This manual contains important instructions that should be followed during installation of your
Liebert
Read this manual thoroughly, paying special attention to the sections that apply to your installation,
before working with the UPS. Retain this manual for use by installing personnel.
®
NX™ UPS and ancillary equipment.
WARNING
Risk of heavy unit tipping over. Can cause property damage, injury and death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel. The UPS module weight ranges from 1180 to 2205 lb. (535 to 1000kg).
Determine unit weight and locate center of gravity symbols
before handling the UPS. Test lift and balance the cabinet
before transporting. Never tilt equipment more than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
followed implicitly at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In
addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 480VDC
and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance. Be constantly aware that the
UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.
WARNING
Risk of electric shock. Can cause injury and death.
Dangerous voltages are present within the UPS and battery enclosure. The risk of contact
with these voltages is minimized as the live component parts are housed behind a hinged,
lockable door. Further internal safety screens make the equipment protected to IP20
standards.
No risk exists to any personnel when operating the equipment in the normal manner,
following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be
carried out only by trained personnel.
WARNING
Risk of electric shock from high leakage current. Can cause injury, property damage and
death.
High ground leakage current: Ground connection is essential before connecting the input
supply.
This equipment must be grounded in accordance with local electrical codes.
Maximum load must not exceed that shown on the UPS rating label.
1
!
WARNING
!
Risk of electric shock. Can cause injury and death.
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess
moisture and debris.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system and the batteries. Observe all safety precautions in this
manual before handling or installing the UPS system. Observe all precautions in this manual,
before as well as during performance of all maintenance procedures. Observe all battery
safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only
test equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making
contact or using tools. Even when the power is turned Off, dangerously high electric charges
may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power
and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system.
When performing maintenance with any part of the equipment under power, service
personnel and test equipment should be standing on rubber mats. The service personnel
should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should
be standing by to assist and summon help in case an accident should occur.
CAUTION
This equipment is fitted with RFI suppression filters.
Ground leakage current exceeds 3.5 mA and is less than 30 mA.
Transient and steady-state ground leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous residual current
circuit breakers (RCCBs) or residual current devices (RCDs).
RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to
transient current pulses.
Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.
NOTICE
Risk of improper improper electromagnetic shielding. Can cause radio communication
interference.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. This unit is not designed for use in a residential area.
Operation of this unit in a residential area may cause harmful interference that the user must
correct at his own expense.
2
Battery Cabinet Precautions
!
!
The following warning applies to all battery cabinets supplied with UPS systems. Additional
warnings and cautions applicable to battery cabinets may be found in 4.0 - Battery Installation.
WARNING
Risk of electric shock. Can cause injury, property damage and death.
Special care should be taken when working with the batteries associated with this equipment.
Batteries are always live. Battery terminal voltage will exceed 480VDC and is potentially
lethal.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns.
Batteries should be installed, serviced and replaced only by properly trained and qualified
service personnel trained in safe battery handling methods and who have the correct PPE
(Personal Protection Equipment) and tools.
The following precautions should be observed when working with the batteries:
• Eye protection should be worn to prevent injury from electrical arcs.
• Remove rings, watches and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves and boots.
• When replacing batteries, replace them with the same type and number of batteries or battery packs.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
• Never lay metal objects of any type on top of the batteries.
• Disconnect the charging source before connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance.
WARNING
Risk of heavy unit tipping. Can cause property damage, injury and death.
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
(after initial installation).
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
WARNING
Risk of electric shock. Can cause injury and death.
The Liebert
Off. To minimize the risk of injury, a properly trained and qualified service person should
disconnect the batteries before any maintenance is performed on the unit.
Servicing of batteries should be performed or supervised only by properly trained and
qualified personnel knowledgeable about batteries and the required precautions.
When replacing batteries, replace with the same manufacturer and type, or equivalent. See
your local Emerson
®
NX’s internal batteries are connected and energized even if the UPS is turned
®
representative for a list of approved batteries.
3
!
CAUTION
Risk of replacing battery with an incorrect type. Can cause property damage injury and
death.
Dispose of used batteries according to the instructions.
When replacing batteries, replace with the same manufacturer and type, or equivalent. See
your local Emerson representative for a list of approved batteries.
