Maintenance Calibration 6-32. . . . . . . . . . . . .
Precalibration Procedure 6-32. . . . . . . . . . . .
Aligning the Drive Bracket Assembly 6-32. .
Setting the Travel Stops 6-32. . . . . . . . . . . . .
Aligning the Linkage 6-33. . . . . . . . . . . . . . . .
Capsular Element Controller
Zero and Span Adjustment 6-34. . . . . . . . . .
Remote Set Point (suffix letter M)
Maintenance 6-36. . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Remote Set Point
Assembly 6-36. . . . . . . . . . . . . . . . . . . . . . . . .
Replacing Remote Set Point
Assembly Parts 6-36. . . . . . . . . . . . . . . . . .
Replacing Pivot Assembly A (key 114) 6-36. Replacing Pivot Assembly B (key 115) 6-37.
Replacing the Drive Flexure 6-37. . . . . . . . . .
Replacing the Remote Set Point Tubing 6-38
Replacing Link A 6-38. . . . . . . . . . . . . . . . . . .
Replacing Link B 6-38. . . . . . . . . . . . . . . . . . .
Remote Set Point (suffix letter M)
Maintenance Calibration 6-38. . . . . . . . . . . . . .
Precalibration Procedure 6-38. . . . . . . . . . . . . .
Aligning the Flexures 6-39. . . . . . . . . . . . . . . . . .
Setting the Travel Stops 6-39. . . . . . . . . . . . . . .
Aligning the Linkage 6-39. . . . . . . . . . . . . . . . . .
Remote Set Point Zero and Span
Adjustment 6-40. . . . . . . . . . . . . . . . . . . . . . . .
Remote Set Point Linearity Adjustment 6-41. .
Auto/Manual Station (suffix letter E)
Maintenance 6-41. . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Auto/Manual Station 6-41. . . . . .
1-2
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
W5663-1 / IL
Figure 1-1. 4195K Series Gauge Pressure Controllers
Contents (continued)
Replacing the Switch Body Assembly,
Lever O-Ring, Switch Body O-Ring,
and Tubing Assembly 6-42. . . . . . . . . . . . . . .
Replacing the Loader Range Spring,
Diaphragm Assembly, Ball Seat,
Tubing, and Ball 6-43. . . . . . . . . . . . . . . . . . . .
Replacing the Loader Valve Plug and
Valve Plug Spring 6-44. . . . . . . . . . . . . . . . . .
7. Parts
Parts Ordering 7-1. . . . . . . . . . . . . . . . . . . . . . . . .
Parts Kits 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Abbreviations Used In The Parts List 7-1. . . . .
Controller Common Parts 7-1. . . . . . . . . . . . . . .
Process and Set Point Indicator
Assembly 7-11. . . . . . . . . . . . . . . . . . . . . . . . .
Indicator Assembly 7-14. . . . . . . . . . . . . . . . . . .
Capsular Element Assembly 7-14. . . . . . . . . . .
Remote Set Point Assembly
(suffix letter M) 7-16. . . . . . . . . . . . . . . . . . . . .
Auto/Manual Station (suffix letter E) 7-17. . . . .
Controller Mounting Parts 7-19. . . . . . . . . . . . . .
Pipestand Mounting 7-19. . . . . . . . . . . . . . . . .
Pipestand Mounting with Regulator 7-19. . .
Panel Mounting 7-19. . . . . . . . . . . . . . . . . . . .
Wall Mounting 7-19. . . . . . . . . . . . . . . . . . . . . .
NAMEPLATE
W6831 / IL
Controller Mounting Parts for Actuator
with Casing-Mounted Controller 7-19. . . .
Controller Mounting Parts for Actuator
with Yoke-Mounted Controller 7-19. . . . . .
Regulator Mounting Parts 7-19. . . . . . . . . . . . . .
Regulator Mounting Parts for
Casing-Mounted Regulator 7-19. . . . . . . .
Regulator Mounting Parts for
Yoke-Mounted Regulator (Mounting
Bracket Not Required) 7-19. . . . . . . . . . . .
Regulator Mounting Parts for
Yoke-Mounted Regulator
(With Mounting Bracket) 7-19. . . . . . . . . . .
Fittings 7-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 1 Introduction

Scope of Manual

This instruction manual provides installation, operating, calibration, maintenance, and parts ordering information for 4195KA, KB, KC, and KS Series gauge pressure indicating controllers.
1-3
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007
Portions of this manual apply only to specific 4195K Series controller configurations. These configurations are indicated by letter suffixes in the type number that correspond to the mode and option designated in table 1-2.
The specific controller type number (with letter suffixes) is located on the nameplate shown in figure 1-1. Refer to table 1-2 for the definition of each 4195K Series type number.
Do not install, operate, or maintain this product without first D being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance, and D carefully reading and understanding the contents of this manual. If you have any questions about these instructions, contact your Emerson Process Managementt sales office before proceeding.

Description

The controllers described in this manual provide gauge pressure control with the options as shown in table 1-2.

Specifications

Specifications for the 4195KA, KB, KC, and KS Series controllers are listed in table 1-1.

