Emerson 40-120KVA, 60HZ, 480VAC User Manual

LIEBERT® NX™ 3-PHASE UPS: 40-120KVA, 60HZ, 480VAC - SITE PLANNING DATA

The Liebert NX is a true on-line, double conversion, three-phase UPS system that delivers complete, centralized power protection for mission-critical systems.
Designed to meet the high availability power needs of a wide variety of IT applications, the UPS com­bines a rack form factor, advanced operating fea­tures and low cost of ownership.
• Increases growth flexibility with Softscale™ technology, plus the ability to parallel modules for increased capacity and redundancy.
• Achieves higher availability by reducing the number of UPS units required to power your data center.
• Reduces total cost of ownership through the use of longer life batteries and simplified preventive maintenance.

General Specifications

INPUT
Vol tag e
Voltage Range without derating
Frequency Range 57-63Hz Current
Distortion Current Limit 140% of full load input current Current
Walk-In
Power Factor
Surge Protection
ENVIRONMENTAL
Operating Temperature
Non-Operating Temperature
Relative Humidity 0-95% non-condensing Operating
Altitude Acoustical Noise (full load)
80kVA
120kVA
480VAC, 60Hz 3-phase, 3-wire plus ground
+15%, -25%
3% maximum reflected THD at full load
20 seconds to full load Programmable, 0 to 30 seconds
>0.99 lagging at full load >0.98 lagging at half load Sustains input surges without damage, per criteria listed in IEC 61000-4-5
UPS: 32° to 104°F (0-40°C) Battery: 68° to 86°F (20-30°C)
-13° to 158°F (-25° to 70°C)
Up to 6,500 ft. (2,000m) without derating
<67dB at 80-104°F (27-40°C) ambient <61dB below 80°F (27°C) ambient
<69dB at 80-104°F (27-40°C) ambient <63dB below 80°F (27°C) ambient

External Battery Cabinet

Battery
Manufacturer
C&D
Technologies
Enersys HX205
Battery
Type
UPS12-100MR
UPS12-150MR
UPS12-210MR
Dimensions
in. (mm)
35.3x38.2x78.7
(897x 970x 2000)
35.3x38.2x78.7
(897x 970x 2000)
Weight lb. (kg)
1750 (794)
2000 (907)
2500
(1134)
2620
(1188)
OUTPUT
Voltage
Voltage Adjustment Range
Voltage Regulation
Dynamic Regulation
Transient Response Time
Voltage Distortion
Phasing Balance
Frequency Regulation
Load Power Factor Range
Overload
STANDARDS
Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe high performance UPS operation.
Qty.
Battery
Cabinets
15————
21795——
1127———
2 332013 9 7
119116——
2 483121 15 11
119117——
2 462820 15 12
480VAC, 60Hz, 3-phase, 3-wire plus ground
±5%
1% for balanced load 2% for 100% unbalanced load
±5% deviation for 100% load step ±1% for loss or return of AC input
Recover to ±5% of output voltage within 1/2 cycle
For linear loads, 1% THD Less than 4% THD for 100% nonlinear
loads without kVA/kW derating 120° ±0.5° for balanced load
120° ±1° for 100% unbalanced load ±0.05% single module ±0.25% paralleled modules
0.5 lagging to 1.0 without derating
125% of full load for 10 minutes 150% for one minute, with true
sinusoidal waveform
Battery Time (minutes)
40kVA 60kVA 80kVA 100kVA 120kVA
1
Liebert
®
NX™ 3-Phase UPS: 40-120kVA, 60Hz, 480VAC - Site Planning Data

Site Planning Data - 40-120kVA, 60Hz, 480VAC

UPS Rating Voltage AC Input Battery AC Output Mechanical Data
Current (A)
kVA kW Input Output
40 36 480 480 48 66.8 90 480 98 48 70
60 54 480 480 72 100.2 125 480 146 72 110 1290 (585) 15,204 (4.5) 620 (1050)
80 72 480 480 96 133.6 175 480 195 96 150 1290 (585) 20,273 (5.9) 620 (1050)
100 90 480 480 120 167.1 225 480 244 120 175 1422 (645) 23,496 (6.9) 920 (1550)
120 108 480 480 144 200.5 250 480 293 144 225 1422 (645) 28,196 (8.3) 920 (1550)
See Notes for Table (below): 1 2,3,5,8,12 6 4 1,3,8,12 1,3,8,12 6 13 14
Rec.
OCPD
Nom.
VDC
Max.
Discharge
Current
Dimensions
WxDxH, in. (mm)
23.6 x 38.2 x 78.7
(600 x 970 x 2000)
Weight
lb. (kg)
1290 (585) 11,612 (3.4) 620 (1050)
Heat Dis.
BTU/hr (kWH)
Cooling Air
CFM (m
3
/hr)Nom. Max. Nom. OCPD

Notes for Table

1. Nominal (Nom) current is based on full rated output load at nominal input
voltage.
2. Maximum (Max) current (140% of nominal) is short duration for battery
recharge conditions and low input voltage.
3. UPS input and bypass cables must be run in separate conduit from output
cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. For Single Input units only.
For Dual Input units, see “Electrical Data Specification Sheet, 40-120kVA UPS Module, Single or Dual Input Liebert NX - U3819100.”
6. OCPD = Overcurrent Protection Device. Recommended AC input and AC
output overcurrent protection represents 125% of nominal full load current (continuous) plus 100% of recharge current (non-continuous) per NEC 215.
7. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 1999.
8. Wiring requirements:
AC Input: 3-phase, 3-wire, plus ground AC Output: 3-phase, 3-wire, plus ground
9. All wiring is to be in accordance with national and local electric codes.
10. Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above
the UPS.

Notes for Table (continued)

11. Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace.
12. Control wiring and power wiring must be run in separate conduit.
13. Dimensions and weights in table do not include external battery cabinet.

Additional Notes

• Input and output wiring and breakers for a Liebert NX with Softscale technol-
ogy should be sized for the maximum scalable capacity. For example, a 40kVA Liebert NX that is scalable to 80kVA should be installed with wiring and breakers rated for an 80kVA configuration.
• If site configuration includes a backup emergency generator, it is recom-
mended that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS-compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing.
• If site configuration includes an automatic transfer switch, refer to Liebert
Power Line titled “Criteria for Application of Automatic Transfer Switches (ATS) With Uninterruptible Power Supply (UPS) Systems,” publication 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.
• If site configuration requires an external isolated maintenance bypass circuit,
it should be noted that utility AC input might not be in phase with the UPS AC output. Consult a Liebert sales representative or applications engineer.
© 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-25218_REV0_03-08