4
GLOSSARYOF SYMBOLS
!
PbH2SO4
-
+
R
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
5
1.0INTRODUCTION
The Liebert® NX™ Uninterruptible Power Supply system provides continuous, high-quality AC power
to your business-critical equipment, such as telecommunications and data processing equipment.
The Liebert NX UPS is a SmartAisle
approach.
The Liebert NX supplies power that is free of the disturbances and variations in voltage and
frequency common to utility power, which is subject to brownouts, blackouts, surges and sags.
The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation
technology and fully digital controls to enhance its reliability and increase the ease of use.
Introduction
™
technology, appropriate for use with the SmartAisle design
6
2.0INSTALLATION
!
!
!
This section describes the Liebert® NX™ environmental requirements and mechanical considerations
that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site is unique, this section presents a guide to general procedures and practices that
should be observed by the installing engineer, rather than step-by-step installation instructions.
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the commissioning
engineer.
WARNING
The UPS equipment should be installed by a qualified engineer in accordance with the
information contained in this section.
WARNING
Risk of electric shock. Can cause injury and death.
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the nominal battery voltage is 480VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately
with large amounts of water.
Installation
NOTE
The Liebert NX UPS can be used in TN utility system.
2.1External Inspections
1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for
any signs of damage or mishandling. Do not attempt to install the system if damage is apparent.
If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact
Emerson Network Power
claim and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the
carrier and your local Liebert representative immediately.
2.2Internal Inspections
1. Remove any packaging material, then visually examine the UPS and battery equipment for
transit damage, both internally and externally. Report any such damage to the shipper and to
Liebert immediately.
2. Check the nameplate inside the cabinet door to verify that the model number and rating
correspond to the ones specified. Record the model number and serial number in the front of this
installation manual. This information is necessary should service be required.
3. Check for loose connections or unsecured components in the cabinet.
4. Check for shipping damage to internal components.
®
Liebert Services at 1-800-LIEBERT to inform them of the damage
7
2.2.1Storing for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the humidity is no
higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect
the Liebert
®
NX™ from excessive moisture (see 6.2 - UPS Environmental).
NOTE
If the battery cabinet must remain disconnected from power for more than six (6) months, the
battery must be recharged before use. To charge the batteries, the battery cabinet must be
connected to the Liebert NX UPS and the UPS must be connected to utility power and started
up because the charger operates only while the Liebert NX UPS is operating
NOTE
When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the
UPS—dictates the designed maximum ambient operating temperature.
2.3Preliminary Checks
2.3.1Identification
The equipment supplied has an identification tag on the back of the main door listing the type and
size of the UPS.
2.4UPS Location
2.4.1Positioning the UPS
Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency
2.4.2Environmental Considerations
Installation
Before installing the Liebert NX, verify that the UPS room satisfies the environmental conditions
stipulated in 6.2 - UPS Environmental, paying particular attention to the ambient temperature
and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating
temperature within the range of 74-80°F, (23-27°C).
The Liebert NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit
and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or
cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit
must be a minimum of 8 in. (203mm).
See Table 7 for details on heat dissipation.
8
Battery Location
!
!
Batteries must be installed in Liebert® NX™ 480V battery cabinets or battery room. Temperature is a
major factor in determining battery life and capacity. Battery manufacturers recommend an
operating temperature of 77°F (25°C). Ambient temperatures higher than this reduce battery life;
temperatures lower than this reduce battery capacity. In a typical installation, battery temperature
should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are
no main heat sources or air inlets to prevent portions of batteries from being either much warmer or
much cooler than other parts of the batteries.
2.4.3Special Considerations for Parallel Systems
1. Consider the grounding configuration of your system before finalizing module placement. For
optimal ground performance, the Liebert NX modules should be close together.
2. For optimal load-sharing performance, the UPS output cables should be approximately the same
length, plus or minus 20 percent.
3. Position modules in such a way as to minimize the length of power cables and control wiring
between UPS modules and the paralleling cabinet.
2.5Considerations in Moving the Liebert NX
Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any
handling equipment. See Table 7 for weights of various units.
To move the UPS and optional battery cabinets:
• The Liebert NX may be rolled on its casters when moving the unit a short distance. For longer distances, move the UPS with a forklift or similar equipment to ease the relocation and to reduce
vibration.