Educational Services

For information on available courses for the 4195KA, 4195KB, 4195KC, and 4195KS Series gauge pressure indicating controllers, as well as a variety of other products, contact:
Emerson Process Management Educational Services, Registration P.O. Box 190; 301 S. 1st Ave. Marshalltown, IA 501582823 Phone: 8003388158 or Phone: 6417543771 FAX: 6417543431 e-mail: education@emersonprocess.com
D 4195KA Series: Proportional-only control
D 4195KB Series: Proportional-plus-reset control
D 4195KC Series:
Proportional-plus-reset-plus-rate control
D 4195KS Series: Differential gap control
These controllers show process pressure and set point on an easy-to-read process scale. The controller output is a pneumatic signal that operates a final control element.
Note
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
1-4
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
Table 1-1. Specifications
Available Configurations
See table 1-2
Input Signal (Process Sensor Range
(1)
)
Lower and Upper Range Limits: See tables 1-3
and 1-4
Maximum Allowable Operating Limits: See
tables 1-3 and 1-4
Output Signal
(1)
Proportional-Only, Proportional-Plus-Reset, or Proportional-Plus-Reset-Plus-Rate Range:
0.2 to 1.0 bar or 0.4 to 2.0 bar (3 to 15 psig or 6 to 30 psig)
Differential Gap Range: 0 and 1.4 bar (0 and 20
psig) or 0 and 2.4 bar (0 and 35 psig)
Action: Field-reversible between direct
(increasing sensed process pressure increases output pressure) or reverse (increasing sensed process pressure decreases output pressure).
Process Scale
Standard scale is matched to the range of the sensing element, with the exception of receiver controllers. Optional
(2)
scales are available.
Process Connections
Standard: 1/4 NPT, internal, stainless steel (all
input ranges)
Optional: 1/2 NPT, see table 1-5
Supply and Output Connections
1/4 NPT, internal
Supply Pressure Requirements
(3)
See table 1-6
Supply Pressure Medium
Air or natural gas
(4)
Remote Set Point Pressure Ranges
0.2 to 1.0 bar or 0.4 to 2.0 bar (3 to 15 psig or 6 to 30 psig)
continued
Controller Adjustments
Proportional Band
input span
(1)
Reset
: Adjustable from 0.01 to more than 74
(1)
: 5 to 500% of process
minutes per repeat (from 100 to less than 0.0135 repeats per minute)
(1)
Rate Differential Gap
: Adjustable from 0 to 20 minutes
(1)
Controllers: Adjustable from 5 to 100% of process scale range Set Point: Adjustable from 0 to 100% of the scale
span
Controller Performance
Repeatability Dead Band
(1)
: 0.4% of output span
(1)
: Less than 0.4% of process scale
span
Typical Frequency Response: 1.5 hertz and 90
degree phase shift with 3.05 m (10 feet) of 6.4 mm (1/4-inch) tubing and 1639 cm
3 (
100 cubic
inch) volume
Steady-State Air Consumption
(1,5,6)
0.2 to 1.0 Bar (3 to 15 Psig) Output: 0.1 normal
m3/hr (3.5 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 0.14 normal
m3/hr (5.0 scfh)
Delivery Capacity
(5)
0.2 to 1.0 Bar (3 to 15 Psig) Output: 5.9 normal
m3/hr (240 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 10.4 normal
m3/hr (350 scfh)
Operative Ambient Temperature Limits
(1,3,7)
40 to 71_C (40 to 160_F)
Exhaust Capacity
(5)
0.2 to 1.0 Bar (3 to 15 Psig) Output: 4.6 normal
m3/hr (186 scfh)
0.4 to 2.0 Bar (6 to 30 Psig) Output: 7.0 normal
m3/hr (295 scfh)
Hazardous Area Classification
Complies with the requirements of ATEX Group II Category 2 Gas and Dust
1-5
4195KA, KB, KC, and KS Controllers
Table 1-1. Specifications (continued)
Instruction Manual
Form 5207
April 2007
Housing
Designed to NEMA 3 (Weatherproof) and IEC 529 IP54 Specifications
Declaration of SEP
Fisher Controls International LLC declares this product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive
Mounting
Controller can be mounted on actuator, panel, wall, or pipestand.
Approximate Weight
4.5 kg (10 pounds)
1. These terms are defined in ISA Standard S51.1.
2. Consult your Emerson sales office for additional information.
3. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded.
4. This product can be used with natural gas. Natural gas should not contain more than 20 ppm of H2S.
5. Normal m3/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).
6. Without auto/manual station. With auto/manual station, air consumption is 0.28 normal m3/hr (10.0 Scfh) for either output range.
7. Also use these temperatures for transportation and storage limits.
Table 1-2. Available Configurations for 4195KA, 4195KB, 4195KC, and 4195KS Series Controllers
MODES OPTIONS
Proportional-
Plus-Reset-
Plus-Rate
(Three-Mode
Controllers)
(1)
Proportional-
Only
(One-Mode
Controllers)
X X X X
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
SERIES
4195KA
4195KB
4195KC
4195KS
1. Reverse-acting constructions are designated by the suffix letter R added to the type number.
TYPE
NUMBER
4195KA 4195KAE 4195KAM 4195KAME
4195KB 4195KBE 4195KBF 4195KBFE 4195KBM 4195KBME 4195KBFM 4195KBFME
4195KC 4195KCE 4195KCF 4195KCFE 4195KCM 4195KCME 4195KCFM 4195KCFME
4195KS 4195KSE 4195KSM 4195KSME
Proportional-
Plus-Reset (Two-Mode
Controllers)
− − −
− − −
− − −
− − −
X X X X X X X X
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
(PED) 97 / 23 / EC. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
However, the product may bear the CE marking to indicate compliance with other applicable EC
Directives.
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
X X X X X X X X
− − −
− − −
− − −
− − −
Differential
Gap
Controller
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
− − −
X X X X
Auto/Manual
Internal
Station
E
X
X
X
X
X
X
X
X
X
X
X
X
Anti-Reset
Windup
F
− − −
− − −
− − −
− − −
− − −
− − −
X X
− − −
− − −
X X
− − −
− − −
X X
− − −
− − −
X X
− − −
− − −
− − −
− − −
Remote
Setpoint
M
− − −
− − −
X X
− − −
− − −
− − −
− − −
X X X X
− − −
− − −
− − −
− − −
X X X X
− − −
− − −
X X
1-6
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
Table 1-3. Process Sensor (Capsular Element) Pressure Ratings
(1)
CAPSULE
MATERIAL
Metric units
N09902
U.S. units
1. Minimum or maximum span, or any span in between, may be positioned anywhere within the operating range. For example, if a 0 to 350 mbar (0 to 5 psig) sensing element is used and the minimum span of 1.75 mbar (2.5 psig) is set, the process indication can be calibrated to a range of 340 mbar to 203 mbar (10 inch Hg to 6 inch Hg), 0 to 172 mbar (0 to 2.5 psig), 172 to 345 mbar (2.5 to 5 psig), 305 to 480 mbar (4.5 to 7 psig), or any value between minimum and maximum values of operating range.
2. Capsules with the travel stops set may be pressured to this value without permanent zero shift.
CAPSULAR
STANDARD RANGES
Positive pressure
Vacuum
Compound
Positive pressure
Vacuum
Compound
0 to 150 mbar 0 to 400 mbar 0 to 0.6 bar
0.2 to 1 bar 0 to 1 bar
0 to 1.4 bar 0 to 1.6 bar
0.4 to 2 bar 0 to 2 bar
150 to 0 mbar
340 to 0 mbar
400 to 0 mbar
0.6 to 0 bar
1 to 0 bar
50 to 100 mbar
175 to 175 mbar
150 to 250 mbar
0.2 to 0.4 bar
0.4 to 0.6 bar
0.6 to 0.8 bar
1 to 0.6 bar
1 to 1 bar
0 to 60 inch wc 0 to 5 psig 0 to 10 psig 3 to 15 psig 0 to 15 psig
0 to 20 psig 6 to 30 psig 0 to 30 psig
5 to 0 inch Hg
10 to 0 inch Hg
20 to 0 inch Hg
30 to 0 inch Hg
30 to 30 inch wc
5 inch Hg to 2.5 psig
10 inch Hg to 5 psig
15 inch Hg to 7.5 psig
20 inch Hg to 10 psig
30 inch Hg to 15 psig
SPAN
Min Max Min Max
100 mbar 350 mbar
0.35 bar
0.4 bar
0.5 bar
0.7 bar 1 bar
0.8 bar 1 bar
85 mbar 170 mbar 350 mbar
0.35 bar
0.5 bar 100 mbar
175 mbar 350 mbar
0.35 bar
0.5 bar
0.7 bar 1 bar 1 bar
40 inch wc
2.5 psig 5 psig 6 psig
7.5 psig 10 psig
12 psig 15 psig
2.5 inch Hg 5 inch Hg 10 inch Hg 15 inch Hg
40 inch wc
2.5 psig 5 psig
7.5 psig 10 psig 15 psig
160 mbar 700 mbar
0.7 bar
0.8 bar 1 bar
1.4 bar 2 bar
1.6 bar 2 bar
170 mbar 340 mbar 700 mbar
0.7 bar 1 bar
160 mbar 350 mbar 700 mbar
0.7 bar
1 bar
1.4 bar 2 bar 2 bar
60 inch wc 5 psig 10 psig 12 psig 15 psig
20 psig 24 psig 30 psig
5 inch Hg 10 inch Hg 20 inch Hg 30 inch Hg
60 inch wc 5 psig 10 psig
15 psig 20 psig 30 psig
OPERATING RANGE
350 mbar
1 bar
1 bar
1 bar
1 bar
1 bar
1 bar
1 bar
1 bar
350 mbar
480 mbar
1 bar
1 bar
1 bar
350 mbar
480 mbar
1 bar
1 bar
1 bar
1 bar
1 bar
1 bar
10 inch Hg
14 inch Hg
30 inch Hg
30 inch Hg
30 inch Hg
30 inch Hg
30 inch Hg
30 inch Hg
10 inch Hg
14 inch Hg
30 inch Hg
30 inch Hg
10 inch Hg
14 inch Hg
30 inch Hg
30 inch Hg
30 inch Hg
30 inch Hg
350 mbar 1 bar 1 bar
1.4 bar
1.4 bar
1.7 bar
2.4 bar 2 bar
2.4 bar
350 mbar 480 mbar 1 bar 1 bar
1.4 bar 350 mbar
480 mbar 1 bar 1 bar
1.4 bar
1.7 bar
2.4 bar
2.4 bar
5 psig 7 psig 15 psig 20 psig 20 psig
25 psig 30 psig 35 psig
5 psig 7 psig 15 psig 20 psig
5 psig 7 psig 15 psig
20 psig 25 psig 35 psig
OPERATING
LIMIT
510 mbar
1.5 bar
1.5 bar 2 bar 2 bar
2.5 bar
3.5 bar 3 bar
3.5 bar
510 mbar 724 mbar
1.5 bar
1.5 bar 2 bar
510 mbar 724 mbar
1.5 bar
1.5 bar
2 bar
2.5 bar
3.5 bar
3.5 bar
7.5 psig
10.5 psig
22.5 psig 30 psig 30 psig
37.5 psig 45 psig
52.5 psig
7.5 psig
10.5 psig
22.5 psig 30 psig
7.5 psig
10.5 psig
22.5 psig 30 psig
37.5 psig
52.5 psig
(2)
1-7
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007
Table 1-4. Process Sensor (Bourdon Tube) Pressure Ratings and Materials
BOURDON TUBES
SPAN
Minimum Maximum Minimum Maximum
OPERATING RANGE
(1)
Bar
Metric units
0 to 1.6 0 to 2.5 0 to 4 0 to 6
0 to 10 0 to 16 0 to 25 0 to 40
0 to 60 0 to 100 0 to 160 0 to 300
10 20 20
55
76 160 250
1 2 2
3.5
7
14 20 40 40
70 100 200 350
2 4 4 7
1
1
1
1
1
1
0 0
0 0 0 0
Psig Psig Psig Inch Hg Psig Psig
0 to 30 0 to 60 0 to 100 0 to 200
U.S. units
0 to 300 0 to 600 0 to 1000 0 to 1500
0 to 3000 0 to 5000
1. Minimum or maximum span, or any span in between, may be positioned anywhere within the operating range. For example, if a 0 to 2 bar (0 to 30 psig) sensing element is used and the minimum span of 1 bar (15 psig) is set, the process indication can be calibrated to a range of 1 to 0 bar (30 inch Hg to 0 psig), 0 to 1 bar (0 to 15 psig), 1 to 2 bar (15 to 30 psig), 2 to 3 bar (27 to 42 psig) or any value between the operating range minimum and maximum values.
2. Travel stops should be used when the maximum or minimum process pressure will be 5% over or under the calibrated range. For example, a 0 to 2 bar (0 to 30 psig) sensing element is calibrated for 0.7 to 2 bar (10 to 30 psig), the desired range. The minimum expected pressure is 0 psig and the maximum expected pressure is 2.8 bar (40 psig). Travel stops must be used to prevent excessive overtravel and undertravel since the maximum allowable overpressure and underpressure is higher than 5% of the 1.4 bar (20 psig) span which is ±70 mbar (±1 psig).
3. Bourdon tube without travel stops may be pressured to this value without permanent zero shift.
4. Bourdon tube with travel stops set may be pressured to this value without permanent zero shift.
15 30 50
100
150 300 750
1100
2200 3700
30
60 100 200
300 600
1000 1500
3000 5000
30
30
30
30
30
0 0 0
0 0
10
20 30 60 60
90 135 270 420
42
84 140 280
420 840
1300 1950
3900 6000
(2)
(3)
3 6 6
OPERATING
LIMITS
(4)
3.3
6.6
6.6
STANDARD
MATERIAL
11
22 33 66
S31600 (316 SST)
66
103 155 310 482
STANDARD
MATERIAL
48
96 160 320
480 960
S31600 (316 SST)
1500 2250
4500 7000
Table 1-5. Optional Process Connections
INPUT RANGE CONNECTION
Bar Psig Size Material
Up to 0 to 400
0 to 400 to 0 to 600
0 to 400 to 0 to 600
Up to 0 to 5000
0 to 5000 to 0 to 10,000
0 to 5000 to 0 to 10,000
J 1/2 NPT external
or J 1/2 NPT internal
1/2 NPT internal Stainless steel
1/2 NPT external Stainless steel
J Steel or J stainless
steel
Table 1-6. Supply Pressure Data
OUTPUT SIGNAL
RANGE
Bar
Psig
1. If this pressure is exceeded, control may be impaired.
2. If this pressure is exceeded, damage to the controller may result.
0.2 to 1.0 1.4 2.8
0.4 to 2.0 2.4 2.8
3 to 15 20 40
6 to 30 35 40
NORMAL
OPERATING
SUPPLY
PRESSURE
MAXIMUM
PRESSURE LIMIT
(1)
(2)
1-8
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers

Section 2 Installation

WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure:
D Always wear protective clothing, gloves, and eyewear when performing any installation operations.
D Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and preventative measures are not taken. Preventative measures may include: Remote venting of the unit, re-evaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any ignition sources. For information on remote venting of this controller, refer to page 2-5.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
D If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section of this instruction manual.

Controller Mounting Orientation

Mount the controller with the housing vertical, as shown in figure 2-1, so the vent points down.
TYPE 657 ACTUATOR
TYPE 4195K CONTROLLER
TYPE 67CFR FILTER REGULATOR
MOUNTING
W84621
Figure 2-1. Typical Actuator Mounting
PLATE

Panel Mounting

Using the dimensions shown in figure 2-3, cut a hole in the panel surface. Slide the controller into the hole and attach the bracket (key 68) to the rear of the controller using three cap screws (key 66) and lock washers (key 67). Tighten the screws (key 70) to seat the case snugly and evenly against the panel surface.

Wall Mounting

Using the dimensions in figure 2-4, drill holes in the wall to align with the four holes in the bracket (key
68). If the tubing is to run through the wall, drill a hole in the wall large enough to accept the tubing. Mount the controller to the bracket using three cap screws (key 66) and lock washers (key 67). Attach the bracket to the wall, using suitable screws or bolts.

Pipestand Mounting

Refer to figure 2-2. Pipestand mounting parts are provided to mount the controller to a 2-inch (nominal) pipe. Attach a bracket (key 68) to the controller with cap screws (key 66) and lock washers (key 67). Attach two clamps (key 69) to the bracket and fasten the controller to the pipe.

Actuator Mounting

Refer to figure 2-1. A controller specified for mounting on a control valve actuator is mounted at the factory. If the controller is ordered separately for installation on a control valve actuator, mount the unit as described in this section. Mounting parts vary for different actuator types.
2-1
4195KA, KB, KC, and KS Controllers
HEX HEAD CAP SCREW (KEY 66)
LOCKWASHER (KEY 67)
HEX HEAD CAP SCREW (KEY 362)
Instruction Manual
Form 5207
April 2007
REGULATOR
49A3196-A A6732 / IL
HEX NUT (KEY 364)
LOCKWASHER (KEY 363)
PIPE CLAMP (KEY 69)
VERTICAL PIPE
LOCKWASHER (KEY 363)
HEX NUT (KEY 364)
HEX HEAD CAP SCREW (KEY 66)
LOCKWASHER (KEY 67)
BRACKET (KEY 68)
ELBOW (KEY 365)
HEX HEAD CAP SCREW (KEY 362)
PIPE CLAMP (KEY 69)
BRACKET (KEY 68)
ELBOW (KEY 365)
HORIZONTAL PIPE
Figure 2-2. Pipestand Mounting
Attach the mounting bracket to the actuator yoke with cap screws, lock washers, and spacer spools. Attach the controller to the bracket with cap screws, lock washers, and spacer spools. On some designs, the mounting bracket is attached to the actuator casing rather than to the yoke.

Pressure Connections

WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure, do not install any
2-2
system component where service conditions could exceed the limits given in this manual. Use pressure-relieving devices as required by government or accepted industry codes and good engineering practices.
Refer to figure 2-5 for pressure connection locations. Supply, output, remote set point, external feedback, and vent connections are 1/4 NPT, internal. Process pressure connections are 1/4 or 1/2 NPT (optional). Use 1/4-inch or 3/8-inch pipe or tubing for supply, output, remote set point, and external feedback connections.
Instruction Manual
Form 5207 April 2007
LOCK WASHER (KEY 67)
HEX HEAD CAP SCREW (KEY 66)
BRACKET (KEY 68)
ROUND HEAD MACHINE SCREW (KEY 70)
TOP VIEW
13 (0.50)
84 (3.29)
62 (2.43)
63 (2.49)
14 R (0.56)
236 (9.31)
4195KA, KB, KC, and KS Controllers
161 (6.35)
306 (12.06)
152 (6.00)
TOP VIEW
260 (10.25)
LOCKWASHER (KEY 67)
HEX HEAD CAP SCREW (KEY 66)
REAR VIEW DIMENSIONS OF
36A9760-A A6733 / IL
PANEL CUTOUT
mm (INCH)
Figure 2-3. Panel Mounting

Process Pressure Connection

The connection marked A on the bottom of the case is the process input for all Bourdon tube controllers and those capsular element controllers used in vacuum pressure applications. The connection marked B is the process input for capsular element controllers used in positive pressure and compound pressure applications. See figure 2-5 for the location of the A and B connections.
When installing process piping, follow accepted practices to ensure accurate transmission of the process pressure to the controller. Install a three-valve bypass, shutoff valves, vents, drains, or seal systems as needed in the process pressure lines. If necessary, install a needle valve in a process pressure sensing line to dampen pulsations.
If the instrument is located such that the adjacent process pressure lines are approximately horizontal,
62
13 (0.50)
13 (0.50)
(2.43)
BRACKET (KEY 68)
REAR VIEW
36A9761-B A6734 / IL
mm (INCH)
Figure 2-4. Wall Mounting
the lines should slope downward to the instrument for liquid-filled lines and upward toward the instrument for gas-filled lines. This reduces the possibility of air becoming trapped in the sensor with liquid-filled lines or of condensation becoming trapped in gas-filled lines. The recommended slope is 83 millimeters per m (1 inch per foot).
If the controller is being used in conjunction with a control valve to control pipeline pressure, connect the process pressure line in a straight section of pipe approximately 10 pipe diameters away from the valve and also away from bends, elbows, and areas of abnormal fluid velocities. For pressure-reducing service, the process pressure line must be connected downstream of the control valve. For pressure-relief service, the process pressure line must be connected upstream of the control valve.
2-3
4195KA, KB, KC, and KS Controllers

Supply Pressure Connection

WARNING
Severe personal injury or property damage may occur if the instrument air supply is not clean, dry and oil-free, or noncorrosive gas. While use and regular maintenance of a filter that removes particles larger than 40 microns in diameter will suffice in most applications, check with an Emerson Process Management field office and industry instrument air quality standards for use with corrosive gas or if you are unsure about the proper amount or method of air filtration or filter maintenance.
Supply pressure must be clean, dry air or noncorrosive gas that meets the requirements of ISA Standard S7.3. Use a suitable supply pressure regulator to reduce the supply pressure source to the normal operating supply pressure shown in table 1-6. Connect supply pressure to the SUPPLY connection on the bottom of the case, shown in figure 2-5.