Installation
The optional battery cabinets should be moved with a forklift or similar equipment.
WARNING
Risk of heavy unit falling. Can cause property damage, injury and death.
Ensure that any equipment that will be used to move the Liebert NX has sufficient lifting
capacity. The Liebert NX weight ranges from 1180 to 2201 lb. (535 to 1000kg). See Table 7 for
details. The UPS presents a tipping hazard. Do not tilt the Liebert NX further than 15
degrees from vertical.
The UPS is fitted with casters—take care to prevent movement when unbolting the
equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are
available when taking the Liebert NX off its shipping pallet. Do not tilt the unit more than 15
degrees from center.
WARNING
Risk of heavy unit falling. Can cause property damage, injury and death.
The casters are strong enough for movement across even surfaces only. Casters may fail if
they are subjected to shock loading, such as being dropped or rolled over holes in the floor or
obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging
the equipment.
Care must be taken when maneuvering cabinets fitted with batteries. Keep such moves to a
minimum. For further information, see Battery Cabinet Precautions on page 3.
Final Position
When the equipment has been finally positioned, ensure that the adjustable stops are set so that the
UPS will remain stationary and stable (see 8.0 - Installation Drawings).
9
2.6Mechanical Considerations
!
The Liebert NX is constructed with a steel frame and removable panels. Top and side panels are
secured to the chassis by screws. The doors may be opened for access to power connections bars,
auxiliary terminal blocks and power switches.
The UPS comes with an operator control panel, which provides basic operational status and alarm
information. Cooling is provided by internal fans. The unit sits on four casters. Adjustable stops are
provided to prevent the UPS from moving once it has been moved to its final position.
2.6.1Clearances
There are no ventilation grilles on the sides or rear of the UPS. The unit may be placed with the rear
against a wall and optional cabinets on either side.
Installation
To enable routine tightening of power terminations within the UPS, make sure there is sufficient
clearance in front of the Liebert
Leave a minimum of 8 in. (203mm) between the top of the UPS and the ceiling to permit adequate air
circulation above the unit. Liebert recommends against using air conditioning or other systems that
blow air onto the top of the unit.
2.6.2Floor Installation
The diagrams in 8.0 - Installation Drawings show the location of holes in the base plate for bolting
the equipment to the floor.
If the equipment is to be placed on a raised floor, it should be mounted on a pedestal that will support
the equipment point loading. Refer to the cabinet-bottom views in 8.0 - Installation Drawings to
design this pedestal.
2.6.3Cable Entry
Cables can enter the Liebert NX from the top or bottom. Cable entry is made possible by removing a
metal plate attached to the UPS.
These plates are designed to allow the personnel to punch holes for fitting and securing the conduit.
Once the conduit holes are punched, these plates should be reattached to the UPS.
WARNING
Risk of explosion and fire. Can cause property damage, injury and death.
To reduce the risk of fire, connect only to a circuit provided with correct amperes maximum
branch circuit overcurrent protection (see Table 8) in accordance with the National Electric
Code, ANSI/NFPA 70.
®
NX™ to permit free passage of personnel with the door fully opened.
NOTE
When installing the UPS, the customer must provide a disconnect with overcurrent protection
at the output of the UPS.
System Composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system
design requirements—e.g., UPS cabinet with External Bypass cabinet and Maintenance Bypass
cabinet. In general, all cabinets used will be the same height and are designed to be positioned sideby-side to form an aesthetically appealing equipment suite.
10
2.6.4Optional Cabinets
Front of Units
Battery
Cabinet
Battery
Cabinet
Battery
Cabinet
Liebert
NX
UPS
Front of Units
Battery
Cabinet
Battery
Cabinet
Battery
Cabinet
Liebert
NX
UPS
Front of Units
Multi-Module
Parallel Cabinet
Battery
Cabinet
Battery
Cabinet
Battery
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Liebert
NX
UPS
Liebert
NX
UPS
Battery
Cabinet
Front of Units
Front of Units
Battery
Cabinet
Liebert
NX
UPS
Battery
Cabinet
Liebert
NX
UPS
The Maintenance Bypass Cabinet must be cabled and bolted to the Liebert NX before the UPS and
bypass cabinet are moved into their final position. Connect the input wiring to the Maintenance
Bypass Cabinet ONLY after the units are connected and positioned.
Battery cabinets may be bolted to either side of the Liebert NX; see Figure 1.
Figure 1Cabinet arrangement—Liebert
®
NX™ units and battery cabinets
Installation
11
Installation
Front of Units
Liebert NX
Bypass
Distribution
Cabinet
Battery
Cabinet
Liebert
NX
UPS
Front of Units
Liebert NX
Bypass
Distribution
Cabinet
Battery
Cabinet
Battery
Cabinet
Battery
Cabinet
Liebert
NX
UPS
Figure 2Cabinet arrangement—Liebert® NX™ UPS, battery cabinets and Liebert NX bypass distribution
cabinets
12
3.0ELECTRICAL CONNECTIONS
!
The UPS requires both power and control cabling once it has been mechanically installed. All control
cables must run separate from power cables in metal conduits or metal ducts that are electrically
bonded to the metalwork of the cabinets to which they are connected.
WARNING
Risk of electrical shock. Can cause injury and death.
Before connecting input power to the Liebert
and operation of the overcurrent protection devices that connect the UPS input/bypass supply
to the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before
installing cables or making any electrical connections.
3.1Power Cabling
3.1.1Cable Rating
The main factors affecting the choice and size of cable are voltage, current (also taking into account
overcurrent), room temperature and conditions of installation of the cable.
The power cables of the system must be sized with respect to the following description:
Electrical Connections
®
NX™, ensure that you are aware of the location
• UPS input cables - The UPS input cables must be sized for the maximum input current, including the maximum battery recharge current, given in Table 8, with respect to the unit rating and
the input AC voltage.
• UPS bypass and output cables - The bypass and output cables must be sized for the nominal
output current, given in Table 8, with respect to the unit rating and the output AC voltage.
• Battery cables - When connecting an external battery cabinet, the battery cables must be sized
for the battery discharge current at the end-of-discharge voltage, as given in Table 8, with
respect to the unit rating.
NOTE
Table 8 gives nominal currents for determining the size of UPS power cables. Other important
factors to consider include cable route length and coordination with protective devices.
The power cables can be sized to suit the UPS unit rating according to Table 8.
NOTE
When installing a Liebert NX with Softscale
bypass and output cabling for the UPS’s maximum rating. Properly sizing the cable will
reduce the work required to upgrade the UPS.
™
capability Liebert recommends sizing the input,
Lug Size and Torque Requirements
Refer to Table 34 for lug size and torque requirements.
13
3.1.2UPS Input Configuration
3-Phase
3W + Gnd
3-Phase
3W + Gnd
AC Input
AC Output
3-Phase
3W + Gnd
Battery Cabinet
2W + Gnd
UPS Cabinet
Conv erter
InverterRectifier
Static Bypass
Internal Maintenance Bypass
Figure 3 illustrates the Liebert® NX™ in a split bypass (dual-input) configuration. In this
configuration, the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed
from the Main input. Both sources must be protected externally with properly sized protective
devices. By default, the unit ships with internal links installed between the bypass input and main
input (Single Input configuration). To wire the unit as a dual input UPS, remove the links and wire
the bypass to the input bus bars, then wire the main input directly to CB1 (see Figure 3).
The following are guidelines only and are superseded by local regulations and codes of practice where
applicable. Use wiring rated at 75°C or greater.
1. The ground conductor should be sized in accordance with the input overcurrent protection device
data in Table 8. The ground cable connecting the UPS to the main ground system must follow the
most direct route possible. Control wiring and power wiring must be run in separate conduit.
Output and input cables must be run in separate conduit.
2. Consider using paralleled smaller cables for heavy currents—this can ease installation.
3. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current
ratings in UPS terminal. For terminal connection sizing, see Table 8.
4. In most installations, especially parallel multi-module systems, the load equipment is connected
to a distribution network of individually protected busbars fed by the UPS output, rather than
connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to
suit the individual distribution network demands rather than being fully load-rated.
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
5. When laying power cables, do not form coils; this will help avoid increasing formation of
electromagnetic interference.
14
3.1.4Cable Connections
!