Remote Set Point (suffix letter M) Pressure Connection

1/4-18 NPT CONTROLLER OUTPUT CONNECTION
NOTES:
1 BOURDON TUBE CONTROLLERS AND FOR THOSE CAPSULAR ELEMENT CONTROLLERS USED IN VACUUM PRESSURE APPLICATIONS.
2 ELEMENT CONTROLLERS USED IN POSITIVE AND COMPOUND PRESSURE APPLICATIONS.
3 ONLY), EITHER THE A OR B CONNECTION IS USED, DEPENDING ON THE LOCA TION OF THE PROCESS CONNECTION.
46A9765-A A2892-4 / IL
Instruction Manual
Form 5207
April 2007
102
147 (5.80)
(4.00)
REAR VIEW
51 (2.00)
5/16 UNC-28 3 HOLES (MOUNTING)
3.44 (87)
10.04 (255)
1/4 NPT REMOTE SET POINT CONNECTION
TOP VIEW
mm (INCH)
260 (10.25)
FRONT VIEW
1/4-18 NPT VENT CONNECTION
BOTTOM VIEW
1/4-18 NPT PROCESS CONNECTION (MARKED A) FOR ALL
1/4-18 NPT PROCESS CONNECTION (MARKED B) FOR CAPSULAR
FOR THE EXTERNAL FEEDBACK CONNECTIONS (4195KB CONTROLLERS
130 (5.13)
330 (13.00)
1/4-18 NPT SUPPLY PRESSURE CONNECTION
66 (2.56)
31 (1.22)
1/4 NPT 4 HOLES
If the controller has remote set point (suffix letter M), connect the remote set point pressure to the top of the controller case at the location shown in figure 2-5. Use clean, dry air or noncorrosive gas. Use a
0.2 to 1.0 bar (3 to 15 psig) remote set point pressure range for a 0.2 to 1.0 bar (3 to 15 psig) controller output signal range or a 0.4 to 2.0 bar (6 to 30 psig) remote set point pressure range for a 0.4 to 2.0 bar (6 to 30 psig) controller output signal range. If pressure is supplied to the remote set point connection with a regulator, a small bleed orifice should be placed between the regulator and remote set point connection to prevent pressure variations due to regulator lock-up.
Figure 2-5. Connection Locations

External Feedback Pressure Connection (4195KB Series Controllers Only)

When a secondary controller in an override application has this option, reset windup is minimized in the secondary controller. Connect the external feedback connection of the secondary controller to the output of the customer-supplied high or low select relay (see figures 2-5 and 4-9).
2-4
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers

Vent

WARNING
Personal injury or property damage could result from fire or explosion of accumulated gas, or from contact with hazardous gas, if a flammable or hazardous gas is used as the supply pressure medium. Because the controller case and cover assembly do not form a gas-tight seal when the assembly is enclosed, a remote vent line, adequate ventilation, and necessary safety measures should be used to prevent the accumulation of flammable or hazardous gas. However, a remote vent pipe alone cannot be relied upon to remove all flammable or hazardous gas. Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside diameter and few bends to reduce case pressure buildup.
CAUTION
When installing a remote vent pipe, take care not to over-tighten the pipe in the vent connection. Excessive torque will damage the threads in the connection.
If a remote vent is required, the vent line must be as short as possible with a minimum number of bends and elbows. Vent line piping should have a minimum inside diameter of 19 mm (3/4 inches) for runs up to
6.1 meters (20 feet) and a minimum inside diameter of 25 mm (1 inch) for runs from 6.1 to 30.5 meters (20 to 100 feet).
The vent must be protected against the entrance of any foreign material that could plug it; or if a remote vent is not required, the vent opening in the case must be protected against the entrance of any foreign material that could plug it. Check the vent periodically to be certain it is not plugged.
2-5
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007
2-6
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
METAL BALL SWITCHING ZONE
INDICATOR
LOADER KNOB
AUTO/MANUAL SWITCH
W6832 / IL
Figure 3-1. 4195KA Series Controller Adjustment Locations

Section 3 4195KA Series Proportional-Only Controllers

Adjustments for 4195KA Series Controllers

This section includes descriptions of adjustments and procedures for prestartup, startup, and calibration. Adjustment locations are shown in figures 3-1 and 3-3. To better understand the adjustments and overall controller operation, refer to the Principle of Operation section and the schematic diagrams in figures 3-4 and 3-5. Unless otherwise noted, key numbers given in this section are found in figure 7-1.
SET POINT INDICATOR
PROCESS POINTER
PROPORTIONAL BAND ADJUSTMENT
PROPORTIONAL BAND INDICATOR COVER
OUTPUT PRESSURE GAUGE
W3679 / IL
AUTO/MANUAL STATION
(SUFFIX LETTER E)

Remote Set Point (suffix letter M) Adjustment

CAUTION
Do not manually move the set point indicator on controllers with remote set point. Manually moving the set point indicator could damage the controller.
If the controller is equipped with remote set point (suffix letter M), vary the remote set point pressure to change the set point. Increase the pressure to increase the set point, and decrease the pressure to decrease the set point.

Manual Set Point Adjustment

Adjust the set point by moving the set point indicator until the line on the set point indicator is over the desired value on the process pressure scale. Move the indicator to the right to increase the set point and to the left to decrease it. Adjusting the set point does not affect the proportional band setting.

Proportional Band Adjustment (PB ADJ)

The proportional band determines the controller output sensitivity. The proportional band adjustment is marked in percentages of process pressure required to drive the controller from zero output to full output.
3-1
4195KA, KB, KC, and KS Controllers
D For reverse control action:
An increasing sensed vacuum decreases output pressure.
After changing the action, tighten the screws on the proportional band indicator cover.

Switching The Auto/Manual Station (suffix letter E)

W3439 / IL
Figure 3-2. Changing Controller Action on
4195KA Series Controllers
To adjust the proportional band, open the controller cover and locate the proportional band adjustment (PB ADJ) knob. Rotate the knob until the desired value is opposite the line on the proportional band indicator cover.

Changing Controller Action

To change the controller action from direct to reverse or vice versa, loosen the screws on the proportional band indicator cover. Lift the cover out as shown in figure 3-2 and rotate the proportional band adjustment to the desired action. Setting the proportional band to the values in the white portion of the adjustment provides direct controller action; setting proportional band in the black portion provides reverse controller action.
Bourdon Tube or Capsular Element Controllers for Positive or Compound Pressure
Refer to figure 3-1 if the controller has the auto/manual station (suffix letter E). To switch from automatic to manual mode, or from manual to automatic, you must first balance the manual output with the controller output. Two balance methods are available to equalize the manual output with the controller output.
To switch from automatic to manual mode, carefully adjust the loader knob until the metal ball inside the plastic tube moves into the switching zone. Then move the automatic/manual switch to MANUAL. Turn the loader knob clockwise to increase the controller output or counterclockwise to decrease it.
To switch from manual to automatic mode, adjust the set point to move the ball into the switching zone. Turn the switch to AUTO and adjust the set point to control the output.
Instruction Manual
Form 5207
April 2007
Note
Switching the controller between automatic and manual, or manual and automatic mode, without balancing the outputs, can disturb the process and cause controller cycling.
D For direct control action:
An increasing sensed pressure increases output pressure.
D For reverse control action:
An increasing sensed pressure decreases output pressure.
Capsular Element Controllers for Vacuum Pressure
D For direct control action:
An increasing sensed vacuum increases output pressure.
3-2
When the auto/manual switch is in AUTO, adjusting the loader knob has no effect on the controller output. When the auto/manual switch is in MANUAL, changing the set point has no effect on the controller output.