Electrical Connections
The rectifier input, bypass and output are easily accessible from the front of the unit for installation.
All require lug type terminations. They are connected to busbars on the front side of the Liebert
and below the circuit breaker, as shown in Figure 3. These busbars are accessible when the front
side panel is removed. Busbars to connect external batteries are accessible from the front of the UPS.
NOTE
External connection access requires removal of a protective panel on the lower front of the UPS.
NOTE
There is no battery fuse in the UPS; the battery cabinet must include a circuit breaker
to cut off the current in case of short circuit. Refer to Table 8 for current ratings.
3.1.5Safety Ground
The safety ground busbar is located below the Maintenance Bypass circuit breaker or to the right of
the UPS Output breaker for 160-200KVA models as shown in Figure 3. The safety ground cable must
be connected to the ground busbar and bonded to each cabinet in the system.
All cabinets and cable conduit should be grounded in accordance with local regulations.
WARNING
Risk of electrical shock from ground fault. Can cause injury and death.
Failure to follow proper grounding procedures can result in electric shock hazard to personnel
or the risk of fire, should a ground fault occur.
NOTE
Proper grounding significantly reduces electromagnetic interference problems in systems.
®
NX™
NOTE
The ground busbar is easily accessible when the lower protective cover plate is removed.
3.1.6Protective Devices
For safety, it is necessary to install circuit breakers in the input AC supply and external battery
battery cabinets, external to the UPS system. Given that every installation has its own
characteristics, this section provides guidelines for qualified installation engineers with knowledge of
operating practices, regulatory standards and the equipment to be installed.
UPS Rectifier and Bypass Input Supply
• Protection from excessive overcurrents and short circuits in power supply input
External overcurrent protection for the AC output circuit is to be provided. See 6.4 - UPS
Electrical Characteristics and Table 9 for overload capacity.
When an external battery supply not made by Liebert is used, the customer must provide
overcurrent protection for the battery circuit.
• Dual Input
When wiring the UPS with dual inputs, the Rectifier input and the Bypass input must be
protected separately. Size the breakers according to the input currents shown in Table 8.
15
3.1.7Cabling Procedure
NOTICE
Risk of improper installation. Can cause improper operation and void warranty.
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If you have any difficulties, contact your local Liebert
representative or Liebert Services.
NOTE
Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect
AC wiring.
Once the equipment has been positioned and secured for operation, and the battery and ground
collars have been connected (see 3.1.4 - Cable Connections), connect the power cables as described
below. (Study the reference drawing in 8.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the front protective cover to gain easier access to the connections busbars.
3. Connect the safety ground and bonding ground bus cables to the copper ground busbar located on
the bottom of the equipment below the power connections. All cabinets in the UPS system must be
connected to the user’s ground connection.
Electrical Connections
®
NOTE
The grounding bonding arrangement must comply with the National Electrical Code and all
applicable local codes.
4. Identify and make power connections with incoming cables according to Steps 5 through 11.
Common Input Connections
5. For common bypass and rectifier inputs, connect the AC input supply cables between the power
distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to
88 lb-in. (10 N-m) using the M8 bolt provided.
Dual Input Connections
6. Remove the internal links installed between the Input circuit breaker (CB1) busbars and Bypass
Input busbars as shown in Figure 3.
7. For the bypass, connect the AC input supply cables between the power distribution panel and the
UPS Rectifier Input busbars (CB1 A-B-C terminals) and tighten the connections to 88 lb-in.
(10 N-m) using the M8 bolt provided.
8. For the Rectifier Input, connect AC input supply cables between the power distribution panel and
the UPS Rectifier Input busbars (CB1 A-B-C terminals).
16
Electrical Connections
!
NOTE
Both the rectifier and bypass feeds must come from the same utility source. The UPS can be
powered from separate sources provided all the following conditions are met:
1. The transformers are delta/wye isolation transformers where the wye secondary’s are
connected to the NX 480V UPS.
2. The individual transformer used to supply the Bypass of the NX 480V is solidly bonded to
earth ground at the transformer.
3. The individual transformer used to supply the Input (rectifier) of the NX 480V is solidly
bonded to earth ground at the transformer.
4. There are no appreciable ground currents flowing between the two transformers.
5. No delta/delta (ungrounded or corner grounded) transformers are used as a source to the
NX 480V UPS.
6. No high resistance or low resistance grounds can be used in the neutral bonding path to
ground of the delta/wye isolation transformers described above in Items 2 and 3.
7. All applicable NEC standards and wiring rules are enforced.
8. The internal bypass to input (rectifier) shorting bars in the NX 480V UPS are removed.
The above all apply to single-module systems.
9. For 1+N paralleled system, the Bypass to each unit must be fed from the same utility
source.
Output System Connections—Ensure Correct Phase Rotation
10. Connect the system output cables between the UPS output busbars (A-B-C terminals) and the
critical load and tighten the connections to 88 lb-in. (10 N-m) (M8 bolt).
WARNING
Risk of electric shock. Can cause injury and death.
If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, then ensure that the system output cables are safely isolated.
Observe the battery cable polarity. Be sure that the battery connector is made with the
correct polarity.
11. Refit all protective covers removed for cable installation.
Frequency Converter Mode
If a frequency converter configuration is used, connect the AC input supply cables to the rectifier
input busbars (A-B-C terminals). Torque to 88 lb-in (10N-m) for M8 bolts. Ensure correct phase
rotation. There will not be any AC bypass supply cables to the bypass input (A-B-C terminals) and
tighten the connections.
NOTE
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If any difficulties arise, contact Liebert
NOTE
For frequency converter operation, ensure that the linking busbars between the bypass and the
rectifier input are removed.
®
at 1-800-LIEBERT.
17
3.2Control Cables
X1
User Interface
Board
U1
DSP Control
K1
Key & LED Board
U2
Monitor Board
M3
Parallel Logic
Board
M5
Auxiliary Power
3.2.1Monitor Board Features
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker, battery temperature sensor), communicate with a personal
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).
The monitor board, arranged for this purpose, is located on the rear of the operator access door. The
main features are:
• Input and Output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
•Liebert
• Modem interface
• Temperature detect interface
Figure 4 shows the relationship and connection between the monitoring (U2) board and other boards
in the UPS.
NOTE: The black square ()
on each slot indicates Pin 1.
J3
J1
J13 J21 J25J28J4J26 J30 J10
J22
J23
J12
J9
J15
J17
J24
X4
X4
J16
X1
X2
X3
Liebert IntelliSlot 2
Liebert IntelliSlot 1
Liebert IntelliSlot 3
J8
J2
LCD
BFP INV ACFEPODry inMBCBCB
X5
X6
X7
PWR
MODEM
SNMP CARD
Electrical Connections
19
3.3Dry Contacts
+12V
GEN
BtG
ENV
GND
GND
+12V
AUX_I
T_IT
AUX_ 0
T_0T
F_F AN
FUSE
OL
FB
DRV
+12V
+12V+12V
+12V
X3
J4J26J30J10
NOTE: The black square () on each slot indicates Pin 1.
The UPS provides input dry contacts and output dry contacts.
NOTE
When operating the Liebert® NX™ with dry contacts, ESD measures must be taken or the
contacts may be damaged.
3.3.1Input Dry Contacts
There are several input dry contacts at the X3 slot.
Figure 6Input dry contacts
Electrical Connections
Table 1Input dry contacts at X3
Position
J4.1ENV
J4.2BtGBattery Ground Fault Detection (Normally Closed)
J4.3GEN
J4.4+12V+12V Power
1 - Must be configured using configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
Name
1,2
Description
3
Battery Room Alarm (Normally Closed)
Generator Detection (Normally Open)
3.3.2Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
Table 2Maintenance bypass cabinet interface
Position
J26.1T_IT
J26.2AUX_IReserved
J26.3+12V+12V Power
J26.4GNDPower Ground
J30.1FUSEReserved
J30.2F_FANFan Fail Alarm (N.C.)
J30.3T_OT
J30.4AUX_OReserved
1
- Must be configured using configuration software before becoming active.
Name
Description
1
Input transformer over temperature (N.C.)
1
Output Transformer Overtemperature (N.C.)
NOTE
All auxiliary cables of terminal must be double-insulated. The wire must be 600V, 18-16 AWG
stranded for maximum runs between 82 and 197 feet (25-60m), respectively.
20
Loading...
+ 102 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.