Prestartup Checks for 4195KA Series Controllers

Refer to figure 3-1 for adjustment locations and refer to figure 7-1 for key number locations.
When performing the checks, open loop conditions must exist. An open loop exists when the controller output does not affect the input pressure or other control signal to the controller.
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
Note
If the controller has the auto/manual station (suffix letter E), be sure the controller is in the automatic mode before performing the prestartup checks.
1. Provide a means of measuring the controller output pressure by connecting the controller output to a pressure gauge. Connect supply pressure to the supply pressure regulator and be sure it is delivering the proper supply pressure to the controller. Do not exceed the normal operating pressure in table 1-6.
2. For a controller with remote set point (suffix letter M), connect regulated pressure of 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.1 bar (6 to 30 psig) to the remote set point connection at the top of the controller case.
3. Remove the two machine screws (key 6) and lift off the proportional band indicator cover (key 36).
4. Adjust the set point a minimum of 20 percent of input span above the process pointer.
5. Adjust the proportional band for 5 percent DIRECT.
6. If necessary, connect a pressure source to the process connection and adjust the process pointer to the last mark on the left side of the scale. If the last scale mark is 0 psig, a pressure source is not required.
7. The controller output pressure should be 0 bar (0 psig).
8. Rotate the proportional band to 5 percent REVERSE.
9. The controller output should be within 0.14 bar (2 psig) of the supply pressure.
Note
When performing the startup procedures, keep in mind that the initial settings are guidelines. They will vary depending on the actual process being controlled.
1. Be sure the supply pressure regulator is delivering the proper supply pressure to the controller.
2. For controllers with:
Manual set point:
Move the set point adjustment to the desired set point.
Remote set point:
a. See figure 2-5 for the location of the remote set point connection. Connect an adjustable pressure source to the remote set point connection.
b. Adjust the pressure source until the set point indicator reaches the desired set point. Remember: Increasing the remote set point pressure increases the set point.
3. Set the proportional band adjustment to 100 percent for fast processes. For slow processes, calculate the proportional band percentage from the equation below:
P.B. +
For example:
200 Allowable Overshoot
Pressure Span
10. If the controller output is within tolerance, adjust the proportional band to 400 percent in the desired action, secure the proportional band indicator cover (key 36) with the machine screws (key 6), and go to the startup procedure. If the controller output pressure is not within tolerance, go to the 4195KA Series calibration procedure for recalibration.

Startup for 4195KA Series Controllers

Perform the prestartup checks and, if necessary, calibrate the controller prior to this procedure.
200 0.14 bar
2.1 bar
4. Create a load upset by momentarily changing the set point. Check for system cycling. If the system does not cycle, lower the proportional band setting (thus raising the gain) and disturb the system again by changing the set point. Continue this procedure until the system cycles. At this point, double the proportional band setting (proportional band setting ×2).
5. Check the stability of the recommended proportional band setting by introducing a disturbance and monitoring the process.
^ 13%
3-3
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007

Calibration of 4195KA Series Controllers

WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure, do not exceed the operating limits given in this manual.

General Calibration Instructions

Note
If the controller has the auto/manual station (suffix letter E), be sure the controller is in the automatic mode before performing calibration.
If the prestartup checks, or startup, reveal faulty controller operation, perform the calibration described in this section. These instructions are valid for either shop or field calibration, provided that open process loop conditions exist. Unless otherwise noted, key numbers are found in figure 7-1.
Do not use the gauges supplied with the controller during calibration. Monitor process pressure, supply pressure, controller output pressure, and if applicable, remote set point pressure with external gauges.

Process Indicator Zero and Span Calibration

Before starting this procedure:
D Provide a regulated process pressure to the controller and a means of measurement external to the controller.
D Provide a means of measuring the controller output pressure by connecting the controller output to a pressure gauge (open loop conditions must exist). Provide a regulated supply pressure to the controller. Do not exceed the normal operating pressure in table 1-6.
readjustment of the process pointer zero adjustment.
1. Remove the two screws (key 6) and lift off the proportional band indicator cover (key 36).
2. Set the proportional band between DIRECT and REVERSE.
3. Apply process pressure equal to the process scale span lower limit.
4. The process pointer should indicate the process scale lower limit. If not, adjust the process pointer to the process scale lower limit by loosening the zero adjustment locking screw and turning the zero adjustment screw. Tighten the zero adjustment locking screw.
5. Apply process pressure equal to the process scale span upper limit.
6. The process pointer should indicate the process scale upper limit. If not, adjust the span screw to correct one-half of the error as follows: clockwise to increase span for a low indication (below the upper limit); counterclockwise to decrease span for a high indication (above the upper limit).
7. Repeat steps 3 through 6 until the error is eliminated.
8. Apply process pressure equal to the mid-scale value of the process scale span. The process pointer should indicate the mid-scale mark, ±2 percent of span. If the error is greater than ±2 percent, refer to the Maintenance section and perform the appropriate zero and span adjustment procedure for a Bourdon tube or capsular element controller.
9. Adjust the process pointer to within ±1 percent of the mid-scale mark by loosening the locking screw and turning the zero adjustment screw. This distributes the error over the entire scale span and brings all points within ±1 percent of the process input span.
10. Apply process pressure equal to the process scale span lower limit.
11. The process pointer should indicate the process scale lower limit ±1 percent of the scale span.
Refer to figures 3-1 and 3-3 for adjustment locations.
Note
Any change to the process pointer span adjustment will require
3-4
12. Apply process pressure equal to the process scale span upper limit.
13. The process pointer should indicate the process scale upper limit ±1 percent of the scale span.
14. If the error is greater than ±1 percent, repeat steps 3 through 13.
Instruction Manual
Form 5207 April 2007
REMOTE SET POINT ZERO ADJUSTMENT (SUFFIX LETTER M)
4195KA, KB, KC, and KS Controllers
POINTER ZERO ADJUSTMENT
POINTER ZERO ADJUSTMENT LOCKING SCREW
W6832 / IL
PROCESS POINTER SPAN ADJUSTMENT
A6730 / IL
REMOTE SET POINT ZERO ADJUSTMENT LOCKING SCREW (SUFFIX LETTER M)
39A1126-B
REMOTE SET POINT SPAN ADJUSTMENT (SUFFIX LETTER M)
SIDE VIEW OF SET POINT/
PROCESS INDICATOR ASSEMBLY
FRONT VIEW
PROCESS POINTER SPAN ADJUSTMENT
SCREW 1
SCREW 2
SCREW 3
56A9752-S SHT 1
SIDE VIEW OF CONTROLLER
SHOWING FLAPPER LEVELING SCREWS
Figure 3-3. 4195KA Series Controller Calibration Adjustment Locations
3-5
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007
Remote Set Point (suffix letter M) Zero and Span Calibration
Refer to figures 3-1 and 3-3 for adjustment locations. Refer to figure 7-1 for key number locations.
Note
Any adjustment of the remote set point span adjustment screw requires readjustment of the remote set point zero adjustment screw.
1. Remove the two screws (key 6) and lift off the proportional band indicator cover (key 36).
2. Set the proportional band between DIRECT and REVERSE.
3. Apply remote set point pressure equal to the lower range limit.
4. The set point indicator should indicate the process scale lower limit. If not, loosen the remote set point zero adjustment locking screw and adjust the remote set point zero adjustment screw until the set point indicator aligns with the process scale lower limit. Tighten the zero adjustment locking screw.
5. Apply remote set point pressure equal to the upper range limit.
6. The set point indicator should indicate the process scale upper limit. If not, adjust the remote set point span adjustment screw to correct one-half the error as follows: clockwise to increase span for a low indication; counterclockwise to decrease span for a high indication.
7. Repeat steps 3 through 6 until the error is eliminated.
8. Apply remote set point pressure equal to the mid-range value.
9. Make sure the set point indicator is within ±1 percent of the mid-scale mark and if so, proceed to step 12. If the set point indicator is not within 1 percent, but is within ±2 percent of the mid-scale mark, then proceed with step 10. If the set point indicator is not within ±2 percent, proceed to the remote set point calibration procedure in the Maintenance section.
10. Loosen the remote set point zero adjustment locking screw and adjust the remote set point zero adjustment screw to correct for half the error at mid-scale. Tighten the zero adjustment locking screw.
11. Apply remote set point pressure equal to the lower and upper range limits and make sure the set point indicator is within ±1 percent.
12. If necessary, perform the process indicator zero and span calibration procedure in this section. Otherwise, perform the flapper alignment procedure in this section.

Flapper Alignment

Note
Perform the process indicator zero and span calibration procedure and, for controllers with remote set point (suffix letter M), the remote set point zero and span calibration procedure before the flapper alignment.
Flapper leveling screw numbers and adjustments are shown in figure 3-3. Key number locations are shown in figure 7-1.
Provide a means of measuring the controller output pressure by connecting the controller output to a pressure gauge (open-loop conditions must exist). Provide a regulated supply pressure to the controller. Do not exceed the normal operating pressure in table 1-6. After performing the flapper alignment procedure, go to the startup procedure.
1. For a controller with manual set point, move the set point indicator to the mid-scale mark on the process scale. For a controller with remote set point (suffix letter M), adjust the remote set point pressure until the set point indicator is at the mid-scale mark on the process scale.
2. Apply process pressure equal to the mid-scale value of the process scale span. If pressure is not available to pressure the input element to the mid-scale value, an alternate method is to disconnect link number 1 at the input element and tape the process pointer at the mid-scale mark on the process scale. If the controller has a capsular input element, note the hole from which link number 1 was removed for proper replacement. This method should only be used if pressure is not available to pressure the input element to the mid-scale value.
3. Remove the two machine screws (key 6) and lift off the proportional band indicator cover (key 36).
4. Adjust the proportional band between DIRECT and REVERSE.
5. The controller output should be 0.62 ±0.007 bar (9 ±0.10 psig) for a 0.2 to 1.0 bar (3 to 15 psig) output or 1.2 ±0.01 bar (18 ±0.2 psig) for a 0.4 to 2.0 bar (6 to 30 psig) output. If not, adjust flapper leveling screw 2 (the screw nearest the nozzle) until the output is within tolerance.
6. Set the proportional band to 30 percent DIRECT.
3-6
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
SET POINT INDICATOR
PROCESS POINTER
REMOTE SET POINT CONNECTED HERE
INPUT ELEMENT CONNECTED HERE
CONNECTING LINK
BEAM
SUPPLY PRESSURE
OUTPUT PRESSURE
PROPORTIONAL PRESSURE
NOZZLE PRESSURE
46A9764-A B1489-2 / IL
PROPORTIONAL BELLOWS
FLAPPER
RESET BELLOWS (VENTED)
NOZZLE
Figure 3-4. 4195KA Series Controller Schematic
7. The controller output should be 0.62 ±0.02 bar (9 ±0.25 psig) or 1.2 ±0.04 bar (18 ±0.5 psig). If not,
adjust flapper leveling screw 3 (the screw nearest the nozzle).
8. Set the proportional band to 30 percent REVERSE.
9. The controller output should be 0.62 ±0.02 bar (9 ±0.25 psig) or 1.2 ±0.04 bar (18 ±0.5 psig). If not, adjust flapper leveling screw 1 (the screw nearest the nozzle).
10. Repeat steps 4 through 9 until the controller output remains in tolerance without further leveling screw adjustments.
REVERSE ACTION QUADRANT
PROPORTIONAL BAND ADJUSTMENT
FEEDBACK LINK
FEEDBACK MOTION
DIRECT ACTION QUADRANT
SUPPLY PRESSURE
INPUT MOTION
FLAPPER DETAIL
OUTPUT PRESSURE TO FINAL CONTROL ELEMENT
RELAY
FLAPPER PIVOT

Principle of Operation for 4195KA Series Controllers

Overall Operation

Refer to the schematic diagram in figure 3-4.
The input element is connected to the process pointer and to the flapper by connecting links. As the process pressure increases (in a direct-acting controller), the flapper moves toward the nozzle, restricting flow through the nozzle and increasing nozzle pressure. When this occurs, relay action increases the output pressure (delivery) of the controller. Output pressure is fed back to the proportional bellows. The action of the proportional bellows counteracts the flapper movement that resulted from the process pressure change and backs the flapper away from the nozzle until equilibrium is reached.
11. If link 1 was disconnected, remove the tape and reconnect link 1 to the input element.
12. Set the proportional band to 400 percent in the desired controller action and replace the proportional band indicator cover.
Moving the set point indicator changes the distance between the nozzle and flapper as does a change in process pressure, except that when the set point is changed, the nozzle moves with respect to the flapper.
The proportional band adjustment positions the nozzle on the flapper. Increasing (widening) the proportional band moves the nozzle to a position on
3-7
4195KA, KB, KC, and KS Controllers
AUTOMATIC POSITION
OUTPUT PRESSURE TO FINAL CONTROL ELEMENT
AUTO/MANUAL SWITCH
PLASTIC TUBE
METAL BALL
Instruction Manual
MANUAL LOADER
MANUAL LOADER KNOB
Form 5207
April 2007
RELAY
SUPPLY PRESSURE
RELAY OUTPUT PRESSURE
SUPPLY PRESSURE
MANUAL LOADER OUTPUT PRESSURE
48A5230-A A2999-1 / IL
Figure 3-5. 4195KA Series Auto/Manual Station Schematic
the flapper where less input and more feedback motion occurs, which decreases the gain of the controller. Decreasing (narrowing) the proportional band moves the nozzle toward a position where more input and less feedback motion occurs, which increases the gain. The controller action is changed from direct to reverse by turning the proportional band adjustment to position the nozzle on the flapper quadrant to a point where the direction of the flapper motion versus input motion is reversed as shown in the flapper detail of figure 3-4. With the controller in the reverse-acting mode, an increase in process pressure causes a decrease in output pressure.

Remote Set Point (suffix letter M) Operation

The capability to adjust the controller set point from a remote location is available with all 4195KA Series controllers. This option is designated by the letter M in the type number.
A control pressure is applied to the capsular element within the remote set point assembly. The expansion and contraction of the capsule moves the set point adjustment via a connecting linkage. Increasing the control pressure to the capsule increases the set point setting and decreasing the control pressure reduces the set point setting.
MANUAL POSITION
AUTO/MANUAL SWITCH
OUTPUT PRESSURE TO FINAL CONTROL ELEMENT

Auto/Manual Station (suffix letter E) Operation

A controller with the auto/manual station (designated by the suffix letter E in the type number) has piping on the output side of the relay as shown in figure 3-5. Supply pressure to the relay is also applied to the manual loader. The manual loader, functioning as a regulator, applies pressure to one side of the plastic tube and to the auto/manual switch. Output pressure from the relay registers on the other side of the plastic tube as well as in the auto/manual switch.
When the auto/manual switch is in the MANUAL position, the manual loader output is channeled through the auto/manual switch and becomes the controller output. When the auto/manual switch is in the AUTO position, the relay output is channeled through the switch to become the controller output.
Before the auto/manual switch is operated, the relay output must equal the manual loader output to avoid bumping the process. Adjusting the set point varies the pressure on the left-hand side of the plastic tube. Adjusting the manual loader knob varies the pressure on the right-hand side. When the pressures are equal, the metal ball is centered in the tube and it is held in place by a small magnet. A pressure imbalance forces the ball to one end of the tube where it forms a seal, blocking air flow through the tube.
3-8
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
METAL BALL SWITCHING ZONE
INDICATOR
LOADER KNOB
AUTO/MANUAL SWITCH
SET POINT INDICATOR
PROCESS POINTER
PROPORTIONAL BAND ADJUSTMENT
ANTI-RESET WINDUP DIFFERENTIAL RELIEF VALVE (SUFFIX LETTER F)
W3679 / IL
AUTO/MANUAL STATION
(SUFFIX LETTER E)
SUPPLY PRESSURE GAUGE
W6833 / IL
RESET ADJUSTMENT
TYPICAL ADJUSTMENTS
4195KB SHOWN
Figure 4-1. 4195KB and KC Series Controller Adjustment Locations
OUTPUT PRESSURE GAUGE
Section 4 4195KB Series Proportional­Plus-Reset Controllers and 4195KC Series Proportional­Plus-Reset-Plus-Rate Controllers

Adjustments for 4195KB and KC Series Controllers

This section includes descriptions of adjustments and procedures for prestartup, startup, and calibration. Adjustment locations are shown in figures 4-1 and 4-3. To better understand the adjustments and overall controller operation, refer to the Principle of Operation section and to the schematic diagrams in figures 4-5 through 4-9. Unless otherwise noted, key numbers given in this section are found in figure 7-1.

Manual Set Point Adjustment

Adjust the set point by opening the controller cover and moving the set point indicator until the line on
RATE ADJUSTMENT
W35991 / IL
4195KC RESET AND RATE ADJUSTMENTS
RESET ADJUSTMENT
the set point indicator is over the desired value on the process pressure scale. Move the indicator to the right to increase the set point and to the left to decrease it. Adjusting the set point does not affect the proportional band setting.

Remote Set Point (suffix letter M) Adjustment

CAUTION
Do not manually move the set point indicator on a controller with remote set point. Manually moving the set point indicator could damage the controller.
If the controller is equipped with remote set point (suffix letter M), vary the remote set point pressure to change the set point. Increase the pressure to increase the set point and decrease the pressure to decrease the set point.
4-1
4195KA, KB, KC, and KS Controllers
Capsular Element Controllers for Vacuum Pressure
D For direct control action:
An increasing sensed vacuum increases output pressure.
D For reverse control action:
An increasing sensed vacuum decreases output pressure.
After changing the action, tighten the screws on the
W3439 / IL
Figure 4-2. Changing Controller Action on
4195KB and KC Series Controllers

Proportional Band Adjustment (PB ADJ)

The proportional band determines the controller output sensitivity. The proportional band adjustment is marked in percentages of process pressure required to drive the controller from zero output to full output.
To adjust the proportional band, open the controller cover and locate the proportional band adjustment (PB ADJ) knob. Rotate the knob until the desired value is opposite the line on the proportional band indicator cover.

Changing Controller Action

To change the controller action from direct to reverse
or vice versa, loosen the screws on the proportional band indicator cover. Lift the cover out as shown in figure 4-2 and rotate the proportional band adjustment to the desired action. Setting the proportional band to the values in the white portion of the adjustment provides direct controller action; setting proportional band in the black portion provides reverse controller action.
Bourdon Tube or Capsular Element Controllers for Positive or Compound Pressure
D For direct control action:
An increasing sensed pressure increases output pressure.
D For reverse control action:
An increasing sensed pressure decreases output pressure.
proportional band indicator cover.

Reset Adjustment

To adjust reset, open the controller cover and locate
the RESET adjustment. Rotate the adjustment clockwise to decrease the minutes per repeat or counterclockwise to increase the minutes per repeat. Increasing the minutes per repeat provides a slower reset action.

Rate Adjustment

To adjust rate, open the controller cover and locate the RATE adjustment. Rotate the adjustment clockwise to decrease the minutes (less rate action) or counterclockwise to increase the minutes (more rate action).

Anti-Reset Windup (suffix letter F) Adjustment

If the arrow on the relief valve points toward the bottom of the controller case, as shown in figure 4-1, the valve opens with increasing controller output pressure. If the arrow points in the opposite direction, the relief valve opens with decreasing controller output pressure. Differential relief pressure is factory set at 0.3 bar (5 psig). Maximum relief pressure is 0.5 bar (7 psig). The minimum is 0.1 bar (2 psig).
Turn the adjusting screw counterclockwise to increase differential relief pressure, clockwise to decrease it.
Instruction Manual
Form 5207
April 2007
4-2
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers

Switching the Auto/Manual Station (suffix letter E)

Note
Switching the controller between automatic and manual, or manual and automatic mode, without balancing the outputs, can disturb the process and cause controller cycling.
Refer to figure 4-1 if the controller has the auto/manual station (suffix letter E). To switch from automatic to manual mode, or from manual to automatic, you must first balance the manual output with the controller output. Two balance methods are available to equalize the manual output with the controller output.
To switch from automatic to manual mode, carefully adjust the loader knob until the metal ball inside the plastic tube moves into the switching zone. Then move the automatic/manual switch to MANUAL. Turn the loader knob clockwise to increase the controller output or counterclockwise to decrease it.
To switch from manual to automatic mode, adjust the set point to move the ball into the switching zone. Turn the switch to AUTO and adjust the set point to control the output.
When the automatic/manual switch is in AUTO, adjusting the loader knob has no effect on the controller output. When the automatic/manual switch is in MANUAL, changing the set point has no effect on the controller output.

Prestartup Checks for 4195KB and KC Series Controllers

Refer to figure 4-1 for adjustment locations, and refer to figure 7-1 for key number locations.
When performing the checks, open loop conditions must exist. An open loop exists when the controller output does not affect the input pressure or other control signal to the controller.
controller output connection to the external feedback connection (see figure 2-5). Adjust the controller for full output pressure and with the RESET knob adjusted to 0.01 minutes/repeat, verify the tubing connections do not leak. Disconnect after completing the prestartup checks.
1. Provide a means of measuring the controller output pressure by connecting the controller output to a pressure gauge. Connect supply pressure to the supply pressure regulator and be sure it is delivering the proper supply pressure to the controller. Do not exceed the normal operating pressure in table 1-6.
2. For a controller with remote set point (suffix letter M), connect regulated pressure of 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.1 bar (6 to 30 psig) to the remote set point connection at the top of the controller case.
3. Remove the two machine screws (key 6) and lift off the proportional band indicator cover (key 36).
4. Adjust the set point a minimum of 20 percent of input span above the process pointer.
5. Turn the reset adjustment to 0.01 minutes per repeat.
6. Turn the rate adjustment to OFF (4195KC Series).
7. Adjust the proportional band for 5 percent DIRECT.
8. If necessary, connect a pressure source to the process connection and adjust the process pointer to the last mark on the left side of the scale. If the last scale mark is 0 bar (0 psig), a pressure source is not required.
9. The controller output pressure should be 0 bar (0 psig).
10. Rotate the proportional band to 5 percent REVERSE.
11. The controller output should be within 0.14 bar (2 psig) of the supply pressure.
Note
If the controller has the auto/manual station (suffix letter E), be sure the controller is in the automatic mode before performing prestartup checks. If the controller has the external feedback option, connect the
12. If the controller output is within tolerance, adjust the proportional band to 400 percent in the desired action. Secure the proportional band indicator cover (key 36) with the machine screws (key 6), and go to the startup procedure. If the controller output pressure is not within tolerance, go to the 4195KB and KC Series calibration procedure for recalibration.
4-3
4195KA, KB, KC, and KS Controllers
Instruction Manual
Form 5207
April 2007

Startup for 4195KB and KC Series Controllers

Perform the prestartup checks and, if necessary, calibrate the controller prior to this procedure.
Note
When performing the startup procedures, keep in mind that the initial settings are guidelines. They will vary depending on the actual process being controlled.
1. Be sure the supply pressure regulator is delivering the proper supply pressure to the controller.
2. For controllers with:
Manual set point:
Move the set point indicator to the desired set point.
Remote set point:
a. See figure 2-5 for the location of the remote set point connection. Connect an adjustable pressure source to the remote set point connection.
b. Adjust the pressure source until the set point indicator reaches the desired set point. Remember: Increasing the remote set point pressure increases the set point.
3. Set the reset adjustment to 0.05 minutes per repeat for fast processes. Set it to 0.5 minutes per repeat for slow processes. For controllers with rate, set the rate adjustment to OFF.
4. Set the proportional band to 100 percent for fast processes. For slow processes, calculate the proportional band percentage from the equation below:
P.B. +
For example:
5. If the controller is used in conjunction with a control valve, return the control valve to service by slowly opening the upstream and downstream manual control valves in the pipeline. Close the manual bypass valve, if one is used.
6. Tune the various controller actions.
200 Allowable Overshoot
Pressure Span
200 0.14 bar
2.1 bar
^ 13%
Tuning proportional action: Create a load upset
by momentarily changing the set point. Check for system cycling. If the system does not cycle, lower the proportional band setting (thus raising the gain) and disturb the system again by changing the set point. Continue this procedure until the system cycles. At this point, double the proportional band setting (proportional band setting ×2).
Tuning reset action: Disturb the system. If the
system does not cycle, speed up the reset by changing the setting to a lower value (faster reset). Disturb the system again. Continue this procedure until the system cycles. When the system cycles, multiply the reset time setting by a factor of three (reset setting ×3) and slow down the reset by changing the reset setting to the higher value. The reset is now tuned.
Tuning rate action: For a controller with rate
(4195KC Series), adjust the rate toward the higher setting until cycling occurs. When the system cycles, divide the rate value by a factor of three (rate setting ÷3) and decrease the rate by changing the setting to the lower value. The rate is now tuned.
7. Check the stability of the recommended proportional band setting by introducing a disturbance and monitoring the process.
8. Once stable control is attained, the process pointer and set point indicator should be in line. If they are aligned, return the set point to the desired value. If they are not, readjust the set point to the desired control point and proceed with step 9.
9. If the process pointer is within 5 percent of the set point indicator, turn the link 3 adjustment (see figure 6-13 or 6-21 for location) until the process pointer aligns with the set point indicator. Turn the link 3 adjustment screw clockwise to increase the process indication or counterclockwise to decrease it. If the process pointer is misaligned with the set point indicator by more than 5 percent of the scale span, perform the calibration procedures for 4195KB and KC Series controllers.

Calibration of 4195KB and KC Series Controllers

WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure, do not exceed the operating limits given in this manual.
4-4
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers

General Calibration Instructions

Note
If the controller has the auto/manual station (suffix letter E), be sure the controller is in the automatic mode before performing calibration.
If the prestartup checks, or startup, reveal faulty controller operation, perform the calibration described in this section. These instructions are valid for either shop or field calibration, provided that open loop conditions exist. Unless otherwise noted, key numbers are found in figure 7-1.
Do not use the gauges supplied with the controller during calibration. Monitor process pressure, supply pressure, controller output pressure, and if applicable, remote set point pressure with external gauges.

Process Indicator Zero and Span Calibration

Before starting this procedure:
D Provide a regulated process pressure to the controller and a means of measurement external to the controller.
D Provide a means of measuring the controller output pressure by connecting the controller output to a pressure gauge (open-loop conditions must exist). Provide a regulated supply pressure to the controller. Do not exceed the normal operating pressure in table 1-6.
Refer to figures 4-1 and 4-3 for adjustment locations.
Note
Any change to the process pointer span adjustment will require readjustment of the process pointer zero adjustment.
1. Remove the two screws (key 6) and lift off the proportional band indicator cover (key 36).
2. Set the proportional band between DIRECT and REVERSE.
3. Apply process pressure equal to the process scale span lower limit.
4. The process pointer should indicate the process scale lower limit. If not, adjust the process pointer to the process scale lower limit by loosening the zero adjustment locking screw and turning the zero
adjustment screw. Tighten the zero adjustment locking screw.
5. Apply process pressure equal to the process scale span upper limit.
6. The process pointer should indicate the process scale upper limit. If not, adjust the process pointer span screw to correct one-half the error as follows: clockwise to increase span for a low indication (below the upper limit); counterclockwise to decrease span for a high indication (above the upper limit).
7. Repeat steps 3 through 6 until the error is eliminated.
8. Apply process pressure equal to the mid-scale value on the process scale span. The process pointer should indicate the mid-scale mark, ±2 percent of span. If the error is greater than ±2 percent, refer to the Maintenance section and perform the appropriate zero and span adjustment procedure for Bourdon tube or capsular element controllers.
9. Adjust the process pointer to within ±1 percent of the mid-scale mark by loosening the zero adjustment locking screw and turning the zero adjustment screw. This distributes the error over the entire scale range and brings all points within ±1 percent of the process scale span.
10. Apply process pressure equal to the process scale lower limit.
11. The process pointer should indicate the process scale lower limit ±1 percent of the scale span.
12. Apply process pressure equal to the process scale upper limit.
13. The process pointer should indicate the process scale upper limit ±1 percent of the process scale span.
14. If the error is greater than ±1 percent, repeat steps 3 through 13.

Remote Set Point (suffix letter M) Zero and Span Calibration

Refer to figures 4-1 and 4-3 for adjustment locations. Refer to figure 7-1 for key number locations.
Note
Any adjustment of the remote set point span adjustment screw requires readjustment of the remote set point zero adjustment screw.
1. Remove the two screws (key 6) and lift off the proportional band indicator cover (key 36).
4-5
4195KA, KB, KC, and KS Controllers
POINTER ZERO ADJUSTMENT
POINTER ZERO ADJUSTMENT LOCKING SCREW
PROCESS POINTER SPAN ADJUSTMENT
ANTI-RESET WINDUP RELIEF VALVE (SUFFIX LETTER F)
ANTI-RESET WINDUP VALVE ADJUSTING SCREW (SUFFIX LETTER F)
Instruction Manual
Form 5207
April 2007
W6833 / IL
REMOTE SET POINT ZERO ADJUSTMENT (SUFFIX LETTER M)
REMOTE SET POINT ZERO ADJUSTMENT LOCKING SCREW (SUFFIX LETTER M)
FRONT VIEW, 4195KB SERIES
PROCESS POINTER SPAN ADJUSTMENT
SIDE VIEW OF
SET POINT/PROCESS
INDICATOR ASSEMBLY
39A1126-B A6731 / IL
RESET ADJUSTMENT
REMOTE SET POINT SPAN ADJUSTMENT (SUFFIX LETTER M)
RATE ADJUSTMENT
W35991 / IL
59A9752-S SHT 1
SIDE VIEW OF
CONTROLLER SHOWING
FLAPPER LEVELING SCREWS
4195KC SERIES
SCREW 1
SCREW 2
SCREW 3
RESET ADJUSTMENT
4-6
Figure 4-3. 4195KB and KC Series Controller Calibration Adjustment Locations
Instruction Manual
Form 5207 April 2007
4195KA, KB, KC, and KS Controllers
2. Set the proportional band between DIRECT and REVERSE.
3. Apply remote set point pressure equal to the lower range limit.
4. The set point indicator should indicate the process scale lower limit. If not, loosen the remote set point zero adjustment locking screw and adjust the remote set point zero adjustment screw until the set point indicator aligns with the process scale lower limit. Tighten the zero adjustment locking screw.
5. Apply remote set point pressure equal to the upper range limit.
6. The set point indicator should indicate the process scale upper limit. If not, adjust the remote set point span adjustment screw to correct one-half the error as follows: clockwise to increase span for a low indication; counterclockwise to decease span for a high indication.
7. Repeat steps 3 through 6 until the error is eliminated.
8. Adjust the remote set point pressure to the mid-range value.
9. Make sure the set point indicator is within ±1 percent of the mid-scale mark, and if so, proceed to step 12. If the set point indicator is not within 1 percent, but is within ±2 percent of the mid-scale mark, proceed with step 10. If the set point indicator is not within ±2 percent, proceed to the remote set point zero and span adjustment procedure in the Maintenance section.
10. Loosen the remote set point zero adjustment locking screw and adjust the remote set point zero adjustment screw to correct for half the error at mid scale. Tighten the zero adjustment locking screw.
11. Apply remote set point pressure equal to the lower and upper range limits and make sure the set point indicator is within ±1 percent.
12. If necessary, perform the process indicator zero and span calibration procedure in this section. Otherwise, perform the flapper alignment procedure in this section.

Flapper Alignment

Note
Perform the process indicator zero and span calibration procedure and, for controllers with remote set point (suffix letter M), the remote set point
zero and span calibration procedure before the flapper alignment.
Flapper leveling screw numbers and adjustments are shown in figure 4-3. Key number locations are shown in figure 7-1.
Provide a means of measuring the controller output pressure by connecting the controller output to a pressure gauge (open-loop conditions must exist). Do not apply supply pressure at this time.
Note
4195KB and KC Series controllers with anti-reset windup (suffix letter F) are supplied with two O-rings (key 52), valve cover (key 51), and two machine screws (key 53). Use these parts in the next step.
1. For controllers with anti-reset windup (suffix letter F), record the direction of the arrow on the anti-reset windup relief valve (key 55). Remove the relief valve and install the two O-rings (key 52) and valve cover (key 51) supplied with the controller. Secure the valve cover with the two machine screws (key 53) provided.
2. If necessary, remove the two machine screws (key 6) and lift off the proportional band indicator cover (key 36).
3. If the controller has the external feedback option (available with the 4195KB Series only), connect the controller output to the external feedback connection. See figure 2-5 for the location of the output and external feedback connections.
4. Provide regulated supply pressure to the controller. Do not exceed the normal operating pressure in table 1-6.
5. For a controller with manual set point, move the set point indicator to the mid-scale mark on the process scale. For a controller with remote set point (suffix letter M), adjust the remote set point pressure until the set point indicator is at the mid-scale mark on the process scale.
6. Set the reset adjustment to 0.01 minutes per repeat.
7. If the controller has rate (4195KC Series), turn the rate adjustment to OFF.
8. Apply process pressure equal to the mid-scale value of the process scale span. If pressure is not available to pressure the input element to mid-scale value, an alternate method is to disconnect link number 1 at the input element and tape the process pointer at mid-scale mark on the process scale. If
4-7
4195KA, KB, KC, and KS Controllers
the controller has a capsular input element, note the hole where link number 1 is connected to the input element, then disconnect link 1. This method should only be used if pressure is not available to pressure the input element to the mid-scale value.
Instruction Manual
Form 5207
April 2007
Note
Because of the high controller gain, the controller output will not remain stable in steps 9 through 13. The controller output gauge is adequate to check the output pressure during this procedure.
9. Set the proportional band between DIRECT and REVERSE.
10. The controller output should be relatively stable at any value within the output range. If not, adjust flapper leveling screw 2 (the screw nearest the nozzle) until the output is relatively stable.
11. Set the proportional band to 30 percent DIRECT. The controller output should be relatively stable at any value within the output range. If not, adjust flapper leveling screw 3 (the screw nearest the nozzle) until the output is relatively stable.
12. Set the proportional band to 30 percent REVERSE. The controller output should be relatively stable at any value within the output range. If not, adjust flapper leveling screw 1 (the screw nearest the nozzle) until the output is relatively stable.
13. Repeat steps 9 through 12 until the controller output remains relatively stable without further flapper leveling screw adjustment.
Note
Steps 14 through 20 check the flapper alignment.
14. Set the proportional band to 30 percent DIRECT.
W4039 / IL
W4038 / IL
Figure 4-4. Alignment of the Process Pointer with the
RIGHT-HAND EDGE
LEFT-HAND EDGE
Set Point Indicator
15. Apply process pressure to the input element or, if link 1 was disconnected, remove the tape from the process pointer and move the pointer until it aligns with the right-hand edge of the set point indicator as shown in figure 4-4.
The controller output should be within 0.14 bar (2 psig) of the supply pressure.
16. Apply process pressure to the input element or, if disconnected, move the process pointer until it aligns with the left-hand edge of the set point indicator as shown in figure 4-4.
The controller output pressure should go to 0 bar (0 psig).
17. Set the proportional band to 30 percent REVERSE.
18. Apply process pressure to the input element or, if disconnected, move the process pointer until it aligns with the right-hand edge of the set point indicator as shown in figure 4-4. The controller output should be 0 bar (0 psig).
19. Apply process pressure to the input element or, if disconnected, move the process pointer until it aligns with the left-hand edge of the set point indicator as shown in figure 4-4. The controller output should be within 0.14 bar (2 psig) of the supply pressure.
20. If the controller does not perform as indicated in steps 14 through 19, the flapper is not correctly
4-8
Loading...
+ 78 hidden pages